Gorai-Sahoo2022 Chapter EnergeticAndExergeticAnalysisO
Gorai-Sahoo2022 Chapter EnergeticAndExergeticAnalysisO
Gorai-Sahoo2022 Chapter EnergeticAndExergeticAnalysisO
Nomenclature
Greek Symbols
ψ̇ Exergy (kW)
η Efficiency (dimensionless)
μ Entrainment ratio (dimensionless)
Difference
v Specific volume (m3 /kg)
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 99
P. Mahanta et al. (eds.), Advances in Thermofluids and Renewable Energy, Lecture Notes
in Mechanical Engineering, https://doi.org/10.1007/978-981-16-3497-0_8
100 B. Gorai and S. Sahoo
Subscripts
AC Air cooled
amb Ambient
comp Compressor
cond Condenser
diff Diffuser
EVC Evaporative cooling
evp Evaporator
in Inflow
out Outflow
p Primary
ref Refrigerant
s Secondary
1 Introduction
Robinson and Groll [3] have established for a given gas cooler exit temperature the
COP of the transcritical CO2 system is a strong function of the gas cooler pressure,
and the maximum COP is achieved at the optimum gas cooler pressure. The study
also demonstrated that the maximum irreversibility associated with expansion valve
resulted in lower 2nd law efficiency. Ahammed et al. [4] have analysed a conven-
tional transcritical CO2 system for simultaneous cooling and heating application for
a dairy plant. The performance of four different configurations with and without
ejectors employing multiple gas coolers and an internal heat exchanger is compared.
The result clearly demonstrates that the position of the IHX plays a vital role, and the
best performance was realised when the IHX was placed between the gas coolers.
Deng et al. [5] described the usefulness of ejectors in CO2 -based transcritical refrig-
eration systems by showing 25% improvement in cooling COP. Experimental study
carried out by Hajidavalloo, Eghtedari [6], established the usefulness of evaporative
condenser over air cooled condenser in air conditioning applications. The exper-
imental study has demonstrated up to 20% reduction in power consumption and
50% improvement in COP by replacing the air cooled condenser by an evaporative
condenser. Additionally, in hot and dry weather conditions, the application of evapo-
rative condenser is commercially recommended. From the survey, it is observed that
not much study on evaporative cooling-based transcritical CO2 systems is available
in open literature. Moreover, the exergetic analysis especially systems incorporating
evaporative cooling system which handles the air water vapour mixture is scarce in
open literature. Hence, a comprehensive thermodynamic comparison both 1st and
2nd law is the prime focus of the present investigation.
Fig. 1 a Schematic of an ejector-based CO2 refrigeration system with air cooled gas cooler.
b Schematic of an ejector-based CO2 refrigeration system with evaporative gas cooler. c T-s plot of
CO2 refrigeration cycle with ejector
Energetic and Exergetic Analysis of an Ejector … 103
the mixing zone (i.e. process 8–9). After the mixing zone, the refrigerant passes
through a diffusing section to recover the pressure. The phase separator installed at
the exit of the diffuser separates the vapour part from that of the liquid part. The
liquid part enters into the evaporator to take care of the cooling load, and the gaseous
part is compressed by the compressor and then cooled in the gas cooler, completing
the cycle. The compressed gas rejects the heat to the cooling medium while passing
through the gas cooler, thus completing the cycle.
The analysis is based on the following simplifying assumptions:
• The heat loss from different components to ambient is negligible.
• The pressure drop in various components is negligible.
• Refrigerant flow is steady state and steady flow condition.
• The kinetic energy at the entry of the nozzle and at the exit of the diffuser is
negligible
• Energy inputs to the air circulation fan and water pump in the heat rejecting unit
are negligible.
The steady-state thermodynamic analyses of both the systems are carried out
applying 1st and 2nd law to each individual component. The thermodynamic cycle
is pictorially presented on T −s plot as given in Fig. 1c.
Evaporator
Applying steady flow energy equation and exergy balance to the evaporator, the
refrigeration capacity and rate of exergy destruction can be expressed as given in
Eqs. 1 and 2, respectively. Here ṁref_s is mass flow rate of refrigerant passing through
the secondary nozzle and also through the evaporator.
where enthalpy of state point 5 and 6 is the functions of evaporator temperature and
dryness fraction at the inlet and exit of the evaporator.
