IO Summary Shared

This document provides a list of HVAC system components at Midas Hospital in Nagpur with descriptions and quantities. It includes items such as water cooled chillers, hot water generators, ventilation fans, TFA units, and air handling units. For each item, it specifies the point addresses for monitoring and controlling parameters like temperature, humidity, equipment status and alarms. It also calculates total point counts with 20% spares.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
333 views7 pages

IO Summary Shared

This document provides a list of HVAC system components at Midas Hospital in Nagpur with descriptions and quantities. It includes items such as water cooled chillers, hot water generators, ventilation fans, TFA units, and air handling units. For each item, it specifies the point addresses for monitoring and controlling parameters like temperature, humidity, equipment status and alarms. It also calculates total point counts with 20% spares.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 7

MIDAS HOSPITAL

AT
NAGPUR

Sr. No. Description AI AO DI DO Qty Remarks


A HVAC SYSTEM
A.1 Water Cooled Chiller (395 TRX 2 Nos.) 2
1 Chiller On/Off Command 2
2 Chiller On/Off Status 2
3 Chiller Trip Status 2
4 Chiller Auto/Manual Status 2
5 Common Supply Header Temperature monitoring 2 2 Immersion Temperature Sensor
6 Common Return Header Temperature monitoring 2 2 Immersion Temperature Sensor
Chiller isolation Motorised valves ON/OFF command &
7 2 2
status.
8 Condenser Pump On/Off Status 2 2 Water DP Switch
9 Condenser Pump On/Off Command 2
10 Condenser Pump Trip Status 2
11 Condenser Pump Auto/Manual Status 2
12 Cooling Tower Fan On/Off Command 2
13 Cooling Tower Fan On/Off Status 2
14 Cooling Tower Fan Trip Status 2
15 Cooling Tower Fan Auto/Manual Status 2
16 Cooling Tower Water Temperature 2 2 Immersion Temperature Sensor
17 Outside Air Temperature & Rh Monitoring 2 1 Outdoor T & Rh
18 Primary Pump On/Off Command 2
19 Primary Pump Trip Status 2
20 Primary Pump Auto/Manual Status 2
21 Primary Pump On/Off Status 2 2 Water DP Switch
22 Secondary Pump On/Off Command 2
23 Secondary Pump Trip Status 2
24 Secondary Pump Auto/Manual Status 2
25 Secondary Pump On/Off Status 2 2 Water DP Switch
Sub-Total 8 0 32 12
Spare - 20% 2 0 6 2
Total with Spare 10 0 38 14

A.2 Hot Water Generator (118 Kw X 2 Nos.) 2


1 Hot Water Generator On/Off Command 2
2 Hot Water Generator On/Off Status 2
3 Hot Water Generator Trip Status 2
4 Hot Water Generator Auto/Manual Status 2
5 Hot Water Generator Outlet Water Temperature 2 2 Immersion Temperature Sensor
6 Hot Water Generator Inlet water temperature 2 2 Immersion Temperature Sensor
7 Hot water pump On/Off command 2
8 Hot water pump run status 2 2 Water DP Switch
9 Hot water pump auto/man status 2
10 Hot water pump trip status 2
Sub-Total 4 0 12 4
Spare - 20% 1 0 2 1
Total with Spare 5 0 14 5

A.3 Ventilation System

A.3.1 Smoke Extraction System Fan Fresh Air Fans 3


1 Fan On/Off command 3
2 Fan On/Off status 3
3 Fan Trip status 3
4 Fan Auto/Manual status 3

A.3.2 Smoke Extraction System Fan Exhaust Air 3


1 Fan On/Off command 3
2 Fan On/Off status 3
3 Fan Trip status 3
4 Fan Auto/Manual status 3

Sub-Total 0 0 18 6

IBMS-IO SUMMARY 1/7


MIDAS HOSPITAL
AT
NAGPUR

Spare - 20% 0 0 4 1
Total with Spare 0 0 22 7

A.4 TFA Units VFD 2


1 TFA On/Off Command 2
2 TFA Motor On/Off Status 2
3 TFA Auto/Manual status 2
4 TFA's VFD Command 2
5 DP Switch for TFA Filter status (Pre & Fine Filter) 4 4 DP Switch
6 Supply Air Duct Temperature Monitoring 2 2 Duct Temperature Sensor
Sub-Total 2 0 8 4
Spare - 20% 0 0 2 1
Total with Spare 2 0 10 5

A.6 Air Handling Units (Including Floor Mounted & Ceilling Suspended)
A.5.1 AHU with 1 Filters 6
1 AHU On/Off Command 6
2 AHU On/Off Status 6
3 AHU Auto/Manual Status 6
4 DP Switch for Filter status (Pre Filter) 6 6 DP Switch
5 VFD Speed Modulation Command 6
6 Supply Air Duct Temperature Sensor 6 6 Duct Temperature Sensor
7 Return Air Duct Temperature & Rh Sensor 12 6 Duct Temperature & Rh Sensor
8 Chilled Water Valve Control 6 6
9 Hot Water 2-Way Valve Control 6 6
10 Chilled Water Inlet Temperature Monitoring 6 6 Immersion Temperature Sensor
11 Chilled Water Outlet Temperature Monitoring 6 6 Immersion Temperature Sensor
Sub-Total 42 12 18 12
Spare - 20% 21 6 9 6
25.2 7.2 10.8 7.2
Total with Spare 63 18 27 18

