Generator With 3201 Control Manual
Generator With 3201 Control Manual
Generator Set
with PowerCommand 3201 Controller
English
Original Instructions 2-2020 0961−0508 (Issue 15)
Table of Contents
SECTION PAGE
SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
ABOUT THIS MANUAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
TEST EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
HOW TO OBTAIN SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
2. CONTROL OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
CONTROL PANEL POWER ON/OFF MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
CONTROL PANEL ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
READING FAULT CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
MENU DISPLAY AND SWITCHES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
LANGUAGE/UNITS SELECTION MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
MAIN MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
ENGINE SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
ALTERNATOR SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
CONTROL SUBMENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
HISTORY/ABOUT SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
HISTORY/ABOUT SUBMENUS (CONT.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
PARALLEL DATA SUBMENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
POWER TRANSFER MAIN/SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
UTILITY (PWR TRAN) SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
STATUS (PWR TRAN) SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20
TRANSFER CONTROL (PWR TRAN) SUBMENU . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
GENSET (PWR TRAN) SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
3. CONTROL CALIBRATION AND ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
SOFTWARE CALIBRATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
MODIFYING SETUP/ADJUST SUBMENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
SETUP MENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Read Safety Precautions and carefully observe all NFPA 70: National Electrical Code compliant gen-
instructions and precautions in this manual. erator sets are required to be protected from an
overload. Cummins generator sets with UL Listed
TEST EQUIPMENT
AmpSentry Protective Relay as a standard feature
To perform the test procedures in this manual, the do not require a circuit breaker or other protective
following test equipment must be available device for NEC compliance or UL 2200 Listing.
True RMS meter for accurate measurement of CEC: Each conductor between the generator termi-
small AC and DC voltages. Fluke models 87 or nal and the point where load receives supply of gen-
8060A are good choices. erator current must be protected by an overcurrent
Battery Hydrometer device in accordance with the requirement of CEC
Power Factor Indicator 14−100: Overcurrent Protection of Conductor.
Jumper Leads UL label indicate to the Authority Having Jurisdiction
Tachometer or Frequency Meter (AHJ) that the generator set incorporates a UL
Wheatstone Bridge or Digital Ohmmeter Listed Protective Relay that provides overload and
Variac short circuit protection for the generator and its
conductors. The generator set does not require
Load Test Panel
use of a circuit breaker or other protective device
Megger or Insulation Resistance Meter for NFPA 70: National Electrical Code compliance
InPower Service Tool (PC based genset ser- or UL 2200 Listing.
vice tool)
HOW TO OBTAIN SERVICE AmpSentry Labels
Always give the complete Model, Specification and These are typical labels for compliant generator
Serial number of the generator set as shown on the sets produced after January 2012.
AmpSentry Protective Relay Time−Over plied, so adjustments to the operation points for this
Current Characteristic Curve curve are not allowed.
The protection provided is shown in the figure Note: The values shown on the current scale are
below, which shows the time−current characteris- shown based on the value of 1.0 being equal to the
tic of the supplied protection. This protection curve nameplate rated current of the generator set for the
is specifically designed to protect the generator sup- specific operating voltage.
REMOTE START,
NOT IN AUTO,
SHUTDOWN,
WARNING
STATUS
ANALOG AC PANEL LAMP/ FAULT INDICATORS EMERGENCY
METERING LAMP TEST ACKNOWLEDGE STOP PUSH
PANEL BUTTON BUTTON BUTTON
Shutdown Status Indicator: This red lamp is lit Manual Run/Stop Button: This button starts and
whenever the control detects a shutdown condition. stops the set locally and will bypass Time Delay to
The generator set can not be started when this lamp Start and Stop sequences. The 0/Manual/Auto
is on. After the condition is corrected, shutdown indi- switch must be in the Manual position to enable this
cators can be reset by turning the 0/Manual/Auto button.
switch to the 0 position, and pressing the Fault Ac- 0/Manual/Auto Switch: Manual position enables
knowledge button. the use of the switch panel Manual Run/Stop button.
Dependent upon the specific fault that occurs, the Auto position enables start/stop control of the en-
engine may or may not shut down immediately. A gine from a remote location. (Disables the use of the
fault that could cause engine damage, causes an switch panel Manual Run/Stop button.)
immediate engine shutdown (bypasses engine
0 (Off) position prevents the starting of the set (local
cool-down sequence). All other faults would allow
or remote). If moved to 0 during set operation, will
the engine to run during the cool-down sequence
cause an immediate engine shutdown (bypasses
before engine shutdown. In this case, the Shutdown
cool-down timers). This hot shutdown should be
Status Indicator blinks during the cooldown period.
avoided, if possible, to help prolong the life of the en-
Warning Status Indicator: This yellow lamp is lit gine. Hot shutdowns are logged by the system soft-
whenever the control detects a warning condition. ware.
