Test Report: Format No.: PTL/FTR-00

The test report summarizes the results of mechanical tests performed on cement and bricks samples. Key details include: 1. Testing of cement sample found it met requirements for fineness, setting time, soundness and compressive strength as per IS standards. 2. A supplement test report provided the 672 hour compressive strength result of 47.5 N/mm2, meeting the required range. 3. Brick sample testing showed dimensions and compressive strength met IS standards, and water absorption and efflorescence were within limits.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
98 views7 pages

Test Report: Format No.: PTL/FTR-00

The test report summarizes the results of mechanical tests performed on cement and bricks samples. Key details include: 1. Testing of cement sample found it met requirements for fineness, setting time, soundness and compressive strength as per IS standards. 2. A supplement test report provided the 672 hour compressive strength result of 47.5 N/mm2, meeting the required range. 3. Brick sample testing showed dimensions and compressive strength met IS standards, and water absorption and efflorescence were within limits.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Format No.

: PTL/FTR-00

TEST REPORT
Issued To: Name of Work: --
M/s

Customer Ref. No. & Date: ATC/Testing/RM001/23-24,


Test Report No.: PTL23D1001-01
Dated: 10.04.2023
Date of Issue of Test Report: 18/04/2023 Name of Agency: M/s Awasthi Tubewell Company
Date of Receipt of sample: 10/04/2023 Contract Bond No.: --
Date of Start of Test: 11/04/2023 Sampling Done By: Customer
Date of Completion of Test: 18/04/2023 Sample Condition: Satisfactory
Sample Description: O.P. Cement 43 Grade Test(s) performed at: Lab
“Ambuja” Customer Name/ Contact:
Addition to, Deviation or Exclusion from the Method(s): None
Discipline: Mechanical Group: Building, Infrastructure & Construction Materials
Page 1 of 1
S. Requirements as per
Test Parameter (s) Test Method Observed Value
No. IS: 269: 2015
1. Standard Consistency, % IS 4031 (Part 4):1988, RA 2019 27.0 --
2. Fineness (by Blaine’s App.), m²/kg IS 4031 (Part 2):1999, RA 2018 292.0 225 Min.
Setting Time, minute
3. a) Initial IS 4031 (Part 5):1988, RA 2019 130 30 Min.
b) Final 210 600 Max.
4. Soundness (by Le-Chatelier method), mm IS 4031 (Part 3):1988, RA 2019 1.5 10 Max.
Compressive Strength, N/mm²
a) After 72±1h 28.5 23 Min.
5. IS 4031 (Part 6):1988, RA 2019
b) After 168±2h 37.5 33 Min.
c) After 672±4h Awaited 43 - 58
***End-of-Test-Report***
Format No.: PTL/FTR-00

TEST REPORT
Supplement Test Report to Report No. PTL23D1001-01, dated 18/04/2023
Issued To: Name of Work: --
M/s Awasthi Tubewell Company
Kamlanagar, Collectorganj Fatehpur – 212601 (U.P.)
Customer Ref. No. & Date: ATC/Testing/RM001/23-24,
Test Report No.: PTL23D1001-01S
Dated: 10.04.2023
Date of Issue of Test Report: 09/05/2023 Name of Agency: M/s Awasthi Tubewell Company
Date of Receipt of sample: 10/04/2023 Contract Bond No.: --
Date of Start of Test: 11/04/2023 Sampling Done By: Customer
Date of Completion of Test: 09/05/2023 Sample Condition: Satisfactory
Sample Description: O.P. Cement 43 Grade Test(s) performed at: Lab
“Ambuja” Customer Name/ Contact: Mr. Ankit/9415033015
Addition to, Deviation or Exclusion from the Method(s): None
Discipline: Mechanical Group: Building, Infrastructure & Construction Materials
Page 1 of 1
S. Requirements as per
Test Parameter (s) Test Method Observed Value
No. IS: 269: 2015
Compressive Strength, N/mm²
1. IS 4031 (Part 6):1988, RA 2019
a) After 672±4h 47.5 43 - 58
***End-of-Test-Report***
Format No.: PTL/FTR-00

