Lecture 9
Lecture 9
Here we consider only simple systems, so that the effect of integral and derivative control action
on system performance can be clearly seen.
Integral Control Action:
1
In the proportional control of a plant whose transfer function does not possess an integrator ,
𝑠
there is a steady-state error, or offset, in the response to a step input. Such an offset can be
eliminated if the integral control action is included in the controller.
Figure: (a) Plots of e(t) and u(t) curves showing nonzero control signal when the actuating error
signal is zero (integral control); (b) plots of e(t) and u(t) curves showing zero control signal when
the actuating error signal is zero (proportional control)
Such a system without an integrator in the feedforward path always has a steady-
state error in the step response. Such a steady-state error is called an offset.
Integral control of system eliminates the steady state error in the response to step input.
The steady state error due to step disturbance torque of magnitude 𝑇𝑑 is given by,
𝑒𝑠𝑠 = lim 𝑠𝐸 (𝑠)
𝑠→0
−𝑠 𝑇𝑑 𝑇𝑑
𝑒𝑠𝑠 = lim = −
𝑠→0 𝐽𝑠 2 + 𝑏𝑠 + 𝐾𝑝 𝑠 𝐾𝑝
The steady-state output due to the step disturbance torque is
𝑇𝑑
𝑐𝑠𝑠 = −𝑒𝑠𝑠 =
𝐾𝑝
The steady-state error can be reduced by increasing the value of the gain 𝐾𝑝 . Increasing
this value, however, will cause the system response to be more oscillatory.
Response to Torque Disturbances (Proportional-Plus-Integral Control):
• If integral control action is added to the controller, then, as long as there is an error
signal, a torque is developed by the controller to reduce this error, provided the
control system is a stable one.
What will happen if the Controller were an Integral Controller like in the below figure ?
then the system always becomes unstable, because the characteristic equation
𝐽𝑠 3 + 𝑏𝑠 2 + 𝐾 = 0
will have roots with positive real parts. Such an unstable system cannot be used in
practice.
Figure: (a) Proportional control of a system with inertia load; (b) response to a unit-step input.
Closed Loop transfer function,
𝐶(𝑠) 𝐾𝑃
= 2
𝑅(𝑠) 𝐽𝑠 + 𝐾𝑃
Characteristic equation,
𝐽𝑠 2 + 𝐾𝑃 = 0
Roots → Imaginary, response to unit step input oscillates.
So, the addition of derivative control is required to stabilize the system.
Figure: (a) Proportional-plus-derivative control of a system with inertia load; (b) response to a
unit-step input
Closed loop transfer function,
𝐶(𝑠) 𝐾𝑝 (1 + 𝑇𝑑 𝑠)
= 2
𝑅(𝑠) 𝐽𝑠 + 𝐾𝑝 𝑇𝑑 𝑠 + 𝐾𝑝
The characteristic equation
𝐽𝑠 2 + 𝐾𝑝 𝑇𝑑 𝑠 + 𝐾𝑝 = 0
now has two roots with negative real parts for positive values of 𝐽, 𝐾𝑝 𝑎𝑛𝑑 𝑇𝑑 .
Thus, derivative control introduces a damping effect.
Steady-State Errors:
Thus the steady state error in terms of static position error constant 𝐾𝑝 ,
1
𝑒𝑠𝑠 =
1 + 𝐾𝑝