We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
You are on page 1/ 46
Generator Protection |
5.1 Introduction
The generators used in the power system are the alternators which produce very
high ac. voltages. The protection of generators is very much complex due to the
following reasons,
nd
1. The generators are very large machines producing very high voltages
connected to busbars.
Various other equipments are always associated with the generators. Such
equipments are prime movers, excitation systems, vollage regulators, cooling
systems etc. Thus protection of generators must consider the presence of these
other equipments also,
3. The generators are v
costly, expensive and very important factor in a power
system, The protection scheme must be such that it should not shut off the
generators as far as possible, The shut off generators result in a power
shortage.
All these factors make the design of protection scheme for the generator, very
much complex
Before studying the various protection schemes for the generators, let us discuss
various faults which can occur associated with the generators,
5.2 Generator Faults
The various fatilis which can occur associated with a generator can be classified as,
1. Stator faults : The faults associated with the stator of the generator.
2 Rotor faults : The faults associated with the rotor of the generator.
3. Abnormal running conditions : This includes number of abnormal conditions
which may occur in practice, from which the generator must be protected
Let us discuss these faults in detail
6-1)Protection and Switchgear 5-2 Gonorator Protection
5.2.1 Stator Faults:
The stator faults means faults associated with the three phase armature windings
of the generator. These faults are mainly due to the insulation failure of the armature
windings. The main types of stator faults are,
1
«¢ to carth faults
hase to phase faults
3. Inter-turn faults involving turns of same phase winding.
The most important and common fault is phase to earth fault. The other two are
not very common while inter-turn fault is very difficult to detect
5.2.4.4 Phase to Earth Faults
These faults mainly occur in the armature slots. The faults are dangerous and can
cause severe damage te the expensive machine. The fault currents less than 20 A cause
egligible burning of core if machine is tripped quickly, But if the fault currents are
high, severe burning of stator core can take place. This may lead to the requirement of
replacing the laminations which is very costly and time consuming. So to avoid the
damage due to phase to earth faults, a separate, sensitive earth fault protection is
necessary for the generators alongwith the earthing resistance.
5.2.1.2 Phase to Phase Favits
The phase to phase faults means short circuit between two phase windings. Such
faults are uncommon because the insulation used between the coils of different phases
in a slot is large. But once phase to earth fault occurs, due to the over heating phase
to phase fault also may occur. This fault is likely to occur at the end connections of
the armature windings which are overheating parts outside the slots. Such a fault
causes severe arcing with very high temperatures, This may lead to melting of copper
and fire if the insulation is not fire resistant,
5.2.1.3 Stator Inter-Turn Faults
The coils used in the altemators are generally multitum coils. So short circuit
between the tims of one coil may eccur which is called an inter-turn fault. This fault
occurs due to current surges with high value of (L di/dt) voltage across the tums. But
if the coils used are single turn then this fault can not occur. Hence for the large
machines of the erder of 50 MVA and more, it is a normal practice to use single turn
coils. But in some countries, multiturn coils are very commonly used where protection
against inter-turn faults is must.Protection and Switchgear 5-3 Generator Protection
5.2.2 Rotor Faults
The rotor of an alternator is generally a field winding as most of the alternators
are of rotating field type. The field winding is made up of number of turns. So the
conductor to earth faults and short circuit between the tums of the field winding, are
the commonly occurring faults with respect toa rotor. These
faults
e caused
the severe mechanical and thermal stresses, acting on the field winding insulation.
The field winding is generally not grounded and hence single line ta ground fault
does not give any fautt current. A second fault to earth will short circuit the part of
the field winding and may there by produce an unsymmetrical field system. Such an
unsymmetrical system gives rise to the unbalanced forces on the rotor and results in
excess pressure on the bearings and the shaft distortion, if such a fault is not cleared
very early. So it is very much necessary to know the existence of the first occurrence
cof the earth fault s0 that corrective measures can be taken before second fault occurs,
The unbalanced loading on the generator is responsible to produce the negative
sequence currents, These currents produce a rotating magnetic field which rotates in
opposite direction to that of rotor magnetic field. Due to this field, there is induced
em. in the rotor winding. This causes overheating of the rotor.
Rotor earth fault protection and rotor temperature indicators
are provided to large rating generators.
re the essential and
§.2.3 Abnormal Running Conditions
In practice there are number of situations in which generator is subjected to some
abnormal running conditions. The protection must be provided against the abnormal
conditions, These abnormal conditions include
1. Overloading
2. Overspeeding
Unbalanced loading
3
4. Overvoltage
5. Failure of prime mover
6
Loss of excitation (Field failure)
Cooling syste failure
5.2.3.1 Overloading
Due to the continuous overloading, the overheating of the stator results. This may
increase the winding temperature. If this temperature rise exceeds certain limit, the
insulation of the winding may get damaged. The degree of overloading decides the
effects anct temperature rise. The overcurrent protection is generally set to very highProtection and Switchgear 5
‘Generator Protection
Je hence continuous overloads of less value than the setting cannot be sensed by
reurrent protection.