After the condition is corrected, warning indicators The connections of Switch Panel components is de-
can be reset by pressing the Fault Acknowledge picted in the tables and image below. Refer to these
button. (It is not necessary to stop the generator set connections for testing the panel buttons.
if the fault becomes inactive during genset opera-
TABLE 2−1. E−STOP AND O/MANUAL/AUTO
tion.)
SWITCH CONNECTION
Fault Acknowledge: Press this button to acknowl- SIGNAL CONNECTION
edge warning and shutdown messages after the
fault has been corrected. Emergency stop button J2−1, J2−2
Warning LED:
Reading Fault codes Using Warning/Shutdown
blink (2 seconds)
Indicators: If the Warning or Shutdown status indi-
cator is lit, press and hold the Fault Acknowledge The light will display the fault codes (active or inac-
button and release after one second or more. After tive) in succession, starting with the most recent. Up
one second, the Shutdown lamp will begin to blink to 32 (unacknowledged) fault codes can be stored in
the active fault code(s) as follows. control panel memory.
The Warning lamp is used to indicate the start of a To return the control to the most recent fault code,
new code. The Warning lamp will remain on for 2 press and release the Fault Acknowledge button
seconds, followed by the Shutdown lamp blinking (less than one second) and repeat procedure.
the fault code. This sequence occurs three times for
each code. The fourth flash of the Warning lamp in- When the fault code is acknowledged and cor-
dicates the beginning of the second fault code. rected, the recorded fault will be deleted from the
LED fault log, but will remain in a data log that main-
There are distinct pauses between repetitions of the tains a fault code history. (The InPower service tool
code blink transmissions of the Shutdown lamp. is required to view this data log.)
STATE LINE
ACTION LINE
DESCRIPTION LINE
MENU DISPLAY
AREA
GRAPHICAL
DISPLAY
MENU MENU
BUTTONS BUTTONS
ENGINE MORE>>
PAGE ALTERNATOR POWER TRAN OR PAGE
2-12 CONTROL _\_
HISTORY/ABOUT 2-9
PAGE PAGE
2-13 2-14
MENU B
SECTIO
N3
ADJUST
PARALLEL DATA PAGE
SETUP BACK<< 2-16
GRAPHICAL
SECTIO DISPLAY MENU
N3 A
MANF TEMP 75 F
MANF PRESS ABS 180 INHG Y
RAIL PRESS ABS 180 PSI
PUMP PRESS ABS 291 PSI B
FUEL INLET TEMP 172 F
COOLANT PRESSURE 59 PSI
If you press the “CONTROL” button in Menu A, the location. This button sequentially lights the LEDs to
Control submenu will appear (Figure 2-10). test the bar graph display.
MODEL 1750DQKB Y
VOLTAGE 416 WYE
FREQUENCY 60 B
RATING STANDBY
CONTROLLER VERSION
RTOP DN30008.DFA Y
BATS APR 23 1999
OP PANEL VERSION B
RTOP 1.09 AUG 17 1999
BATS 1.02 MAY 6 1999
If you press the “POWER TRANS” button in Menu The symbol displayed in the middle of the Power
A, the Power Transfer main menu will appear (Fig- Transfer main menu indicates which breaker (utility
ure 2-13). The Power Transfer Control (PTC) fea- or genset) is closed/opened to the load. The symbol
ture must be installed to display this menu. presently shown indicates that the utility breaker is
closed and supplying power to the load.
The PTC feature enables the PCC to monitor the
utility voltage (mains) and frequency for failure and The Power Transfer main menu also indicates if the
control the opening and closing of the contacts (cir- utility and the generator set are available to accept
cuit breakers) for the utility (S1) and the genset (S2). load. When the control detects that either source is
ready to accept load, UTILITY and/or GENSET will
If utility fails, the control will initiate the genset start- be displayed in inverse video.
ing sequence, open S1 and close S2 to the load.
When utility returns, the load is retransferred to the The Power Transfer main menu has four submenu
utility (S1 closes/S2 opens) and the control initiates groups. Refer to the page numbers shown in Figure
the genset shutdown sequence. 2-13 for the Power Transfer submenu descriptions.
MENU MENU
BUTTONS PAGE PTC STATUS LINE PAGE BUTTONS
2-19 2-22
B UTILITY GENSET B
PAGE STATUS
2-20 TRANSFER CONTROL
DEG −123 SYNCHRONIZING
PAGE MENU
2-21 A
Pressing the OPEN UTIL button will display the << BACK
fourth submenu, indicating that the utility circuit
breaker is now opened.
+ OR − BUTTON + OR − BUTTON
MENU
ENGINE MORE>> B ADJUST
ALTERNATOR POWER TRAN OR PARALLEL DATA
_\_ MENU
CONTROL HISTORY/ABOUT SETUP BACK<<
A
SETUP MENU 1
PAGE MENU
3-4 B
GOVERNING/VOLT REG Y
PAGE CUSTOMER FAULTS B NEXT
3-5 MENU
CALIBRATION
PAGE MENU
3-6 A
SETUP MENU 2
PAGE ABOVE
3-12 MENU
PAGE MENU
3-11 A
If you press the “CUSTOMER FAULTS” button in Note: If these messages are changed, you should
the Setup menu, the Customer Faults submenus note these changes in the Troubleshooting section
will appear (Figure 3-5). of the Operator’s manual for this generator set.
