SLR-E-IS - Installation Guide
SLR-E-IS - Installation Guide
com
The YBN-R/4(IS) Base may only be used with Hochiki Intrinsically Safe specified detector heads. The use of other
detector heads is expressly forbidden and may cause fire or explosion.
Classification – DCD-1E-IS
This Detector has BASEEFA certification classification according to EN 60079-11:2012 and an ATEX Classification of II 1
G Ex ia IIC T5 -20°C<Ta<55°C. Areas suitable for installation: Category 1, 2 or 3 hazardous atmospheres, with a
maximum ambient temperature of up to 55°C.
Refer to the system drawing overleaf for important information concerning installation/wiring requirements which must be
strictly observed in order to comply with BASEEFA certification. These detectors and base MUST be used with either a
Zener Diode Barrier or a Galvanic Isolator, using suitable models as detailed in the system drawing overleaf. The Zener
Diode Barrier or Galvanic Isolator should be installed according to the manufacturer's instructions.
Note
Precautions
Hochiki smoke and heat detectors cannot be used to prevent a fire itself, they are intended only to detect certain
characteristics of fire. When installing the detectors, check that the location of each one has been planned according to
appropriate fire regulations and recommendations.
Hochiki detectors are suitable for indoor use only. A detector should not be installed in the following environmental
conditions:
Excessive ambient temperature.
Where excessive condensation or moisture is present.
Where corrosive gas or any other harmful agent is present.
Where flammable dust or steam is present.
Where obstructions are present which could impede the flow of air to the detector.
Where mechanical stresses could affect the detector when fitted in accordance to these instructions.
Notes
1. The electrical circuit in the hazardous area must be capable of withstanding an a.c. test voltage of 500 volts to
earth or frame of the equipment, for a period of one minute without breakdown.
2. The installation must comply with National requirements.
3. The system must be marked with a durable label which should appear on or adjacent to the principal item of
electrical apparatus in the system or at the interface between the intrinsically safe and non-intrinsically safe
circuits. This marking shall include the word SYST or SYSTEM, for example “System No. BAS Ex 98D2264” or
“BAS No. Ex98D2264 SYST”.
A. Unspecified equipment except that no voltage shall exceed 250V with respect to earth.
B. EITHER:
Any BASEEFA Certified shunt safety Zener Diode Barrier with the following parameters:
30V or less
200mA or less
1W or less
The barrier earth must be connected via a high integrity connection, using an insulated conductor equivalent to a 4mm2
copper conductor, such that the impedance from the point of connection to the main power system earth is less than 1
ohm.
OR:
Any one channel from the following BASEEFA Certified Galvanic Isolators:
Note
Earthing requirements as described above for Zener Diode Barriers, is not required with Galvanic Isolators.
C. Up to 20 SLR-E-IS Intrinsically Safe Photoelectric Smoke Detectors complete with YBN-R/4 IS Bases, BASEEFA
Certificate BAS01ATEX1281X
OR:
Up to 20 DCD-1E-IS Intrinsically Safe Heat Detectors complete with YBN-R/4 IS Bases, BASEEFA Certificate No
BAS01ATEX1021X
OR:
A combination of each type to a maximum of 20 units.
H. Optional cable screen. If used, this must only be connected to earth within the safe area and must be isolated
from the electrical circuit and must be capable of withstanding an a.c. test voltage of 500 volts for a period of one
minute without breakdown.
I. Up to 20 optional devices, for example switches such as manual call points having appropriate BASEEFA
Certification for use in the intended hazardous environment (Hochiki part no. CCP-IS) or otherwise classified as
simple apparatus according to BS EN 60079-11:2012. Such devices may be fitted with a resistor in series with
the switch and /or an end-of-line resistor as per D above. Where such a resistor is used it must have a body
surface area of 230mm2 or more (typical resistance 470 – 680 ohm).
www.acornfiresecurity.com
www.acornfiresecurity.com
www.acornfiresecurity.com
www.acornfiresecurity.com
www.acornfiresecurity.com
www.acornfiresecurity.com
www.acornfiresecurity.com
www.acornfiresecurity.com
Certain actions can cause permanent damage to the detector. If the detector is subjected to any of the following it should
not be used:
Dis-assembly and re-assembly, apart from chamber replacement in the case of photoelectric smoke detectors
(the detectors cannot be repaired and must be replaced in their entirety).
Impact or shock.
Suspected damage following a fire.
In the case of heat detectors, touching the thermistor element.
These detectors must be subject to periodic maintenance during regular service visits. This period should be outlined in
the appropriate standards or recommendations. If there are no such standards existing, Hochiki recommend that the
minimum period of maintenance should be 1 year and that the following should be taken into account:
A regular operation test should be performed using suitable test equipment (certain types of test equipment
should not be used in flammable/combustible atmospheres).
A visual check for staining and mechanical damage should be made.
A magnetic test facility is incorporated into both detectors which can be operated using a suitable magnet.
A dust cover is included with these detectors to prevent contamination during installation and prior to commissioning. The
dust cover must be removed for the detectors to operate.
The detectors can be locked on to the base by removing a plastic lug on the underside, please refer to the diagram
below. The locked detector can then only be removed by using a special removal tool which is available from Hochiki
Europe (UK) Ltd (part number TSC-A100/ALG).
SLR-E-IS 0832-CPR-F2415 18
EN54-7 Point type smoke detectors
SLR-E-IS(WHT) 0832-CPR-F2415 18
Please note: SLR sensors that require VdS certification are not approved for activating of extinguishing systems.