National Electrical Code of The Philippines
National Electrical Code of The Philippines
National Electrical Code of The Philippines
Article 517 of the 2020 National Electrical Code (NEC) covers requirements to
Part I covers general requirements such as the scope and definitions that apply to
these facilities.
Chapters 1 through 7.
When most people think of health care facilities, they think of hospitals or
emergency care units. However, the informational note in the NEC 517.2 definition of
hospitals
nursing homes
clinics,
Article 517 applies to electrical construction and installation criteria in health care
Article 517.2 defines patient care vicinity as a space intended for the examination
and treatment of patients that extends 1.8 m (6 ft) beyond the normal location of the bed,
chair, or other device that supports the patient during examination and treatment and
extending vertically to 2.3 m (7 ft 6 in.) above the floor (see figure above).
Part II of Article 517 applies to all patient care spaces within health care facilities.
Part II is required to apply to areas where patients are intended to be placed on life
It does not apply to business offices, corridors, waiting rooms, and the like in
clinics, medical and dental offices, outpatient facilities, or areas used exclusively for
Wiring methods for health care facilities are required to comply with the
amended by Article 517. See also 90.3, Code Arrangement.90.3 Application Example.
In Article 517, the equipment grounding conductor requirements for branch
circuits serving patient care locations is amended to be more restrictive. Two equipment
metal raceway that qualifies as an equipment grounding return path in accordance with
Section 250.118.
These are two more restrictive requirements than what is normally acceptable in
Section 250.118.
Part III covers essential electrical systems as noted in Section 517.25. The section
mandates that Type 1 and Type 2 essential electrical services (ESS) for healthcare
lighting and power service, considered essential for the life safety and orderly cessation
should be construed as specifying safeguards against the useful beam or stray X-ray
Department of Health and Human Services and are regulated under Public Law 90-602.
In patient care spaces, 517.80 requires that equivalent insulation and isolation to
that required for the electrical distribution systems shall be provided for
communications, signaling systems, data system circuits, fire alarm systems, and systems
less than 120 volts, nominal. Class 2 and Class 3 systems are not required to comply with
specified by Chapter 7 or 8.
Part VII of Article 517 covers the installation requirements for isolated power
systems in health care facilities. These systems are an optional protection technique that
can be used for certain patient care areas of health care facilities as provided in
517.19(E). Isolated power systems are required to be used where interruption by a GFCI
Each circuit shall be controlled by a switch that has a disconnecting pole in each
conductor that will disconnect all power simultaneously. Isolation shall be accomplished
and secondary windings. Motor generators and batteries are permitted. Secondary of
Health care facilities are special occupancies falling under the requirements of
through 4 of the Code are applicable and are modified to be more restrictive in many
areas.
Redundancy of power systems, circuits, grounding and bonding all are directed
toward continuity of power and service for patient care. Careful planning, design,
engineering, installation, and inspection is critical for health care facility electrical system
installations.