§.2.3.2 Overspeeding
In case of hydraulic generators a sudden loss of load results in overspeeding of
the generator. This is because the water flow to the turbine cannot be stopped of
reduced instantly. Generally a turbogovernor is provided to prevent the ovespeeding,
But if there is any fault in the turbine governor then the dangerous overspeeding may
take place, Hence it is necessary to supervise the working of turbine governor and
take some corrective measures if there is some fault in the governor.
5.2.3.3 Unbalanced Loading
The unbalanced loading of the generator results in the circulation of negative
sequence currents. These currents produce the rotating magnetic field. This rotating
magnetic field rotates at the synchronous speed with respect to rotor. The direction of
rotation of this magnetic field is opposite to that of rotor. Hence effectively the relative
speed between the two is double the synchronous speed.
Thus the em. gets induced, having double the normal frequency, in the rotor
winding. The circulating currents due to the induced ¢.m.f. are responsible to overheat
the rotor winding as well as rotor stampings. Continuous unbalanced load more than
10% of the rated load causes tremendous heating which is dominant incase of
cylindrical rotor of truboaltemators
The reasons for the unbalanced load conditions are,
1. Occurrence of unsymmetrical faults near the generating station.
2. The failure of
phases,
cuit breaker near the generating station in clearing all the three
Negative sequence protection is important to prevent dangerous situations due to
negative sequence currents which are because of unbalanced load conditions.
5.2.3.4 Overvoltage
The overvoltages are basically due to the overspeeding of generators, Another
son for the overvoltages is the faulty operation of voltage regulators. Not only’ the
ternal overvoltages are dangerous but atmospheric surge voltages can also reach to
the generators, Such atmospheric surge voltages are generated by direct lighting
strokes to the aerial lines of high voltage system. Inductively and capacitively, these
surges can get transferred to the generator. To protect the generators from surge
voltages, the surge arresters and surge capacitors are often used.
At the time of restriking across the contacts of circuit breakers, the transient over
voltages get generated. Such surges are called switching surges and can be limited byProtection and Switchgear 5-5 Generator Protection
the uses of modern circuit breakers. R-C surge suppressors also help in reducing
switching surges. Another situation, when the transient overvoltages are generated, is
when the ares are grounded. During arcing grounds, the transient voltages having
amplitudes five times more than the normal line to neutral peak amplitude are
generated. Such transient voltages are dangerous and can be reduced by using
resistance earthing.
5.2.3.5 Failure of Prime Mover
The failure of prime mover results in motoring operation of synchronous
generator. The generator draws active power from the network and conti
at synchronous speed as a synchronous motor. This may lead to dangerous mechanical
e ng
of the steam turbine blades may result. To prevent this the reverse power protection
wes to run
nditions if allowed to persist for more than twenty seconds. The serious overhea
achieved by directional power relays is used.
5.2.3.6 Loss of Excitation
The loss of excitation or reduced excitation is possible due to the field failure ie
opening of field winding or due to short ci
exciter system,
ft in field or due to some fault in
Such loss of excitation results in loss of synchronism within a second and this
causes the increase in speed of the generator. Since power input to the machi
remains same, the generator starts working as an induction generator, drawing the
reactive power from the bus. The machine starts drawing an exciting current from the
system, which is equal to the full load rated value. This leads to the overheating of
the stator winding and the rotor body due to induced currents. The loss of excitation
may also lead to the pole slipping condition which results in the voltage reduction for
the output above half the rated load,
Loss of excitatien should not persist for long and corrective measures like
disconnection of altemator should be taken immediately. For this a tripping scheme
can be used which can trip the generator circuit breaker immediately when there is a
field failure.
5.2.3.7 Cooling System Failure
The {allure of cooling system also causes severe overheating to rise the
temperature above safe limit. This may lead to insulation failure, causing some other
faults to occur. The thermocouples or resistance thermometers are used in large
machines to sense the temperature. The corrective measures are taken whenever the
temperature exceeds the limit
Apart from the above dominant abnormal conditions, some conditions may exist
wiich are rare in practice, Such conditions are, wrong synchronization, localProtection and Switchgear 5-6 Generator Protection
overheating, leakage in hydrogen circuit, moisture in the generator winding, oxygen in
water circuit, vibrations, bearing currents, excessive bearing temperature etc.