CUSTOMER FAULT1:
+ ENABLE ON Y
− ACTIVE CLOSED B
RESPONSE WARNING
***CUSTOMER FAULT1
******************
CUSTOMER FAULT2:
+ Y
− RESPONSE WARNING B
***CUSTOMER FAULT2
******************
UTILITY SENSORS Y
PAGE GENSET SENSORS B NEXT
3-15 MENU
TIMERS
PAGE
3-17
PTC MAIN MENU 2
PAGE
TEST/EXERCISE Y
3-18
If you press the “UTILITY SENSORS” button in the U CT RATIO: Enter the CT Ratio of the Utility L2 CT.
PTC Main Menu 1, the Utility Sensors submenus This is the Ratio to 1 Amp. Range: 1−18000 (1A).
will appear (Figure 3-10).
CAUTION This CT must be rated for 1 Amp out-
The following field descriptions show the valid field
put (e.g. NOT 5 Amp). Be sure CT secondary cir-
entries and default value (shown in parenthesis) for
cuit has burden resistor or a shorting jumper in
each field.
place before putting power through the CT. Ex-
Note: Use the + and − buttons to increase or decrease ample: CT Ratio = 2650:1. Thus enter 2650.
the values in the following fields. Use the arrow ()
button to move the cursor within a field or to the next U SENSOR TYPE: Enter the line-to-line (L-N) for 3
field. Exit menu to save changes. phase line-neutral voltage sensing or line-to-line
(L-L) for 3 phase line-line voltage sensing. This ap-
U PT VOLT LL: Enter the value of the utility line-to-
plies to both the utility undervoltage and overvoltage
line voltage which yields 100% voltage at the termi-
sensors. Range: L−L, L−N (L−N).
nals of the utility (bus) PT module.
Range: 1−15000V, adjustable by standard nominal U <wye> <delta>: Enter utility connection type.
voltage values, 100V, 10V and 1V increments (1V). Range: Delta, Wye (Wye).
The 100% voltages for each of the four possible util- U UNLOADED KW: Enter the kW on utility Line 2 at
ity (bus) PT modules are as follows, based on mod- which the utility is considered as unloaded. This is
ule dash number: the L2 kW level at which a closed transition soft
−01 = 208 volts LL transfer will disconnect from the utility.
−02 = 416 volts LL
−03 = 600 volts LL UTILITY UNDERVOLTAGE: Non-adjustable field,
−04 = 120 volts LL always enabled.
Example 1: Nominal Utility voltage is 480V. This
means that utility (bus) PT module number −02 UTILITY OVERVOLTAGE, FREQUENCY: Used to
should be used. The voltage which will yield 100% enable or disable menu function. Choose Enabled
volts at this PT module is 416 per the above table. or Disabled (Enabled).
Thus enter 416V.
UV PICKUP: Enter a number between 85 and 100%
Example 2: Nominal Utility voltage is 4160V. A pri- of the nominal voltage (90%).
mary stage transformer with a ratio of 4200/240 is
used. This means that utility (bus) PT module num- UV DROP OUT: Enter a number between 75 and
ber −01 should be used. The voltage which will yield 98% of the under-voltage pick-up percentage
the 100% volts (208V from above table) is calcu- (90%).
lated as follows:
208 x (4200/240) = 3640. Thus enter 3640V.
UV DELAY: Enter a time between 0.1 and 5.0 sec-
U NOM VOLT LL: Enter the nominal utility line-to- onds (0.5 seconds).
line voltage. For example, 480, 4160, etc.. Range:
1−15000 V, adjustable by standard nominal voltage UV MIN PHASE: Displays the lowest line voltage of
values, 100V, 10V and 1V increments (1V). the three utility phases.
If you press the “GENSET SENSORS” button in the G RAMP UNLOAD: Enter the ramp time for the
PTC Main Menu 1, the Genset Sensors submenus genset ramp unload rate during a closed transition
will appear (Figure 3-11). soft load retransfer. Ramp rate is −100%kW divided
by this time setting. Range: 0−900 seconds (20
The following field descriptions show the valid field sec).
entries and default value (shown in parenthesis) for
each field. G UNLOADED KW: Enter the %kW (based on
standby rating) that the genset is considered un-
Note: Use the + and − buttons to increase or decrease loaded. This is the %kW level at which a closed tran-
the values in the following fields. Use the arrow () sition soft retransfer will disconnect from the genset.
button to move the cursor within a field or to the next Range: 0−100% (5%).
field. Exit menu to save changes.
