Catalogo Upgrade Manual For AccuLoad III Models S and Q Ferrum Energy
Catalogo Upgrade Manual For AccuLoad III Models S and Q Ferrum Energy
Catalogo Upgrade Manual For AccuLoad III Models S and Q Ferrum Energy
Aliado Comercial:
Caution
The default or operating values used in this manual and in the program of the AccuLoad IV are for factory testing
only and should not be construed as default or operating values for your metering system. Each metering system
is unique and each program parameter must be reviewed and programmed for that specific metering system ap-
plication.
Disclaimer
TechnipFMC hereby disclaims any and all responsibility for damages, including but not limited to consequential
damages, arising out of or related to the inputting of incorrect or improper program or default values entered in
connection with the AccuLoad IV.
Technical Support
Contact Information:
Field Service Response Center
24/7 Technical Support/Schedule a Technician: 1-844-798-3819
System Installation Supervision, Start-Up, and Commissioning Services Available
Customer Support
Contact Information:
Customer Service
TechnipFMC
FMC Technologies Measurement Solutions Inc.
1602 Wagner Avenue
Erie, Pennsylvania 16510 USA
P: +1 814 898-5000
F: +1 814 899-8927
[email protected]
TechnipFMC.com
Literature Library:
http://info.smithmeter.com/literature/online_index.html
Diagrams ........................................................................... 12
Figure 1 – ALIV-ST Board Placement ........................ 12
Figure 2 – ALIV-QT Exploded View ........................... 12
Figure 3 – ALIV-ST Hinge Bolt Location .................... 13
Figure 4 – ALIV-QT Cover Hinge Location................. 13
Figure 5 – Display Ethernet Port Location ................. 14
Figure 6 – Power Connection for HMI........................ 14
Figure 7 – ALIV-ST clamp locations ........................... 15
Figure 8 – ALIV-QT clamp locations .......................... 15
Figure 9 – Cover screw pattern for AccuLoad IV-ST.. 15
Figure 10 – Cover screw torque pattern for AccuLoad ..
IV-QT.......................................................................... 16
Figure 11 – Feeler Gauge Test of Cover Flame Path ....
Joint ........................................................................... 16
Ethernet connection to A4M ....................................... 21
ALIV-ST without A4I ................................................... 22
ALIV-ST with A4I ........................................................ 22
ALIV-QT without A4I................................................... 23
ALIV-QT with optional A4I(s) ...................................... 23
Introduction
This manual provides installation instructions for the AccuLoad III to IV Upgrade Kits,
Models ALIV-ST-UG3 and ALIV-QT-UG3. These kits replace all of the electronics of the
AccuLoad III S and Q creating units equivalent to the AccuLoad IV ST and QT models.
Using the upgrade kits reduces the time and expense required to gain the advantages
of the new electronics by leaving the field wiring and the back half of the enclosure in-
tact. The new AccuLoad IV circuit boards and front cover fit to the existing rear housing
exactly as the AccuLoad III counterparts and the field wiring plugs directly into the new
boards with minimal modification.
• For wiring systems utilizing conduit, an Ex d certified sealing device must be used
immediately at the entrance of the enclosure.
• Any unused entry must be suitably blocked with an Ex d IIB IP65 certified plug for
ATEX and IECEx applications. For North America Zone applications, the plug must
be listed close up type.
• Equipment bonding shall be provided at the external grounding facility terminal,
external connection is not required when using metallic conduit or armored cable.
External grounding facility terminal wire range: 10-12 AWG (5.26 mm2 to 3.31
mm2 wire).
• Special Fasteners: Cover Bolts are steel grade 12.9, M8 x 1.25; substitution is
not allowed.
• The Touch Keypad sensor is protected by an intrinsic safe barrier, the enclosure
must be grounded as per national electrical code regulations, for example NEC/
CEC, etc.
Note: The maximum ambient temperature for the enclosure is 60°C for ATEX and IECEx
applications and 55°C for North American Zone applications.
• Select wiring and cable glands suitable for 81°C operation.
Receipt of Equipment
Inspect the packaging of the upgrade equipment and immediately report any damage to
the shipping agent. If the packing is intact, open the shipping container and remove the
upgrade equipment. Verify that the upgrade kit is complete using the parts list for your
particular model found in Appendix (C). If there are missing or damaged parts, a written
report should be submitted to TechnipFMC FMC Technologies Measurement Solutions
ATTN: Customer Service Department 1602 Wagner Ave. Erie, PA 16510.
