0613CT0001
0613CT0001
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Masterpact™ Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3
Micrologic™ Electronic Trip Systems . . . . . . . . . . . . . . . . . . . . . . . . Page 19
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 37
Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 63
Masterpact NT Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . Page 69
Masterpact NW Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . Page 98
Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 154
Trip Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 167
™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
INTRODUCTION ............................................................................................................................................ 4
CODES AND STANDARDS ........................................................................................................................... 4
FEATURES AND BENEFITS ......................................................................................................................... 5
OPERATING CONDITIONS ........................................................................................................................... 8
MASTERPACT NW CIRCUIT BREAKER DESIGN ....................................................................................... 9
MASTERPACT NW CRADLE DESIGN ....................................................................................................... 10
MASTERPACT NT CIRCUIT BREAKER AND CRADLE DESIGN .............................................................. 12
RATINGS ..................................................................................................................................................... 13
CORRECTION FACTORS ........................................................................................................................... 17
SHIPPING WEIGHTS .................................................................................................................................. 18
3
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
Introduction
HA10 12kV
NX 08 Uimp
Ui 1000V
Ue (V)
690
s
50kA/1
50/60Hz
AS NBMA
947-2 UNE
IEC
EN 60947-2BS CEI
VDE
UTE
800–3200 A Masterpact NW Drawout Circuit Breaker 4000–6300 A Masterpact NW Drawout Circuit Breaker
Masterpact circuit breakers are manufactured and tested in accordance with the following standards:
NOTE: Throughout this document, the phrase “ANSI® Certified” means the product meets the
requirements of UL 1066 and ANSI C37. When “UL® Listed” appears, the product meets the requirements
of UL 489.
The 800–2000 A ANSI Low Voltage Power Circuit Breakers type L1F and Insulated Case Circuit
Breaker type LF are tested to show the arc flash hazard risk category as referenced by NFPA® 70E.
Circuit breakers should be applied according to guidelines detailed in the National Electrical Code®
(NEC®) and other local wiring codes.
Masterpact circuit breakers are available in Square D™ or Schneider Electric™ brands.
4
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
UL File Numbers:
• Masterpact NW: E161835 Vol. 2 Sec. 1
• Masterpact NT: E161835 Vol. 2 Sec. 2
High Ampere Interrupting Rating (AIR): ANSI Certified Masterpact NW circuit breakers have an
interrupting rating of 200,000 A at 508 Vac without fuses.
High Short-Time Current Rating: Masterpact NW circuit breakers have exceptional short-time
ratings—up to 100,000 A.
100% Rated Circuit Breaker: Masterpact circuit breakers are designed for continuous operation at
100% of their current rating.
Reverse Fed Circuit Breaker: Masterpact circuit breakers can be fed either from the top of the circuit
breaker or from the bottom.
True Two-Step Stored Energy Mechanism: Masterpact circuit breakers are operated via a stored-
energy mechanism which can be manually or motor charged. The closing time is less than five cycles.
Closing and opening operations can be initiated by remote control or by push buttons on the circuit
breaker front cover. An O–C–O cycle is possible without recharging.
Drawout or Fixed Mount, 3-Pole (3P) or 4-Pole (4P) Construction: ANSI Rated, UL Listed and IEC
Rated Masterpact circuit breakers are available in drawout or fixed mounts, with either 3P or 4P
construction.
Field-Installable Trip Units, Sensor Plugs and Accessories: Trip units, sensor plugs and most
accessories are field installable with only the aid of a screwdriver and without adjusting the circuit
breaker. The uniform design of the circuit breaker line allows most accessories to be common for the
whole line.
Reinforced Insulation: Two insulation barriers separate the circuit breaker front from the current path.
Isolation Function by Positive Indication of Contact Status: The mechanical indicator is truly
representative of the status of all the main contacts.
Segregated Compartment: Once the accessory cover has been removed to provide access to the
accessory compartment, the main contacts remain fully isolated. Furthermore, interphase partitioning
allows full insulation between each pole even if the accessory cover has been removed.
Front Connection of Secondary Circuits: All accessory terminals (ring terminals are available as an
option) are located on a connecting block which is accessible from the front in the connected, test and
disconnected positions. This is particularly useful for field inspection and modification.
Anti-Pumping Feature: All Masterpact NT and NW circuit breakers are designed with an anti-pumping
feature that causes an opening order to always takes priority over a closing order. Specifically, if
opening and closing orders occur simultaneously, the charged mechanism discharges without any
movement of the main contacts keeping the circuit breaker in the open (OFF) position.
In the event that opening and closing orders are simultaneously maintained, the standard mechanism
provides an anti-pumping function which continues to keep the main contacts in the open position.
In addition, after fault tripping or opening the circuit breaker intentionally (using the manual or electrical
controls and with the closing coil continuously energized) the circuit breaker cannot be closed until the
power supply to the closing coil is discontinued and then reactivated.
NOTE: When the automatic reset after fault trip (RAR) option is installed, the automatic control system
must take into account the information supplied by the circuit breaker before issuing a new closing
order or before blocking the circuit breaker in the open position. Information on the type of fault, e.g.
overload, short-circuit or ground fault.
5
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
Disconnection Through the Front Door: The racking handle and racking mechanism are accessible
through the front door cutout. Disconnecting the circuit breaker is possible without opening the door
and exposing live parts.
Door Escutcheon
Racking Mechanism
Drawout Mechanism: The drawout assembly mechanism allows the circuit breaker to be racked in
four positions (connected, test, disconnected, or withdrawn), as shown in the figure below.
NOTE: For UL/ANSI circuit breakers, the clusters are mounted on the circuit breaker; for IEC circuit
breakers, the clusters are mounted on the cradle.
6
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
7
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
Operating Conditions
See bulletin 0613IB1202, available in the Schneider Electric technical library, for information on normal
and adverse operating conditions.
Ambient Temperature:
Masterpact circuit breakers can operate under the following temperature conditions:
• The electrical and mechanical characteristics are stipulated for an ambient temperature between
-13°F (-25°C) and 158°F (70°C).
Mechanical closing of the circuit breaker (by pushbutton) is possible down to -31°F (-35°C)
• At altitudes +13,000 ft. (3900 m).
Masterpact circuit breakers have been tested for operation in industrial atmospheres. It is
recommended that the equipment be cooled or heated to the proper operating temperature and kept
free of excessive vibration and dust. Operation at temperatures above 104°F (40°C) may require
derating or overbussing the circuit breaker. See the appropriate instruction bulletin and page 17 of this
catalog for additional information.
Storage Temperature
Circuit breakers with trip units without LCD displays may be stored in the original packaging at
temperatures between -40°F (-40°C) and 185°F (85°C).
For circuit breakers with trip units with LCD displays, this range is -13°F (-25°C) to 185°F (85°C).
Altitude:
Masterpact circuit breakers are suitable for use at altitudes of 13,000 ft. (3900 m) and below. See
Table 15 on page 17 for Altitude correction factors.
Vibration:
Humidity:
8
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
NOTE: For UL Listed and ANSI Certified circuit breakers, the clusters are mounted on the circuit
breaker; for IEC Rated circuit breakers, the clusters are mounted on the cradle.
9
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
Primary Stabs
10
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
The Masterpact NW low-voltage power circuit breaker and insulated case circuit breaker are available
with ArcBlok technology designed to mount in an ArcBlok drawout cradle.
The Masterpact NW with ArcBlok technology interfaces with the ArcBlok cradle to prevent arcing
events by enclosing the phases at the primary connection of the cradle. If for any reason an arcing
event happens, with the separation between phase to phase and phase to ground, the arc is
extinguished in less than 12 ms to reduce arc flash energy.
The Masterpact NW with ArcBlok technology is tested as part of Arc Resistant Equipment to ANSI
C37.20.7.
Figure 5: Masterpact NW Circuit Breaker and Cradle with ArcBlok Technology
A
Q
C H B
F G
D E P
Cradle
A—Terminal Cover
B—Lifting Flanges N
C—Extension Rail Handle I M
D—Padlock Provision
J K L
E—Stop Release Button
F—Racking Handle Insertion Opening Drawout Circuit Breaker
G—Position Indicator
H—Racking Handle Storage Space
I—Fault Trip Reset Button
J—Trip Unit
K—Push to Open Button Racking Handle
L—Push to Close Button
M—Charging Handle
N—Faceplate
O—Accessory Cover
P—Cradle Date Code
Q—ArcBlok Shield
(rotated for clarity)
11
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
Terminal Cover
Lifting Handle
Padlock Provision
Position Indicator
Accessory Cover
Charging Handle
Extension Rail Handle
Lifting Tab
12
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
Ratings
100–800 A 2000–4000 A
Sensor Rating 1000–2000 A 1600–4000 A 2500–5000 A
800–1600 A 3000–6000 A
Endurance Rating (C/O Mechanical 12,500 10,000 10,000 5000 5000
Cycles)
Electrical 2800 1000 1000 1000 1000
(with no maintenance)
1 4000 A standard width circuit breaker is not available in L1 interrupting rating code or drawout construction.
2 ArcBlok circuit breakers are available only to 5000 A.
3 Interrupting ratings (kAIR) at 50 Hz: 200 kA (254 Vac), 150 kA (508 Vac), 100 kA (635 Vac).
4 The interrupting ratings L1 and L1F are available only in 3P, drawout construction.
5 55 kA for 800 A circuit breaker frame with 100 A or 250 A sensor.
13
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
14
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
15
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
16
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
Table 12: Ratings for IEC 60947-2 Rated Masterpact NT Circuit Breakers
Frame Rating 800/1000 A 1250/1600 A
Interrupting Rating Code H1 H2 L1 H1 H2
220/415 Vac, 50/60 Hz 42 50 150 42 50
440 Vac, 50/60 Hz 42 50 130 42 50
Ultimate Breaking Capacity (kA) Icu 525 Vac, 50/60 Hz 42 42 100 42 42
690 Vac, 50/60 Hz 42 42 25 42 42
1000 Vac, 50/60 Hz — — — — —
Service Breaking Capacity (kA) Ics %Icu 100% 100% 100% 100% 100%
Short-Time Withstand Current (kA) Icw Vac 50/60 Hz, 1 s 42 42 10 x In1 42 36
Built-In Instantaneous Override (kA ±10%) — 90 102 — —
220/415 Vac, 50/60 Hz 88 105 330 88 105
440 Vac, 50/60 Hz 88 105 286 88 105
Rated Making Capacity (Peak kA) Icm 525 Vac, 50/60 Hz 88 88 220 88 88
690 Vac, 50/60 Hz 88 88 52 88 88
1000 Vac, 50/60 Hz — — — — —
Break Time ms 25 25 9 25 25
Closing Time ms 50 50 50 50 50
Mechanical 12,500 12,500 12,500 12,500 12,500
Endurance Rating (C/O cycles)
Electrical 440 V 6000 6000 3000 60003 60003
(with no maintenance)
Electrical 1000 V — — — — —
1 For Icw, 10 kA is for 0.5 s.
2 SELLIM system.
3 1600 A at 690 V is 3000 electrical operations.
