Subsation BOQ

Download as pdf or txt
Download as pdf or txt
You are on page 1of 22

RASTRIYA PRASARAN GRID COMPANY LIMITED Annex-5

NEW MEWA 132/33 kV Hybrid GIS SUBSTATION


Bill of Quantity (BoQ)
Plant and Equipment including Mandatory Spare Parts List

Estimated
Sl. No. Item Description
Unit Quantity
PART - A: OWNER ASSESSED QUANTITIES
1 POWER TRANSFORMER
30 MVA, 132/33 kV, three phase, power transformer complete with on load tapchanger (OLTC),
1.1 Nos. 1
RTCC and all accessories (LV side LA mounted)
2 Testing & Maintenance Equipments
2.1 Oil Storage Tank of 6 KL No. 1
2.2 Transformer Oil Filtration plant (6KLPH) No 1
3 LT Transformer
3.1 250 KVA, 33/0.400 kV with DO fuse and all necessary accessories Nos. 1
4 145KV GIS HYBRID EQUIPMENT
4.1 145kV, SF6 GIS Hybrid Bus Coupler bay Module as per section project
4.1.1 3150A, 40 kA for 1 sec Set 1
4.2 145 kV, SF6 GIS Hybrid Line feeder bay Module as per section project
4.2.1 3150A, 40 kA for 1 sec Set 2
4.3 145 kV, SF6 GIS Hybrid transformer bay Module as per section project
4.3.1 3150A, 40 kA for 1 sec Set 1
5 145 kV Outdoor AIS Equipment (31.5 kA for 1 sec)
5.1 120 KV Surge Arrester (1-phase) Nos. 9
145 kV, 8800pF, 50 VA, 132/√3 /110/√3 kV, Class 0.2/3P Capacitor Voltage Transformer complete
5.2 Nos. 12
with all accessories as per specification (1-Phase)
5.3 145 kV Bus Post Insulator (1-Phase) Nos. 24
6 33 kV Outdoor AIS Equipment
6.1 Polymer or porcelain type 33 kV cable Sealing end with support insulators (if required) Nos 3
6.2 30 kV, 10 kA Surge arrester (1 phase) including discharge counter Nos 3
6.3 36 kV, 50 VA, 33/√3 V/110/√3 V potential transformer Nos 6
6.4 36 kV, 50 VA current transformer Nos 3
6.5 36 KV, 1250 A, 31.5 kA, 1 sec, 3 phase, SF6 circuit breaker complete with all accessories Set 1
Annex-5

Estimated
Sl. No. Item Description
Unit Quantity
6.6 36 kV, 1250 A, 3 phase disconnecting switch with out grounding switch Set 1
6.7 33 kV Bus Post Insulator Nos 9
7 Testing & Maintenance Equipment for 145 kV GIS Hybrid
7.1 SF6 Gas processing Unit Set 1
7.2 Partial Discharge Monitoring System (portable type) Set 1
7.3 Dew Point Meter Set 1
7.4 SF6 Gas Leak Detector Set 1
8 CONTROL AND RELAY PANEL (WITH SUBSTATION AUTOMATION SYSTEM)
132/33 kV transformer control and relay panel complete with all accessories as per technical
8.1 Set 1
specifications
132 kV bus coupler/bar control and relay protection panel complete with all accessories as per
8.2 Set 1
technical specifications
8.3 132 kV line control and relay panel complete with all accessories as per technical specifications Set 2
8.4 Three phase Relay test kit No 1
9 CABLES ALONG WITH CLAMPS, GLANDS, LUGS ETC.
33 kV HT Copper Cable (1CX300 SQmm, two cable per phase) for 33 kV side of 132/33 kV
9.1 RM
transformer alongwith accessories and termination equipments 1,000.00
9.2 Complete Cable termination Kit for abobe (1) Nos 6
0.4 kV HT Aluminum Cable (3.5 C, 300 SQmm) for 0.4 kV side of 33/0.4 kV LT transformer alongwith
9.3 LS 1
accessories and termination equipments
9.4 Complete Cable termination Kit for abobe (3) Nos 3
10 Power Cables - (1.1 kV grade)
10.1 3.5Cx50 sqmm (XLPE) cable for filter Machine along with 2 nos outdoor receptacles -100A LS 1
10.2 3.5Cx50 sqmm (XLPE) cable for staff quarter building main supply LS 1
10.3 3.5Cx25 sqmm (XLPE) cable for Guard cum store building main supply LS 1
11 1.1 kV GRADE LOW VOLTAGE CABLES
11.1 Power Cables (PVC) LS 1
11.2 Control Cables (PVC) LS 1
11.3 Cable glands, lugs for Power & Control cables LS 1
12 Sheild wire and Grounding for new substation
Galvanized E.H.S. steel wires of size 7/3.35 for lightning shield wire in take-off and internal structures
12.1 LS 1
complete with all accessories
Annex-5

Estimated
Sl. No. Item Description
Unit Quantity
Lightning protection system with lightning mast, copper conductor, electrodes complete with all
12.2 LS 1
accessories for control building
Earthing of substation with conductors (150 Sq. mm, minimum), electrode, grounding materials
12.3 LS 1
complete with all accessories
13 BATTERIES AND BATTERY CHARGER
13.1 Float cum boost battery charger for 110 V battery complete with all accessories set 1
13.2 Float cum boost battery charger for 48 V battery complete with all accessories set 1
13.3 110 V, 600 AH batteries complete with all accessories set 1
13.4 48 V, 400 AH batteries complete with all accessories set 1
14 ERECTION & MISCELLANEOUS MATERIALS
132 kV insulator strings, hardware, clamp, connectors & accessories to complete the specified scope
14.1 LS 1
of works including for line tower
120 and 70 kN Disc insulators & accessories to complete the specified scope of works including for
14.2 LS 1
line tower
14.3 ACSR "Moose" conductors and accessories to complete the specified scope of works LS 1
Main Tubular bus, branch buses, connectors, expansion joint including all other accessories required
14.4 to complete 132 kV double bus-bar configuration (Minimum Outer diameter and thickness of main bus LS 1
100.0 and 7.0 mm respectively and that of branches 75.0 & 5.0 mm)
33 kV insulator strings, hardware, clam, connectors & accessories to complete the specified scope of
14.5 LS 1
works
70 and 45 kV Disc insulators & accessories to complete the specified scope of works including for line
14.6 LS 1
tower (if require)
Main Tubular bus, branch buses, connectors, expansion joint including all other accessories required
14.7 to complete 33 kV single bus-bar configuration (Minimum Outer diameter and thickness of main bus LS 1
75.0 and 5.0 mm respectively and that of branches 40.0 & 3.0 mm)
15 Air conditioning System:
Ceilling cassette type split AC unit of 3 TR capacities including ceilling cassette type for 132 kV
15.1 sets 4
control room
15.2 High wall type split AC unit of 2 TR capacities for 11 kV switchgear room sets 2
High wall type split AC unit of 1.5 TR capacities for communication, battery, office room and staff
15.3 sets 8
quarter building
16 Fire Protection System (Portable Trolley Wheel mounted extinguishers)
16.1 50 litre water type Nos 1
Annex-5

