IR140Y
IR140Y
Product Description
The BENDER A-ISOMETER IR140Y monitors the insulation
resistance of ungrounded (floating) AC systems up to AC 300 V.
The response value is steplessly adjustable.
A1 A2 L1 L2 KA LT1 LT2 PT
ON
Versions IR140Y-40 and IR140Y-60 operate with a higher
+ measuring voltage. Therefore, the increased response sensitivity
~ ALARM kΩ
-
MONITOR
to insulation faults behind directly connected rectifiers will be
TEST reduced in comparison to the sensitivity with lower measuring
RESET
voltage (see characteristic curve).
kΩ
10 200 The device is fitted into a standard plastic casing for quick
RESET/- A-ISOMETER®
Serie 140 assembly onto support rail according to DIN EN 50 022 or for
KE 11 12 14 21 22 24 screw mounting.
Operational Information
and ground. When the insulation value of the system falls below
the pre-set response value, the alarm LEDs "ALARM" illuminate
and the alarm relay switches. The alarm LEDs indicate either "AC
ground fault" or "DC ground fault".
If the ground fault indication is to be stored, the terminals LT1/LT2
DIN Rail mounting as
per DIN EN 50 022 have to be bridged by an external reset button (NC contact) or by
selecting "with fault memory" at the respective DIP switch on the
front plate. The memory can be reset by pushing the <TEST/
RESET> button located at the front plate or the external button
for a short period provided that the insulation resistance exceeds
■ For Ungrounded (floating) AC systems the selected alarm response value by at least 25%.
from AC 0 to 300 V
By pushing the test button, the correct function of the measuring
■ Adjustable set-point ranges available from: circuit, the alarm LEDs and the alarm relay can be checked.
- 1kΩ...20kΩ
- 10kΩ...200kΩ Note: Insulation faults on directly connected DC circuits are
- 0.5MΩ..5MΩ indicated with an increased response sensitivity. The preset
■ Operation and alarm LEDs response values apply to the pure AC system only. In order to
avoid complex system conditions, DC supplied components
■ Two voltage-free chage-over contacts should be isolated galvanically from the system to be monitored or
■ Connection monitoring a BENDER A-ISOMETER IR140Y should be used.
■ Fault memory, selectable
■ Test and reset button Standards
■ UL / CSA listed, Meets VDE/IEC standards, CE mark The A-ISOMETER corresponds to the standards of DIN 57 413
■ Meets IEC801-4, Class III EMC requirements Bl2/VDE 0413 T2/01.73, IEC 1557-8; 1995, prEN 50197-8: 1994,
ASTM F1207-89, UL508.
Page 1 of 4
1.1 - 10.1A / Jan 1997
Bender Industrial Products - 700 Fox Chase - Coatesville, PA 19320 - Toll-free: (800) 356-4266 - Fax: (610) 383-7100
Technical Data IR140Y
Response Values
Model Response value Hysteresis Response time Response time Response time System leakage
R ALARM (RE=0kΩ,CE=1µF) (RE=0.5xRALARM,CE=1µF) (RE=RALARM) capacitance CE, max.
Measuring Circuit
Model Measuring voltage UM Measuring current IM Internal DC resistance/impedance Max. admissible stray DC voltage
acc. to DIN VDE 0413
Bender Industrial Products - 700 Fox Chase - Coatesville, PA 19320 - Toll-free: (800) 356-4266 - Fax: (610) 383-7100
IR140Y-..
Wiring diagram
L1
L2
L1 L2 KA
PE
Important Instructions
Only one insulation monitoring device may be used in each For checking the measuring circuit, the BENDER A-ISOMETERs are
interconnected system. Please check for correct system and supply equipped with connection monitoring. The following fault indications are
voltage. possible:
The terminal KA must be connected by a separate wire to one phase Fault Indication Alarm LED Alarm relay
conductor (L1 or L2) of the system to be monitored. This KA connection + -
monitors the connections between the system being monitored and the
AC faults x x x
Ground Fault Monitoring Device. There must be a connection between
L1/L2/KA for connection monitoring (e.g. via the winding of the isolation DC faults L+ x x
transformer). This function is disabled if L1/L2 or KE/ are bridged. DC faults L- x x
In order to check the proper connection of the device, it is recommended Interruption /KE or L1/L2 o o x
to carry out a functional test using a genuine ground fault, e.g. via a
suitable resistance, before starting the operation. o = flashing
x = continuous indication
When insulation and voltage tests are to be carried out, the device must
be isolated from the system for the test period. Electrical equipment
If one of these fault indications occurs, the connections have to be
shall only be installed by qualified personnel in consideration of the
checked as soon as possible.
current national and local safety regulations.
Page 3 of 4
1.1 - 10.3A / Jan 1997
Bender Industrial Products - 700 Fox Chase - Coatesville, PA 19320 - Toll-free: (800) 356-4266 - Fax: (610) 383-7100
Characteristic Curve IR140Y/IR140Y-.0
180 1600
160
1400
DC+ (10kΩ)
140
1200
120
1000
DC+ (100kΩ)
100
800
DC+
80
600
60 DC-
400
DC+
40
200
20
0
50 100 150 200 250 300
0 UN (V)
25 50 75 100 125 150
UN (V)
1400
14
1200
12
1000
DC- 10
800
DC+
600 8
400 6
200
DC-
4
DC+
0
50 100 150 200 250 300
2
UN (V)
0
50 100 150 200 250 300
UN (V)
RAN (MΩ) IR140Y-6
40
DC+ (3MΩ)
Response Sensitivity for DC ground faults
30 DC+ Y version, response value in center position
(midscale) (only relay)
DC+ (1 MΩ) the middle DIP switch for the response value
20 is activated
DC+ alarm LED + and relay
10
DC- alarm LED - and relay
DC-
DC+
0
50 100 150 200 250 300
UN (V)
Page 4 of 4
Right to modifications reserved 1.1 - 10.4A / Jan 1997