5.3 Basic Differential Protection Scheme for Generators
A basic differential protection scheme used for the generators is shown in the
Fig. 5.1. It is known that the differential relay operates when the phasor difference of
two or more similar electrical quantities exceeds a predetermined value
Generator
ct. ‘wineang cr
External
faut
~~ pitferentis!
Fig. 5.1
Suppose the current | flows through the primary of CTs to the external fault. If
the twa CTs have same ratio, then no current will flow through the relay and it
remains inoperative.
relay
But now if an internal fault occurs at point X as shown in the Fig. 5.2, the current
flows through the fault from both the sides. The primary currents are [, and I; while
the secondary currents are i, and iy, So the current flowing through the relay will be
i; + ip Even some current flowing out of one side while a large current entering the
other side will cause the differential current. Such a current is responsible to operate
the relay
Different
relayProtection and Switchgear $-7 Generator Protection
‘Thus the relay current is proportional to the phasor difference between the
currents entering and leaving the protected circuit and if the differential current
exceeds the pickup value, the relay operates
This basic differential scheme has following disadvantages
1, This circuit operates inaccurately with heavy external faults.
2 The CTs may saturate and cause unequal secondary currents and the
difference of secondary currents may approach the pickup value to operate the
relay unnecessarily.
These disadvantages are overcome in the percentage differential relay.
§.4 Basic Percentage Differential Protection Scheme for Generators
This protection scheme is also called biased differential protection scheme. The
Fig. 5.3 shows the connections of the percentage differential relay, in such a protection
scheme.
Generator
winding
——— Operating
5 ' call
Restraining cot
Fig. 5.3 Percentage differential protection scheme
The fault occurs at point X and the primary currents in the circuit are 1, and I;
The CT, secondary currents are i, and i;. The current flowing through the operating
coil of the relay is i, ~ i While the current flowing through the restraining coil of the
relay is;
\
the restraining coil.
+2). This is because the operating coil is connected to the midpoint of
Thus if the number of tums of the restraining coil is N then i, flows through
N,N
im
vol
and i; flows through remaining N, The total ampere tums are eN
2Protection and Switchgear 5-8 ‘Generator Protection
4 | This is as good as the flow of current 2} through the entire restraining
coil
The operating characteristics
of such a biased differential
relay is shown in the Fig. 5.4
The characteristics shows that t
except at low currents, ratio of
differential operating current to
average restraining current is a
Operating currant
Operating region
ine
Nonoperating region
= ve torque
fixed percentage. Hence the
relay is called the percentage
differential relay
This basic percentage Resting
differential protection scheme current
forms the basis of _ the
practically very commonly used
percentage differential protection scheme for alternator stator windings. This popular
as Biased differential protection or Mers-Price protection
scheme is know
Let us discuss the details of Merz-Price protectis
n scheme for the three phase
ernator stator windings
5.5 Merz-Price Protection of Alternator Stator Windings
This is most commonly used protection scheme for the alternator stator windings.
The scheme is also called biased differential protection and percentage differential
protection
In this method, the currents at the two ends of the protected section are sensed
using current transformers. The wires connecting relay coils to the current transformer
secondaries are called pilot wires
Under normal conditions, when there is no fault in the windings, the currents in
the pilot wires fed from C.T. secondaries are equal. The differential current i) - iy
through the operating coils of the relay is zero, Hence the relay is inoperative and
system is said to be balanced.
When fault occurs inside the protected section of the stator windings, the
differential current i, - {, flows through the operating coils of the relay. Due to this
current, the relay operates, This trips the generator circuit breaker to isolate the faulty
section. The field is also disconnected and is discharged through a suitable impedance.
The Fij
star connected 4
5.5 shows a schematic arrangement of Merz-Price protection scheme for a
'
nator.Protection and Switchgear Generator Protection
‘iar sonnectes
sSlamalr stale cH.
‘weg a rota
Arena - eartng
on i
coreg
ol ¥
8
aot
wn 0.6.» Oporaing ont
RC. Restraining cot
CB Creat breaker
Peteeniags ——
(terete ralay
Fig. 5.5 Merz-Price protection for star connected alternator
The differential relay gives protection against short circuit fault in the stator
winding of a generator. The C.T.s are connected in star and are provided on both, the
eutgoing side and machine winding connections to earth side. The restraining coils are
energized from the secondary connection of C.T.s in each phase, through pilot wires
The operating, coils are energized by the tappings from restraining coils and the CT
neutral earthing connec
¢ delta connected alternator stator winding,
as shown in the Fig. 5.6.
