Lecture Notes On Electrical Engineering
Lecture Notes On Electrical Engineering
INTRODUCTION
Electrical engineering drawing is one of the means by which effective planning of a successful electrical power and
lighting project depend on. Electrical engineering drawing provides a concise picture of the objectives for the
electrical project work to be done. It also serves as a record of intent for owners and as instructions and guidance for
contractors, electricians, installers, and others performing the work. It also serves as Contract documents, can be
used as evidence in court cases involving contractor malfeasance, or failure to comply with the intent of the
drawings and specifications.
The present conformity to accepted formats for drawings and specifications is the result of years of practical
experience reinforced by accepted national and international standards issued by government agencies and private
standards organizations. The standards organizations are advised by experienced personnel from the ranks of
manufacturers,contractors, and other interested parties. The intent of standards is to produce unambiguous
documentation that is understandable by all project participants, from engineers and architects to contractors, project
supervisors, electricians, and installers.
2 Instructs and guides electricians in performing the required wiring and equipment installation while also warning
them of potential hazards such as existing wiring, gas pipes, or plumbing systems.
3 Provides the owner with an “as-built” record of the installed electrical wiring and equipment for the purposes of
maintenance or planning future expansion. The owner then becomes responsible for recording all wiring and
equipment changes.
A typical electrical drawing consists of solid or dashed lines representing wiring or cables and symbols for
luminaires, socket outlets, switches, auxiliary systems, and other electrical devices and their locations on a scaled
architectural floor plan of a home or building. The drawings also include title blocks to identify the project, the
designers or engineers, and the owner, and change blocks to record any changes that have been made since the
drawing was first issued.
In any given set of electrical drawing there are also specialized drawings such as one-line, elevation or riser, and
electrical equipment installation drawings. There might be no drawing requirements for relatively simple electrical
projects such as updating the amperage capacity of a home or extending branch wiring into a basement, attic, or
extension. In these situations, all information needed can be included in a written proposal or other contractual
agreement.
Computer-Aided Drawing
Most large engineering consulting and architectural firms around the world have made the transition from manual to
computer-aided drawing (CAD). These companies have had to purchase computer workstations, applications
software, and plotters, as well as pay for personnel training in CAD. The dedicated workstations and off-theshelf
High-performance desktop computers now available are capable of supporting the most sophisticated commercial
CAD software available.
Some CAD programs are capable of producing the proper forms and making the necessary calculations to produce
material lists and cost estimates based on the number and type of symbols placed on the drawing.
2. Eliminating the tedious tasks of lettering and drawing uniform lines and symbols.
3. Permitting the transfer of large sections of drawings prepared originally for one project to be reused on a
different project.
4. Providing databases of “families” of master digitized drawings that can be modified for reuse on other projects
or become de facto templates for new drawings.
5. Making rapid changes on completed and approved drawings to reflect field changes such as the substitution of
different equipment.
7. Reproducing corrected drawings rapidly for use in the field, eliminating concern that work might be done against
obsolete drawings, necessitating costly rework.
8. Permitting work to be done on a specific drawing by two or more persons at separate workstations within the
same office or miles apart, because data can be transmitted over networks to a master workstation. This permits
two or more persons to participate in the design work in real time.
9. Reducing the space required to store completed drawings, because digital data can be stored on a centralized
server, computer disks, or CD-ROMs.
10. Accelerating the distribution of drawings to all concerned parties: owners, contractors, equipment
manufacturers, and suppliers. The drawing data can be transmitted over computer networks and printed out by
the recipient, saving time and delivery cost.
11 Providing a secure backup for all master drawings files if the drafting offices are destroyed by fire or flood,
saving the time and expense needed to reconstruct the drawings from alternative sources.
.
ELEMENTS OF MOTOR CONTROL SYSTEMS
1 . Relays:
Control magnetic relays are used as auxiliary devices to switch control circuits and large motor
starter and contactor coils and to control small loads such as small motors, solenoid ,electric
heaters, pilot lights, audible signal devices and other relays. A magnetically held relay is
operated by an electromagnet which opens or closes electrical contacts when the electromagnet
is energized. The position of the relay changes by spring and gravity action when the
electromagnet is de-energized. They are normally used to enlarge or amplify the contact
capability, or multiply the switching functions of a pilot device by adding more contacts to the
circuit. Control relays are available in single or double throw arrangements with various
combination of normally open (NO) and normally closed (NC) contact circuits.