Tools Required
The tools required for the upgrade procedure vary depending on the model as follows:
AccuLoad III S and Q Ex-proof models:
• 6 mm hex key
• #2 flat blade screwdriver
• Terminal screwdriver
• #2 Phillips screwdriver
• 0.0015” (0.04mm) feeler gauge
• Torque wrench with 6mm hex allen key adaptor, with torque units of (In-Lb or Ft-Lb)
or (Nm or kg•cm)
General Description
The upgrade process will vary slightly depending upon the AccuLoad model but gener-
ally consists of replacing the internal electronics and the front cover display assembly,
leaving the rear housing and field wiring plugs intact. The new electronics are installed
in place of the old electronic board assemblies according to the tables below:
Warning: Hazardous Voltages – Ensure all power to the AccuLoad and any as-
sociated wiring is disconnected / de-energized. All circuits must be de-energized
and locked out prior to starting this procedure for both personal and hazardous
locations safety.
Warning: Do not use enclosures with damaged flame path surfaces or threaded
entries, this condition could lead to fire or explosion risk! It is the owner / operator’s
responsibility to maintain the hazardous locations protection method.
Disassembly
1. Unplug the field wiring plug connectors identified as TB1 through TB5 from the KDC
board assembly. The field wiring terminal functionality has been moved to the new
A4M board assembly and is now identified as TBK1 through TBK5. The factory
wiring ribbon cable(s) to the EAAI and the BSE board assembly(s) (if equipped) is
no longer used and should be discarded.
2. Unplug the field wiring plug connectors from the BSE and PIB board assemblies
combination (if equipped), the field wiring terminal identification from the BSE to
A4B are identical with the exception of Terminal Block PT1 where the Pulse input
assignments have been modified as follows:
The original PIB board PT1 connector had pulse inputs identified as Pulse In 7
through Pulse In 12; the new assignment for PT1 on the A4B board is Pulse In 9
through Pulse In 14.
Note: No wiring changes should be required, the function of the pulse inputs is
unchanged; only the numbering is changed.
Page 8 • MN06203 ║ Issue/Rev. 0.0 (4/17)
AccuLoad III to IV Upgrade Manual for S and Q Models
3. Unplug the field wiring plug connectors from the AICB board assembly (if equipped),
the field wiring terminal identification from the AICB to A4I are identical.
Note: Serial communications via connector TB2 will not be required as the
communication link to the new A4I board will utilize the Ethernet communications.
4. Unplug the field wiring plug connectors from the EAAI and PIB board assembly
combination. The field wiring terminal identification from the EAAI to the A4M is also
nearly identical, with the differences as follows:
The terminal plugs on the EAAI that were identified as TB1 through TB7 have been
renamed to TBE1 through TBE7 on the A4M.
The terminal plug on the PIB that was identified as PT1 has been moved to PT1 on
the A4M and remain the same Pulse Inputs for Pulse In 1 through Pulse In 6.
A new Pulse input plug identified as PT2 has been added to the A4M board, this
serves for the Pulse Inputs for Pulse In 7 and Pulse In 8 which are new in the ALIV.
Since these are new, there will not be any connections for a simple upgrade. Only
if additional equipment is added as part of the upgrade will there be connections
to PT2.
5. Using Figure 1 (ALIII-S) or Figure 2 (ALIII-Q) as a guide, remove the circuit board
assemblies from the back housing. The EAAI board is standard for all ALIII models
and, therefore, it is always installed. The BSE is standard on the ALIII-Q and the AICB
board(s) is optional. (It may or may not be installed in either the -S or -Q model.)
6. While supporting the front cover assembly, remove the four bolts securing the
cover hinges to the rear housing and remove the front cover assembly. See Figure
3 for ALIII-S and Figure 4 for ALIII-Q.
Caution: The front covers are heavy - 18 lbs (8 kg) for the ALIII-S cover and 36 lbs.
(16 kg) for the ALIII-Q cover. It is recommended to either mechanically support the
front cover or have assistants help support it during this procedure to avoid injury
or damaging the equipment.
Reassembly
1. ALIV-QT: Mount the new front cover assembly using the two hinges and four hinge
bolts removed in the previous step. ALIV-ST: Mount the new front cover assembly
using the two hinges and four hinge bolts supplied in the upgrade kit. The original
hinges cannot be re-used as the design has changed.
Caution: The front covers are heavy - 24 lbs. (11 kg) for ALIV-ST and 43 lbs. (19
kg) for ALIV-QT. It is recommended to either mechanically support the front cover
or have assistants help support it during this procedure to avoid injury or damaging
the equipment.