Delta carmela abarsatae ex.
state vending a cata
= eaching
mewn |
OS —— Operating cot
RE —e Rosimining oot
CB = Creu oroaker
Percentage
‘amarentalrsiay
Fig. 5.6 Merz-Price protection for delta connected alternatorProtection and Switchgear
Generator Protection
The C.T.s on the delta connected machine winding side are conne
while the C.T.s at outgoing ends are connected in star. The restraining coils are placed
in each phase, energized by the secondary connections of C.T.s while the operating
coils are energized from the restraining coil tappings and the C.T. neutral earthing.
If there is a fault due to a short circuit in the protected zone of the windings, it
produces a difference between the currents in the primary windings of C.T.s on both
sides of the generator winding of the same phase, This results in a difference between
ndary currents af the two current transformers. Thus, under fault conditions,
a differential current flows through the operating coils which is responsible to trip the
relay and open the circuit breaker. The differential relay operation depends on the
relation between the current in the operating coil and that in the restraining coil.
the se
addition to the tripping of circuit breaker, the percentage differential relay trip
hand reset multicontact auxiliary relay. This auxiliary relay simultaneously initiates the
following operations,
L. Tripping of the main circuit breaker of generator
2 Tripping of the field circuit breaker
3. Tripping of the neutral circuit breaker if it is present
4. Shut down of the prime mover
Turn on of CO, gas if provided for safety of generator under faulty conditions,
6. Operation of alarm and for annunciator to indicate the occurrence of the fault
and the operation of the relay the field must be opened immediately otherwise
it starts feeding the fault.
When differential relaying is used for the protection, C.T's at both the ends of
generator must be of equal ratio and equal accuracy otherwise if the error is excessive,
wrong operation of the relay may result. The causes of unequal currents on both the
sides of C-T’s without any fault are ratio errors, unequal lengths of the leads, unequal
secondary burdens ete
This scheme provides very fast protection to the stator winding against phase to
phase faults and phase to ground faults. If the neutral is not grounded or grounded
through resistance then additional sensitive earth fault relay should be provided.
The advantages of this scheme are,
1. Very high speed operation with operating time of about 15 msec.
2. It allows low fault setting which ensures maximum protection of machine
windings.
3. It ensures complete stability under the most severe through and external faults.Protection and Switchgear 5-14 Generator Protection
4. It does not require current transformers with air gaps or special balancing
features.
5.6 Restricted Earth Fault Protection of Generator
Generally Merz-Price protection based on circulating current principle provides the
tion against intemal earth faults. But for large genes
tors, as tl
se are cos
nal protection scheme called restricted earth fault protection is provided
When the neutral is solidly grounded then the generator gets completely protected
against earth faults. But when neutral is grounded through earth resistance, then the
stator windings get partly protected against earth faults. The percentage of winding
protected depends on the value of eart
ing resistance and the relay setting,
In this scheme, the value of earth resistance, relay setting, current rating of earth
resistance must be carefully selected, ‘The earth faults are rare near the neutral point as
the voltage of neutral point with respect to earth is very less. But when earth fault
occurs near the neutral point then the insufficient voltage across the fault drives very
low fault current than the pick up current of relay coil. Hence the relay coil remains
inoperative. Thus 15 to 20% winding from the neutral side remains unprotected in this
scheme. Hence it is called restricted earth fault protec
protect 85% of the winding
jon. It is usual practice to
The restricted earth fault protection scheme is shown in the Fig,
Neutral
point
Restricted earth fault relay
Fig. 5.7 Restricted earth fault protection
Consider that earth fault occurs on phase B due to breakdown of its insulation to
earth, as shown in the Fig. 5.7. The fault current |, will flow through the core, frameProtection and Switchgear 5-12 Generator Protection
of machine to earth and complete the path through the earthing resistance, The C:T
secondary current |, flows through the operating coil and the restricted earth fault
relay coil of the differential protection. The setting of restricted earth fault relay and
setting of overcurrent relay are independent of each other. Under this secondary
current I, the relay operates to trip the circuit breaker. The voltage V\. is sufficient to
drive the enough fault current I, when the fault point x is away from the neutral
point
If the fault point x is nearer to the neutral point then the voltage Vp, is small and
not sufficient to drive enough fault current 1. And for this 1, relay cannot operate.