GEN UNDERVOLTAGE: Non-adjustable field, al-
G NOM VOLT LL: Non-adjustable field, displays
ways enabled.
current setting of genset nominal voltage. (See Ad-
just submenu to adjust the output voltage 5%.) GEN OVERVOLTAGE, FREQUENCY: Used to en-
able or disable menu function. Choose Enabled or
G SENSOR TYPE: Enter the line-to-line (L-N) for 3
Disabled (Enabled).
phase line-neutral voltage sensing or line-to-line
(L-L) for 3 phase line-line voltage sensing. This ap- UV PICKUP: Enter a number between 85 and 100%
plies to both the genset undervoltage and overvol- of the nominal voltage (90%).
tage sensors. Range: L−L, L−N (L−N).
UV DROP OUT: Enter a number between 75 and
G BASE LOAD: Enter the maximum load the gen- 98% of the under-voltage pick-up percentage
set will carry during a closed transition. Range: (90%).
0−100% (80%).
UV DELAY: Enter a time between 0.1 and 5.0 sec-
G RAMP LOAD: Enter the ramp time for the genset onds (4 seconds).
ramp load rate during a closed transition soft load
transfer. Ramp rate is +100%kW divided by this time UV MIN PHASE: Displays the lowest line voltage of
setting. Range: 0−900 seconds (20 sec). the three genset phases.
Changes are automatically saved when you exit this FREQUENCY: Used to adjust the frequency 3 Hz.
menu.
VOLTAGE/SPEED DROOP: These two submenus
If the generator set is operating in parallel with a sys- apply to a genset that has the paralleling option and
tem bus, the voltage and frequency adjustments are is configured to operate in droop mode.
MENU A
ADJUST:
MENU START DELAY 5 SEC
ENGINE MORE>> + Y
B STOP DELAY 11 SEC
ALTERNATOR _\_ − VOLTAGE 208 1.2 % B
CONTROL HISTORY/ABOUT FREQ 60.0 HZ -0.0 HZ
MENU B
ADJUST:
+ STANDBY Y
VOLTAGE DROOP OFF
ADJUST − BUS L1 480 V B
BUS DATA POWER FACTOR 0.80
MENU VOLT 4.99 %
SETUP BACK<<
A
ADJUST:
STANDBY
+ SPEED DROOP OFF Y
− BUS FREQ 60.0 HZ
TOTAL KW 300 KW
FREQ 60.0 0.40 HZ
CONTROL
BOX DOOR
TB8
CARD
CAGE
CUSTOMER
K11, K12, K13
CONNECTIONS
NO NO NO
NC NC NC
COIL TB3-9
TB3-5
(SWITCHED B+) COM (GND)
K16
CUSTOMER
K16
CONNECTIONS
K16
K16
SHUTDOWN ALARM
NO
NC
COIL TB3-24
TB3-20
(SWITCHED B+) COM (COM ALARM - GND)
ENGINE
FLYWHEEL
RING GEAR
EXCITER
RECONNECTION
STATOR
TERMINALS
END BRACKET
PMG
STATOR
END
STATOR BEARING
BLOWER PMG
ROTOR
COUPLING
EXCITER
ROTOR
ROTATING
RECTIFIER
ASSEMBLY
DRIVE ROTOR
DISCS
FRAME
END BRACKET/ENGINE
ADAPTOR
AIR DISCHARGE
PRESSURE COVERS
ROTOR
PLATE
SHAFT
FIGURE 4-1. TYPICAL GENERATOR
Megger and PI testing must be performed on all unless fully trained in medium voltage ground-
medium voltage (601 through 15,000 volts) genera- ing procedures and have necessary safety
tor sets before initial start-up. Failure to do so, may equipment. Severe injury or death due to high
void generator set warranty. PI testing for low volt- voltage electrical shock may result.
age (less than 600 volts) generator sets is also rec- 1. Open, lock-out and tag-out all sources of power
ommended by Cummins. to the immediate work area.
These tests are used to verify that the windings are 2. Disable the starting system of the generator
dry before the generator set is operated and devel- set:
ops a reference point for future test comparison. a. Move the O/Manual/Auto switch on the
Care should be taken when dealing with windings control panel to the O (OFF) position.
which are suspected of being excessively damp or b. Turn off or remove AC power from the bat-
dirty. The initial measurement of insulation resist- tery charger.
ance should be established using a low voltage c. Press the Emergency Stop button and wait
(500V) megger type instrument and if manually at least 30 seconds before completing
powered the handle should initially be turned slowly. Step d.
Full voltage megger tests or any other form of high d. Remove the negative battery cable (−)
voltage test should not be applied until the windings from the battery.
have been dried out and if necessary cleaned. e. Install a lockout device on the battery cable
CAUTION The AVR plus any voltage trans- end. (For engines equipped with an air-
formers should be disconnected, and any tem- powered starting system, close air valve
perature detector leads (RTDs/thermistors) and install valve locking device.)
should be grounded during the test. Refer to the 3. Put on high voltage gloves with leather protec-
generator wiring diagram for details. tors.