TEST REPORT
Issued To: Name of Work: --
M/s Awasthi Tubewell Company
Kamlanagar, Collectorganj Fatehpur – 212601 (U.P.)
Customer Ref. No. & Date: ATC/Testing/RM001/23-24,
Test Report No.: PTL23D1001-02
Dated: 10.04.2023
Date of Issue of Test Report: 24/04/2023 Name of Agency: M/s Awasthi Tubewell Company
Date of Receipt of sample: 10/04/2023 Contract Bond No.: --
Date of Start of Test: 11/04/2023 Sampling Done By: Customer
Date of Completion of Test: 24/04/2023 Sample Condition: Satisfactory
Test(s) performed at: Lab
Sample Description: Bricks 1st Class “GAGAN”
Customer Name/ Contact: Mr. Ankit/9415033015
Addition to, Deviation or Exclusion from the Method(s): None
Discipline: Mechanical Group: Building, Infrastructure & Construction Materials
Page 1 of 2
S. Observed Requirements as per
Test Parameter (s) Test Method
No. Value IS: 1077: 1992
Dimension, mm
Length of 20 Bricks IS 1077: 1992, 4580 4600±80
1.
Width of 20 Bricks RA 2021 2210 2200±40
Height of 20 Bricks 1420 1400±40
10.8
11.3
11.6 7.5 Min. for Class 7.5
2. Compressive Strength, N/mm² IS 3495(Part-1): 2019 10 Min. for Class 10
10.6 12.5 Min. for Class 12.5
11.8
Avg. 11.2
Format No.: PTL/FTR-00

Sample Description: Bricks 1st Class “GAGAN” Test Report No.: PTL23D1001-02
Page 2 of 2
S. Test Parameter (s) Test Method Observed Requirements as per
No. Value IS: 1077: 1992
14.8
13.0
14.4 20 Max. for upto Class 12.5
Water Absorption, %
3. IS 3495(Part-2): 2019 15 Max. for higher classes.
(by 24-hour water absorption test) 12.4
13.3
Avg. 13.5
Nil
Not more than “Moderate”
Nil for upto Class 12.5
4. Efflorescence IS 3495(Part-3): 2019 Slight Not more than “Slight” for
Slight higher classes.

Nil
***End-of-Test-Report***
Format No.: PTL/FTR-00

TEST REPORT
Issued To: Name of Work: --
M/s Awasthi Tubewell Company
Kamlanagar, Collectorganj Fatehpur – 212601 (U.P.)
Customer Ref. No. & Date: ATC/Testing/RM001/23-24,
Test Report No.: PTL23D1001-03
Dated: 10.04.2023
Date of Issue of Test Report: 22/04/2023 Name of Agency: M/s Awasthi Tubewell Company
Date of Receipt of sample: 10/04/2023 Contract Bond No.: --
Date of Start of Test: 11/04/2023 Sampling Done By: Customer
Date of Completion of Test: 22/04/2023 Sample Condition: Satisfactory
Test(s) performed at: Lab
Sample Description: Coarse Aggregate 10mm
Customer Name/ Contact: Mr. Ankit/9415033015
Addition to, Deviation or Exclusion from the Method(s): None
Discipline: Mechanical Group: Building, Infrastructure & Construction Materials
Page 1 of 1
S. Observed Requirements as per
Test Parameter (s) Test Method
No. Value IS: 383: 2016
Sieve Analysis, % passing through IS
Sieve size, mm
12.5 100 100
1. 10.0 IS 2386(Part-1):1963, RA 2021 96.7 85 – 100
4.75 13.2 0 – 20
2.36 2.9 0–5
Combined Flakiness and Elongation By Calculation
2. 24.8 40 Max.
Index, % (IS 383: 2016 / IS 2386(Part-1)
3. Specific Gravity IS 2386(Part-3):1963, RA 2021 2.61 2.1 – 3.2
4. Water Absorption, % IS 2386(Part-3):1963, RA 2021 0.40 5 Max.
5. Compacted Bulk Density, kg/l IS 2386(Part-3):1963, RA 2021 1.55 --
6. Aggregate Impact Value, % IS 2386(Part-4):1963, RA 2021 20.8 30 Max.
30 Max. for wearing surfaces
7. Crushing Value, % IS 2386(Part-4):1963, RA 2021 23.7 45 Max. for non-wearing
surfaces
8. Soundness (by Na2SO4), % IS 2386(Part-5):1963, RA 2021 0.24 12 Max.
***End-of-Test-Report***
Format No.: PTL/FTR-00