Estimated
Sl. No. Item Description
Unit Quantity
16.2 30 litre foam type Nos 2
16.3 4.5 kg CO2 type Nos 10
16.4 22.5 kg Dry Chemical Powder (DCP) type Nos 2
16.5 Smoke detection system LS 1
16.6 Fire detection and Alarm System for control room LS 1
16.7 Identification plate, danger notice etc LS 1
17 LT Switchgear (As per Technical specification)
17.1 400 V AC Main switchboard panel Sets 1
17.2 110 V DCDB Sets 1
17.3 48 V DCDB Sets 1
18 Illumination System
Outdoor Switchyard, Substation area, Street lighting, Pole, MCB, Switch etc as per technical
18.1 LS 1
specification
18.2 Emergency DC lighting system for switchyard Nos 5
19 SUBSTATION AUTOMATION/ COMMUNICATION / SCADA (Based on IEC 61850)
19.1 SUBSTATION AUTOMATION SYSTEM:
Complete Substation automation system including hardware and software for the substation & remote
19.1.1
control stations alongwith associated equipments for the followings as per Technical Specification.
19.1.2 132 kV System Bays 4
19.1.3 33 kV System Bays 2
Integration of all 132/33 kV Bays under present scope with the SCADA of SIEMENS (SINAUT
19.1.4 Spectrum) at Load Dispatch Centre, Kathmandu including supply of Hardware, Software, accessories LS 1
etc. as per TS Section Project.
19.2 COMMUNICATION AND SCADA
19.2.1 Digital Protection Coupler nos 2
Communication Panel including allied equipment such as SDH Equipment (STM - 4 upgradable to
STM-5 ADM, upto two directions) , Ethernet tributaries card (min. 4 port), Termination Equipment
19.2.2 (Drop/Insert Multiplexer, Subscriber Line Interface Cards, Equipment Cabinets complete in all LS 1
respects including establishment of Fibre Optic (FO) links for far end substation/s(Dungesangu) as
per technical specifications

19.2.3 Optical Distribution Frame complete in all respects as per technical specifications LS 1
Annex-5

Estimated
Sl. No. Item Description
Unit Quantity
Optical Approach Cable -24 pair Fibre (DWSM -G.652D) along with Installation hardware set for
19.2.4 above 24 Fibre, Fibre Optic Approach Cable, outdoor encloser etc complete in all respects as per LS 1
technical specifications
20 CIVIL WORKS

Steel structure for post, beam and equipment supporting frame complete with insertion
20.1 bolts/rod, bolts, fastner, pack washer, nuts, guest paltes and all accessories: (For 132 and 33
kV side)

20.1.1 132 kV take off gantry structures Bays 3


20.1.2 132 kV internal gantry structures including 132/33 kV transformer gantry structure Bays 4
20.1.3 132 kV GIS Hybrid for Line feeder Nos 2
20.1.4 132 kV GIS Hybrid for Bus feeder Nos 1
20.1.5 132 kV GIS Hybrid for Transformer feeder Nos 1
20.1.6 132 kV capacitor voltage transformer Nos 12
20.1.7 120 kV surge arrestor Nos 9
20.1.8 132 kV Bus post insulator Nos 24
Rail Structure for 132/33 Power Transformer including access from inter road (For transformer
20.1.9 LS
shifting)
20.1.10 Drop out fuse support for 33/0.4 kV, 250 KVA transformer Nos 1
20.2 For 33 kV Side:
2.1 33 kV take off gantry structures LS 1
20.2.1 33 kV internal gantry structures to complete the specified job LS 1
20.2.2 33 kV SF6 gas circuit breaker Sets 1
20.2.3 33 kV disconnecting switch with earth switch Sets 4
20.2.4 33 kV disconnecting switch with out earth switch Sets 1
20.2.5 33 kV voltage transformer Nos 6
20.2.6 33 kV current transformer Nos 3
20.2.7 30 kV surge arrestor Nos 3
20.2.8 33 kV Bus post insulator Nos 9
20.2.9 33 kV Cable sealing end and support insulator Nos 3
20.2.10 Lightning Mast (Minimum height 19.0 meter) Sets 1
Annex-5