Thus part of the winding from the neutral point remains unprotected. To overcome
this, if relay setting is chosen very low to make it sensitive to low fault currents, then
wrong operation of rel
y may result, The relay can operate under the conditions of
he.
y through faults, inaccurate CTs, saturation of C.T.s ete. Hence practically 15% of
from
neutral point is kept unprotected, protecting the remaining 85% of
the winding against phase fo earth faults
5.6.1 Effect of Earth Resistance on % of Winding Unprotected
Let us see the effect of earth resistance on the % of the winding which remains
unprotected
Consider the earth
resistance R used to limit earth
fault current as shown in the
Fig. 58
The value of the resistance
K limits the earth fault current
If the resistance R is very
small i.e, the neutral is almost
solidly grounded, then the fault
current is very high. But high
Earth fault currents are not desirable
resistance hence small R is not preferred
Fig. 8.8 for the large machines
For low resistance R, the value of R is selected such that full load current passes
through the neutral, for a full line to neutral voltage V.
In medium resistance R, the earth fault current is limited to about 200A for full
line to neutral voltage V, for a 60 MW machine.
In high resistance R, the earth fault current is limited to about 10 A. This &
for distribution transformers and generator-transformer units.
usedProtection and Switchgear $-13 Gonerator Protection
Now higher the value of earth resistance R, less is the earth fault current and less
percentage of winding gets protected. Large percentage of winding remains
unprotected.
Let V = Full line to neutral voltage
1 = Full lond current of largest capacity generator
R = Earth resistance
Then the value of the resistance R is.
Vv
Req
And the percentage of windi protected
given by,
| % of winding unprotected = ®!s 100
ue
where 1, = Minimum operating current in the primary of CT
If relay setting used is 15% then 1, is 15
machine and so on.
€
protect
of the full load current of the largest
ge of windings of small capacity ma
nes running parallel get
iter percenta
4
‘amp Example 5.1: A generator is protected by restricted earth finult protection. ‘The
are 13.2 kV, 10 MVA. The percentnge of winding protecied against
phase to ground fiult is 85%, The relay setting is such thot it trips for 20% ont of
balance. Calculate the resistance to be added in the neutral to ground connect
Solution : ‘The given values,
Vo = 12kV Ra
ng = 10 MVA
From rating, calculate the full load current,
Rating in VA 10108
hs = a
V3 Vy V3*13.2«108
= 437.386 A
Relay setting is 20% out of balan
¢ i. 20% of the rated current activates the relay
+ 20 ay
L 4387 .386x 87.477 A
Minimum operating currentrotection and Switchgea
5-14 Generator Protection
V = Line to neutral voltage
°% of winding u
R= 13.0680
mp Example 5.2: A star connected 3 phase, 12 MVA, T1 KV alternator has a phase
reactance of 10%. It is protected by Mera-Price circulating current scheme which is set
to operate for fault current not less than 200 A. Calculate the value of earthing
resistance to be provided im order to ensure that only 15% of the alternator winding
remains unprotected
Solution : The given values are,
V, nkV Rating = 12 MVA
Rating = V3 I,
12«10® = V3«11%109 x1,
12x10
=
¥3x 11x 10%
= 629.8366 A = I = rated current
_ Hx
= 29 V
Gi 6350.85:
‘% Reactance = —>x100
where
reactance per phase
and 1 = rated current
629.8366 X
6350, 8529
6
®
100
xX = 100830
Reactance of unprotected windingProtaction and Switchgear 5-45 Generator Protection
(@e of unprotected winding) « (X)
15
79572-0083
= 015122
v = voltage induced in unprotected winding
15 5
= =x V = 0.15% 6350,8529
709% V = 0-15%6350.852:
= 992.6279 V
i = Fault current
= 200A
Z = Impedance offered to the fault
v _ 982.6270
i 200
4.76310 (l}
Z = f+] (reactance of unprotected winding)
Z = rej O15I2R
12Z| = Je? (0.15127 » Q)
Equating (1) and 2),
47631 = fr? + (0.1512)?
22.6875 = r* + 0.02286
P= 266d
r= 476079
This is the earthing resistance required.
5.7 Unrestricted Earth Fault Protection
The unrestricted earth fault protection uses a residually connected earth fault relay.
It consists of three C-T.s, one in each phase. The secondary windings of these CT's are
connected in parallel, The earth fault relay is connected across the secondaries which
carries a residual current. The scheme is shown in the Fig. 5.9-
When there is no fault, under normal conditions, vector sum of the three line
currents is zero, Hence the vector sum of the three secondary currents is also zero.Protection and Switchgear
Earthing
resistance:
To tip creult
Fig. 5.9 Unrestricted earth fauit protection
. and I, are €.T, secondary currents then under normal conditions we
i,tiget, = 0
The sum of the three currents is residual current Ig, which is zero under normal
conditions.