TEST REPORT
Issued To: Name of Work: --
M/s Awasthi Tubewell Company
Kamlanagar, Collectorganj Fatehpur – 212601 (U.P.)
Customer Ref. No. & Date: ATC/Testing/RM001/23-24,
Test Report No.: PTL23D1001-04
Dated: 10.04.2023
Date of Issue of Test Report: 22/04/2023 Name of Agency: M/s Awasthi Tubewell Company
Date of Receipt of sample: 10/04/2023 Contract Bond No.: --
Date of Start of Test: 11/04/2023 Sampling Done By: Customer
Date of Completion of Test: 22/04/2023 Sample Condition: Satisfactory
Test(s) performed at: Lab
Sample Description: Coarse Sand (Stone Dust)
Customer Name/ Contact: Mr. Ankit/9415033015
Addition to, Deviation or Exclusion from the Method(s): None
Discipline: Mechanical Group: Building, Infrastructure & Construction Materials
Page 1 of 2
S. Requirements as per
Test Parameter (s) Test Method Observed Value
No. IS: 383: 2016
Sieve Analysis, % passing through IS
Zone-II
Sieve size, mm
10 100 100
4.75 94.2 90-100

1. 2.36 IS 2386(Part-1):1963, RA 2021 86.2 75-100


1.18 68.5 55-90
0.600 43.2 35-59
0.300 14.5 8-30
0.150 6.2 0-20
2. Specific Gravity IS 2386(Part-3):1963, RA 2021 2.70 2.1-3.2
3. Water Absorption, % IS 2386(Part-3):1963, RA 2021 0.39 5 Max.
4. Loose Bulk Density, kg/l IS 2386(Part-3):1963, RA 2021 1.74 --
5. Compacted Bulk Density, kg/l IS 2386(Part-3):1963, RA 2021 1.76 --
CPWD Vol. 1- 2019
6. Silt Content, % 4.1 --
Appendix C (Cl. 3.1.3.2)
Format No.: PTL/FTR-00

Sample Description: Coarse Sand (Stone Dust) Test Report No.: PTL23D1001-04
Page 2 of 2
S. Requirements as per
Test Parameter (s) Test Method Observed Value
No. IS: 383: 2016
Deleterious Material
a) Material Finer Than 75µ IS sieve, % IS 2386(Part-1):1963, RA 2021 3.60 15.00 Max.
7. b) Clay Lumps, % IS 2386(Part-2):1963, RA 2021 0.03 1.00 Max.
c) Coal & Lignite, % IS 2386(Part-2):1963, RA 2021 Nil 1.00 Max.
d) Total Deleterious Material, % By Calculation (IS 383:2016) 0.03 2.00 Max.
8. Soundness (by Na2SO4), % IS 2386(Part-5):1963, RA 2021 2.32 10 Max.
9. Fineness Modulus IS 6461(Part-1) 1972, RA 2021 2.87 --
10. Voids (Porosity) IS 2386(Part-3):1963, RA 2021 34.8 --
The colour of sample
Lighter than Std. solution should be
11. Organic Impurities IS 2386(Part-2):1963, RA 2021
Solution lighter than std.
Tannic acid solution.
***End-of-Test-Report***