SURGE SUPPRESSER
REMOVE TO TEST
WINDING SCHEMATIC
WHEATSTONE
BRIDGE
MAIN STATOR
FRAME EXCITER EXCITER MAIN
WINDING WINDING WINDING WINDING
SIZE STATOR ROTOR ROTOR
11 12 17 07
6G 17 0.158 1.44 0.0037 0.0148 N/A 0.011
6H 17 0.158 1.54 0.0027 0.0108 N/A 0.0072
6J 17 0.158 1.73 0.0024 0.0096 N/A 0.006
6K 17 0.158 1.95 0.0019 0.0076 N/A 0.0052
P7B 17.5 0.048 1.67 N/A 0.0016 N/A 0.0026
P7C 17.5 0.048 1.85 N/A 0.00126 N/A 0.0020
P7D 17.5 0.048 1.98 N/A 0.00114 N/A 0.0018
P7E 17.5 0.048 2.17 N/A 0.00093 N/A 0.0015
P7F 17.5 0.048 2.31 N/A 0.00076 N/A 0.0011
P7G 17.5 0.048 2.42 N/A 0.00080 N/A 0.00212
PMG
ASSEMBLY
GENERATOR AIR INLET GENERATOR
COVER (ROTATING AIR DISCHARGE
RECTIFIER ACCESS) COVERS
12. Insert two bolts (M10) in the two holes provided FIGURE 4-8. HC6 GENERATOR LIFTING POSITIONS
for “jacking” purposes, on the endbracket cen-
ter line. Screw bolts in until endbracket pilot is
GENERATOR
clear of locating recess. LIFTING EYE
LOCATION
13. Carefully tap the whole assembly off the bear-
ing cartridge housing, ensuring the endbracket
is supported to prevent the exciter stator from
damaging the windings on the exciter rotor.
STATOR ROTOR
ASSEMBLY ASSEMBLY
LIFT LIFT
USE FORKLIFT OR
OTHER ADEQUATE
LIFTING DEVICE TO
SLIGHTLY LIFT ROTOR
SHAFT UNTIL ROTOR
CAN BE SUPPORTED
BY HOIST/SLING.
STATOR
ROTOR
ASSEMBLY
ASSEMBLY
STATOR ROTOR
ASSEMBLY ASSEMBLY
STATOR LIFT
(EXAMPLE)
ROTOR LIFT
(EXAMPLE)
WOOD
BLOCKS
3. Disconnect the PMG wiring harness connector. 3. Connect the PMG wiring harness connector.
4. Remove the four bolts and clamps retaining the 4. Install the PMG assembly cover using the four
exciter stator housing to the endbracket. screws and lockwashers, and tighten securely.
DIAL
CLAMP INDICATOR
+.010
+.010
MEASURED AT
BOLT CIRCLE
DIAMETER
-.002
-.004
10.7 IN.
-.010
-.010
-.015
-.015
ANGULAR ALIGNMENT,
SEE FIGURE 6-15
GENERATOR
SHAFT HUB
DIAL
INDICATOR
GENERATOR
CLAMP
AND ENGINE
CRANKSHAFT SEE DETAIL A FAN HOUSING
CENTERLINE
DETAIL A
INTERNAL FUEL
ALARM PANEL
Overfill Indicator/Horn/Silence Button Indicates the amount of fuel that is contained in the
sub-base tank.
The overfill alarm Indicates that the fuel has Test Button
reached an abnormally high level (95%). Immedi-
ately stop adding fuel. It also indicates a possible Press the TEST switch to test the indicator light and
failure of the “pump-off” float gauge for fuel systems the horn. The test will remain active for as long as
that contain the fuel transfer pump. the button is pressed.
OVERFILL
INDICATOR/ FUEL
TEST BUTTON GAUGE
HORN
HORN
SILENCE
BUTTON
HORN SILENCE/
TEST BUTTON
The rupture basin leak detect switch (Figure 5-4) is 2. Activate leak detect switch (move float up-
provided with sub-base fuel tanks used with the op- ward).
tional enclosure. This switch should be checked
once a year to make sure switch is properly operat- 3. Check control display for Rupture Basin fault
ing. In some areas, weekly inspections may be re- message. If no indication of fault, repair defec-
quired by safety code regulations. tive circuit. Refer to Enclosure/Options Wiring
(DQCA−DQCC) diagram in Section 6.
To test the leak detect switch:
1. Remove the pipe fitting/switch assembly from 4. Apply thread sealant to pipe fitting and install
the rupture basin tank. switch assembly.
ENCLOSURE
SUB-BASE
LEAK DETECT FUEL TANK
SWITCH ASSEMBLY
FAULT
ACKNOWLEDGE
BUTTON
STATE LINE
ACTION LINE
DESCRIPTION LINE
MENU DISPLAY
AREA
OPERATOR SWITCH
GRAPHICAL
PANEL PANEL
DISPLAY
Category B Fault Codes: Consist of faults that can Category E Fault Codes: Indicates non-critical op-
affect generator set performance or can cause en- erational status of generator set, external faults, or
gine, alternator, or connected equipment dam- customer fault inputs. May require repair by trained
age. Operate generator set only when it is powering and experienced service personnel.