Table 13: Ratings for IEC 60947-3 Rated Non-Automatic Masterpact NT Switches
Frame Rating 800/1000 A 1250/1600 A
Withstand Rating Code HA HA
220/415 Vac, 50/60 Hz 75 75
440 Vac, 50/60 Hz 75 75
Rated Making Capacity (Peak kA) Icm
500/690 Vac, 50/60 Hz 75 75
1000 Vac, 50/60 Hz — —
Short-Time Withstand Current (kA) Icw Vac 50/60 Hz, 0.5 s 36 36
Breaking Capacity (kA at 690 Vac)
Icu maximum delay 350 ms 36 36
(with external protection relay)
Correction Factors
Table 14: Temperature Correction Factors per ANSI C37.20.1 par. 7.4.2
Table 15: Altitude Correction Factors per ANSI C37.20.1 par. 7.1.4.1 (Table 10)
17
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
Shipping Weights
Table 16: Shipping Weights for UL Listed/ANSI Certified Masterpact NW Circuit Breakers
1
Circuit Breaker Rating Circuit Breaker (lb/kg) Cradle (lb/kg) Connector Type and Weight (lb/kg) Pallet Total Weight (lb/kg)
(A) 3P 4P 3P 4P Type 3P 4P (lb/kg) 3P 4P
800 FCF 42/19 55/25 17/8 265/121 320/151
1600 109/50 142/65 97/44 116/53 FCT 84/38 109/50 17/8 307/140 384/176
2000 RCTH or RCTV 17/8 22/10 17/8 240/110 297/136
2500 FCT 80/36 104/47 17/8 348/159 435/198
127/58 165/75 124/57 149/68
3000 RCTH or RCTV 26/12 34/15 17/8 294/135 365/166
2000 (L1, L1F)
RCOV (standard 100/46 130/59 368/169 461/210
3200 (H1, H2, H3)
127/58 165/75 124/57 149/68 17/8
RCOV (ArcBlok) 153/69 NA 421/191 NA
4000 W-Frame (H1, H2, H3) RCOV (special) 115/52 145/66 259/118 327/149
FCF 84/38 109/50 39/18 628/285 777/354
3200 (L1)
227/103 295/134 278/126 334/152 FCT 168/77 218/99 39/18 712/324 886/403
4000
RCTH or RCTV 52/24 68/31 39/18 596/271 736/335
FCT 168/77 218/99 39/18 712/324 886/403
5000 227/103 295/134 278/126 334/152
RCTH or RCTV 52/24 68/31 39/18 596/271 736/335
6000 227/103 295/134 278/126 334/152 RCTH or RCTV 396/180 528/240 39/18 940/427 1196/544
1 Fixed circuit breaker weight = total weight – cradle weight.
Table 17: Shipping Weights for IEC 60947-2 Rated Masterpact NW Circuit Breakers
Circuit Breaker Circuit Breaker1 (lb/kg) Cradle (lb/kg) Connector Type and Weight (lb/kg) Pallet Total Weight (lb/kg)
Rating (A) 3P 4P 3P 4P Type 3P 4P (lb/kg) 3P 4P
800 FCF 42/19 55/25 17/8 265/121 320/145
109/50 132/60 97/44 116/53
1000, 1250, 1600, 2000 RCTH or RCTV 17/8 22/10 17/8 240/110 287/131
2500 FCF 42/19 55/25 17/8 310/142 386/175
127/58 165/75 124/57 149/68
3200 RCTH or RCTV 17/8 22/10 17/8 285/131 353/161
4000 127/58 165/75 124/57 149/68 RCTH or RCTV 42/19 55/25 17/8 310/142 386/176
4000b, 5000, 6300 227/103 295/134 278/126 334/152 RCTH or RCTV 52/24 68/31 39/18 596/271 736/335
1 Fixed circuit breaker weight = total weight – cradle weight.
Table 18: Shipping Weights for UL Listed/ANSI Certified Masterpact NT Circuit Breakers
Circuit Breaker Circuit Breaker1 (lb/kg) Cradle (lb/kg) Connector Type and Weight (lb/kg) Pallet Total Weight (lb/kg)
Rating (A) 3P 4P 3P 4P Type 3P 4P (lb/kg) 3P 4P
800 FCF 15/7 20/9 10/5 101/46 125/58
40/18 52/24 36/16 43/20
1200 RCTH or RCTV 6/3 8/4 10/5 92/42 113/53
16002 40/18 52/24 N/A N/A RCTV 18/8 20/9 10/5 68/31 82/38
1 Fixed circuit breaker weight = total weight – cradle weight.
2 Fixed circuit breaker only.
Table 19: Shipping Weights for IEC 60947-2 Rated Masterpact NT Circuit Breakers
1
Circuit Breaker Circuit Breaker (lb/kg) Cradle (lb/kg) Connector Type and Weight (lb/kg) Pallet Total Weight (lb/kg)
Rating (A) 3P 4P 3P 4P Type 3P 4P (lb/kg) 3P 4P
800 FCF 15/7 20/9 10/5 91/41 113/52
35/16 46/21 31/14 37/17
1000, 1250, 1600 RCTH or RCTV 6/3 8/4 10/5 82/38 101/47
1 Fixed circuit breaker weight = total weight – cradle weight.
18
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
19
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
All Masterpact™ circuit breakers are equipped with the Micrologic trip system to protect power circuits
and loads. Micrologic trip systems use a set of current transformers (called CTs or sensors) to sense
current, a trip unit to evaluate the current, and a tripping solenoid to trip the circuit breaker. Adjustable
rotary switches on the trip unit allow the user to set the proper overcurrent or equipment ground-fault
current protection required in the electrical system. If current exceeds a set value for longer than its set
time delay, the trip system opens the circuit breaker. Alarms may be programmed for remote
indications. Measurements of current, voltage, frequency, power, and power quality optimize continuity
of service and energy management. Micrologic trip units can be changed on-site.
Integration of protection functions in the Application Specific Integrated Circuit (ASIC) electronic
component used in all Micrologic trip units guarantees a high degree of reliability and immunity to
conducted or radiated disturbances. On Micrologic P and H trip units, advanced functions are
managed by an independent microprocessor.
Masterpact circuit breakers are shipped with the long-time pickup switch set at 1.0 and all other trip unit
adjustments set at their lowest settings. Actual settings required for a specific application must be
determined by a qualified consultant or plant engineer. A coordination study is recommended to
provide coordination between all circuit breakers in the distribution system.
Thermal Imaging
The thermal imaging function protects the cables or bus bars from overheating in case of low
amplitude repetitive faults. Such overheating can be due to repetitive motor starting, fluctuating load,
intermittent ground faults, or subsequent closing after a fault.
Traditional electronic protection does not protect against repetitive faults because the duration of each
overload above the pickup setting is too short to achieve effective tripping. Nevertheless, each
overload involves a temperature rise in the installation, the cumulative effect of which could lead to
overheating of the system.
The thermal imaging function remembers and integrates the thermal heating caused by each pickup
setting overrun. Before tripping, the integrated heating value will reduce the associated time delay and,
therefore, the reaction of the trip unit will be closer to the real heating of the power network system.
After tripping, the function will also reduce the time delay when closing the circuit breaker on an
overload.
20
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
Power (P) and Harmonic (H) Trip Unit Without 24 Vdc Power Supply at F1 and F2
The P and H trip units were designed to be used with the external 24 Vdc power supply. The large LCD
display requires too much current to be powered by current flow through the circuit breaker. The P and
H trip units do have a voltage power supply which will power the trip unit with 100 Vac or more between
two phases or phase to neutral. The standard configuration for the voltage probes inside the circuit
breaker is at the bottom connections. If the circuit breaker was open in a top fed application, there
would be no voltage at the bottom of the circuit breaker and the trip unit would not be powered.
• Provides fault protection for LSIG functions
• Provides LED trip indication (powered by an onboard battery)
NOTE: Ground-fault push-to-trip button works for testing ground fault if the trip unit is powered by the
voltage power supply. The ground-fault push-to-trip is also functional if a hand-held test kit or full-
function test kit is powering the trip unit.
Power (P) and Harmonic (H) Trip Unit With 24 Vdc Power Supply at F1 and F2
21
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
The sensing system responds to the flow of current through the circuit breaker. Electronic trip circuit
breakers are limited to ac systems because the electronic trip system uses current transformers to
sense the current.The Micrologic trip unit samples the current waveform to provide true RMS
protection through the 15th harmonic.
This true RMS sensing gives accurate values for the magnitude of a non-sinusoidal waveform.
Therefore, the heating effects of harmonically distorted waveforms are accurately evaluated.
The Micrologic H trip unit provides additional sampling of the waveforms to measure and provide
waveform capture of harmonic distortion to the 31st harmonic.
Masterpact universal power circuit breakers use Micrologic electronic trip systems to sense overcurrents
and trip the circuit breaker. The Micrologic basic trip unit is standard and all Masterpact circuit breakers can
be equipped with the optional Micrologic trip systems listed below:
• Micrologic Basic Trip Unit (standard).
— 2.0 basic protection (LS0, IEC)
— 3.0 basic protection (LI, UL®/ANSI)
— 5.0 selective protection (LSI)
• Micrologic A: Trip Unit with Ammeter.
— 2.0A basic protection (LS0, IEC)
— 3.0A basic protection (LI, UL/ANSI)
— 5.0A selective protection (LSI)
— 6.0A selective protection with ground-fault protection for equipment (LSIG)
• Micrologic P: Trip Unit with Power Metering.
— 5.0P selective protection (LSI)
— 6.0P selective protection with ground-fault protection for equipment (LSIG)
• Micrologic H: Trip Unit with Harmonic Metering.
— 5.0H selective protection (LSI)
— 6.0H selective protection with ground-fault protection for equipment (LSIG)
Micrologic 3.0 and 5.0 Basic Trip Units Micrologic 3.0A, 5.0A and 6.0A Trip Units
22
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
Micrologic 5.0P and 6.0P Trip Units Micrologic 5.0H and 6.0H Trip Units
23
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
The Micrologic 2.0, 3.0, and 5.0 trip units protect power circuits.
Protection Settings
Protection thresholds and delays are set using the rotary switches.