The earth fault relay is connected in such a way that the residual current flows
through the relay operating coil. Under normal condition, residual current is zero se
relay does not carry any current and is inoperative. However in presence of earth fault
condition, the balance gets disturbed and the residual current Ips is no more zero. If
this current is more than the pickup value of the earth fault relay, the relay operates
and opens the circuit breaker through tripping of the trip circuit
In the scheme shown in the Fig. 5.9, the earth fault at any location near or away
from the location of C-T's can cause the residual current. Hence the protected zone is
not definite. Such a scheme is hence called unrestricted earth fault protection.
5.8 Balanced Earth Fault Protection
In practice for small rating alternators, the neutral ends of the three phases are
connected to a single point. Hence it is not possible to introduce C.T. in each phase on
neutral side as required in Merz-Price protection. In such cases, the balanced earth
fault protection can be used.Protection and Switchgear 5-17 Generator Protection
The balanced earth fault protection is shown in the Fig. 5.10.
Generator
Jnvoes, er
casi Popp
Fig. 5.10 Balanced earth fault protection
At the outgoing side, the three C-T-s are connected in parallel as are connected in
unrestricted earth fault protection. A single CT. is connected on the neutral side in the
pilot wire connecting neutral of alternator fo earth. The neutral earthing is achieved
through the earthing resistance. A relay is connected across the C-T. secondaries
Under norma! conditions, the alternator line currents add to zero. Hence the vector
sum of the currents through the secondaries of C.T. ig also zero. Thus no current flows
igh the relay and as ne
tral carries zero current hence no current is supplied to
lay is inoperative
If the fault appears at F, at a position outside the protected zone then the sum of
the alternator line currents is exactly equal to the current in the neutral. Thus zero
current flows through the relay is inoperative
But if the fault occurs at F, which is the protected zone t
alternator line currents is different than the current through neutral side current
transformer, Hence a residual current flows through the relay. If this is greater than
the pickup value of the relay, the relay operates. This trips the tripping circuit,
opening the circuit breaker
vector sum of
By this scheme, the protection against earth faults is restricted to the region
between the neutral and the position where line current transformers installed.Protection and Switchgear 5-18 Generator Protection
5.9 100% Earth Fault Protection
AS seen uptill now, no protection scheme is in a position to give complete
protection to the stator of generator against earth faults. The maximum protection
achieved is upto 85 to 90% from the schemes discussed uptitl now
But in modern days it is possible to provide 100% earth fault protection to the
jor of the generator. It uses a coupling transformer and the coded signal current:
scheme is shown in the Fig, 5.11
of 125 Hz
Fig. 5.11 100% earth fault protection
A coupling transformer is connected between the earth and the earthing resistance
R ie, in neutral to ground circuit, The primary of the coupling transformer is excited
by coded signal current source. This coded signal current has a frequency of 12.5 Hz.
This current is continuously injected into the generator stator winding through the
secondary of the coupling transformer.
During the normal condition the signal current injected into the stator flows
through stray capacitance of the generator and directly connected system. But when
earth fault occurs,
.e stray capacitance is bypassed. This increases the monitoring
current. This increase is measured by a measuring device. Depending upon this
measurement an immediate corrective action is taken.
This scheme gives the protection of 15 to 20% of stator winding from the neutral
side, the portion which is unprotected by Merz-Price protection. The remaining
portion is protected by Mere-Price protection. Overall 100% of stator winding gets
protected against earth faultsProtection and Switchgear 5-19 Generator Protection
$.10 Stator Protection Against Interturn Faults
The Merz-Price protection system gives protection against phase to phase faults
and earth faults. It does not give protection against intertumn faults. The interturn fault
is a short circuit between the turns of the same phase winding. Thus the current
produced due te such fault is a local circuit current and it does not affect the currents
entering and leaving the winding at the two ends, where CTs are located. Hence
Merz-Price protection cannot give protection against interturn faults.
In single turn generator, there is no question of interturn faults but in multiturn
generators, the interturn fault protection is necessary. So such interturn protection is
provided for multiturn generators such as hydroelectric generators. These generators
have double winding armatures, This means, each phase winding is divided into two
halves, due to the very heavy currents which they have to carry. This splitting of
single phase winding into two is advantageous in providing interturn fault protection
to such hydroelectric generators,
The Fig. 5.12 shows the interturn fault protection scheme used for the generator
with double winding armatures.
GL.
Two parallel paths.
Siem phase P-———> Phase
winding
Fig. 5.12 Interturn fault protectionProtection and Switchgear §-20 Generator Protection
The scheme uses cross differential principle, Each phase of the generator is doubly
wound and split into two parts $, and $; as shown in the Fig. 5.12. The current
transformers are connected in the two parallel paths of the each phase winding. The
secondaries of the current transformers are cross connected. The current transformers
work on circulating current principle. The relay is connected across the cross
connected secondaries of the current transformers.