2. Replace the EAAI board with the new A4M board assembly. Insert the field wiring
connectors into the A4M board into the same locations that were used on the EAAI
board. The connectors on the EAAI that were labelled TB1 through TB7 are now
labelled TBE1 through TBE7 on the A4M board. These are located in the same
position on the A4M as they were on the EAAI board. Connect Meter Pulse Inputs 1
through 6 to TP1; reference Appendix (D) for Meter Pulse configuration details. See
Figures 1 and 2. May require program parameter changes - reference MN06201.
3. Insert the field wiring plugs that were connected to the KDC board assembly identified
as TB1 through TB5 into the A4M board assembly in positions TBK1 through TBK5
respectively. If an Ethernet cable from the local network was plugged into the KDC,
insert it into the RJ-45 connector labeled as ETH4 on the A4M board. See Figure (E).
4. If a BSE/PIB board set was removed (ALIII-Q only), replace it with the new A4B
board and reconnect all of the original field connection. Apply the supplied A4B
wiring label over the BSE label (after cleaning) that is located on the inside of
the -Q housing. The parallel communications ribbon cable that originally con-
nected the BSE to The KDC has been replaced with Ethernet communications on
the A4B board assembly. Connect the supplied Ethernet jumper cable from
the A4B RJ-45 connector labeled ETH1 to the RJ-45 connector labeled ETH3 on
the A4M board.
5. If an AICB board was removed, replace it with the new A4I board and reconnect
the field connections from TB1and TB3 through TB9, which includes the 24 VDC
power connection plug TB1. Also connect the supplied Ethernet jumper cable from
the A4I RJ-45 connector labeled ETH1 to the RJ-45 connector labeled ETH3 on
the A4M (ALIII-S only); if an A4B (ALIII-Q) is installed, make the connection to the
RJ-45 connector labeled ETH2 on the A4B board to create a daisy chain commu-
nications link. If a second (optional) A4I board is installed, then connect the RJ-45
connector labeled ETH1 on the second A4I board to the RJ-45 connector labeled
ETH2 on the first A4I board. See Appendix E.
Note: Connector TB2 was used for the serial communications link from the old
AICB to the old EAAI assembly and is no longer required.
6. Install the cable clamp(s) used to hold the power and Ethernet cable assembly in
the locations as shown. One clamp for the -ST (refer to Figure 7) and two clamps
for the -QT (refer to Figure 8). The clamps are installed so that the top edge of the
clamp is 1 1/2" down from the housing flange on the -ST housing, and 5 1/2" down on
the -QT housing.
Proper Installation Steps:
Surface Preparation – For rubber and acrylic based foam tape, a mixture of water
and isopropyl may be used on most surfaces. Ensure the area is dry before apply-
ing the mount.
Installing the Mount – For proper installation of adhesive backed mounts with foam
tape, remove the release liner from the foam adhesive. Without touching the adhe-
sive, place the mount in the proper location. Apply firm pressure for five seconds to
the foam tape mount to ensure proper adhesion. The dwell time for rubber-based
adhesive foam tape is two hours.
7. Install the Ethernet jumper and power cable that will be used to connect the
new display module identified as the HMI assembly as shown in Appendix E from
the A4M board assembly. Plug the supplied Ethernet jumper cable into RJ-45
connector ETH2 on the A4M board. The other end of this jumper cable will plug
into the RJ-45 connector on the back of the display. Connect the supplied twisted
pair power cable (red wire) to TBE4 terminal 10, or 11 or 12 and the common (black
wire) to TBE4 terminal 13 or 14 or 15; refer to Figure 6.
8. Connect the other end of the twisted pair power cable from the A4M to the connector
identified as CN4 +24VDC (red) to CN4 Terminal 1; Common (black) to CN4
terminal 2 or 3. (Refer to Figure 5.)
9. Connect the Intrinsic safety ground wire (Green wire) ring terminal from the front
cover to the selected board assembly mounting screw to establish a ground
connection to the back housing. See Figure 7 for the -ST housing location, and
Figure 8 for the -QT location. Remove the captive mounting screw to place
the ring terminal.
10. Route and secure the Ethernet jumper and power cables as shown in Figure 5.
11. Grease exposed metal on mating surfaces of cover flange with petroleum jelly or
TechnipFMC grease (P/N 644886401) before reattachment of the cover to the
housing. Close the front cover and follow the bolt torquing sequence shown in
Figure 9 for ALIV-ST or Figure 10 for ALIV-QT, to secure the front cover to the rear
housing using the new 8 mm cap screws provided in the upgrade kit.
Note the locations for the two longer bolts used for the security seal wire.
Final torque bolts to 20 FT-LB / 240 IN-LB (27.1 Nm / 276.4 Kg.cm).
12. Apply power to the unit and follow the steps outlined in Appendix B to restore
the configuration.