2. Overload relays:
The overload relay is added to the magnetic switch of a motor to form what is called a starter. It
acts to open the motor circuit when full load is exceeded. The ideal overload protection for motor
should be an element with current sensing properties very similar to the heating curve of a motor.
A motor with an overload can do no more work than the motor can permit. However, like a fuse
the overload relay has a characteristic permitting it to hold on during the accelerating period
when the inrush current is drawn.
I. On -delay relay (Delay on energizing, DOE) ii. Off -delay relay (Delay on de-energizing,
DODE).
Timer relays are similar to other control relays in that they use a coil to control the operation of
some number of contacts. The difference between a normal relay and a timer is that the contact
of a normal timer delay changing their position the coil is energized.
When power is connected to a coil of an on -delay timer, the contacts delay changing their
positions for some period of time. For this example assume that the timer has to be set for a delay
of 10 seconds. Also assume that the contact is normally open. When voltage is connected to the
coil of the on-delay timer, the contacts will remain in the open position for 10 seconds and then
close. When voltage is removed and the coil is de-energized, the contact will immediately
change back to its normally open position. The contact symbols for the on-delay relay are shown
in the figure below.
The operation of the off-delay timer is the opposite of the on-delay timer. For this example, again
assume that the timer has been set for a delay of 10 seconds, and also assume that the contact is
normally open. When voltage is applied to the coil of the off-delay timer, the contact will change
immediately from open to closed. When the coil is de-energized, however, the contact will
remain in the closed position for 10 seconds before it reopens. The contact symbols for an off-
delay relay are shown in figure below. Time delay relays can have normally open, normally
closed, or a combination of normally open and normally closed contacts.
4. Contactors
They are electromagnetically operated switches that provide a safe and convenient means for
connecting and interrupting branch circuits. The principal difference between a contactor and a
motor starter is that the contactor does not contain overload relays. Contactors are used in
combination with pilot control devices to switch lighting and heating loads and to control AC
motors in those cases where overload protection is provided separately.
5. Limit switches
They are designed to pass an electrical signal only when a predetermined limit is reached.The
limit may be specific position for a machine part or piece of work, or a certain rotating speed
These devices take the place of a human operator and are often used under conditions where it
would be impossible or impractical for the operator to be present or to efficiently direct the
machines. Limit switches are used most frequently as the over travel stops for
machines ,equipments and products in process .These devices are used in control circuits of
magnetic starters to govern the starting, stopping and reversal of electric motors.
The raising or lowering of a float that is mechanically attached to electrical contacts may start
motor driven pumps to empty or fill a tank. Float switches are also used to open or close piping
solenoid valves to control fluids. A float switch is used when a pump motor must be started and
stopped according to changes in the water (or other liquid) level in a tank or sump. Float
switches are designed to provide automatic control of ac and dc pump motor magnetic starters
and automatic direct control of light motor loads.
The operation of a float switch is controlled by the upward or downward movement of a float
placed in a water tank. The float movement causes a sod-operated, or chain and counterweight
assembly to open or close electrical contacts. The float switch contacts may be either normally
open or normally closed and may not be submerged. Float switches may be connected to a pump
motor for tank or sump pumping operations or tank filling, depending on the contact
arrangement.
7. Pressure switches:
They are used to control the pressure of liquids and gases (including air) within a desired range.
Air compressors, for example are started directly or indirectly on a call for more air by a pressure
switch. Any industrial application that has a pressure sending requirement can use a pressure
switch. A large variety of pressure switches are available to cover the wide range of control
requirements for pneumatic or hydraulic machines such as welding equipment, machine tools,
high pressure lubricating systems, and motor driven pumps and air compressors.
The pressures ranges over which pressure switches can maintain control also vary widely. For
example, a diaphragm-actuated switch can be used when a sensitive response is required to small
pressure changes at low-pressure ranges. In all of pressure controlled devices, a set of contacts is
operated.
In addition to pilot devices sensitive to liquid levels, gas pressure and time of day, thermostat
sensitive to temperature changes are widely used. Thermostat indirectly control large motors in
air conditioning systems and in many industrial applications to maintain the desired temperature
range of air, gases, liquids, or solids.