Under normal operating, conditions, when the two paths are sound then currents
in the two parallel paths S, and S, are equal. Hence currents in the secondaries of the
current transformers are also equal. The secondary current flows round the loop and
is same at all the points. Hence no current flows through the relay and the relay is
inoperative
If the short cireuit is developed between the adjacent turns of the part S, of the
winding say then currents theough S; and S; no longer remain same, Thus unequal
currents will be induced in the secondaries of the current transformers. The difference
of these currents flows through the relay R. Relay then closes its contacts to trip the
circuit breaker which isolates the generator from the system.
Such an interturn fault protection system is extremely sensitive but it can be
vound armatures.
applied to the generators having doubly
5.11 Rotor Earth Fault Protection
The rotor circuit of the alternator is not earthed and dc. voltage is imposed on it:
And hence single ground fault in rotor does not cause circulating current to flow
through the rotor circuit. Hence single ground fault in rotor does not cause any
damage to it. But single ground fault causes an increase in the stress to ground at
*r points in the field winding when voltages are induced in the rotor due to
jents. Thus the probability of second ground fault increases.
If the second ground fault occurs then part of the rotor winding is bypassed and
the currents in the remaining portion increase abruptly. This causes the unbalance of
rotor circuit and hence the mechanical and thermal stresses on the rotor. Due to this,
rotor may get damaged. Sometimes damage of bearings and bending of rotor shaft
takes place due to the vibrations, Hence the rotor must be protected against earth
fault
Method 1; In this method a high resistance is connected across the rotor circuit. It
is provided with centre tap and the centre tap point is connected to the ground
through a sensitive earth fault relay as shown in the Fig. 5.13.Protection and Switchgear Genorator Protection
High resistance:
+ Sensitive
‘earn
Loot Bt tear
Brete 2 slay
Fiat warding oe
5,13 Rotor earth fault protection
Except the centre point, the earth fanlt relay detects the earth faults for most of the
rotor circuit. Thus most of the rotor winding part is protected against the earth faulis
Method 2 : The modem method of providing earth fa
injection or a.c, injection. The scheme is shown in the Fig. 5.14
it protection includes dic
A small dc. power
supply is connected to
the field circuit. A fault
detecting sensitive
relay and the resistance
Excher
Generator
ees ernie
are also connected in
series with the circuit
This high resistance
limits the current
through the circuit.
Resistance for current lening
Sensitive
A fault at any relay
point on the field
circuit will pass a
current of — sufficient
usilary
magnitude through the | 5
relay to cause its
operation. The dc.
supply is preferred and
simple to use and it
has no problem of the =
leakage currents. In
case of ac. injection, Fig. 5.14 Rotor earth fault protection
the high resistance is
replaced by a capacitor.Protection and Switchgear 5-22
The earth fault relays are instantaneous in operation and are connected to an
alarm circuit for indication and to take the proper action. This is because, a single
ground fault does not require an immediate action of isolating the generator.
5.12 Protection Against Loss of Excitation
The lose of excitation of the generator may result in the loss of synchronism and
slightly increase in the generator speed. The machine starts behaving as an induction
generator, It drawn reactive power from the system which is undesirable, The loss of
excitation may lead to the pole slipping condition. Hence protection against loss of
excitation must be provided.
The protection is provided using directional distance type relay with the generator
terminals
When there is loss of excitation, the equivalent generator impedance varies and
traces a curve as shown in the Fig. 5.15. This Fig. 5.15 shows the loss of excitation
aracteristics alongwith the relay operating characteristics, on R-X diagram.
wR
Locus of equivalent
(gonerasor impecance
dug fe ascii
Fig. 5.15 Loss of excitation characteristics
The equivalent generator impedance locus traces a path from first quadrant of R-X
diagram to the fourth quadrant, The distance relay is used which covers the portion of
the fourth quadrant where impedance locus path exists. Thus when the impedance
takes value in the region covered by the relay characteristics, the relay operates. The
relay operates when generator first starts to slip poles. Then relay trips the field circuit
breaker. And it disconnects the generator from the system, too. When the excitation is
regained and becomes normal, the generator can then be retumed to service instantlyProtection and Switchgear 5-23 Generator Protection
5.13 Negative Sequence Relays
The negative relays are also
provide protection against negative sequence component of unbalanced currents
existing due to unbalanced loads or phase-phase faults, The unbalanced currents are
w as these currents can cause
lied phase unbalance relays because these relays
us from generators and motors point of v
overheating, Negative sequence relays are g
generators and motors against unbalanced currents
lly used to give protection t
A negative sequence relay has a filter circuit which is operative only for negative
sequence components. Low order of over current also can cause dangerous situations
hence a negative sequence relay has tow current settings. The earth relay provides
protection for phase to earth fault but not for phase to phase fault. A negative
sequence relay provides protection against phase to phase faults which are responsible
to produce negative sequence components.