Caution: If this step is to be performed prior to the installation of the cover bolts in
the previous step (i.e. restoring the hazardous locations protection) it is imperative
that the area is known to be non-hazardous, or a valid hot work permit is issued by
the authority in charge of the facility.
Diagrams
Optional
A4I board
ETH3 ETH2
ACIM1
1
ACIM2
AM1 AM2 AM3 AM4 AM5 AM6 1
ETH4 ETH1
ACIM3
TBE2
ACIM4
TBE5
CN7
1 1 6
ACIM5
PT2
CN6 S2 U22
PT1
U41
LMOD1
18 U29 U38 P4
SSR1 1
1
S1 P3
12
SSR2
1
TBE6
U28 SSR3
TBE3
SW2
TBK1
SSR4
10 CN4
SSR5
1 10 12
SSR6
1
SSR7 1
TBK4
SSR8
1
TBE4
TBE7
SSR9
TBK2
10
C119 SSR10
1
8
10
C94 D11 SSR11
TBK5
1 T1
16 HS1
TBK3
TBE1
1 3
C95
8 5
7 3 2 6 10
11
18
12 17
13 16
14 15
8 4 1 5 9
15 11 7 3 2 6 10 14 18
19
28
20 27
21 26
22 25
23 24
16 12 8 4 1 5 9 13 17
Figure 11 – Feeler gauge test of cover flame path joint, inspect joint around the complete
perimeter using a 0.0015" (0.0381 mm) feeler gauge. (ALIV-QT shown - use the same procedure
for ALIV-ST)
Model ALIV-ST
Optional Items
Model ALIV-QT
Optional Items
Pgm – Indicates a pulse input which is programmable to function as a metered injector or densitometer
pulse input.
Single Pulse
A In #1
M1A
In #2
M2A
In #3
M3A
In #4
Pgm
In #5
Pgm
In #6
Pgm
In #7
Pgm
In #8
Pgm
Dual Pulse
4 M1A M1B M2A M2B M3A M3B Pgm Pgm
Dual/Integrity M N/A N/A N/A N/A N/A N/A N/A N/A
In #9 In #10 In #11 In #12 In #13 In #14
Single Pulse
A M4A M5A M6A Pgm Pgm Pgm
Dual Pulse 4 M4A M4B M5A M5B M6A M6B
Dual/Integrity B N/A N/A N/A N/A N/A N/A
A4M
ETH3 ETH2
ACIM1
1
ACIM2
AM1 AM2 AM3 AM4 AM5 AM6 1
ETH4 ETH1
ACIM4
TBE5
CN7
1 1 6
ACIM5
PT2
CN6 S2 U22
PT1
U41
LMOD1
18 U29 U38 P4
SSR1 1
1
S1 P3
12
SSR2
1
CN1
TBE6
SSR3
Eth 4 - External Eth 1 - to CPU U28
TBE3
SW2
TBK1
SSR4
Network module
10 CN4
SSR5
1 10 12
SSR6
1
SSR7 1
TBK4
SSR8
1
TBE4
TBE7
SSR9
TBK2
10
C119 SSR10
1
8
10
C94 D11 SSR11
TBK5
1 T1
16 HS1
TBK3
TBE1
1 3
C95
8 5
Front Cover
ETH3 ETH2
THMI ACIM1
1 3 2 ACIM2
AM1 AM2 1
ETH4 ETH1
ACIM3
4 1
TBE2
ACIM4
TBE5
CN7
1 1 6
ACIM5
PT2
4
CN6 S2 U22
PT1
U41
LMOD1
18 U29 U38 P4
SSR1 1
1
S1 P3
12
SSR2
1
CN1
TBE6
U28 SSR3
TBE3
SW2
TBK1
CN9 SSR4
10 CN4 U1 U8
U7 U4 P1 SSR5
L1
1 10
P2
CPU U10
U11
SSR6
12
1
U3
U9 SSR7
CN5 U5 1
U17 SW1 U2
A4M
TBK4
SSR8
1
External Ethernet
TBE4
TBE7
CN8
SSR9
TBK2
10
C119 SSR10
1
8
10
C94 D11 SSR11
TBK5
1 T1
16 HS1
TBK3
TBE1
1 3
C95
8 5
Front Cover
ETH3 ETH2
THMI ACIM1
1 3 2 ACIM2
AM1 AM2 1
ETH4 ETH1
ACIM3
4 1
TBE2
ACIM4
TBE5
CN7
1 1 6
ACIM5
PT2
CN6 S2 U22
PT1
U41
LMOD1
18 U29 U38 P4
SSR1 1
1
S1 P3
12
SSR2
1
CN1
TBE6
U28 SSR3
TBE3
SW2
TBK1
CN9 SSR4
10 CN4 U1 U8
U7 U4 P1 SSR5
L1