It is a device that provides control of a motor through a motor starter by pressing a button which
opens or closes contacts. It is possible to control motor from as many stations as there are,
through the same magnetic controller. This can be done by using more than one push button
station. Push buttons are momentary contacts and they return to their normal position a pressure
on them are released. They may be normally closed or open ie the contacts are in a rest position,
held there by spring tension and are not subject to either mechanical or electrical external force.
They are switches that make contact positions by turning the operator knob - not pushing it. They
usually maintain contact positions with three and sometimes two selector positions.
It is another type of push button control. It contains two sets of contacts in one unit. One set of
contacts is operated by pulling outward on the button and the other set is operated by pushing the
button. They may consist of two normally open momentary contacts i.e. in its normal position;
neither movable contact connects with stationary contacts. When pushed or pulled outward
(inward) one of the movable contacts will connect with one stationary contact. Another type of a
Push pull operator consists of a normally open momentary contact and a normally closed
momentary contact. In its normal position one movable contacts (normally closed) connect with
a stationary contacts and the other movable contacts (normally open) stays open. When the
button is pulled outward the normally open movable contacts connect with its stationary contact
and the normally closed movable contacts maintains it connection.
Fig 12 Symbols used to represent push pull operator on a schematic diagram
12 Flow switches
A flow switch is a device that can be inserted in a pipe so that when liquid or air flows against a
part of the device called a paddle, a switch is activated This switch either closes or opens a set of
electrical contacts. The contacts may be connected to energize motor starter coils, relays, or
indicating lights. In general, a flow switch contains both normally open and normally closed
electrical contacts, figure 13.
The applications of flow switches are commonly found in the chemical and petroleum industries.
Vapour proof electrical connections must be used with vapour proof switches. The insulation of
the wire leading to the switches must be adequate to withstand the high temperature of the liquid
inside the pipe. Airflow or sail switches are also used in ducts in air conditioning systems.
Another use of these switches is to prevent duct heaters from energizing when there is no air
movement in the duct. While the construction of airflow switches is different from that of liquid
flow switches, the electrical connections are similar.
Schematic and wiring diagrams are the written language of control circuits. If a maintenance
electrician is going to install control equipment, he must be able to interpret schematic and
wiring diagrams. Schematic diagrams show components in their electrical sequence without
regard to physical location. Schematics are used more than any other type of diagram to connect
or troubleshoot a control circuit.
Wiring diagrams show a picture of the control components with connecting wires. Wiring
diagrams are sometimes used to install new control circuit, but they are seldom used for
troubleshooting existing circuits. Figure 14 below shows a schematic diagram of a start-stop,
push-button circuit.
A. Read a schematic as you would a book – from top to bottom and from left to right.
B. Contact symbols are shown in their de-energized or off position.
C. When a relay is energized, all the contacts controlled by that relay change position. If a
contact is shown normally open on the schematic, it will close when the coil controlling it
is energized.
Circuit #1
The circuit shown in the figure16. is an alarm silencing circuit. The purpose of the circuit is to
sound the horn and turn on a red warning light when the pressure of a particular system becomes
too great. After the alarm has sounded, the reset button can be used to turn the horn off, but the
red warning light must remain on until the pressure in the system drops to a safe level. Notice
that no current can flow in the system because of the open pressure switch, PS.
If the pressure rises high enough to cause pressure switch PS to close, current can flow through
the normally closed S contact to the horn. Current can also flow through the red warning light.
Current cannot, however, flow through the normally open reset button or the normally open S
contact.
If the reset button is pushed, a circuit is completed through the S relay coil. When relay coil S
energizes, the normally closed S contact opens and the normally open S contact closes. When the
normally closed S contact opens, the circuit to the horn is broken. This causes the horn to turn
off. The normally open S contact is used as a holding contact to maintain current to the coil of
the relay when the reset button is released.
The red warning light will remain turned on until the pressure switch opens again. When the
pressure switch opens, the circuit is broken and current flow through the system stops. This
causes the red warning light to turn off, and it de-energizes the coil of relay S. when relay S de-
energizes, both of the S contacts return to their original position. The circuit is now back to the
same condition it was in figure Fig 16.