Estimated
Sl. No. Item Description
Unit Quantity
21.00 Spare Parts:
21.1 132/33 kV Transformer:
21.1.1 OLTC motor with contactor sets 1
21.1.2 Cooler Fan with motor nos 1
21.1.3 Local & Remote WTI and OTI with sensing device & contact (each type) sets 1
21.1.4 Buchholz relay complete with contacts (Main tank) sets 1
21.1.5 Magnetic oil level gauge nos 1
21.1.6 Starters, contactors, switches & relays for electrical control panels (one set of each type) sets 1
21.1.7 Complete set of pressure relief device set 1
21.1.8 145 kV Bushing with metal parts and gaskets and lifting tools nos 1
21.1.9 36 kV Bushing with metal parts and gaskets and lifting tools nos 1
21.1.10 Spare insulating oil to be handed over to NEA after commissioning for O&M requirement KL 5
21.2 145 kV GIS Hybrid
General
21.2.1 SF6 gas Pressure Relief Devices, 1Nos. of each type Set 1
SF6 Pressure gauge cum switch OR Density monitors and pressure switch as applicable (1 no. of each
21.2.2 Set 1
type)
21.2.3 Coupling device for pressure gauge cum switch for connecting Gas handling plant Set 1
21.2.4 Rubber Gaskets, “O” Rings and Seals for SF6 gas of each type Set 1
21.2.5 Molecular filter for SF6 gas with filter bags (20% of total weight) Set 1
21.2.6 All types of Control Valves for SF6 gas of each type Set 1
21.2.7 SF6 gas (20 % of total gas quantity) Set 1
21.2.8 All types of coupling for SF6 gas (1 no. of each type) Set 1
21.2.9 Pipe length (Copper or Steel as applicable) for SF6 Circuit of each type Set 1
Locking device to keep the Dis-connectors (Isolators) and Earthing switches in close or open position
21.2.10 Set 1
in case of removal of the driving Mechanism
21.2.11 SF6 to air bushing (145 kV - 1 No. of each type & rating) as applicable Set 1
21.3 145 kV AIS
21.3.1 132kV, 8800pF CVT (excluding support structure/ common JB) Nos 1
Annex-5
Estimated
Sl. No. Item Description
Unit Quantity
21.3.2 33 kV PT (excluding support structure/ common JB) Nos 1
120kV Surge Arrestor with insulating base, terminal connector , Surge counter & accessories
21.3.3 Nos 1
(excluding support structure)
30 kV Surge Arrestor with insulating base, terminal connector , Surge counter & accessories
21.3.4 Nos 3
(excluding support structure)
9 kV Surge Arrestor with insulating base, terminal connector , Surge counter & accessories (excluding
21.3.5 Nos 3
support structure)
21.4 33 KV SF6 CIRCUIT BREAKER:
21.4.1 Complete set of interrupting chamber set 1
21.4.2 Rubber gaskets, `O' rings and seals for SF6 gas (1 No. of each type) sets 1
21.4.3 Trip coil assembly with resistor as applicable sets 4
21.4.4 Closing coil assembly with resistor as applicable sets 4
Relays, pressure switch, Power contactors, push buttons, timers & MCBs etc (1 No. of each type &
21.4.5 sets 1
rating)
21.4.6 Motor for mechanism nos 1
21.5 33 KV ISOLATORS :
21.5.1 Poecelain insulators nos 3
21.5.2 Main contact assemblies (one assembly) sets 4
21.5.3 Auxiliary contact assemblies (one assembly) sets 4
21.5.4 Interlocking coil sets 2
21.5.5 Push button switch - (1 No. of each type & rating) as applicable sets 1
21.5.6 Limit switch and Aux. Switches for complete 3 phase equipment
21.5.7 For isolator sets 1
21.5.8 For earth switch sets 1
21.6 36 kV Current transformer (excluding support structure and common JB) Nos 1
21.6.1 36 kV Post Insulators Nos 3
21.6.2 36 kV Sealing end with support insularor Nos 3
21.7 110 V Battery Chargers
21.7.1 Set of Control Cards sets 1
21.7.2 Set of relays sets 1
Annex-5
Estimated
Sl. No. Item Description
Unit Quantity
21.7.3 Rectifier transformer nos 1
21.7.4 Thyristor/ Diode sets 1
21.7.5 Fuses of Thyristor with indicators sets 1
21.8 48V Battery Chargers
21.8.1 Set of Control Cards sets 1
21.8.2 Set of relays sets 1
21.8.3 Rectifier transformer no 1
21.8.4 Thyristor/ Diode sets 1
21.8.5 Fuses of Thyristor with indicators (minimum 4 nos of each type) sets 1
21.9 Line Relay & Protection (132 kV):
21.9.1 Numerical distance relay ( 1 no. of each type) set 1
21.10 Transformer Protection Panel
21.10.1 Transformer differential protection no 1
21.10.2 Restricted earth fault protection relay with non-linear resistor no 1
21.10.3 Directional over current & E/F Protection Relay no 1
21.11 COMMON SPARES
21.11.1 Breaker failure relay no 1
21.11.2 Trip circuit supervision relay nos 2
21.11.3 Self reset trip relay (relay of each type) set 1
21.11.4 Hand reset trip relay (relay of each type) set 1
21.11.5 Timer relay (relay of each type) set 1
21.11.6 DC supervision relay (relay of each type) set 1
21.11.7 Flag relays (relay of each type) set 1
21.11.8 Auxiliary relays (relay of each type) set 1
21.11.9 Indicating lamps of each type nos 5
21.11.10 Fuse of each type nos 5
21.11.11 Color caps of each color for indicating lamp nos 3
21.11.12 Ammeter nos 2
21.11.13 Voltmeter nos 2
Annex-5