B 554 Wrng Fuel rail pressure sensor B 1319 Wrng High alternator temp
B 555 Wrng Blowby pressure C 1321 Wrng Common warning driver
A 556 Shtdn Blowby pressure A 1322 Shtdn Load gov kW setpoint oor hi
A 586 Shtdn Run/Stop switch A 1323 Shtdn Load gov kW setpoint oor lo
A 587 Shtdn Run/Stop switch B 1324 Wrng Load gov kVAR oor hi
D 611 Wrng Engine hot B 1325 Wrng Load gov kVAR oor lo
D 688 Shtdn High oil level alarm B 1326 Wrng Backup starter disconnect
B 689 Wrng Crank shaft sensor A 1327 Shtdn Load gov kW analog oor
B 719 Wrng Blowby pressure sensor D 1328 Wrng Genset CB tripped
B 729 Wrng Blowby pressure sensor B 1329 Wrng AVR DC power failure
B 731 Wrng Cam/Crank misalignment A 1331 Shtdn AVR driver shorted
B 778 Wrng Camshaft sensor A 1332 Shtdn Manual switch oor lo
C 1118 Wrng Prelube relay driver A 1333 Shtdn Manual switch oor hi
A 1121 Shtdn Failed to Disconnect A 1334 Shtdn Critical scaler oor
C 1219 Wrng Utility CB tripped
B 1335 Wrng Non critical scaler oor
C 1222 Wrng Power transfer not in auto
E 1336 None Cooldown complete
C 1223 Wrng Utility frequency sensor
E 1337 None Network wink
C 1224 Wrng Gen over voltage sensor
E 1341 Shtdn Load demand stop
C 1225 Wrng Gen under voltage sensor
A 1342 Shtdn Slot 0 card
C 1226 Wrng genset frequency sensor
A 1343 Shtdn Slot 1 card
E 1311 Shtdn/ Customer input #1
Wrng A 1345 Shtdn Slot 3 card
E 1312 Shtdn/ Customer input #2 A 1346 Shtdn Slot 4 incorrect
Wrng C 1351 Wrng Slot 4 / network enabled
E 1313 Shtdn/ Network Fault 1 C 1414 Wrng Run relay contact
Wrng
C 1415 Wrng Run relay driver
E 1314 Shtdn/ Network Fault 2
Wrng D 1417 Wrng Power down error
E 1315 Shtdn/ Network Fault 3 B 1419 Wrng Fuel rail driver
Wrng
B 1421 Wrng Timing rail driver #1
E 1316 Shtdn/ Network Fault 4
B 1422 Wrng Timing rail driver #2
Wrng
C 1424 Wrng High side driver
E 1317 Shtdn/ Customer input #3
Wrng C 1427 Wrng Overspeed relay driver
WARNING Many troubleshooting procedures present hazards which can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and
mechanical hazards should perform service procedures. Review safety precautions.
CODE: 146 Indicates engine is operating near cooling system capacity. Increase in
LAMP: Warning load or higher ambient temperature may cause High Coolant Temp
MESSAGE: (151) shutdown. Review code 151 correction list for other possible
HIGH COOLANT TEMP WARNING causes.
CODE: 151 Indicates engine has overheated (engine coolant temperature has ris-
LAMP: Shutdown en above the shutdown trip point. Allow engine to cool down complete-
MESSAGE: ly before proceeding with the following checks:
HIGH COOLANT TEMP ALARM
a. Check coolant level and replenish if low. Look for coolant leaks
and repair if necessary.
b. Check for obstructions to cooling airflow and correct as neces-
sary.
c. Check fan belt and repair if necessary.
d. Check blower fan and circulation pumps on remote radiator
installations.
e. Reset control and restart after locating and correcting problem.
CODE: 152 Indicates engine coolant heater is not operating or is not circulating
LAMP: Warning coolant. Set is in standby mode but is not operating. Warning occurs
MESSAGE: when engine jacket water coolant temperature is 70 F (21 C) or lower.
LOW COOLANT TEMP
NOTE: In applications where the ambient temperature falls below
40 F (4 C), Low Coolant Temp may be indicated even though the
coolant heaters are operating.
CODE: 197 Indicates engine coolant level has fallen to an unacceptable level. If
LAMP: Warning generator is powering critical loads and cannot be shut down, wait until
MESSAGE: next shutdown period, then follow 235 Coolant Level Alarm proce-
COOLANT LEVEL WARNING dure. If engine can be stopped, follow code 235 procedure.
CODE: 235 Indicates engine coolant level has fallen below the alarm trip point. Al-
LAMP: Shutdown low engine to cool down completely before proceeding.
MESSAGE:
a. Check jacket water coolant level and replenish if low. Look for
COOLANT LEVEL ALARM
possible coolant leakage points and repair if necessary.
b. Reset control and restart after locating and correcting problem.
WARNING Many troubleshooting procedures present hazards which can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and
mechanical hazards should perform service procedures. Review safety precautions.