1—Overload signal (LED) 1 A full-range of long-time settings are available via field-
2—Long-time rating plug 3
2
installable adjustable rating plugs.
screw
• Overload protection
3—Long-time current setting
and tripping delay — True RMS long-time protection
5 4
4—Instantaneous pickup — Thermal imaging: Active thermal imaging before and
5—Short-time pickup and after tripping
tripping delay
• Short-circuit protection.
6—Test connector
6 — Short-time RMS
— Selection of I2t type (ON or OFF) for short-time delay
• Instantaneous protection.
Micrologic 5.0 Basic Trip Unit • Neutral protection on four-pole circuit breakers.
Table 21: Micrologic 2.0 and 3.0 Basic Trip Unit Settings
Current Setting (A) 2.0: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
Tripping Between 1.05 Ir = ln x... 3.0: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
and 1.20 x Ir Other ranges are available by changing rating plug
Long-Time
tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Protection Time Delay (s)
tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24
Accuracy: 0 to –20%
tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal Imaging 20 minutes before or after tripping
Current Setting (A)
Short-Time
Accuracy: ±10% Isd = Ir x... 2.0: 1.5 2 2.5 3 4 5 6 8 10
Protection
No Delay
Instantaneous Current Setting (A)
Ii = In x... 3.0: 1.5 2 3 4 5 6 8 10 12
Protection Accuracy: ±10%
Current Setting (A) IEC: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
Tripping Between 1.05 Ir = ln x... UL/ANSI: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
and 1.20 x Ir Other ranges are available by changing rating plug
Long-Time
tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Protection Time Delay (s)
tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24
Accuracy: 0 to –20%
tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal Imaging 20 minutes before or after tripping
Current Setting (A)
lsd = Ir x... 1.5 2 2.5 3 4 5 6 8 10
Accuracy: ±10%
I2t OFF 0 0.1 0.2 0.3 0.4
Settings
Short-Time I2t ON 0.1 0.2 0.3 0.4
Protection
Time Delay (s) Min. trip
at 10 x Ir 20 80 140 230 350
time (ms)
tsd
Max. trip
80 140 200 320 500
time (ms)
Instantaneous Current Setting (A)
Ii = In x... 2 3 4 6 8 10 12 15 off
Protection Accuracy: ±10%
24
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
Micrologic 2.0A, 3.0A, 5.0A, & 6.0A Trip Units with Ammeter
Micrologic A trip units protect power circuits and provide current measurements, overload protection,
and short-circuit protection. In addition, the 6.0A trip units also provide ground-fault protection for
equipment.
Protection Settings
Protection thresholds and delays are set using the rotary switches. The
1
selected values are momentarily displayed in amperes and in seconds.
1—Test lamp and reset A full-range of long-time settings are available via field-installable rating
2
2—Indication of tripping plug.
cause
• Overload protection (true RMS long-time protection).
3—Digital display 3
• Thermal imaging (active thermal imaging before and after tripping).
4—Three-phase bar graph
and ammeter • Short-circuit protection.
5—Navigation buttons — Short-time RMS
6—Overload signal (LED) — I2t ON or OFF for short-time delay
7—Long-time rating plug 4
screw
• Instantaneous protection.
8—Long-time current setting
• Ground-fault protection for equipment.
5
and tripping delay
— Residual ground-fault protection for equipment
9—Short-time pickup and
tripping delay — Source ground-return ground-fault protection for equipment
10—Instantaneous pickup 6 — Modified differential ground-fault protection (MDGF) for
8 7 equipment
11—Electronic push-to-trip
12—Ground-fault pickup and • Neutral protection on four-pole circuit breakers.
tripping delay 9 10
• ZSI: Zone-selective interlocking (a ZSI terminal block may be used to
13—Test connector interconnect a number of trip units to provide total discrimination for
11
12
short-time and equipment ground-fault protection, without delay for
13 tripping). Not available for 3.0 A trip unit. Not available for 2.0 A trip
unit if installed as upstream device.
Ammeter Measurements
Micrologic A trip units measure the true RMS value of currents. They provide continuous current
measurement from 0.2 to 20 x In with an accuracy of 1.5% (including sensors). No auxiliary source is
needed where I > 0.2 x In. The optional external power supply (24 Vdc) makes it possible to display
currents where I < 0.2 x In and to store values of the interrupted current. A digital LCD screen
continuously displays the most heavily loaded phase (Imax) or displays the Ia, Ib, Ic, Ig, and (on 4P circuit
breakers only) In stored current and setting values by successively pressing the navigation button.
Communication Network
t 2.0A: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
Current Setting (A)
Ir Tripping Between 1.05 Ir = ln x... 3.0A: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
and 1.20 x Ir
Other ranges are available by changing rating plug
Long-Time
tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
tr Protection
Time Delay (s)
tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24
Accuracy: 0 to –20%
tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Ii Thermal Imaging 20 minutes before or after tripping
0 Current Setting (A)
Short-Time
Accuracy: ±10% Isd = Ir x... 2.0A: 1.5 2 2.5 3 4 5 6 8 10
Protection
No delay
Instantaneous Current Setting (A)
Ii = In x... 3.0A: 1.5 2 3 4 5 6 8 10 12
Protection Accuracy: ±10%
Ground-Fault Pickup (A) ln ≤ 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Accuracy: ±10% 400 A < ln ≤ 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
ln > 1200 A 500 640 720 800 880 960 1040 1120 1200
I2t OFF 0 0.1 0.2 0.3 0.4
Settings
Time Delay (s) I2t ON 0.1 0.2 0.3 0.4
at 10 x Ir Minimum Trip Time (ms) 20 80 140 230 350
tg
Maximum Trip Time (ms) 80 140 200 320 500
26
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
Protection Settings
1—Test lamp and indication The adjustable protection functions of the 5.0P and 6.0P trip units
reset
are identical to those of Micrologic A trip unit (overloads, short
2—Indication of tripping circuits, equipment ground-fault protection); see page 25.
cause
3—High resolution screen These units also feature:
4—Measurement display • Fine adjustment: Within the range below the rotary switch
5—Maintenance indicators setting, fine adjustments of pickups/delays in steps of 1 A/s
(except for short-time and ground-fault) are possible on the
6—Protection settings
keypad or remotely by the communication network.
7—Navigation buttons
8—Overload signal (LED)
• Inverse definite minimum time lag (IDMTL) setting:
Coordination with fuse-type or medium-voltage protection systems
9—Long-time rating plug
screw
is optimized by adjusting the long-time delay curve around 6 x Ir
axis. This setting ensures better coordination with certain loads.
10—Long-time current
setting and tripping delay • Neutral protection: On three-pole circuit breakers, neutral
11—Short-time pickup and protection may be set using the keypad or remotely using the
tripping delay communication network to one of four positions:
12—Instantaneous pickup
— OFF
13—Hole for settings
lockout pin — 1/2N (1/2 x In)
14—Electronic push-to-trip — 1N (1 x In)
15—Ground-fault pickup and — 2N (2 x In)
tripping delay
NOTE: The neutral protection is disabled if the long-time curve is set
16—Test connector
to one of the IDMTL protection settings.
When the cover is closed, the keypad may no longer be used to change the protection settings, but it
still provides access to the displays for measurements, histories, indicators, etc. Depending on the
thresholds and time delays set, the Micrologic P trip unit monitors current, voltage, power, frequency,
and phase sequence. Each threshold overrun may be signalled remotely via the communication
network.
Each threshold overrun may be combined with tripping (protection) or an indication carried out by an
optional M2C/M6C programmable contact (alarm), or both (protection and alarm).
Maintenance Record
The maintenance record can be consulted using the full-function test kit or remotely via the
communication network. It can be used as an aid in troubleshooting and to assist scheduling for device
maintenance operations.
Recorded indications include:
• Highest current measured
• Operation counter (both cumulative total and total since last reset)
• Number of test kit connections
• Number of trips in operating mode
• Contact wear (Masterpact NW only)
27
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
Load shedding and reconnection parameters can be set according to the power or the current flowing
through the circuit breaker. Load shedding is carried out by a remote computer via the communication
network or by an M2C or M6C programmable contact.
The M2C (two contacts) and M6C (six contacts) programmable contacts may be used to signal
threshold overruns or status changes. They can be programmed using the keypad on the Micrologic P
and H trip units or remotely using the communication network. These contacts are required to obtain
data from the protective relay functions on Type P and Type H trip units.
Ground-Fault Pickup (A) ln ≤ 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Accuracy: ±10% 400 A < ln ≤ 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
ln > 1200 A 500 640 720 800 880 960 1040 1120 1200
I2t OFF 0 0.1 0.2 0.3 0.4
Time Delay (s) Settings
I2t ON 0.1 0.2 0.3 0.4
at 10 x Ir
Minimum trip time (ms) 20 80 140 230 350
tg
Maximum trip time (ms) 80 140 200 320 500
Table 28: Settings for Alarms for Other Protection Functions for Micrologic 5.0P and 6.0P
Trip Units
28
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
Table 29: Load-Shedding Settings for Current and Power Metering for Micrologic 5.0P and
6.0P Trip Units
Pick-Up Drop-Out
The last ten trips and ten alarms are recorded in two separate history files that can be displayed on the
screen (sample displays are shown to the right). The following information is contained in these files:
Trip History
• Type of fault Trip Trip
history 05 / 20 / 00
• Date and time of fault 10:23:42 am
• Interrupted current Ii Ii 7200 A
05 / 20 / 00
• Contact wear Ia = 7800 A
Ii Ib = 7800 A
04 / 28 / 00 Ic = 7800 A
Vmin In = 7800 A
04 / 28 / 00
Alarm History
Alarm Trip
• Type of alarm 05 / 20 / 00
history
• Date and time of the alarm Al 996A
Al
• Values measured at the time of the 05 / 20 / 00
alarm
Al
04 / 28 / 00
Al
02 / 28 / 00
29
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
Metering
The Micrologic P trip unit calculates in real time all electrical values V, A, W, VAR, VA, Wh, VARh,
VAh, Hz, power factor, and crest factor. The Micrologic P trip unit also calculates demand current and
demand power over an adjustable time period.
Real-Time Metering: The value displayed on the screen is refreshed every second. Minimum and
maximum measurement values are stored in memory.
Demand Metering: The demand is calculated over a fixed or sliding time window that can be
programmed from five to 60 minutes. Depending on the contract signed with the power supplier,
specific programming makes it possible to avoid or minimize the cost of overrunning the subscribed
power. Maximum demand values are systematically stored and time stamped.
Communication Network
Four wire Modbus, RTU, RS485—The communication network may be used to:
• Remotely read parameters for the protection functions
• Transmit all the measurements and calculated values
Power • Signal the causes of tripping and alarms
Metering • Consult the history files and the maintenance indicator record
In addition, an event log of the last 100 events and a maintenance record, which is stored in the trip
unit memory but not available locally, may be accessed via the communication network.