Estimated
Sl. No. Item Description
Unit Quantity
21.12 Communication and SCADA:
21.12.1 Digital protection coupler Set 1
21.12.2 SDH and Multiplexer (each type of card) Set 1
21.13 SAS
21.13.1 Bay Control Unit (IED) of each type set 1
21.13.2 Ethernet Switch of each type set 1
21.14 COMMON SPARES
21.14.1 Bay unit Module No 1
21.14.2 2 wire local subscriber interface card for PABX No 1
21.14.3 E1 Interface card for PABX No 1
22 Mandatory Spares of Communication Equipments
22.1 SDH Equipment (STM-4 MADM upto 5 MSP protected directions)
Common cards, Cross-connect/control cards, Optical base card, Power supply cards, power cabling,
22.1.1 Set 1
other hardware & accessories (each).
22.2 Optical Interface Cards/SFP
22.2.1 S4.1 SFP Nos. 1
22.2.2 L4.1 SFP Nos. 1
22.2.3 L4.2 SFP Nos. 1
22.3 Tributary cards
22.3.1 E1 Interface card (Min.16 interfaces per card) Nos. 1
22.3.2 Ethernet Interface 10/100 Base T with Layer-2 switching (Min 8 Interfaces per card) Nos. 1
22.4 Miscellaneous:
22.4.1 Tonge tester as per specification nos 1
22.4.2 5 kV Insulation tester (Megger) nos 1
22.4.3 Transformer oil test kit set 1
PART - B: OWNER ASSESSED QUANTITIES FOR DUNGESANGU SS
23 ELECTRICAL WORKS:
23.1 145 kV AIS Equipments:
23.1.1 CIRCUIT BREAKERS & SWITCHGEARS
145 kV, 1250 A, 40 kA, 3 Phase, SF6 circuit breakers complete with all accessories Sets 2
23.1.2 DISCONNECTING SWITCHES
Annex-5
Estimated
Sl. No. Item Description
Unit Quantity
23.1.3 145 kV, 3 Phase, center break disconnecting switch with grounding switch Sets 2
21.1.4 145 kV, 3 Phase, center break disconnecting switch with out grounding switch Sets 4
23.2 INSTRUMENT TRANSFORMERS:
145 kV, 8800pF, 50 VA, 132/√3 /110/√3 kV, Class 0.2/3P Capacitor Voltage Transformer complete
23.2.1 Nos 6
with all accessories as per specification
23.2.2 145 kV, 50 VA, 1200 A with 120 % extended rating current transformer Nos 6
23.3 LIGHTNING ARRESTORS:
23.3.1 120 kV, 10 kA Surge arrester (1 phase) including discharge counter Nos 6
23.4 CONTROL AND RELAY PANEL (WITH SUBSTATION AUTOMATION SYSTEM)
23.4.1 132 kV line control and relay panel complete with all accessories as per technical specifications sets 2
23.5 1.1 kV GRADE LOW VOLTAGE CABLES
23.5.1 Power Cables (PVC) LS 1
23.5.2 Control Cables (PVC) LS 1
23.5.3 Cable glands, lugs for Power & Control cables LS 1
23.6 GROUNDING
Galvanized E.H.S. steel wires of size 7/3.35 for lightning shield wire in take-off and internal structures
23.6.1 LS 1
complete with all accessories

Earthing of substation with conductors (of same size used in underconstruction substation), electrode,
23.6.2 LS 1
grounding materials complete with all accessories

23.7 Bus post Insulator:


23.7.1 132 kV Bus post insulators (Minimum) Nos 12
23.8 ERECTION & MISCELLANEOUS MATERIALS
132 kV insulator strings, Disc insulator & accessories to complete the specified scope of works
23.8.1 LS 1
including for line tower
132 kV hardware, clamp, connectors & accessories to complete the specified scope of works
23.8.2 LS 1
including for line tower
ACSR conductors and accessories to complete the specified scope of works (The conductor should
23.8.3 LS 1
be same as used in TL)

Main Tubular bus, branch buses, connectors, expansion joint including all other accessories required
23.8.4 to complete 132 kV double bus-bar configuration (Minimum Outer diameter and thickness of main bus LS 1
100.0 and 7.0 mm respectively and that of branches 75.0 & 5.0 mm)
Annex-5

Estimated
Sl. No. Item Description
Unit Quantity
23.9 Illumination System
23.9.1 Outdoor Switchyard, Substation area, Street lighting etc as per technical specification LS 1
24 SUBSTATION AUTOMATION/ COMMUNICATION / SCADA (Based on IEC 61850)
24.1 SUBSTATION AUTOMATION SYSTEM:
Inclusion of complete Substation automation system for new bays including hardware and software
24.1.1 for the substation & remote control stations alongwith associated equipments for the followings as per
Technical Specification.
24.1.2 132 kV System Bays 2
Integration of all 132/33/11kV Bays under present scope with the SCADA of SIEMENS (SINAUT
24.1.3 Spectrum) at Load Dispatch Centre, Kathmandu including supply of Hardware, Software, accessories
etc. as per TS Section Project.
24.2 COMMUNICATION AND SCADA
24.2.1 Digital Protection Coupler Nos 2
Extension and interfacing of existing Communication Panel/equipment including Ethernet tributaries
card Termination Equipment (Drop/Insert Multiplexer, Subscriber Line Interface Cards, Equipment
24.2.2 LS 1
Cabinets complete in all respects including establishment of Fibre Optic (FO) links for far end
substation/s (Papung, Mewa hub SS) as per technical specifications
24.2.3 Optical Distribution Frame complete in all respects as per technical specifications LS 1
Optical Approach Cable -24 pair Fibre (DWSM -G.652D) along with Installation hardware set for
24.2.4 LS 1
above 24 Fibre, Fibre Optic Approach Cable complete in all respects as per technical specifications
25 CIVIL WORKS
Steel structure for post, beam and equipment supporting frame complete with bolts, fastner,
25.1
pack washer, nuts, guest paltes and all accessories: (Extension works for 132 side)
25.1.1 132 kV take off gantry structures Bays 2
25.1.2 132 kV internal gantry structures gantry structure Bays 2
25.1.3 132 kV SF6 gas circuit breaker Sets 2
25.1.4 132 kV disconnecting switch with earth switch Sets 2
25.1.5 132 kV disconnecting switch with out earth switch Sets 6
25.1.6 132 kV capacitor voltage transformer Nos 6
25.1.7 132 kV current transformer Nos 6
25.1.8 120 kV surge arrestor Nos 6
25.1.9 132 kV Bus post insulator Nos 12
26 132 kV Double circuit Dead end Towers Nos 2
Annex-5
RASTRIYA PRASARAN GRID COMPANY LIMITED
NEW MEWA 132/33 kV Hybrid GIS SUBSTATION
Bill of Quantity (BoQ)
Construction, Installation, Testing and Commissioning