CODE: 359 Indicates possible fuel system or air induction problem. (Engine cranks
LAMP: Warning but fails to start)
MESSAGE:
a. Check for empty fuel tank, fuel leaks, or plugged fuel lines and
ENGINE FAILED TO START
correct as required.
b. Check for dirty fuel filter and replace if necessary.
c. Check for dirty or plugged air filter and replace if necessary.
d. Reset the control and restart after correcting the problem.
CODE: 611 Indicates that an engine hot shut down has occurred (cool-down timers
LAMP: Warning were bypassed). This condition will occur when the operator presses
MESSAGE: the Emergency Switch or moves the 0/Manual/Auto switch to the 0
ENGINE HOT (Off) position before the genset completes the cooldown operation.
(Genset should run at 10% or less load for 3 minutes before engine
shutdown.) This type of shutdown should be avoided. Can cause pos-
sible loss of performance and engine damage.
CODE: 1311 through 1318 When any one of these customer defined inputs is detected by the con-
LAMP: Shutdown/Warning trol, the corresponding fault message is displayed. The nature of the
MESSAGE: fault is an optional customer selection. These fault functions can be
Customer Defined Fault programmed to initiate a shutdown or warning as indicated by the
Warning or Shutdown lamp.
WARNING Many troubleshooting procedures present hazards which can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and
mechanical hazards should perform service procedures. Review safety precautions.
CODE: 1417 Indicates that the control can not power down due to some unknown
LAMP: Warning condition. Possible drain on battery. Contact an authorized service
MESSAGE: center for service.
POWER DOWN ERROR
CODE: 1433 / 1434 Indicates local or remote Emergency Stop. Emergency Stop shutdown
LAMP: Shutdown status can be reset only at the local control panel.
MESSAGE: To reset the local/remote Emergency Stop button:
EMERGENCY STOP − LOCAL / Pull the button out.
EMERGENCY STOP − REMOTE Move the O/Manual/Auto switch to O (Off).
Press the front panel Fault Acknowledge button.
Select Manual or Auto, as required.
CODE: 1438 Indicates possible fault with control, speed sensing or starting system.
LAMP: Warning See code 441 for corrective action.
MESSAGE:
FAIL TO CRANK
CODE: 1439 Indicates fuel supply is running low. Check fuel supply and replenish as
LAMP: Warning required.
MESSAGE:
FUEL LEVEL LOW IN DAY
CODE: 1441 Indicates fuel supply is running low. Check fuel supply and replenish as
LAMP: Warning required.
MESSAGE:
FUEL LEVEL LOW IN MAIN
CODE: 1442 Indicates battery voltage drops below 14.4 volts for two seconds dur-
LAMP: Warning ing starting.
MESSAGE: Discharged or defective battery. See code 441 for corrective action.
BATTERY IS WEAK
CODE: 1443 Indicates battery has dropped below genset operating range (3.5 volts
LAMP: Warning when cranking) to power the starter and the control circuitry. See code
MESSAGE: 441 for corrective action.
BATTERY IS DEAD
WARNING Many troubleshooting procedures present hazards which can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and
mechanical hazards should perform service procedures. Review safety precautions.
CODE: 1472 If the AmpSentry High Current shutdown threshold has been exceed-
LAMP: Warning ed, fault code 1472 (shutdown) becomes active.
MESSAGE:
OVERCURRENT
This fault remains active and cannot be reset until the Alternator
Overheat Integral time has expired (which takes up to five min-
utes). The Alternator Overheat Integral time allows the alternator
to cool down before allowing a restart.
Possible Causes:
1. Short or Overload
2. Incorrect CT ratio, CTs, or CT connections
3. Incorrect generator set rating set up
Diagnosis and Repair:
1. Short or Overload
a. Inspect the load cables and AC harness connections. Check for a
short circuit to engine block ground. Refer to fault code 1444 for over-
load condition troubleshooting.
2. Incorrect CT ratio, CTs, or CT connections
a. Check that correct CT’s have been installed. Verify that the CTs are
installed in the correct order and location. With the use of InPower ad-
just the CT ratio appropriately in the generator setup menu.
CODE: 3611 If the ”Custom Overcurrent Protection Enable” is enabled and current
LAMP: Warning flow exceeds the ”Custom Overcurrent Threshold” for a period of time
MESSAGE: as determined by the ”Custom Overcurrent Time Characteristic” pa-
CUSTOM OVERCURRENT FAULT rameter the genset will limit the current flow amount with the warning
fault code 3611.
This fault remains active and cannot be reset until the Alternator
Overheat Integral time has expired. The Alternator Overheat Inte-
gral time allows the alternator to cool down before accepting the
load again.
Possible Causes:
1. The ”Custom Overcurrent Threshold” parameter is configured incor-
rectly (low).
2. The ”Custom Overcurrent Characteristic” parameter is configured
incorrectly.
3. There is excessive current flow.
Diagnosis and Repair:
1. The ”Custom Overcurrent Threshold” parameter is configured incor-
rectly (low).
a. Make sure that the ”Custom Overcurrent Threshold” percent value is
set appropriately for the application. Verify the corresponding setting
with the use of InPower software. Go to Setup > Advanced Setup >
OEM Setup > OEM Alternator Setup and set the parameter appropri-
ately for the application.