The Modbus communication system is compatible with Powerlogic™ System Manager™ (SMS) software.
Event Log
The event log may be accessed by a remote computer via the communication network. All events are
Frequency
time stamped and include:
• Trips
• Beginning and end of alarms
• Modifications to settings and parameters
• Loss of time
• Overrun of wear indicators
• Test kit connections
Power • Counter resets
Demand • System faults (thermal self-protection, major fault and minor fault alarms)
30
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
Metering
The Micrologic H trip unit offers all the measurements carried out by the Micrologic P trip unit, with the
addition of phase-by-phase measurements of power and energy as well as calculation of:
• Current and voltage total harmonic distortion (THD, thd).
• Current, voltage and power fundamentals (50/60 Hz).
• Harmonic components (amplitude and phase) up to the 31st current and voltage harmonic.
Real-Time Metering: The value displayed on the screen is refreshed every second. The table below
shows what is measured in real-time metering.
Demand Metering: Similar to the Micrologic P trip unit, demand values are calculated over a fixed or
sliding time window that can be set from five to 60 minutes.
Waveform Capture
Micrologic H trip units can capture and store current and voltage waveforms using digital sampling
techniques similar to those used in oscilloscopes. Using the information available in the captured
waveform, it is possible to determine the level of harmonics as well as the direction and amplitude of
the flow of harmonic power.
Users of Micrologic H trip units can record manually via the keypad the following waveforms:
• The four currents: Ia, Ib, Ic, and IN
• The three phase-to-phase voltages: Vab, Vbc, and Vca
31
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
Waveforms may be displayed on the graphic screen of Micrologic H trip units or communicated over a
networked system. The recording takes place over one cycle with a measurement range of 0 to 1.5 IN
for current and 0 to 690 volts for voltage. The resolution is 64 points per cycle.
The instantaneous value of each measurement can be compared to user-set high and low thresholds.
Overrun of a threshold generates an alarm. Programmable action can be linked to each alarm, including
circuit breaker opening, activation of an M2C or M6C contact, recording of measurements in a log, etc.
Event Logs
• Setting the display language: System messages can be displayed in six different languages:
— English - US
— English - UK
— French
— German
— Spanish
— Italian
The desired language is selected via the keypad.
• Protection functions: All current-based protection functions require no auxiliary source. Voltage-
based protection functions are connected to AC power via a voltage measurement input built into
the circuit breaker on the bottom side. (Optional external voltage measurement is available.)
• Accuracy of measurements (including sensors):
— Voltage (V) 1%
— Current (A) 1.5% (higher accuracy [1%] may be achieved with special calibration on the current
transformer [CT characterization option])
— Frequency (Hz) 0.1 Hz
— Power (W) and energy (Wh) 2.5%
— The Micrologic H trip unit uses a dedicated metering data chain separate from the protection
data chain so that a greater number of data samples can be used for metering. This increases
the number of samples taken per time period, which in turn gives the H trip unit a higher degree
of metering accuracy.
• Stored information: The fine setting adjustments, the last 100 events and the maintenance record
remain in the trip unit memory even when power is lost.
• Reset: An individual reset, via the keypad or remotely, will reset alarms, minimum and maximum
data, peak values, counters and the indicators.
32
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
The long-time pickup switch sets the maximum current level the circuit Long-Time
Pickup
breaker will carry continuously. The maximum current level (Ir) is the long-
time pickup setting multiplied by the sensor plug amperage (In). If the current Long-Time
Ir
long time
.8 tr
(s) 4
8
alarm Delay
exceeds this value for longer than the long-time delay time, the circuit
.7 .9 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In @ 6 Ir
Alarm
breaker will trip. Isd
3
short time
4
5
tsd
(s) .4 .4 .3
Ii
instantaneous
6 8 10 Indicator
2.5 6 .3 .2 4 12
2 8 .2 .1 3 15
1.5 10 .1 0 2 off
The long-time delay switch sets the length of time that the circuit breaker will Ig
x Ir
setting
on
tg
I2t off
delay
x In
test
D
E
F (s) .4 .4 .3
seconds of overcurrent at six times the ampere rating. For maximum ground fault
coordination, there are eight delay bands. Long-time delay is an “inverse Long-Time Trip Functions
time” characteristic in that the delay time decreases as the current
increases.
The trip unit includes an alarm indicator that will be lit continuously when the
current is above 100% of the pickup setting.
The short-time pickup switch sets the short-circuit current level at which
the circuit breaker will trip after the set short-time delay. The short-time
current (Isd) equals the short-time pickup setting multiplied by the long-
time pickup (Ir).
The short-time delay switch sets the length of time the circuit breaker will
carry a short circuit within the short-time pickup range. The delay (based
on 10 times the ampere rating Ir) can be adjusted to four positions of I2t
ramp operation (I2t ON) or five positions of fixed time delays (I2t OFF). I2t Short-Time and
ON delay is an “inverse time” characteristic in that the delay time Instantaneous Trip
Functions
decreases as the current increases. Short-time delay for the 2.0 trip unit is
fixed at a delay band of 20 to 80 ms.
The instantaneous pickup switch sets the short-circuit current level at which the circuit breaker will trip
with no intentional time delay. The instantaneous current (Ii) is equal to the instantaneous pickup
setting multiplied by the sensor plug amperage (In).
The instantaneous function will override the short-time function if the instantaneous pickup is adjusted
at the same or lower setting than the short-time pickup. In trip units with both adjustable short-time and
instantaneous trip functions, the adjustable instantaneous trip can be disabled by setting
Instantaneous pickup to OFF.
The ground-fault pickup switch sets the current level at which the circuit
breaker will trip after the set ground-fault delay. Ground-fault pickup values Ir
.7
long time
.8
.9
tr
(s) 4
8
12
alarm
Ground-
(Ig) are based on circuit breaker sensor plug (In) only, not on the rating plug .6
.5
.4
x In
1
.95 2
.98 1
.5
16
20
24
@ 6 Ir Fault
multiplier (Ir). Changing the rating plug multiplier has no effect on ground-fault Isd
short time
tsd
.4 .4 .3
Ii
instantaneous
Pickup
3
4
5 (s) 6 8 10
2.5 6 .3 .2 4 12
pickup values.
2
1.5 10
8 .2
on
.1 0
.1
I2t off
3
2
15
off Ground-
x Ir x In
setting delay
test Fault
Ig tg
D
E
F (s)
.3
.4 .4 .3
.2
Delay
The ground-fault delay switch sets the length of time the circuit breaker will
C G
B H .2 .1
A J .1 0
on I2t off
ground fault
carry ground-fault current which exceeds the ground-fault pickup level before
tripping. The delay (based on the sensor plug amperage (In) can be adjusted
Ground-Fault Trip
to four positions of I2t ramp operation (I2t ON) or five positions of fixed time Functions
delays (I2t OFF). I2t ON delay is an “inverse time” characteristic in that the
delay time decreases as the current increases.
33
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
Communication Network
Masterpact NW/NT circuit breaker, and Micrologic trip unit information is available via a Modbus network to
Powerlogic™ System Manager™ software (SMS) or other applications for reporting and recording.
Information available includes:
The Modbus circuit breaker communication feature is standard on the Micrologic P and H trip units and
available for the Micrologic A trip unit.
The Modbus circuit breaker communication module (BCM) is installed in the circuit breaker and
requires a separate, isolated 24 Vdc power source. The BCM is optically coupled to the Micrologic trip
unit to ensure a high level of isolation between the trip unit and the communication network. The
Modbus BCM provides circuit breaker status via dedicated O/F (open or closed), SDE (fault tripped),
CH (spring charged), and PF (ready-to-close) switches and provides the capability of remotely
controlling the circuit breaker. It also maintains an event log of circuit breaker status containing the
number of times the circuit breaker has experienced each status position with the date and time of the
last transition. This information and the remote control capability are available to a Modbus supervisor
system via a Modbus communication network.
34
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
Status Indication
z ON/OFF Indication
z Connected/Disconnected/Test Pos.
z Ready-to-Close
z Fault Trip
Controls
z Opening/Closing
Circuit
Breaker and
Settings Trip Unit
A P H
z Reading of Settings on Rotary Switches X X X
z Fine Settings in the Range Imposed by the Rotary Switches X X
z Setting of Protection and Alarms X X
z Customized Alarm Programming X
35
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
Powerlogic System
System Manager, used for power systems and energy management, provides the human-machine
interface (HMI) for electrical system information on a PC:
• Screens including real-time readings, breaker status and remote control operation.
• Tables displaying real-time readings, maintenance information and date and time of last operation.
• Waveform captures including harmonic content.
• Tabular displays of event logs and data logs.
• Alarm annunciation and recording.
36
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Section 3—Accessories
37
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Two options are available for remote operation of Masterpact™ circuit breakers: direct connection or a
communication network.
NOTE: When remote operation features are used, a minimum of four seconds is required for the spring
charging motor (MCH) to completely charge the circuit breaker closing springs prior to actuating the
shunt close (XF) device.
The wiring diagrams for these two options are shown below.
The remote ON/OFF function is used to remotely open and close the circuit breaker. It is made up of
the following components:
• A spring-charging motor (MCH) equipped with a spring-charged limit switch; see page 39 for more
information.
• A shunt close (XF); see page 40 for more information.
• A shunt trip (MX1); see page 40 for more information.
Optionally, the function may be completed with:
• A ready-to-close contact (PF).
• An electrical closing push button (BPFE).
• A remote reset following a fault (RES).
The remote operation function may be completed with:
Masterpact Circuit Breaker Equipped
• Auxiliary contacts (OF). for Remote ON/OFF Function
Cluster shield is not shown
• Overcurrent trip switch (SDE).
38
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Terminals
Characteristics MCH
Vac 50/60 Hz 48/60, 100/130, 200/250, 240/277, 380/415, 400/440, 480
Voltage Ratings (Vn)
Vdc 24/30, 48/60, 100/125, 200/250
Operating Threshold 0.85 to 1.1 Vn
Power Consumption 180 VA
Motor Overcurrent 2–3 x In for 0.1 s
Charging Time 4 s maximum on NW, 3 s maximum on NT
Duty Cycle 3 cycles per minute maximum
10,000 cycles for NW < 4000 A
Endurance
5000 cycles for NW ≥ 4000 A
CH Contact 10 A at 240 V
39
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Maximum Wire Length—The inrush currents for these devices are approximately 200 VA. When low
supply voltages (12, 24 or 48 V) are used, the maximum allowable wire length is dependent on the
voltage and the wire size.
40
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
The undervoltage trip (MN) instantaneously opens the circuit breaker when its supply voltage drops to
a value between 35% and 70% of its rated voltage.