Estimated
S. No. Item Description
Unit Quantity
PART - A: OWNER ASSESSED QUANTITIES
1 POWER TRANSFORMER
30 MVA, 132/33 kV, three phase, power transformer complete with on load tapchanger (OLTC),
1.1 Nos. 1
RTCC and all accessories (LV side LA mounted)
2 Testing & Maintenance Equipments
2.1 Oil Storage Tank of 6 KL No. 1
2.2 Transformer Oil Filtration plant (4KLPH) No 1
3 LT Transformer
3.1 250 KVA, 33/0.400 kV with DO fuse and all necessary accessories Nos. 1
4 145KV GIS HYBRID EQUIPMENT
4.1 145kV, SF6 GIS Hybrid Bus Coupler bay Module as per section project
4.1.1 3150A, 40.0 kA for 1 sec Set 1
4.2 145 kV, SF6 GIS Hybrid Line feeder bay Module as per section project
4.2.1 3150A, 40.0 kA for 1 sec Set 6
4.3 145 kV, SF6 GIS Hybrid transformer bay Module as per section project
4.3.1 3150A, 40.0 kA for 1 sec Set 1
5 145 kV Outdoor AIS Equipment (31.5 kA for 1 sec)
5.1 120 KV Surge Arrester (1-phase) Nos. 9
145 kV, 8800pF, 50 VA, 132/√3 /110/√3 kV, Class 0.2/3P Capacitor Voltage Transformer complete
5.2 Nos. 12
with all accessories as per specification (1-Phase)
5.3 145 kV Bus Post Insulator (1-Phase) (Except auxiliary buses of transformer and others) Nos. 24
6 33 kV Outdoor AIS Equipment
6.1 Polymer or porcelain type 33 kV cable Sealing end with support insulators (if required) Nos 3
6.2 30 kV, 10 kA Surge arrester (1 phase) including discharge counter Nos 3
6.3 36 kV, 50 VA, 33/√3 V/110/√3 V potential transformer Nos 6
Annex-5
Estimated
S. No. Item Description
Unit Quantity
6.4 36 kV, 50 VA current transformer Nos 3
6.5 36 KV, 1250 A, 31.5 kA, 1 sec, 3 phase, SF6 circuit breaker complete with all accessories Set 1
6.6 36 kV, 1250 A, 3 phase disconnecting switch with out grounding switch Set 1
6.7 33 kV Bus Post Insulator Nos 9
7 CONTROL AND RELAY PANEL (WITH SUBSTATION AUTOMATION SYSTEM)
132/33 kV transformer control and relay panel complete with all accessories as per technical
7.1 Set 1
specifications
132 kV bus coupler/bar control and relay protection panel complete with all accessories as per
7.2 Set 1
technical specifications
7.3 132 kV line control and relay panel complete with all accessories as per technical specifications Set 6
7.4 Three phase Relay test kit No 1
8 CABLES ALONG WITH CLAMPS, GLANDS, LUGS ETC.
33 kV HT Copper Cable (1CX300 SQmm, two cable per phase) for 33 kV side of 132/33 kV
8.1 RM
transformer alongwith accessories and termination equipments 1,000.00
8.2 Complete Cable termination Kit for abobe (1) Nos 6.00
0.4 kV HT Aluminum Cable (3.5 C, 300 SQmm) for 0.4 kV side of 33/0.4 kV LT transformer alongwith
8.3
accessories and termination equipments
LS 1
8.4 Complete Cable termination Kit for abobe (3) Nos 3
9 Power Cables - (1.1 kV grade)
91 3.5Cx50 sqmm (XLPE) cable for filter Machine along with 2 nos outdoor receptacles -100A LS 1
9.2 3.5Cx50 sqmm (XLPE) cable for staff quarter building main supply LS 1
9.3 3.5Cx25 sqmm (XLPE) cable for Guard cum store building main supply LS 1
10 1.1 kV GRADE LOW VOLTAGE CABLES
10.1 Power Cables (PVC) LS 1
10.2 Control Cables (PVC) LS 1
10.3 Cable glands, lugs for Power & Control cables LS 1
11 Sjield wire and Grounding for new substation
Galvanized E.H.S. steel wires of size 7/3.35 for lightning shield wire in take-off and internal
11.1
structures complete with all accessories
LS 1
Lightning protection system with lightning mast, copper conductor, electrodes complete with all
11.2 LS 1
accessories for control building
11.3 Earthing of substation with conductors, electrode, grounding materials complete with all accessories LS 1
Annex-5
Estimated
S. No. Item Description
Unit Quantity
12 BATTERIES AND BATTERY CHARGER
Float cum boost battery charger for 110 V battery complete with all accessories as per technical
12.1 set 1
specification
12.2 Float cum boost battery charger for 48 V battery complete with all accessories set 1
12.3 110 V, 600 AH batteries complete with all accessories set 1
12.4 48 V, 400 AH batteries complete with all accessories set 1
13 ERECTION & MISCELLANEOUS MATERIALS
132 kV insulator strings, hardware, clamp, connectors & accessories to complete the specified
13.1 LS 1
scope of works including for line tower
120 and 70 kN Disc insulators & accessories to complete the specified scope of works including for
13.2 LS 1
line tower
13.3 ACSR "Moose" conductors and accessories to complete the specified scope of works LS 1
Main Tubular bus, branch buses, connectors, expansion joint including all other accessories
13.4 required to complete 132 kV double bus-bar configuration (Minimum Outer diameter and thickness LS 1
of main bus 100.0 and 7.0 mm respectively and that of branches 75.0 & 5.0 mm)
33 kV insulator strings, hardware, clam, connectors & accessories to complete the specified scope
13.5 LS 1
of works
70/45 kV Disc insulators & accessories to complete the specified scope of works including for line
13.6 LS 1
tower (if require)
Main Tubular bus, branch buses, connectors, expansion joint including all other accessories
13.7 required to complete 33 kV single bus-bar configuration (Minimum Outer diameter and thickness of LS 1
main bus 75.0 and 5.0 mm respectively and that of branches 40.0 & 3.0 mm)
14 Air conditioning System:
Ceilling cassette type split AC unit of 3 TR capacities including ceilling cassette type for 132 kV
14.1
control room
sets 4