NO. 625-3100 SH 1 OF 2
REV. H
MODIFIED 2/2011
NO. 625-3100 SH 2 OF 2
REV. H
MODIFIED 2/2011
7-4
Copyright 2020 Cummins Inc. 7-4
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO. 630-2645 SH 1 OF 1
REV. A
MODIFIED 4-03
NO. 630-3210 SH 1 OF 7
REV. D
MODIFIED 6/2012
7-6
Copyright 2020 Cummins Inc. 7-6
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO. 630-3210 SH 2 OF 7
REV. D
MODIFIED 6/2012
NO. 630-3210 SH 3 OF 7
REV. DE
MODIFIED 6/2012
7-8
Copyright 2020 Cummins Inc. 7-8
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO. 630-3210 SH 4 OF 7
REV. D
MODIFIED 6/2012
NO. 630-3210 SH 5 OF 7
REV. D
MODIFIED 6/2012
7-10
Copyright 2020 Cummins Inc. 7-10
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO. 630-3210 SH 6 OF 7
REV. D
MODIFIED 6/2012
NO. 630-3210 SH 7 OF 7
REV. D
MODIFIED 6/2012
7-12
Copyright 2020 Cummins Inc. 7-12
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO. 630-3178 SH 1 OF 7
REV. F
MODIFIED 10/2012
NO. 630-3178 SH 2 OF 7
REV. F
MODIFIED 10/2012
7-14
Copyright 2020 Cummins Inc. 7-14
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO. 630-3178 SH 3 OF 7
REV. F
MODIFIED 10/2012
NO. 630-3178 SH 4 OF 7
REV. F
MODIFIED 10/2012
7-16
Copyright 2020 Cummins Inc. 7-16
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO. 630-3178 SH 5 OF 7
REV. F
MODIFIED 10/2012
NO. 630-3178 SH 6 OF 7
REV. F
MODIFIED 10/2012
7-18
Copyright 2020 Cummins Inc. 7-18
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO. 630-3178 SH 7 OF 7
REV. F
MODIFIED 10/2012
NO. 620-0281 SH 1 OF 2
REV. A
MODIFIED 11-04
7-20
Copyright 2020 Cummins Inc. 7-20
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO. 620-0281 SH 2 OF 2
REV. A
MODIFIED 11-04
NO. 500-4196 SH 1 OF 1
REV. C
MODIFIED 12/2010
7-22
Copyright 2020 Cummins Inc. 7-22
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO. A040V834 SH 1 OF 2
REV. B
MODIFIED 9−2011
NO. A040V834 SH 2 OF 2
REV. B
MODIFIED 9−2011
7-24
Copyright 2020 Cummins Inc. 7-24
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO. A047M944 SH 1 OF 3
REV A
MODIFIED 10−2013
NO A047M944 SH 2 OF 3
REV A
MODIFIED 10−2013
7-26
Copyright 2020 Cummins Inc. 7-26
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO. A047M944 SH 3 OF 3
REV A
MODIFIED 10−2013
NO.A034P810 SH1 OF 13
REV F
MODIFIED 4−2015
7-28
Copyright 2020 Cummins Inc. 7-28
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO.A034P810 SH2 OF 13
REV F
MODIFIED 4−2015
NO.A034P810 SH3 OF 13
REV F
MODIFIED 4−2015
7-30
Copyright 2020 Cummins Inc. 7-30
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO.A034P810 SH4 OF 13
REV F
MODIFIED 4−2015
NO.A034P810 SH5 OF 13
REV F
MODIFIED 4−2015
7-32
Copyright 2020 Cummins Inc. 7-32
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO.A034P810 SH6 OF 13
REV F
MODIFIED 4−2015
NO.A034P810 SH7 OF 13
REV F
MODIFIED 4−2015
7-34
Copyright 2020 Cummins Inc. 7-34
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO.A034P810 SH8 OF 13
REV F
MODIFIED 4−2015
NO.A034P810 SH9 OF 13
REV F
MODIFIED 4−2015
7-36
Copyright 2020 Cummins Inc. 7-36
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO.A034P810 SH10 OF 13
REV F
MODIFIED 4−2015
NO.A034P810 SH11 OF 13
REV F
MODIFIED 4−2015
7-38
Copyright 2020 Cummins Inc. 7-38
THIS IS A REPRESENTATIVE DRAWING.
FOR SERVICE, USE DRAWING SUPPLIED
WITH GENSET, IF AVAILABLE.
NO.A034P810 SH12 OF 13
REV F
MODIFIED 4−2015
NO.A034P810 SH13 OF 13
REV F
MODIFIED 4−2015
7-40
Copyright 2020 Cummins Inc. 7-40
power.cummins.com
Copyright E 2020 Cummins Inc. All rights reserved.
Cummins, the “C” logo, PowerCommand, AmpSentry, and InPower are trademarks of Cummins Inc.
Other company, product, or service names may be trademarks or service marks of others.
Specifications are subject to change without notice.