A.5.2 AHU with 2 Filters 23

1 AHU On/Off Command 23


2 AHU On/Off Status 23
3 AHU Auto/Manual Status 23
4 DP Switch for Filter status (Pre & Fine Filter) 46 46 DP Switch
5 VFD Speed Modulation Command 23
6 Supply Air Duct Temperature Sensor 23 23 Duct Temperature Sensor
7 Return Air Duct Temperature & Rh Sensor 46 23 Duct Temperature & Rh Sensor
8 Chilled Water Valve Control 23 23
9 Hot Water 2-Way Valve Control 23 23
10 Chilled Water Inlet Temperature Monitoring 23 23 Immersion Temperature Sensor
11 Chilled Water Outlet Temperature Monitoring 23 23 Immersion Temperature Sensor
Sub-Total 161 69 92 23
32.2 13.8 18.4 4.6

Spare - 20% 32 14 18 5
Total with Spare 225.2 96.8 128.4 32.6

A.5.3 AHU with 3 Filters 4


1 AHU On/Off Command 4
2 AHU On/Off Status 4
3 AHU Auto/Manual Status 4
4 DP Switch for Filter status (Pre, Fine & HEPA Filter) 12 12 DP Switch
5 VFD Speed Modulation Command 4 4
6 Supply Air Duct Temperature Sensor 4 4 Duct Temperature Sensor
7 Return Air Duct Temperature & Rh Sensor 8 4 Duct Temperature & Rh Sensor
8 Chilled Water Valve Control 4 4
9 Hot Water 2-Way Valve Control 4 4
10 Chilled Water Inlet Temperature Monitoring 4 4 Immersion Temperature Sensor

IBMS-IO SUMMARY 2/7


MIDAS HOSPITAL
AT
NAGPUR

11 Chilled Water Outlet Temperature Monitoring 4 4 Immersion Temperature Sensor


Sub-Total 28 12 20 4
14 6 10 2
Spare - 20% 16.8 7.2 12 2.4
Total with Spare 58.8 25.2 42 8.4

B ELECTRICAL SYSTEM
1 OT Panel - Breaker On/Off Status. 7
2 Utility Panel - Breaker On/Off Status. 1
3 Fire Emergency Panel - Breaker On/Off Status. 1
4 LT Panel I/c breaker On/Off Status. 1
5 UPS Input Panel On/Off Status. 1
6 UPS Output Panel On/Off Status. 1
7 ATS panel On/Off Status. 1
8 Medical Equipment Panel On/Off Status. 1
9 Floor Panel On/Off Status. 8
Sub-Total 0 0 22 0
Spare - 20% 0 0 4 0
Total with Spare 0 0 26 0

C FIRE FIGHTING SYSTEM


1 Sprinkler Fire pump On/Off status. 1
2 Jockey pump On/Off status. 2
3 Jockey pump trip status. 2
4 Diesel engine driven pump ON/OFF status. 1
5 Hydrant Fire Pump On/Off Status 1
6 Terrace Booster Pump On/Off status 2
7 Terrace Booster Pump Trip status 2
Sub-Total 0 0 11 0
Spare - 20% 0 0 2 0
Total with Spare 0 0 13 0

D WATER MANAGEMENT SYSTEM


1 Domestic tank High/ Low Monitoring 1 1 Level Transmitter
2 Domestic water pump ON/OFF status. 2
3 Domestic water pump trip status. 2
4 Domestic water pump Auto / Manual status. 2
5 Flushing tank High/ Low monitoring 1 1 Level Transmitter
6 Flushing water pump ON/OFF status. 2
7 Flushing water pump trip status. 2
8 Flushing water pump Auto / Manual status. 2
9 Booster Pump ON/OFF status. 2
10 Booster Pump trip status. 2
11 Booster Pump Auto / Manual status. 2
Sub-Total 0 0 20 0
Spare - 20% 0 0 4 0
Total with Spare 0 0 24 0

FINAL HARD IO's 301 122 317.4 72

E SOFT INTEGRATION PARAMETERS


Sr. No. Description Qty Per Pts Total Pts Protocol Remarks
1 Water Meter 1 2 2 RS485
2 FAS 1 1050 1050 Bacnet IP /Modbus
3 Energy Meters 22 10 220 RS485/Modbus
4 Lifts 7 9 63 - Need to Confirm From Lift Vendor
5 Conventional UPS 2 15 30 Modbus/ SNMP
FINAL SOFT IO's 1365

Sensors & Field Devices Qty


DP Switch For Filter 68
Water DP 8
Return Air Duct T+Rh 33

IBMS-IO SUMMARY 3/7


MIDAS HOSPITAL
AT
NAGPUR

SA Duct Temp 35
Immersion Temp Sensor 76
Outdoor T & Rh 1
Water DPT 2
Level Transmitter 2

IBMS-IO SUMMARY 4/7


MIDAS HOSPITAL
AT
NAGPUR

CG REMARK

CPM Hard Point


DDC has not
considered as
per the BOQ

IBMS-IO SUMMARY 5/7


MIDAS HOSPITAL
AT
NAGPUR

3RD FL - 1 NO. + TERRACE FL - 1 NO

GR. FL. 3NOS.+F.FL. 2NOS+S.FL. 1NO

GF-5NOS. + FF-2NOS + SF-5NOS + TF-


8NOS + 4TH FL - 1NO + 5TH FL - 1NO +
TE FL. - 1NO

SECOND FLOOR OT 1,2,3,4

IBMS-IO SUMMARY 6/7


MIDAS HOSPITAL
AT
NAGPUR

IBMS-IO SUMMARY 7/7