Substation Inspection Report - Khali

This report summarizes the inspection of the 33/11 KV Khali substation in Sangamner-2 subdivision. Key findings include: 1) The physical premises and control room are in good condition but some repairs are required. 2) The power transformers and circuit breakers are generally working properly but the OLTC is only functioning in local mode and not remotely. 3) Some minor issues were found with the 11kV circuit breakers that require repair or replacement of parts. 4) The substation's capacitor bank is only partially working due to a damaged cell and requires attention. 5) Testing last occurred in July 2023 and identified issues with

Uploaded by

Rahul Gagare
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
77 views3 pages

Substation Inspection Report - Khali

This report summarizes the inspection of the 33/11 KV Khali substation in Sangamner-2 subdivision. Key findings include: 1) The physical premises and control room are in good condition but some repairs are required. 2) The power transformers and circuit breakers are generally working properly but the OLTC is only functioning in local mode and not remotely. 3) Some minor issues were found with the 11kV circuit breakers that require repair or replacement of parts. 4) The substation's capacitor bank is only partially working due to a damaged cell and requires attention. 5) Testing last occurred in July 2023 and identified issues with

Uploaded by

Rahul Gagare
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO LTD.

NASHIK ZONE, NASHIK


Substation Inspection Report

Circle- A.Nagar Division-Sangamner Subdivision - Sangamer-2

Name of S/Stn : - 33/11 KV Khali Commissioned : - 5/8/2010 Scheme : - Infra

1) Physical premises Inspection-


i. Whether fencing/Compound provided :- Yes
a) Condition :- Good
ii. Approach to the S/Stn :-
iii. Control Room :- Yes
a) Condition :- Good
iv. Grass in Sub Stn :- yes
v. Black Metal Provision :- yes
vi. S/Stn. water provision :- Available
vii. Water Storage :- Available
viii. Water Circulation & Piping :- Available
ix. Leakages, if any :- NO
x. Painting a) Premises :- Requierd
b) Sub Stn equipments :- Requierd
xi. Yard Lighting :- Requierd
a) No. of non working units :- 9
xii. Whether fire fighting equipments provided & maintained provided Maintenance Requierd
2) Sub Station-
Power T/F TF 1 TF2 TF3 TF4
i Dt. Commissioned
ii Capacity 5 MVA
iii. Avg. Load in % 80%
iv. If equipped with OLTC-(Yes/No)- Yes
v If yes
vi Whether OLTC is working in Working
a) Local mode Working
b) Remote mode Not Working

Yes
vii Whether oil in conservator is adequate.
Yes
viii. Whether oil in OLTC conservator adequate.
ix. Last oil BDV checked Date Not Checked
x BDV Value Nill
xi Last oil filteration Date Nill
xii. Earthing intact Neutral Nill
xiii Earthing intact Body Nill

3) Breaker
a) 33 KV side
i. No. of breakers provided :- 1 No
ii. Type :- VCB
iii. Capacity :- 33 KV
iv. No of breakers in service :- 1 NO
v. Problems observed :- Nill
(Attach separate sheet if reqd.) :-
vi. Addl. Breakers reqd :- Yes
Purpose :- Backfeeding Supply 33 kv ashwi line
b) 11 KV side
i. No. of breakers provided :- 4 no
ii. Type :- VCB
iii. Capacity :- 11 KV
iv. No of breakers in service :- 4 No
v. Problems observed :- yes

:- 11 KV Khamba Breekar Mach. Fail, 11 kv


(Attach separate sheet if reqd.) Pimpri Breeckr Spring Charge Assy. Fail
vi Addl. Breakers reqd :- No
Purpose :- Nill
C) C.T.-
33 KV side –
i. No of CTs provided :- 1 Set
CTR :- 400-200-100/1-1-1A

ii. No of CTs not in service :- Nill


CTR :-

iii. Additional CTs required :- Nill


CTR :-

11 kv side -
i. No of CTs provided 09 nos :- 4 Set
CTR :- 400-200-100/5-5A

ii. No of CTs not in service :- Nill


CTR :-

iii. Additional CTs required :- Nill


CTR :-

4) P.T.-
33kv side-
i. No of PTs provided :- 1 Set
ii. No of PTs in Service :- 1 Set
iii. No of PT required :- No
11 kv side-
i. No of PTs provided :- 1 Set
ii. No of PTs in Service :- 1 Set
iii. No of PT required :- No
5) Relaying & metering –
i. Whether metering provided 33 kv side :- No
11 kv side :- No
ii. Meters not in service 33 kv side :- Nill
11 kv side :- Nill
iii. Reasons for not in service 33 kv side :- NA
11 kv side :- NA
iv. Relays provided Type :- Digital
v. Relays not in service :- Nill
vi. Relays to be upgraded :- No
6) Battery & Charger
i. Battery Charger :- Fail
ii. Battery Condition :- New
iii. Cells to be replaced :- No
7) Sub Stn Capacitor bank
i. Whether equipped with S/Stn. capacitor bank
If yes a) Capacity :- 2.4 MVAR
b) Working :- 1.2 MVAR
If no, a) Dt.of failure :- 24/04/2023
b) Reasons for non working :- Sell Damaged
Cells damaged. :- 1 Nos
NDCT/RVT Faulty. :- No
Breaker /Relay Faulty. :- No
Cable Faulty. :- No
Others specify :- No
8) TESTING HISTORY:-
i Substation last checked by testing DIV :- 21/07/2023
All SDT Bypassed, OLTC Motor Burnt, OLTC
:- Panal Wiring Burnt, Re Erthing of all SDT
ii Remarks therein Requierd
iii Whether complied :-