GCB Specs
GCB Specs
7.08.01 General
The Generator circuit breaker (GCB) will be designed and fabricated for
installation in generator isolated phase bus duct system. The GCB will be used to
perform the following functions:
d) Interrupting load and fault currents from network and generator source
within the interrupting capability specified.
7.08.02.1 The switchgear covered by this contract specification is intended for indoor use
and consists of SF6 circuit breaker; disconnect switches; earthing switches on
both sides of the circuit breaker; one common control cabinet; common base
frame for mounting GCB; structure and platforms for maintenance of breaker.
a) General
i) The circuit breaker will be of self blast type and use SF6 as
insulating and interrupting medium having two separate contact
systems, one for load current carrying and one for arc
interruption. The circuit breaker will have a basic impulse level
rating as per enclosed data sheet. The circuit breaker will be
operated with a spring drive mechanism
b) Operating Mechanism
f) SF6 Supervision
A SF6 gas density monitor will be supplied for each three phase circuit
breaker. One contact will be provided to indicate that the gas density has
reached a level where refilling the gas volumes is necessary.
Dual trip coils will be provided. One circuit (primary) will be wired in
the normal breaker control scheme; and the secondary circuit wired to
terminal blocks for Owner’s use. This secondary trip circuit will include
all the interlocking associated with the primary circuit.
h) Accessories
a) The disconnect switches will be of the sliding tube type, air insulated,
gang-operated, motor driven with emergency manual drive; and each
phase assembly will be integrated with the circuit breaker into one single
phase, tubular aluminum enclosure forming a straight section of an
isolated phase bus. The disconnect switch will have the same current
carrying capacity as the circuit breaker.
a) The grounding switches will be of the rotary blade type, air insulated,
gang-operated motor driven with emergency manual drive; and will be
integrated with circuit breaker and the disconnect switches into one
single phase, tubular aluminium enclosure forming a straight section of
an isolated phase bus. The isolating gap will be visible from outside. No
making or breaking capabilities are required for the grounding switches,
via window scope.
b) The controls of the each grounding switch including the interlocking
circuits will be accommodated in the circuit breaker control cabinet. A
local remote switch and push buttons for local control of each grounding
switch will be provided.
7.08.02.6 Insulation
a) The circuit breaker with contacts open and insulating gas at atmospheric
pressure will be capable of withstanding an out-of-phase voltage across
the terminals with the phase angle between the two voltages continuously
varying. This requirement will assure that the circuit breaker in the open
position is capable of withstanding voltages to which they can be
subjected under such conditions as system being out-of-phase.
7.08.028 Nameplate
7.08.02.9 Conductors
c) Peak : 300
a) Ambient : 50
b) Busbar : 90
c) Enclosure : 70