ṁ ref_p (h 2s − h 1 )
Ẇcomp = ṁ ref_p (h 2 − h 1 ) = (4)
ηcom
Ejector
Based on the simplifying assumption mentioned earlier, the ejector part which
comprises the primary, secondary nozzle, mixing chamber and diffuser is simulated
using governing mass, energy and exergy balance equations given below. The ratio
of secondary to primary mass flow rate of the refrigerant in secondary and primary
nozzles, respectively, is termed as entrainment ratio and is expressed as:
Primary Nozzle
h3 − h7
ηejec_np = (7)
h 3 − h 7s
u 27
h3 = h7 + (9)
2
Secondary Nozzle
h 6 − h 10
ηejec_ns = (11)
h 6 − h 10s
u 210
h 6 = h 10 + (13)
2
Energetic and Exergetic Analysis of an Ejector … 105
Diffuser
u 28
h9 = h8 + (17)
2
h 9s − h 8
ηejec_d = (18)
h9 − h8
Phase separator
It separates the saturated liquid and vapour from the vapour and liquid mixture. The
isothermal separation is expressed as:
ṁ total h 9 = ṁ p h 1 + ṁ s h 11 (21)
where (mair ) mass flow of water through gas cooler and Tair is temperature rise of
air in the gas cooler.
Exergy destruction on the gas cooler is calculated using following equations:
ψ̇ref_in = ṁ ref_p h 2 − h amb_ref − Tamb s2 − samb_ref (27)
ψ̇ref_out = ṁ ref_p h 3 − h amb_ref − Tamb s3 − samb_ref (28)
ψ̇air_in = 0 (29)
h air_out − h air_amb −
ψ̇air_out_AC = ṁ air (30)
Tamb sair_out − sair_amb
h water,in = f Twater,in (36)
v = f Twater,in (37)
Pv,in
ωin = 0.622 (38)
Patm − Pv,in
Pv,out
ωout = 0.622 (39)
Patm − Pv,out
ṁ w_makeup
ṁ air = (40)
ωout − ωin
Applying the steady flow energy equation to the evaporative cooling-based gas
cooler.
Q̇ gc_EVC = ṁ ref_p (h 2 − h 3 )
(41)
= ṁ air h air_out − h air_in − h water_ in .ṁ w_makeup
The expressions for flow exergy associated with refrigerant in, out and air in are
the same as given in Eqs. 27, 28 and 29, respectively.
⎡ ψ̇air_out_EVC = ṁ air ⎤
T Tair_output
c p_air + ωout cp_water . Tair_input Tair_output − 1 − ln +
⎢ ⎡ air_input Tair_input ⎤ ⎥
⎢ (1+1.608.ωin ) ⎥ (42)
⎢ (1 + 1.608.ωout ). ln (1+1.608.ωout ) + ⎥
⎣ 0.287. Tair_input .⎣ ⎦ ⎦
ωout
1.608.ωin . ln ωin
ψ̇water_in = ṁ w_makeup
⎡ ⎤
(h water_in − h water_atm ) − Tatm .(swater_in − swater_atm )+
⎢ ⎥ (43)
⎣ 8314 ⎦
( patm − psat_in ).vwater − .Tair_input . ln Rh input
18
Expansion valve
In an ejector-based system, the expansion valve is installed at the exit port of phase
separator. While flowing through the expansion valve, no change in enthalpy is
observed. However, exergy destruction takes place due to irreversible pressure drop
by frictional dissipation and is estimated using the expression given in Eq. 44.
Q̇ evp
C O Psystem = (47)
Ẇcomp
All the simulations are carried out for the input parameters included in Table 1. If
nothing is mentioned, the RH is assumed to be 40%.