If the undervoltage trip is not energized, it is impossible to close the circuit breaker, either manually or
electrically. An attempt to close the circuit breaker produces no movement of the main contacts.
Closing is allowed when the supply voltage of the undervoltage trip reaches 85% of rated voltage.
Characteristics MN
24 Vac
48 Vac
120 Vac
Vac
240 Vac
50/60 Hz
277 Vac
380 Vac
Voltage Ratings (Vn)
480 Vac
12 Vdc
24 Vdc
Vdc 48 Vdc
125 Vdc
250 Vdc
Power Consumption (VA or W) Constant/Inrush 4.5/200
Opening 0.35 to 0.70 Vn
Operating Threshold
Closing 0.85 Vn
NW 90 ms ±10
Circuit Breaker Response Time at Vn
NT 40 ms ±10
41
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Ready-to-Close
Switch (PF)
42
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
• Following tripping, the remote reset (RES) resets the overcurrent trip switch (SDE) and the
mechanical indicator. (Voltage rating: 110/130 Vac and 200/240 Vac.) RES is not compatible with
an additional overcurrent trip switch (SDE2).
• Automatic reset after fault-trip: following tripping, a reset of the mechanical indicator (reset button)
is no longer required to enable circuit breaker closing (factory adjustable only).
43
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
44
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Three series of optional auxiliary switches are available for the cradle:
• Cradle position switches (CE) to indicate the connected position.
• Cradle position switches (CD) to indicate the disconnected position. This
position is indicated when the required clearance for isolation of the power
and auxiliary circuits is reached.
• Cradle position switches (CT) to indicate the test position. In this position, the
Cradle Position
power circuits are disconnected and the auxiliary circuits are connected. Switch (CE, CD, CT)
45
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
NOTE: MDGF and SGR are for use on circuit breakers with 400 A and higher sensors.
For SGR System: The sensor is installed around the connection of the transformer neutral point to
ground and connects to the Micrologic 6.0A, 6.0P or 6.0H trip units. SGR requires a modified
differential ground-fault (MDGF) sensor and MDGF interface module to connect to the trip unit.
For MDGF System: An MDGF sensor is installed on each phase and neutral of each circuit breaker
and connects to the Micrologic trip unit through an MDGF module. See MDGF Instruction Bulletin
48049-182.
Sensor plugs (standard) are used to set the sensor rating (In) of the
circuit breaker, are field replaceable and are offered at 50–100% of
frame rating. For a complete list of available sensor plugs see
Sensor Plug
selection information in Section 7.
46
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Power supply modules are available in six input voltages: 24/30 Vdc,
48/60 Vdc, 125 Vdc, 110/130 Vac, 200/240 Vac, and 380/415 Vac
(all +10%, -15%). The output voltage for each is 24 Vdc; the output power is
5 VA/5 W (ripple < 5%). The modules are not UL Listed.
When used with the Micrologic A, P, and H trip units, a power supply module
makes it possible to:
• Display currents less than 20% of sensor (In). External Power
Supply Module
• Maintain display of tripping causes after opening of the circuit breaker
(P and H trip units only).
• Store the value of the interrupted current (P and H trip units only).
• Power the M2C module (P and H trip units only).
External Battery
Backup Module
47
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
These contacts are used with the Micrologic P and H control units, and indicate the type of fault and
instantaneous or delayed threshold overruns (i.e trip unit protection pick-up, current/voltage
unbalance, under/over voltage, reverse power, phase rotation, under/over frequency, and load
shedding). The M2C unit is powered from the control unit’s 24 Vdc source (100 mA consumption); the
M6C unit requires an external 24 Vdc power supply (100 mA consumption).
They are programmed via the control unit using a
keypad or via a supervisory station with the COM
communication option. They may be programmed:
• with instantaneous return to the initial state;
• without return to the initial state;
• with return to the initial state following a delay.
M6C Programmable M2C Programmable
Contact Module Contact Module
48
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
GC-200 Relay
Merlin Gerin
Micrologic
Square D
Square D
Downstream Device
(sends output to RIM)
49
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Cradle Connections
Table 45: Masterpact NW UL Listed/ANSI Certified 3P/4P Drawout Circuit Breakers (Rear Connections)
Connector Ampere
3P Layout (Back/Side/Top) 4P Layout (Back/Side/Top)
Type Rating
800 to 2000 A
2500 to 3000 A
Rear-Connected
“T” Vertical
(RCTV)
3200 A (L1)
4000 to 5000 A
6000 A
800 to 2000 A
Rear-Connected
“T” Horizontal
(RCTH) 2500 to 3000 A
3200 A (L1)
4000 to 5000 A
Rear-Connected
Offset Vertical 3200 A
(RCOV) 2000 A (L1/L1F)
50
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Table 46: Masterpact NW UL Listed/ANSI Certified 3P/4P Drawout Circuit Breakers (Front Connections)
Connector Ampere
3P Layout (Back/Side/Top) 4P Layout (Back/Side/Top)
Type Rating
800 to 2000 A
Front-Connected
Flat (FCF)
3200 A (L1)
4000 A
800 to 3000 A
Front-Connected
“T” (FCT)
3200 A (L1)
4000 to 5000 A
Table 47: Masterpact NW UL Listed/ANSI Certified 3P/4P Fixed Circuit Breakers (Rear Connections)
Connector
Ampere Rating 3P Layout (Back/Side/Top) 4P Layout (Back/Side/Top)
Type
800 to 2000 A
2500 to 3000 A
Rear-Connected
“T” Vertical
(RCTV)
4000 to 5000 A
06133700
6000 A
51
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Table 47: Masterpact NW UL Listed/ANSI Certified 3P/4P Fixed Circuit Breakers (Rear Connections) (continued)
800 to 2000 A
Rear-Connected
“T” Horizontal 2500 to 3000 A
(RCTH)
4000 to 5000 A
Rear-Connected
Offset Vertical 3200 A
(RCOV)
06135503
06135504
Rear-Connected
Offset Vertical 4000 A (B)
(W-Frame)
(Special)
Table 48: Masterpact NW UL Listed/ANSI Certified 3P/4P Fixed Circuit Breakers (Front Connections)
Connector
Ampere Rating 3P Layout (Front/Side/Top) 4P Layout (Front/Side/Top)
Type
Front-Connected
800 to 2000 A
Flat (FCF)
06134409
Front-Connected
800 to 3000 A
“T” (FCT)
52
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Connector Ampere
3P Layout 4P Layout
Type Rating
Front-Connected
800 to 3200 A
Flat (FCF)
800 to 3200 A
4000 A
Rear-Connected
“T” Vertical
(RCTV)
5000 A
6300 A
800 to 3200 A
Rear-Connected
“T” Horizontal 4000 A
(RCTH)
4000b,
5000 A
53
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Connector Ampere
3P Layout 4P Layout
Type Rating
Front-Connected
800 to 3200 A
Flat (FCF)
800 to 3200 A
4000 A
Rear-Connected
“T” Vertical
(RCTV)
4000b,
5000 A
6300 A
800 to 3200 A
4000
Rear-Connected
“T” Horizontal
(RCTH)
4000b,
5000 A
54
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Table 51: Masterpact NT UL Listed/ANSI Certified 3P/4P Fixed and Drawout Circuit Breakers
Rear-Connected Vertical
N/A
1600 A
55
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Table 52: Masterpact NT IEC Rated 3P/4P Fixed and Drawout Circuit Breakers
56
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Test Equipment
57
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
58
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
The racking interlock is standard for UL and ANSI circuit breakers, and optional for IEC circuit
breakers. It prevents insertion of the racking handle unless the OFF push button is pressed. Not
available for IEC Rated Masterpact NT circuit breakers.
This option prevents the compartment door from being opened when the circuit breaker is in the closed
position. This kit includes:
A B C
Kit Contents
(A) Panel Interlocking Plate
(B) Circuit Breaker Interlocking Plate
(C) Interlocking Cables
(D) Bolts with Washers
D (E) Guide-Bolt with Washer
G (F) Interlocking Bracket
F (G) Calibration Tray
E
59
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
• Source changeover interlocks allow mechanical interlocking between two or three circuit breakers
(fixed and drawout).
NOTE: Source changeover interlocks for Masterpact NT circuit breakers are IEC only.
The racking interlock prevents racking in the circuit breaker when the door is
open. (Insertion of the circuit breaker racking handle is not possible when the
compartment door is open.)
The cradle rejection feature (standard) ensures that only the properly designated circuit breaker or
switch is matched with the selected cradle assembly.
Rail Padlocking
Rail padlocking is standard for UL, ANSI, and IEC cradles. When used in combination with the
disconnected position locking device, rail padlocking prevents the movement of the circuit breaker from
the disconnected position to the fully withdrawn position when the padlock hasp is pulled out and locked.
60
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
Miscellaneous Accessories
The mechanical operation counter (CDM) registers the total number of Mechanical
operating cycles. One CDM is installed per circuit breaker. Operation
Counter (CDM)
These door escutcheons provide a frame and seal for the circuit breaker.
61
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
The remote racking device allows the operator to perform circuit breaker racking operations from a
distance of up to 30 ft away from the circuit breaker using the controller. This distance exceeds the arc
flash boundary described in the arc flash safety guidelines outlined in NFPA-70E.
NW Cradle
Remote
Racking
Device
Controller
62
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Wiring Diagrams
63
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Wiring Diagrams
D NOTE: All diagrams show circuit breaker open, connected and charged.
C
A—Do not remove factory-installed jumpers between Z3, Z4 and Z5 unless ZSI is connected.
B—Do not remove factory-installed jumper between T1 and T2 unless neutral CT is connected. Do not install jumper between T3 and T4.
C—For proper wiring of neutral CT, refer to Instrucion Bulletin 48041-082-01 shipped with it.
D—24 Vdc power supply for trip unit must be separate and isolated from 24 Vdc power supply for communication modules.
E—When remote operation features are used, make sure there is a minimum of four seconds for the spring charging motor (MCH) to completely charge the circuit
breaker closing springs prior to actuating the shunt close (XF) device.
834 824 814 E5 E6 Z5 M1 M2 M3 F2+ V3 484/Q3 184/K2 84 334 324 314 D2/C12 C2 A2 254 B2
832 822 812 E3 E4 Z3 Z4 T3 T4 VN V2 474/Q2 182 82 332 322 312 C13 C3 A3 252 B3
831 821 811 E1 E2 Z1 Z2 T1 T2 F1– V1 471/Q1 181/K1 81 331 321 311 D1/C11 C1 A1 251 B1
or
CE6 CE5 CE4
64
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Wiring Diagrams
244 234 224 214 144 134 124 114 44 34 24 14 934 924 914
242 232 222 212 142 132 122 112 42 32 22 12 932 922 912
241 231 221 211 141 131 121 111 41 31 21 11 931 921 911
or or or or
EF24 EF23 EF22 EF21 EF14 EF13 EF12 EF11 CD6 CD5 CD4 CE9 CE8 C7
248 238 228 218 148 138 128 118 864 854 844 394 384 374
246 236 226 216 146 136 126 116 862 852 842 392 382 372
245 235 225 215 145 135 125 115 861 851 841 391 381 371
1 Fixed-mounted circuit breaker does not have cell switches (CE, CD, CT).
65
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Wiring Diagrams
A
E
B NOTE: All diagrams show circuit breaker open, connected and charged.