14.2 High wall type split AC unit of 2 TR capacities for 11 kV switchgear room sets 2
High wall type split AC unit of 1.5 TR capacities for communication, battery, office room and staff
14.3
quarter building
sets 8

15 Fire Protection System (Portable Trolley Wheel mounted extinguishers)


15.1 50 litre water type Nos 1
15.2 30 litre foam type Nos 2
15.3 4.5 kg CO2 type Nos 10
15.4 22.5 kg Dry Chemical Powder (DCP) type Nos 2
Annex-5

Estimated
S. No. Item Description
Unit Quantity
15.5 Smoke detection system LS 1
15.6 Fire detection and Alarm System for control room LS 1
15.7 Identification plate, danger notice etc LS 1
16 LT Switchgear (As per Technical specification)
16.1 400 V AC Main switchboard panel Sets 1
16.2 220 V DCDB Sets 1
16.3 48 V DCDB Sets 1
17 Illumination System
Outdoor Switchyard, Substation area, Street lighting, Pole, MCB, Switch etc as per technical
17.1 LS 1
specification
17.2 Emergency DC lighting system for switchyard Nos 5
18 SUBSTATION AUTOMATION/ COMMUNICATION / SCADA (Based on IEC 61850)
18.1 SUBSTATION AUTOMATION SYSTEM:
Complete Substation automation system including hardware and software for the substation &
remote control stations alongwith associated equipments for the followings as per Technical
Specification.
18.1.1 132 kV System Bays 4
18.1.2 33 kV System LS 2
Integration of all 132/33 kV Bays under present scope with the SCADA of SIEMENS (SINAUT
18.1.3 Spectrum) at Load Dispatch Centre, Kathmandu including supply of Hardware, Software, LS 1
accessories etc. as per TS Section Project.
18.2 COMMUNICATION AND SCADA
18.2.1 Digital Protection Coupler nos 2
Communication Panel including allied equipment such as SDH Equipment (STM - 4 upgradable to
STM-5 ADM, upto two directions) , Ethernet tributaries card (min. 4 port), Termination Equipment
18.2.2 (Drop/Insert Multiplexer, Subscriber Line Interface Cards, Equipment Cabinets complete in all LS 1
respects including establishment of Fibre Optic (FO) links for far end substation/s as per technical
specifications
18.2.3 Optical Distribution Frame complete in all respects as per technical specifications LS 1
Optical Approach Cable -24 pair Fibre (DWSM -G.652D) along with Installation hardware set for
18.2.4 above 24 Fibre, Fibre Optic Approach Cable, outdoor encloser etc complete in all respects as per LS 1
technical specifications
Annex-5