U10
1 10
1
CPU P2 U11
SSR6
12
A4I
U3
U9 SSR7
CN5 U5 1
SW1 U2
A4M
U17
TBK4
SSR8
1
External Ethernet
TBE4
TBE7
CN8
SSR9
TBK2
10
C119 SSR10
1
8
10
C94 D11 SSR11
TBK5
1 T1
16 HS1
TBK3
TBE1
1 3
C95
8 5
Front Cover
THMI
ETH3 ETH2
ACIM1
PT1 1
1 3 2 ACIM2
LMOD1
1 10 1
ETH4 ETH1
1
1
ACIM3
4 1
SSR1
TBE2
CN1
SSR2
ACIM4
TB14
SSR3
TBE5
TB10
CN7
1 2 1 1 6
SSR4
ACIM5
PT2
TB14
SSR5 9 10
4
SSR6
1 CN6 S2 U22
ETH2
PT1
U41
SSR7 LMOD1
SSR8
18 U29 U38 P4
TB9 SSR9 ETH1 SSR1
1 1
S1 P3
SSR10 12
SSR2
1
SSR11
1
CN1
TBE6
CN2 U28 SSR3
TBE3
SSR12 SW2
1
TBK1
SSR13
CN3 CN9 SSR4
TB12
SSR14
10 CN4 U1 U8
TB8 U7 U4 P1 SSR5
SSR15 L1
U10
1 10 12
SSR16
1 P2 CPU U11
SSR6
1 U3
A4B CN5 U5
SW1 U2
U9 SSR7 1
A4M
1 U17
TBK4
ACIM1
SSR8
1
TBE4
TB13
TB11
TBE7
ACIM2 CN8
SSR9
TBK2
10
C119 SSR10
ACIM3
1
8
10
C94 D11 SSR11
TBK5
ACIM4
C14
1 T1
16 HS1
TB2
TBK3
TBE1
1 3
C95
8 5
External Ethernet
Front Cover
THMI
ETH3 ETH2
ACIM1
PT1 1
1 3 2 ACIM2
LMOD1
1 10 1
ETH4 ETH1
1
1
ACIM3
4 1
SSR1
TBE2
CN1
SSR2
ACIM4
TB14
SSR3
TBE5
TB10
CN7
1 2 1 1 6
SSR4
ACIM5
PT2
TB14
SSR5 9 10
4
SSR6
1 CN6 S2 U22
ETH2
PT1
U41
SSR7 LMOD1
SSR8
18 U29 U38 P4
TB9 SSR9 ETH1 SSR1
1 1
S1 P3
SSR10 12
SSR2
1
SSR11
1
CN1
TBE6
SSR12 SW2
1
TBK1
SSR13
CN3 CN9 SSR4
TB12
SSR14
10 CN4 U1 U8
TB8 U7 U4 P1 SSR5
SSR15 L1
U10
SSR16
1 10
1
CPU P2 U11
SSR6
12
A4I
1 U3
A4B CN5 U5
SW1 U2
U9 SSR7 1
A4M
1 U17
TBK4
ACIM1
SSR8
1
TBE4
TB13
TB11
TBE7
ACIM2 CN8
SSR9
A4I
TBK2
10
C119 SSR10
ACIM3
1
8
10
C94 D11 SSR11
TBK5
ACIM4
C14
1 T1
16 HS1
TB2
TBK3
TBE1
1 3
C95
8 5
External Ethernet
Related Publications
The following literature can be obtained from TechnipFMC FMC Technologies Measurement Solutions Literature Fulfillment at
[email protected] or online at http://info.smithmeter.com/literature/online_index.html.
When requesting literature from Literature Fulfillment, please reference the appropriate bulletin number and title.
Technical Support
Contact Information:
Field Service Response Center
24/7 Technical Support/Schedule
a Technician: 1-844-798-3819
System Installation Supervision,
Start-Up, Commissioning Services,
and Training Available
The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in
effect. Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect.
USA Operation
1602 Wagner Avenue
Erie, Pennsylvania 16510 USA
TechnipFMC P:+1 814.898.5000
FMC Technologies
Measurement Solutions Inc. Germany Operation
13460 Lockwood Road Smith Meter GmbH
TechnipFMC.com Building S01 Regentstrasse 1
Houston, Texas 77044 USA 25474 Ellerbek, Germany
© TechnipFMC 2017 All rights reserved. MN06203 Issue/Rev. 0.0 (4/17) P:+1 281.591.4200 P:+49 4101 304.0