The Fig, 5.16 shows the schematic arrangement of negative phase sequence relay
cr,
Fig. 5.16 Negative phase sequence relayProtection and Switchgear 5-24
Basically it consists of a resistance bridge network. The magnitudes of the
impedances of all the branches of the network are equal. The impedances Z, and Z,
are purely resistive while the impedances Z, and Z, are the combinations of resistance
and reactance. The currents in the branches Z> and Z, lag by 60° from the currents in
the branches Z, and Z,. The vertical branch B-D consists of inverse time characteristics
relay, The relay has negligible impedance.
The current Iy gets divided
™ 72 into two equal parts f, and I;. And
I, lags 1; by 60% The phasor
diagram is shown in the Fig. 5.17.
Rt = ie
Let 1, = L
The perpendicular is drawn
from point A on the diagonal
meeting it at point B, as shown in
° aA? the Fig. 5.17. This bisects the
Fig. 5.17 diagonal.
« |e
OB = >
Now in triangle OAB,
oB
cos = OR
8 (5)
2
ree =k (uy
Now I, leads Ip by 30° while [, lags I by 30°
Similarly the current Ip gets divided into two equal parts 1, and 1,. The current
lags t, by 60°. Fromm equation (1) we can write,
1
K =h=h (2)
‘The current 1, leads Ig by 30° while current I, lags Ip by 30°
The current entering the telay at the junction point B in the Fig. 5.16 is the vector
sum of Ij, Iy and lyProtection and Switchgear 5-25 Generator Protection
Tray = hh +1;
le ly
+ -& (leads Ix by 30% + 2 (lags Ip by
y a! 30) va igs In by 309)
The vector sum is shown in the Fig. 518 when the load is balanced and no
tive sequence currents exist.
neg.
te
Tk can be seen from the
i+i
haley =
Thus the current entering the relay at point B is zero. Similarly the newultant
current at junction D is also zero, Thus the relay is inoperative for a balanced system
Now consider that there is unbalanced load on generator or motor due to which
negative sequence currents exist. The phase sequence of C.T. secondary currents is as
shown in the Fig. 5.19 (a). The vector diagram of I, Is and Ty is shown in the
Fig, 5.19 (b) under this condition.
The components 1, and I are equal and opposite to each other at the junetion
point B. Hence 1, and ly cancel each other. Now the relay coil carries the current ly
and when this current is more than a predetermined value, the relay trips closing the
contacts of trip circuit which opens the circuit breaker,Protectio
(a) GT. secondary currents
Fig, 5.19 Negative sequence currents
Zero Sequence Currents ; The zero sequence components of secondary currents
are shown in the Fig. 5.20 (a). We know that,
~ |
(a) (b) te)
Fig. 5.20 Zero sequence currents
ta ty by
ie = Tal,
iy = fyoty
These sums are shown in the Fig. 5.20 (b) and (c). It can be seen from the
Fig. 5.20 (d) that,
i+, = fy in phase with by
The total current through relay is f) +i, +[y, Thus under zero sequence currents
the total current of twice the zero sequence current flows through the relay. Hence the
relay operates to open the circuit breakerProtection and Switchgear 8-27 Generator Protection
To make the relay sensitive to only
et negative sequence currents by making it
inoperative under the influence of zero
sequence currents is possible by
GT. connecting the current transformers int
delta as shown in the Fig. 5.21. Under
delta connection of current transtor
in the
eT no zero sequence current can flow
network.
Fig. 5.21 Delta connection of C.T.s
5.13.1 Induction Type Negative Sequence Rel
y
her commonly used negative sequence relay is induction type. Its construction
is similar to that of induction type over current relay. The schematic diagram of this
type of relay is shown in the Fig. 5.22
ny ®
Fig. 5.22 Induction type negative sequence relay
The central limb of upper magnet carries the primary which has a centre tap. Due
to this, the primary winding has three terminal 1, 2, and 3. The section 1-2 is
energized from the secondary of an auxiliary transformer to R-phase. The section 2-3
is directly energized from the Y-phase current
The auxiliary transformer is a special device having an air gap in its magnetic
circuit. With the help of this, the phase angle between its primary and secondary can