C D
A—Do not remove factory-installed jumpers between Z3, Z4 and Z5 unless ZSI is connected.
B—Do not remove factory-installed jumper between T1 and T2 unless neutral CT is connected. Do not install jumper between T3 and T4.
C—For proper wiring of neutral CT, refer to Instrucion Bulletin 48041-082-01 shipped with it.
D—24 Vdc power supply for trip unit must be separate and isolated from 24 Vdc power supply for communication modules.
E—When remote operation features are used, make sure there is a minimum of four seconds for the spring charging motor (MCH) to completely charge the circuit
breaker closing springs prior to actuating the shunt close (XF) device.
Remote Operation
D2 / C12 C2 A2 254 B2
C13 C3 A3 252 B3
D1/C11 C1 A1 251 B1
66
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Wiring Diagrams
CN1 - 440/480 V
9 11
“Spring
Charged“ R
Light
440/480 V
B3 B2
CH
MCH
380V
Spring-Charging Motor 440/480 Vac
(380 Vac Motor + Additional Resistor)
B1
CN2 - 440/480 V
67
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Wiring Diagrams
Alarm Contacts (OF1, OF2, OF3 and OF4 are standard equipment) Cradle Contacts
OF4
OF24: Open/Closed Circuit Breaker or Switch Position Contact CD3 CE3 CT3
OF3 Open/Closed Circuit Connected
Disconnected Test Position
Breaker or Switch or CD2 CE2 Position CT2
OF2 Position Contacts Contacts
Position Contacts Contacts
EF24: Combined Connected and Closed Contact CD1 CE1 CT1
OF1
OF23 or EF23 or or
OF22 or EF22 CE6 CE9
Connected
Connected
OF21 or EF21 CE5 CE8 Position
Position Contacts
CE4 Contacts
OF14 or EF14 CE7
OF13 or EF13 or
OF12 or EF12 CD6
Disconnected
OF22 or EF22 CD5 Position
OF11 or EF11 CD4 Contacts
68
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
Section 5—Masterpact NT Dimensional Drawings
MASTERPACT NT ENCLOSURE INFORMATION ..................................................................................... 70
UL LISTED AND ANSI CERTIFIED 3P DRAWOUT CIRCUIT BREAKERS ................................................ 70
800–1200 A Masterpact NT 3P Drawout—Master Drawing ................................................................... 71
800–1200 A Masterpact NT UL/ANSI 3P Drawout—RCTH Rear Connected “T” Horizontal ................. 71
800–1200 A Masterpact NT UL/ANSI 3P Drawout—RCTV Rear Connected “T” Vertical ..................... 72
800–1200 A Masterpact NT UL/ANSI 3P Drawout—FCF Front Connected Flat ................................... 72
800–1200 A Masterpact NT UL/ANSI 3P Drawout—Door Cutout Dimensions ...................................... 72
800–1200 A Masterpact NT UL/ANSI 3P Drawout—Pan Dimensions ................................................... 73
UL LISTED AND ANSI CERTIFIED 3P FIXED CIRCUIT BREAKERS ........................................................ 74
800–1200 A and 1600 A Masterpact NT UL/ANSI 3P Fixed—Master Drawing ..................................... 74
800–1200 A Masterpact NT UL/ANSI 3P Fixed—RCTH Rear Connected “T” Horizontal ...................... 75
800–1200 A Masterpact NT UL/ANSI 3P Fixed—RCTV Rear Connected “T” Vertical .......................... 75
800–1200 A Masterpact NT UL/ANSI 3P Fixed—FCF Front Connected Flat ........................................ 76
1600 A Masterpact NT UL/ANSI 3P Fixed—RCV Rear Connected Fixed Vertical ................................. 77
800–1200 A Masterpact NT UL/ANSI 3P Fixed—Door Cutout Dimensions .......................................... 77
800–1200 A Masterpact NT UL/ANSI 3P Fixed—Pan Dimensions ....................................................... 78
UL LISTED AND ANSI CERTIFIED 4P DRAWOUT CIRCUIT BREAKERS ................................................. 79
800–1200 A Masterpact NT UL/ANSI 4P Drawout—Master Drawing .................................................... 79
800–1200 A Masterpact NT UL/ANSI 4P Drawout—RCTH Rear Connected “T” Horizontal ................. 79
800–1200 A Masterpact NT UL/ANSI 4P Drawout—RCTV Rear Connected “T” Vertical ..................... 80
800–1200 A Masterpact NT UL/ANSI 4P Drawout—FCF Front Connected Flat ................................... 80
800–1200 A Masterpact NT UL/ANSI 4P Drawout—Door Cutout Dimensions ...................................... 81
800–1200 A Masterpact NT UL/ANSI 4P Drawout—Pan Dimensions ................................................... 81
UL LISTED AND ANSI CERTIFIED 4P FIXED CIRCUIT BREAKERS ........................................................ 82
800–1200 A Masterpact NT UL/ANSI 4P Fixed—Master Drawing ........................................................ 82
800–1200 A Masterpact NT UL/ANSI 4P Fixed—RCTH Rear Connected “T” Horizontal ...................... 82
800–1200 A Masterpact NT UL/ANSI 4P Fixed—RCTV Rear Connected “T” Vertical .......................... 83
800–1200 A Masterpact NT UL/ANSI 4P Fixed—FCF Front Connected Flat ........................................ 83
800–1200 A Masterpact NT UL/ANSI 4P Fixed—Door Cutout Dimensions .......................................... 84
800–1200 A Masterpact NT UL/ANSI 4P Fixed—Pan Dimensions ....................................................... 84
IEC RATED 3P DRAWOUT CIRCUIT BREAKERS ...................................................................................... 85
800–1600 A Masterpact NT 3P Drawout—Master Drawing ................................................................... 85
800–1600 A Masterpact NT IEC 3P Drawout—RCTV Rear Connected “T” Vertical ............................. 85
800–1600 A Masterpact NT IEC 3P Drawout—RCTH Rear Connected “T” Horizontal ......................... 86
800–1600 A Masterpact NT IEC 3P Drawout—FCF Front Connected Flat ........................................... 86
800–1200 A Masterpact NT IEC 3P Drawout—Rear Cutout Dimensions .............................................. 87
IEC RATED 3P FIXED CIRCUIT BREAKERS ............................................................................................. 88
800–1600 A Masterpact NT 3P Fixed—Master Drawing ....................................................................... 88
800–1600 A Masterpact NT IEC 3P Fixed—RCTV Rear Connected “T” Vertical .................................. 88
800–1600 A Masterpact NT IEC 3P Fixed—RCTH Rear Connected “T” Horizontal .............................. 89
800–1600 A Masterpact NT IEC 3P Fixed—FCF Front Connected Flat ................................................ 89
800–1200 A Masterpact NT IEC 3P Fixed—Rear Cutout Dimensions .................................................. 90
IEC RATED 4P DRAWOUT CIRCUIT BREAKERS ..................................................................................... 91
800–1600 A Masterpact NT 4P Drawout—Master Drawing ................................................................... 91
800–1600 A Masterpact NT IEC 4P Drawout—RCTV Rear Connected “T” Vertical ............................. 91
800–1600 A Masterpact NT IEC 4P Drawout—RCTH Rear Connected “T” Horizontal ......................... 92
800–1600 A Masterpact NT IEC 4P Drawout—FCF Front Connected Flat ........................................... 92
800–1200 A Masterpact NT IEC 4P Drawout—Rear Cutout Dimensions .............................................. 93
IEC RATED 4P FIXED CIRCUIT BREAKERS ............................................................................................. 94
800–1600 A Masterpact NT 4P Fixed—Master Drawing ....................................................................... 94
800–1600 A Masterpact NT IEC 4P Fixed—RCTV Rear Connected “T” Vertical .................................. 94
800–1600 A Masterpact NT IEC 4P Fixed—RCTH Rear Connected “T” Horizontal .............................. 95
800–1600 A Masterpact NT IEC 4P Fixed—FCF Front Connected Flat ................................................ 95
800–1200 A Masterpact NT IEC 4P Fixed—Rear Cutout Dimensions .................................................. 96
NEUTRAL CURRENT TRANSFORMERS FOR MASTERPACT NT CIRCUIT BREAKERS ....................... 96
800–1200 A External Neutral Current Transformer ................................................................................ 96
800–1200 A External Neutral Current Transformer (Switchboards and Switchgear .............................. 97
800–1200 A External Neutral Current Transformer (Panelboards) ........................................................ 97
69
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
70
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
71
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
72
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
DRAWOUT
FIXED
in.
Dimensions:
[mm]
73
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
74
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
75
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
76
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
77
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
DRAWOUT
FIXED
in.
Dimensions:
[mm]
78
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
79
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
80
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
81
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
82
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
83
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
84
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
85
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
86
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
87
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
88
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
89
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
90
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
91
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
92
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
93
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
94
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
95
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
96
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NT Dimensional Drawings
Figure 66: 800–1600 A External Neutral Current Transformer (Switchboards and Switchgear)
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
97
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
98
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
99
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
Enclosure Information
Figure 68: 800–3000 A and 4000 A (H1, H2, H3) Master Drawing
in.
Dimensions:
[mm]
100
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
101
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
102
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
103
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
104
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
105
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
106
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
107
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
Figure 83: 800–3000 A and 3200 A (H1, H2, H3) Door Cutout
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
108
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
109
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
110
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
111
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
112
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
113
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
114
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
115
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
116
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
Figure 99: 800–3200 A and 4000 A (W-Frame) Circuit Breaker Door Cutout
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
117
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
118
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
119
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
120
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
121
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
122
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
123
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
124
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
125
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
126
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
127
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
128
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
129
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
130
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
131
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
132
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
133
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
Dimensions: in.
134
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
135
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
136
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
137
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
138
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
139
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
140
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
141
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
142
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
143
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
144
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
145
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
146
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
147
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
148
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
149
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
150
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
151
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
in.
Dimensions:
[mm]
152
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact NW Dimensional Drawings
in.