Fig. 2 Effects of ambient temp on system COP and the total irreversibility
Figure 2 presents the effect of ambient temperature on COP and total irreversibility
for both the systems. The figure clearly demonstrates a significant improvement in
COP and reduction in total irreversibility for EVC-based gas coolers compared that of
the air cooled system, and this may be attributed to lower gas cooler exit temperature
in the earlier case which results in lower operating pressure. It has been observed that
for a given gas cooler exit temperature, there exists an optimum gas cooler pressure
at which the transcritical system gives its best performance. Hence, for the present
comparison, the operating pressures for both the air cooled and EVC-based gas
coolers are fixed at their optimum values corresponding to the respective gas cooler
exit temperatures. Because of the reduced operating pressure of the EVC-based gas
cooler system, the power input to the compressor decreases resulting in improved
COP. However, the difference decreases with increase in the ambient temperature. In
case of air cooled systems because of the large temperature difference between the
refrigerant and the air and higher heat rejection rate due to high operating pressure
significantly increases the system irreversibility.
Figure 3 is a pictorial representation of exergy destruction or irreversibility present
in various components. The figure clearly depicts that in case of air cooled systems,
the maximum irreversibility is recorded in the ejector; however, in EVC-based
systems, the gas cooler overtakes the ejector in terms of exergy destruction. It is note-
worthy to mention here that in all the components except the evaporator, the exergy
destruction is higher in case of air cooled systems compared to that of EVC-based
systems. One of the major reasons behind this large difference in the irreversibility
associated with all the components is the high operating gas cooler pressure in case
of air cooled systems. High operating gas cooler pressure results in higher work of
compression, increased compressor inefficiency, higher heat rejection rate in the gas
110 B. Gorai and S. Sahoo
cooler with larger temperature difference and consequently higher exergy destruc-
tion. Similarly for the expansion valve the exergy destruction is higher for systems
with air cooled gas coolers due to its higher operating pressure ratio.
Figure 4 indicates the effects of relative humidity on the system COP as well as
the makeup water requirement for different ambient conditions. It has been observed
that for dry atmosphere, the COP of the EVC-based system is significantly higher
compared to the air cooled system. This is due to lower WBT of ambient air which
decides the refrigerant exit temperature in case of EVC-based gas coolers. As RH
of the ambient air increases, the COP of the EVC systems approaches that of the air
Fig. 4 Variation of system COP and makeup requirement with the relative humidity of the ambient
air
Energetic and Exergetic Analysis of an Ejector … 111
cooled system. This is more pronounced at lower DBT of the air. The makeup water
requirement reduces with increase in RH and increases with DBT.
4 Conclusion
References
1. Liu, Y., Groll, E. A., Yazawa, K., & Kurtulus, O. (2017). Energy-saving performance and
economics of CO2 and heat pumps with simultaneous cooling and heating applications in food
processing Case studies. International Journal of Refrigeration, 73, 111–124.
2. Omer, C., Yuksel, B., Kara, Y. A., Caglar, A., & Tulek, Y. (1994). Heat pump utilization in milk
pasteurization. Energy Conversion and Management, 35(2), 91–96.
3. Robinson, D. M., & Groll, E. A. (1998). Efficiencies of transcritical CO2 cycles with and without
an expansion turbine. International Journal of Refrigeration, 21(7), 577–589.
4. Ahammed, E., Bhattacharyya, S., & Ramgopal, M. (2018). Analysis of CO2 based refriger-
ation systems with and without ejector for simultaneous pasteurization and chilling of milk.
International Journal of Refrigeration, 95, 61–72.
5. Deng, J., Jiang, P., Lu, T., & Lu, W. (2007). Particular characteristics of transcritical CO2
refrigeration cycle with an ejector. Applied Thermal Engineering, 27, 381–388.
6. Hajidavalloo, E., & Eghtedari, H. (2010). Performance improvement of air-cooled refrigeration
system by using evaporatively cooled air condenser. International Journal of Refrigeration, 33,
982–988.
7. Arora, R. C. (2010). Refrigeration and air conditioning. PHI Learning Private Limited, p. 507
8. Ahammed, E., Bhattacharyya, S., & Ramgopal, M. (2014). Thermodynamic design and simu-
lation of a CO2 based transcritical vapour compression refrigeration system with an ejector.
International Journal of Refrigeration, 45, 177–188.
9. Singh, S., & Dasgupta, M. S. (2017). CO2 heat pump for waste heat recovery and utilization
in dairy industry with ammonia based refrigeration. International Journal of Refrigeration, 78,
108–120.