Estimated
S. No. Item Description
Unit Quantity
19 CIVIL WORKS
Steel structure for post, beam and equipment supporting frame complete with bolts, fastner,
19.1
pack washer, nuts, guest paltes and all accessories: (For 132 and 33 kV side)
19.1.1 132 kV take off gantry structures Bays 3
19.1.2 132 kV internal gantry structures including 132/33 kV transformer gantry structure Bays 4
19.1.3 132 kV GIS Hybrid for Line feeder Nos 4
19.1.4 132 kV GIS Hybrid for Bus feeder Nos 1
19.1.5 132 kV GIS Hybrid for Transformer feeder Nos 1
19.1.6 132 kV capacitor voltage transformer Nos 12
19.1.7 120 kV surge arrestor Nos 12
19.1.8 132 kV Bus post insulator Nos 24
Rail Structure for 132/33 Power Transformer including access from inter road (For transformer
19.1.9 LS
shifting)
19.1.10 Drop out fuse support for 33/0.4 kV, 250 KVA transformer Nos 1
19.2 For 33 kV Side:
19.2.1 33 kV take off gantry structures LS 1
19.2.2 33 kV internal gantry structures to complete the specified job LS 1
19.2.3 33 kV SF6 gas circuit breaker Sets 1
19.2.4 33 kV disconnecting switch with earth switch Sets 4
19.2.5 33 kV disconnecting switch with out earth switch Sets 1
19.2.6 33 kV voltage transformer Nos 6
19.2.7 33 kV current transformer Nos 3
19.2.8 30 kV surge arrestor Nos 3
19.2.9 33 kV Bus post insulator Nos 9
19.2.10 33 kV Cable sealing end and support insulator Nos 3
19.2.11 Lightning Mast (Minimum height 19.0 meter) Sets 1
20 Civil Works:
Concrete Foundation for equipments and Steel Structures complete with excavation,
20.1
backfilling, form works, lean concrete concrete works and reinforcement bars:
20.1.1 132 kV take off gantry structures LS 1
20.1.2 132 kV internal gantry structures including 132/33 kV transformer gantry structure LS 1
Annex-5
Estimated
S. No. Item Description
Unit Quantity
20.1.3 132 kV GIS Hybrid for Line feeder Nos 6
20.1.4 132 kV GIS Hybrid for Bus feeder Nos 1
20.1.5 132 kV GIS Hybrid for Transformer feeder Nos 1
20.1.6 132 kV capacitor voltage transformer Nos 24
20.1.7 120 kV surge arrestor Nos 18
20.1.8 132 kV Bus post insulator Nos 36
Rail Structure for 132/33 Power Transformer including access from inter road (For transformer
20.1.9 LS 1
shifting with Pulling block)
20.1.10 132/33 kV, 3 phase, 30 MVA power transformer with fire wall, oil slump pit LS 1
20.1.11 33/0.4 kV, 3 phase, 250 KVA station transformer LS 1
20.2 For 33 kV Side:
20.2.1 33 kV take off gantry structures LS 1
20.2.2 33 kV internal gantry structures to complete the specified job LS 1
20.2.3 33 kV SF6 gas circuit breaker Sets 1
20.2.4 33 kV disconnecting switch with earth switch Sets 4
20.2.5 33 kV disconnecting switch with out earth switch Sets 1
20.2.6 33 kV voltage transformer Nos 6
20.2.7 33 kV current transformer Nos 3
20.2.8 30 kV surge arrestor Nos 3
20.2.9 33 kV Bus post insulator Nos 9
20.2.10 33 kV Cable sealing end and support insulator Nos 3
20.2.11 Lightning Mast (Minimum height 19.0 meter) Sets 1
20.2.12 Drop out fuse support for 33/0.4 kV, 250 KVA transformer Sets 1
Cable Trench, Duct Bank, Conduit and Hand hole and cable trays/cover slab to complete the
20.3 LS
specified job
20.3.1 Drains system including RCC slab cover:
20.3.2 Section A-A (300 mm wide X depth up to 600 mm) RM 200
20.3.3 Section C-C (600 mm wide X depth from 900 mm) RM 200
20.3.4 Section D-D (750 mm wide X depth from 1200 mm) with RCC cover slab RM 200
Providing and laying NP2, 150 mm internal diameter perforated RCC hume pipes for drainage works
20.3.5 RM 1500
in switchyard area at 5 meter interval with water collection pits including RCC cover slab.
Annex-5
Estimated
S. No. Item Description
Unit Quantity
20.4 Lightning/Earth Mast Nos 1
Contruction of Regular small gate (Single door) attached with main boundary wall Gate as
20.5 LS
per technical specification
20.6 Construction of Boundary wall:
20.6.1 Excavation of soft clay and silty soil including disposal up to 10 M lead and 1.5 M (minimum) lift Cu.M 1200
20.6.2 Earth works in backfilling Cu.M 1100
20.6.3 Stone soiling works in foundation Cu.M 150
20.6.4 Cement Concrete works
20.6.5 C10 Plain cement concrete (1:3:6) in foundation Cu.M 100
C20 Plain cement concrete (1:2:4) in top of stone masonry, column of main gate, in bed level of
20.6.6 Cu.M 120
hume pipe for cross drainage work etc
Cutting bending, placing as per drawing and binding of steel reinforcement bar for RCC works
20.6.7 Kg 800
including supply of all materials and hulage tp to 30 M
Construction of wooden form for RCC column including supply of all materials, dismantling and
20.6.8 Sq.M 170
hulage up to 30 m.
20.6.9 Stone masonry in drain around the compound wall( 1:4 cement sand mortar) Cu.M 2000
20.6.10 First class brick work( 1:4 cement sand mortar) Cu.M 250
20.6.11 Cement pointing and plaster work
20.6.12 20 mm thick cement plaster in inside of brick wall in 1: 4 cement sand mortar Sq.M 1000
20.6.13 12.5 mm thick cement plaster in outside of brick wall in 1:4 cement sand mortar Sq.M 1100
20.6.14 Flushed rulled cement pointing work in outside of stone masonry in 1:2 cement sand mortar Sq.M 1300
Fabrication of fencing with 50 mm dia iron black pipe post erecting in spacing of 2/2 m c/c
20.6.15 connecting by 25*25*4 mm angle frame and fitting 10 SWG GI chain link of 2"*2" jmesh and welding Sq.M 750
of 3*20 mm grill of height 0.15mm
Construction of gate of compound with fixing 16 guage iron sheet in frame angle 50*50*5 mm
20.6.16 Kg 600
external and 40*40*5 internal as per drawing
20.7 BULIDING:
20.7.1 Control building as per specification and drawing (16 x 20 m 2) LS 1
20.7.2 Staff Quarter building as per specification and drawing (11.5 x 20 m2) LS 1
20.7.3 Guard cum Store Building as per specification and drawing:(6.5 x 22.5 m2) LS 1
Annex-5

Estimated
S. No. Item Description
Unit Quantity
20.8 MISCELLANEOUS WORKS:
Clearing and stripping of substation area as per specification including new bays at Dungesangu
20.8.1 LS 1
substation
20.8.2 Exploration works for soil strength of foundations including laboratory tests locations 6
20.8.3 Soil resistivity test lot 1
Site grading with earth filling by borrow pit earth including compaction and leveling etc all to
20.8.4 Cu.M 2000
complete the specified works as per technical specification
20.9 Crushed rock surfacing as per technical specification on switchyard are
20.9.1 Fine Sand filling (100 MM) Cu.M 800
20.9.2 Crushed rock surfacing Sq.M 8000
20.9.3 Asphalt Road as per technical specification Sq.M 1400
20.9.4 Water supply system including testing of water quality LS 1
20.9.5 Under ground water tank including motor/s and motor house house LS 1
20.10 Protection works:
20.10.1 Brick masonary works (1:4) Cu.M 75
20.10.2 Reinforcement contrete M20 (RCC including reinforcement steel) Cu.M 40
20.10.3 Stone masonary works including PCC on the top (1:4) Cu.M 100
20.10.4 Gavion work Cu.M 90
21 BAY EXPANSION WORKS AT DUNGESAGU SS
PART - B: OWNER ASSESSED QUANTITIES FOR DUNGESANGU SS

21.1 145 kV AIS Equipments:


CIRCUIT BREAKERS & SWITCHGEARS
21.1.1 145 kV, 1250 A, 40 kA, 3 Phase, SF6 circuit breakers complete with all accessories Sets 2
DISCONNECTING SWITCHES
21.1.2 145 kV, 3 Phase, center break disconnecting switch with grounding switch Sets 2
21.1.3 145 kV, 3 Phase, center break disconnecting switch with out grounding switch Sets 4
21.2 INSTRUMENT TRANSFORMERS:
145 kV, 8800pF, 50 VA, 132/√3 /110/√3 kV, Class 0.2/3P Capacitor Voltage Transformer complete
21.2.1 Nos 6
with all accessories as per specification
21.2.2 145 kV, 50 VA, 1200 A with 120 % extended rating current transformer Nos 6
Annex-5
Estimated
S. No. Item Description
Unit Quantity
21.3 LIGHTNING ARRESTORS:
21.3.1 120 kV, 10 kA Surge arrester (1 phase) including discharge counter Nos 6
21.4 CONTROL AND RELAY PANEL (WITH SUBSTATION AUTOMATION SYSTEM)
21.4.1 132 kV line control and relay panel complete with all accessories as per technical specifications Sets 2
21.5 1.1 kV GRADE LOW VOLTAGE CABLES
21.5.1 Power Cables (PVC) LS 1
21.5.2 Control Cables (PVC) LS 1
21.5.3 Cable glands, lugs for Power & Control cables LS 1
21.6 GROUNDING
Galvanized E.H.S. steel wires of size 7/3.35 for lightning shield wire in take-off and internal
21.6.1 structures complete with all accessories LS 1
Earthing of substation with conductors (of same size used in underconstruction substation),
21.6.2 electrode, grounding materials complete with all accessories LS 1