Dimensions:
[mm]
153
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
Section 7—Selection
INTRODUCTION ........................................................................................................................................155
Overview of Selection Procedure .........................................................................................................155
FACTORY-ASSEMBLED CIRCUIT BREAKERS AND SWITCHES ...........................................................157
T-Frame Circuit Breaker Selection ........................................................................................................157
T-Frame Switch Selection......................................................................................................................158
W-Frame Circuit Breaker Selection .......................................................................................................159
W-Frame Switch Selection ....................................................................................................................162
Y-Frame Circuit Breaker Selection .......................................................................................................164
Y-Frame Switch Selection ....................................................................................................................165
154
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
Introduction
1. Select the completely assembled circuit breaker (circuit breaker frame plus trip unit):
— The frame ampere rating required
— The interrupting rating required
— The sensor plug rating required
— The connections
2. Select the trip unit, rating plug, and trip unit options.
3. Select circuit breaker frame options, if required.
4. Select cradle options, if required.
155
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
Model Number NT NW NW
Frame type T W Y (wide-construction)
ANSI UL UL IEC ANSI ANSI UL IEC ANSI UL IEC
Maximum frame rating
800 A 1200 A 1600 A 1600 A 3200 A 4000 A 3000 A 4000 A 6000 A 6000 A 6300 A
Construction
Drawout X X — X X — X X X X X
Fixed (UL Listed and IEC Rated only) X X X X X X X X X X X
Termination
Rotatable rear terminals X X X X X X X X X X X
Front-connected terminals X X X X X X X X X X X
156
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
Table 64: ANSI C37 Certified/UL 1066 Listed T-Frame Circuit Breakers
NOTE: L1F and LF circuit breakers are tested to show the arc flash hazard risk category as referenced
by NFPA 70E.
157
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
Table 67: ANSI C37 Certified/UL 1066 Listed, Non-Automatic T-Frame Switch
158
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
NOTE: L1F circuit breakers are tested to show the arc flash hazard risk category as referenced by
NFPA 70E.
159
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
NOTE: LF circuit breakers are tested to show the arc flash hazard risk category as referenced by
NFPA 70E.
160
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
161
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
800 A NW08HA 65 kA 65 kA 65 kA 65 kA
1600 A NW16HA 65 kA 65 kA 65 kA 65 kA
2000 A NW20HA 65 kA 65 kA 65 kA 65 kA
3200 A NW32HA 65 kA 65 kA 65 kA 65 kA
1 When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Table 74: ANSI C37 Certified/UL 1066 Listed, Drawout Automatic Switch
Table 75: ANSI C37 Certified/UL 1066 Listed, Fixed Automatic Switch
162
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
800 A NW08HF 85 kA 85 kA 85 kA 85 kA
1000 A NW10HF 85 kA 85 kA 85 kA 85 kA
1250 A NW12HF 85 kA 85 kA 85 kA 85 kA
1600 A NW16HF 85 kA 85 kA 85 kA 85 kA
2000 A NW20HF 85 kA 85 kA 85 kA 85 kA
2500 A NW25HF 85 kA 85 kA 85 kA 85 kA
3200 A NW32HF 85 kA 85 kA 85 kA 85 kA
4000 A NW40HF 85 kA 85 kA 85 kA 85 kA
1 The withstand rating is the fault current (at rated voltage) that the switch will withstand without
damage when protected by a circuit breaker with an equal continuous current rating.
163
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
NW08NA 42 kA 42 kA 42 kA — 42 kA
800 A NW08HA 50 kA 50 kA 50 kA — 50 kA
NW08HA102 — — — 50 kA 50 kA
NW10NA 42 kA 42 kA 42 kA — 42 kA
1000 A NW10HA 50 kA 50 kA 50 kA — 50 kA
NW10HA102 — — — 50 kA 50 kA
NW12NA 42 kA 42 kA 42 kA — 42 kA
1250 A NW12HA 50 kA 50 kA 50 kA — 50 kA
NW12HA102 — — — 50 kA 50 kA
NW16NA 42 kA 42 kA 42 kA — 42 kA
1600 A NW16HA 50 kA 50 kA 50 kA — 50 kA
NW16HA102 — — — 50 kA 50 kA
NW20HA 50 kA 50 kA 50 kA — 50 kA
2000 A
NW20HA102 — — — 50 kA 50 kA
NW25HA 50 kA 50 kA 50 kA — 50 kA
2500 A
NW25HA102 — — — 50 kA 50 kA
NW32HA 50 kA 50 kA 50 kA — 50 kA
3200 A
NW32HA102 — — — 50 kA 50 kA
NW40HA 50 kA 50 kA 50 kA — 50 kA
4000 A
NW40HA102 — — — 50 kA 50 kA
1 When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
2 Not available for fixed-mounted circuit breakers.
Table 80: ANSI C37 Certified/UL 1066 Listed Y-Frame Circuit Breakers
164
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
4000 A NW40HA 85 kA 85 kA 85 kA 85 kA
5000 A NW50HA 85 kA 85 kA 85 kA 85 kA
1 When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Table 84: ANSI C37 Certified/UL 1066 Listed, Drawout Automatic Switches
Table 85: ANSI C37 Certified/UL 1066 Listed, Fixed Automatic Switches
165
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
4000 A NW40BHA 85 kA 85 kA 85 kA 85 kA
5000 A NW50HA 85 kA 85 kA 85 kA 85 kA
6300 A NW63HA 85 kA 85 kA 85 kA 85 kA
1 When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
166
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Trip Curves
167
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Trip Curves
.06
.07
.08
.09
.15
1.5
10
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
6
7
8
9
10000 10000
9000 9000
8000 8000
7000 7000 Characteristic Trip Curve No. 613-1
6000 6000
5000 5000
Ground Fault I2t OFF and ON
4000 4000
1500 1500
1000 1000
900 900
800 800
700 700
600 600
500 500
400 400
300 300
200
GROUND-FAULT
200 The time-current curve information is to be used for
150 PICKUP
x In
150 application and coordination purposes only.
100
90
100
90
Curves apply from -30°C to +60°C (-22°F to +140°F)
80
70
80
70
ambient temperature.
60 60
50 50
40 40
30 30
15 15
10 0.4 10
9 9
8 8
7 7
6 6
TIME IN SECONDS
5 5
4 4
0.6 0.8 1.0
3 3
2 2
1.5 1.5
DELAY
SECONDS AT 1 x In
1 1
.9
0.1 .9
0.2
0.4
.8 .8
.7 0.3 .7
ON
0.4
0.3
.6 .6
ON
.5 .5
0.2
.4 .4
DELAY BANDS
I2t ON
0.1
.3 .3
ON
0.3 OFF
MAXIMUM
.2 .2
UNRESTRAINED
GROUND-FAULT 0.2 OFF
.15 DELAY .15
.1 0.1 OFF .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
GROUND-FAULT
.04 DELAY BANDS .04
I2t OFF
.03
(FIXED DELAY) .03
0
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.05
.06
.07
.08
.09
1.5
6
7
8
9
10
168
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Trip Curves
Figure 165: Micrologic 6.0 A/P/H Trip Units: 400 A < In ≤ 1200 A
.06
.07
.08
.09
.15
1.5
10
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
6
7
8
9
10000 10000
9000 9000
8000
7000
8000
7000 Ground Fault I2t OFF and ON
6000 6000
5000 5000
400 A < In ≤ 1200 A
4000 4000
3000 3000
2000 2000
1500 1500
1000 1000
900 900
800 800 The time-current curve information is to be used for
700 700
600 600 application and coordination purposes only.
500 500
150 150
100 100
90 90
80
GROUND-FAULT 80
70
PICKUP 70
x In
60 60
50 50
40 40
30
0.2 0.3 0.5 0.7 0.9 30
20 20
15 15
10 10
9 9
8 8
7 7
6
0.4 0.6 0.8 1.0 6
TIME IN SECONDS
5 5
0.4
4 4
ON
3 3
0.2
2 2
ON
1.5 1.5
DELAY
SECONDS AT 1 x In
1 1
.9 0.1 .9
.8 0.2 .8
.7 0.3 .7
0.4
.6 .6
.5 .5
0.3
DELAY BANDS
I2t ON
.3 .3
0.3 OFF
0.1
N O
MAXIMUM
.2 .2
UNRESTRAINED
GROUND-FAULT 0.2 OFF
.15 DELAY .15
.1 0.1 OFF .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
GROUND-FAULT
.04 DELAY BANDS .04
I2t OFF
.03 (FIXED DELAY) .03
0
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.05
.06
.07
.08
.09
1.5
6
7
8
9
10
169
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Trip Curves
.06
.07
.08
.09
.15
1.5
10
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
6
7
8
9
10000 10000
9000 9000
8000
7000
8000
7000
Ground Fault I2t OFF and ON
6000 6000
3000 3000
2000 2000
1500 1500
400 400
ambient temperature.
300 300
200 200
150
GROUND-FAULT 150
PICKUP
1120 A
800 A
x In
100 100
90 90
80 80
70 70
960 A
60 60
50 50
640 A
40 40
30 30
20 20
880 A
15 15
10 10
9 9
8 8
7 7
1040 A
6 6
TIME IN SECONDS
5 5
720 A
4 4
3 3
2 2
1200 A
1.5 1.5
500 A
DELAY
SECONDS AT 1 x In
1 1
.9
0.1 .9
0.4
.8
0.2 .8
0.3
ON
.7 .7
0.2
0.4
.6 .6
ON
.5 .5
0.3
.4 .4
DELAY BANDS
I2t ON
.3 .3
0.1
0.3 OFF
ON
MAXIMUM
.2 .2
UNRESTRAINED
GROUND-FAULT 0.2 OFF
.15 DELAY .15
.1 0.1 OFF .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
GROUND-FAULT
.04 DELAY BANDS .04
I2t OFF
.03 (FIXED DELAY) .03
0
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.05
.06
.07
.08
.09
1.5
6
7
8
9
10
170
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Trip Curves
Figure 167: Micrologic 5.0/6.0 A/P/H Trip Units: Long-Time Pickup and Delay, Short-Time Pickup, and I2t OFF Delay
100
Characteristic Trip Curve No. 613-4
1.5
10
15
20
30
40
50
60
70
80
90
.5
.6
.7
.8
.9
1
6
7
8
9
10000 10000
9000 9000
8000 8000
7000 7000 Long-Time Pickup and Delay
6000 6000
2000 2000
The time-current curve information is to be used for
1500 1500
application and coordination purposes only.
1000 1000
900
800
900
800 Curves apply from -30°C to +60°C (-22°F to +140°F)
700 700
600 600 ambient temperature.
500
24 500
16
400 400
300 300
24
normal. The amount of time delay reduction is
15 15
5 5
4 4
2. The end of the curve is determined by the
3 3
interrupting rating of the circuit breaker.
2 2 3. With zone-selective interlocking ON, short-time
1.5 1.5 delay utilized, and no restraining signal, the
1
8
1
maximum unrestrained short-time delay time band
SHORT-TIME 10 SHORT-TIME
.9
.8 PICKUP 6 DELAY I2t OFF
.9
.8 applies regardless of the setting.
.7 x Ir 1.5 2 2.5 (FIXED-TIME DELAY) .7
SECONDS AT 10 x Ir
.6
4 .6
4. Total clearing times shown include the response
.5 .5
.4
3 5 0.4 OFF .4
times of the trip unit, the circuit breaker opening, and
.3 .3
the extinction of the current.
0.3 OFF
.2
MAXIMUM
.2
5. For a withstand circuit breaker, instantaneous can
UNRESTRAINED
.15
SHORT-TIME
DELAY
0.2 OFF
.15
be turned OFF. See trip curve 613-7 for
instantaneous trip curve. See trip curve 613-10 for
0.1 OFF
.1
.09
.1
.09 instantaneous override values.
.08 .08
.07
.06
.07
.06
6. Overload indicator illuminates at 100%.
.05 .05
.04 .04
.03 .03
0
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
1
1.5
6
7
8
9
10
.5
.6
.7
.8
.9
15
20
30
40
50
60
70
80
90
100
171
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Trip Curves
Figure 168: Micrologic 5.0/6.0 A/P/H Trip Units: Short-Time Pickup and I2t ON Delay
CURRENT IN MULTIPLES OF Ir (Ir = LONG-TIME SETTING x In) Micrologic 5.0/6.0 A/P/H Trip Units
100
1.5
10
15
20
30
40
50
60
70
80
90
.5
.6
.7
.8
.9
1
6
7
8
9
10000
9000
10000
9000
Characteristic Trip Curve No. 613-5
8000 8000
5000 5000
4000 4000
3000 3000
2000 2000
1500 1500
1000 1000
900 900
800 800 The time-current curve information is to be used for
700 700
600 600 application and coordination purposes only.
500 500
150 150
SHORT-TIME
100
90
PICKUP
x Ir
100
90 NOTE:
80 80
70
1.5 2 2.5 6 8 10 70
60 60 1. There is a thermal-imaging effect that can act to
50 50
shorten the long-time delay. The thermal-imaging
40 40
3 4 5 effect comes into play if a current above the long-time
30 30
delay pickup value exists for a time and then is cleared
20 20 by the tripping of a downstream device or the circuit
15 15 breaker itself. A subsequent overload will cause the
circuit breaker to trip in a shorter time than normal. The
10 10
9
8
9
8
amount of time delay reduction is inverse to the
7
6
7
6
amount of time that has elapsed since the previous
TIME IN SECONDS
0.4
4 4
between overloads to completely reset thermal-
3 3
imaging.
0.2
ON
1.5 1.5
0.3
ON
1 1
.9 .9
.8 .8 utilized, and no restraining signal, the maximum
.7 .7
.6 .6 unrestrained short-time delay time band applies
.5
0.4 ON
.5
regardless of the setting.
.4 .4
SHORT-TIME
.3
DELAY I2t ON .3
4. Total clearing times shown include the response times
SECONDS AT 10 x Ir 0.3 ON
of the trip unit, the circuit breaker opening, and the
MAXIMUM
.2
UNRESTRAINED
SHORT-TIME
.2
extinction of current.
0.2 ON
.15 DELAY .15
5. For withstand circuit breaker, instantaneous can be
.1
.09
0.1 ON .1
.09
turned OFF. See trip curve 613-7 for instantaneous trip
.08
.07
.08
.07
curve. See trip curve 613-10 for instantaneous
.06
.05
.06
.05
override values.
.04 .04 6. See trip curve 613-4 for long-time pickup and delay trip
.03 .03 curve.
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
1
1.5
6
7
8
9
10
.5
.6
.7
.8
.9
15
20
30
40
50
60
70
80
90
100
172
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Trip Curves
Figure 169: Micrologic 5.0/6.0 Trip Units: Instantaneous Pickup, 2x to 15x and OFF
08/7,3/(62)6(16255$7,1* ,Q
MICROLOGIC® 5.0/6.0 A/P/H TRIP UNIT
CHARACTERISTIC TRIP CURVE NO. 613-7
Instantaneous Pickup
2x–15x and OFF
The time-current curve information is to be used
for application and coordination purposes only.
Curves apply from -30° to +60°C ambient
temperature.
Notes:
1. The end of the curve is determined by the
interrupting rating of the circuit breaker.
2. Total clearing times shown include the
response times of the trip unit, the circuit
breaker opening, and the extinction of the
current.
3. The instantaneous region of the trip curve
shows maximum total clearing times. Actual
clearing times in this region can vary
depending on the circuit breaker mechanism
,167$17$1(286
design and other factors. The actual clearing
3,&.83
[,Q
time can be considerably faster than indicated.
Contact your local Sales Office for additional
information.
4. For a withstand circuit breaker, instantaneous
can be turned OFF. See 613-7 for
10 x
instantaneous trip curve. See 613-10 for
instantaneous override values.
5. See 613-4 and 613-5 for long-time pickup,
long-time delay, short-time pickup, and short-
time delay trip curves.
7,0(,16(&21'6
2x 3x 4x 6x 8x 12 x 15 x
&<&/(
&<&/(
08/7,3/(62)6(16255$7,1* ,Q
173
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Trip Curves
Figure 170: Micrologic 3.0A Trip Unit: Long-Time Pickup and Delay
CURRENT IN MULTIPLES OF Ir (Ir = LONG-TIME SETTING x In) Micrologic 3.0A Trip Unit
100
1.5
10
15
20
30
40
50
60
70
80
90
.5
.6
.7
.8
.9
1
6
7
8
9
10000
9000
10000
9000 Characteristic Trip Curve No. 613-6
8000 8000
7000 7000
6000 6000 Long-Time Pickup and Delay
5000 5000
2000 2000
The time-current curve information is to be used for
1500 1500
application and coordination purposes only.
1000 1000
900
800
900
800
Curves apply from -30°C to +60°C (-22°F to +140°F)
700
700
600 600
ambient temperature.
500 500
5 5
1.5 1.5
4. See trip curve 613-8 for instantaneous pickup trip
curve.
1 1
.9 .9
.8 .8
.7 .7
.6 .6
.5 .5
.4 .4
.3 .3
.2 .2
.15 .15
.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
.04 .04
.03 .03
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
1
1.5
6
7
8
9
10
.5
.6
.7
.8
.9
15
20
30
40
50
60
70
80
90
100
174
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Trip Curves
Figure 171: Micrologic 3.0A Trip Unit: Instantaneous Pickup, 1.5X to 12X
08/7,3/(62)6(16255$7,1* ,Q
MICROLOGIC® 3.0 A TRIP UNIT
CHARACTERISTIC TRIP CURVE NO. 613-8
Instantaneous Pickup
1.5x-12x
The time-current curve information is to be used
for application and coordination purposes only.
Curves apply from -30° to +60°C ambient
temperature.
Instantaneous override values are given on
613-10.
Notes:
1. The end of the curve is determined by the
interrupting rating of the circuit breaker.
2. Total clearing times shown include the
response times of the trip unit, the circuit
breaker opening, and the extinction of the
current.
3. The instantaneous region of the trip curve
shows maximum total clearing times. Actual
,167$17$1(286
3,&.83
clearing times in this region can vary
[,Q depending on the circuit breaker mechanism
design and other factors. The actual clearing
time can be considerably faster than indicated.
Contact your local Sales Office for additional
information.
5x 10 x 4. See 613-6 for long-time pickup and delay trip
curves.
7,0(,16(&21'6
&<&/(
&<&/(
08/7,3/(62)6(16255$7,1* ,Q
175
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Trip Curves
100
1.5
10
15
20
30
40
50
60
70
80
90
.5
.6
.7
.8
.9
1
6
7
8
9
10000 10000
9000 9000
8000
7000
8000
7000
Short-Time Pickup with No Delay
6000 6000
5000 5000
4000 4000
LONG-TIME PICKUP
3000
x In = Ir 3000
30
2 30
amount of time delay reduction is inverse to the
1 amount of time that has elapsed since the previous
.5
20 20
overload. Approximately twenty minutes is required
24
15 15
between overloads to completely reset thermal-
16
10 10
imaging.
9 9
LONG-TIME
8
7
DELAY BANDS
8
7
2. The end of the curve is determined by the short-time
SECONDS AT 6 x Ir
6 6
setting.
TIME IN SECONDS
5 5
.4 3 5 .4
.3 .3
.2 .2
.15 .15
.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
.04 .04
.03 .03
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
1
1.5
6
7
8
9
10
.5
.6
.7
.8
.9
15
20
30
40
50
60
70
80
90
100
176
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Trip Curves
Figure 173: Micrologic 2.0/3.0/5.0/6.0 A/P/H Trip Unit Instantaneous Override Values
177
© 2000–2014 Schneider Electric 05/2014
All Rights Reserved ™
Masterpact™ NT and NW Universal Power Circuit Breakers
Trip Curves
Figure 174: Masterpact NW Low Arc Flash Circuit Breaker: L1F and LF
.5
USER DEFINED RANGE: AUTOMATIC RANGE:
FAULT LEVEL MUST NO USER CONFIGURABLE SETTINGS
.4 TRIP BREAKER IN
INSTANTANEOUS MODE
.3 (1.2X PICKUP)
.2
.15
TIME IN SECONDS
.1
.09
.08
.07
.06
.05
.04
.03
.02
.015
.01
.009
.008
.007
.006
.005
1
7
8
9
10
15
20
30
40
50
60
70
80
90
100
150
200
300
400
500
600
700
800
900
1000
2 In - NW08 FAULT CURRENT (KA)
Figure 175: Masterpact NT Low Arc Flash Circuit Breaker: L1F and LF
.2
.15
TIME IN SECONDS
.1
.09
.08
.07
.06
.05
.04
.03
.02
.015
.01
.009
.008
.007
.006
.005
1
6
7
8
9
10
15
20
30
40
50
60
70
80
90
100
150
200
300
400
500
600
700
800
900
1000
178
05/2014 © 2000–2014 Schneider Electric
™
All Rights Reserved
© 2000–2014 Schneider Electric All Rights Reserved
Schneider Electric USA, Inc. Square D™, Schneider Electric™, Masterpact™, and Micrologic™ are trademarks owned by
1415 S. Roselle Road Schneider Electric Industries SAS or its affiliated companies. All other trademarks are the property
Palatine, IL 60067 USA of their respective owners.
1-888-778-2733
www.us.SquareD.com 0613CT0001 R05/14 Replaces 0613CT0001 R12/13
05/2014