21.7 Bus post Insulator:


21.7.1 132 kV Bus post insulators (Minimum) Nos 12
21.8 ERECTION & MISCELLANEOUS MATERIALS
132 kV insulator strings, Disc insulator & accessories to complete the specified scope of works
21.8.1 LS 1
including for line tower
132 kV hardware, clamp, connectors & accessories to complete the specified scope of works
21.8.2 LS 1
including for line tower
ACSR conductors and accessories to complete the specified scope of works (The conductor should
21.8.3 be same as used in TL) LS 1
Main Tubular bus, branch buses, connectors, expansion joint including all other accessories
21.8.4 required to complete 132 kV double bus-bar configuration (Minimum Outer diameter and thickness LS 1
of main bus 100.0 and 7.0 mm respectively and that of branches 75.0 & 5.0 mm)
21.9 Illumination System
21.9.1 Outdoor Switchyard, Substation area, Street lighting etc as per technical specification LS 1
22 SUBSTATION AUTOMATION/ COMMUNICATION / SCADA (Based on IEC 61850)
22.1 SUBSTATION AUTOMATION SYSTEM:
Inclusion of complete Substation automation system including hardware and software for the
22.1.1 substation & remote control stations alongwith associated equipments for the followings as per
Technical Specification.
22.1.2 132 kV System Bays 2
Annex-5

Estimated
S. No. Item Description
Unit Quantity
Integration of new bays all under present scope with the SCADA of SIEMENS (SINAUT Spectrum)
22.1.3 at Load Dispatch Centre, Kathmandu including supply of Hardware, Software, accessories etc. as LS 1
per TS Section Project.
22.2 COMMUNICATION AND SCADA
22.2.1 Digital Protection Coupler Nos 2
Extension and interfacing of existing Communication Panel/equipment including Ethernet tributaries
card Termination Equipment (Drop/Insert Multiplexer, Subscriber Line Interface Cards, Equipment
22.2.2 LS 1
Cabinets complete in all respects including establishment of Fibre Optic (FO) links for far end
substation/s (Papung, Mewa hub SS) as per technical specifications
22.2.3 Optical Distribution Frame complete in all respects as per technical specifications LS 1
Optical Approach Cable -24 pair Fibre (DWSM -G.652D) along with Installation hardware set for
22.2.4 LS 1
above 24 Fibre, Fibre Optic Approach Cable complete in all respects as per technical specifications
23 CIVIL WORKS
Steel structure for post, beam and equipment supporting frame complete with bolts, fastner,
23.1
pack washer, nuts, guest paltes and all accessories: (Extension works for 132 side)
23.1.1 132 kV take off gantry structures Bays 2
23.1.2 132 kV internal gantry structures gantry structure Bays 2
23.1.3 132 kV SF6 gas circuit breaker Sets 2
23.1.4 132 kV disconnecting switch with earth switch Sets 2
23.1.5 132 kV disconnecting switch with out earth switch Sets 6
23.1.6 132 kV capacitor voltage transformer Nos 6
23.1.7 132 kV current transformer Nos 6
23.1.8 120 kV surge arrestor Nos 6
23.1.9 132 kV Bus post insulator Nos 12
24 132 kV Double circuit Dead end Towers Nos 2
Concrete Foundation for equipments and Steel Structures complete with excavation,
24.1
backfilling, form works, lean concrete concrete works and reinforcement bars:
24.1.1 132 kV take off gantry structures Bays 2
24.1.2 132 kV internal gantry structures gantry structure Bays 2
24.1.3 132 kV SF6 gas circuit breaker Sets 2
24.1.4 132 kV disconnecting switch with earth switch Sets 2
24.1.5 132 kV disconnecting switch with out earth switch Sets 6
Annex-5

Estimated
S. No. Item Description
Unit Quantity
24.1.6 132 kV capacitor voltage transformer Nos 6
24.1.7 132 kV current transformer Nos 6
24.1.8 120 kV surge arrestor Nos 6
24.1.9 132 kV Bus post insulator Nos 12
24.2 132 kV Double circuit Dead end Towers Nos 2
24.2.1 Cable Trench, Duct Bank, Conduit and Hand hole and cable trays to complete the specified job Lot 1
24.2.2 Drains system including RCC slab cover Lot 1
Providing and laying NP2, 150 mm internal diameter perforated RCC hume pipes for drainage works
24.2.3 RM 500
in switchyard area at 5 meter interval with water collection pits including RCC cover slab.
24.3 MISCELLANEOUS WORKS:
24.3.1 Clearing and stripping of substation area as per specification including new bay at Parsa substation LS 1
Site grading with earth filling by borrow pit earth including compaction and leveling etc all to
24.3.2 CUM 1000
complete the specified works as per technical specification
24.4 Crushed rock surfacing as per technical specification on switchyard are
24.4.1 Fine Sand filling (100 MM) Cu-M 200
24.4.2 Crushed rock surfacing Sq-M 2000
24.4.3 Asphalt Road as per technical specification Sq-M 200
24.4.4 Supplying and laying of 600 mm dia NP3 hume pipe in cross drainage and cable trench work RM 50
24.5 Protection works:
24.5.1 Brick masonary works (1:4) Cu-M 50
24.5.2 Reinforcement contrete M20 (RCC including reinforcement steel) Cu-M 50
24.5.3 Stone masonary works including PCC on the top (1:4) Cu-M 50
24.5.4 Gavion work Cu-M 50