SESSION 2-2: REPRESENTATION OF ELECTRICAL SERVICES
EQUIPMENT AND DEVICES BY STANDARD ELECTRICAL
SYMBOLS
2-2.1 Standard electrical symbols used for electrical services equipment and devices
Lighting outlet
Socket outlet
Signalling system outlet
Circuiting
Underground distribution
Panel board, Switch Board and related equipment
Table 2.18 Recommended lighting ratings for lighting medium sized homes
Location Watts
Passages 60
Stairs 60
Landing 60
Kitchen 200
Bedrooms 100-150
Mirror 2×60
Bathroom 100
Garage 150
The above power values refer to tungsten filament lamps. If fluorescent lamps are to be used,
1 1
multiply the above power values by factors from to .
3 2
1
To prevent the risk of under designing, use the upper limit i.e. of the above powers.
2
Table 2.19 Minimum number of socket outlets allowable for various rooms in a building
Kitchen 3
Living room 4
Dining room 2
Double/Master bedroom 3
Single bedroom 2
Study bedroom 2
Study 2
Garage 1
Store 1
2-2.2 Determination of maximum number of a given type of lamps that can be connected in
a circuit and the representation of the lamps on an architectural plan
If the circuit supplies current using equipment, wiring from one fuse or CB is known as the final
circuit, and all the outlets fed from the same fuse or CB are on the same final circuit. The fuse or
CB must be large enough to carry the largest steady current ever taken at any one instant by the
A final circuit for lighting is usually supplied by a fuse or MCB rated 5A and it may feed an
unlimited number of points provided that the total current demand does not exceed 5A. For
example, if it is required that a number of 100W incandescent lamps be supplied by a 240V
circuit which is protected by 5A fuse then the maximum number of such 100W lamps can be
determined as follows
1) Determine the current requirement, I l , of the 100W incandescent lamp
P 100
ie I l = V = 240 = 0.42A
But the rating of the protective fuse (the maximum permissible current) of the circuit is 5A
5
The maximum number of incandescent lamps required N l = = 12
0.42
However, in order to minimize the pressure on the protective device should any instability occur
in the system, IEE regulation stipulates that we load the circuit to about 80% of its rated value .
In design, it is better to round down the figure to 9 lamps especially when power consumption
The arrangement of the lamps in a circuit when at least one lamp is controlled by one switch is
Now if the lamps were to be fluorescent tubes , the procedure will be almost the same except that
the circuit in this case is feeding fluorescent lamps (discharge lamps). The consideration of the
rating of the discharge lamps outlets, has a different meaning from the one used for incandescent
lighting points. The reason is that owing to the losses in the lamp control gear (ballast) plus low
power factor, it is necessary to multiply the rated lamp watt by a factor 1.8 and divide the
product by the lamps rated voltage to obtain the actual current flowing in the circuit. This factor
Suppose the rating of the fluorescent lamp is 40W, then from the above consideration the current
1.8× 40
requirement per a fluorescent tube is I F = = 0.3 A
240
5
The maximum number of fluorescent lamps required N F = = 16.7
0,30
By applying a factor of 0.8 , the actual number of fluorescent tubes required will be
Fig 2.11
2-2.3 Determination of maximum number of a given type of lamps that can be controlled
by a switch and the representation of the lamps and the switch on an architectural plan
Although commercial and industrial lighting may require the use of 15A switches, interior
lighting are mostly controlled by switches rated 5A.. If it is required that a number of certain
types of lamps be controlled by one 5A switch, 240V single phase , then the procedure may be
as follows
1. Determine the current requirement, I l , of the lamp ,say, one 100W incandescent lamp
P 100
ie I l = V = 240 = 0.42A
But the rating of the controlling switch is 5A , (the maximum permissible current is 5A )
.
.. The maximum number of 100W incandescent lamps that can be controlled by one 5A switch is
5
Nl = = 12 .
0.42
Thus one 5A switch can control not more than 12 lamps at the same time.
The arrangement of one 5A switch controlling say 12 incandescent lamps are as shown below in
fig 2.12.
inductiveness associated with discharge lamps , it is necessary to derate the 5A or 15A switch
rating of the 5A or 15A switch is say 2.5A for the 5A switch or 7.5A for 15A switch. Then
proceed to determine the number of, say, 40W fluorescent lamps as follows:
1. Multiply the rating of the lamp by 1.8 (owing to the losses in the lamp control gear (ballast)
plus low power factor), and divide the product by the lamps rated voltage to obtain the actual
1.8× 40
The current requirement of one fluorescent tube I F = = 0.3 A.
240
2.5
The maximum number of fluorescent lamps required N F = = 8.33 = 8 .
0,30
Thus one switch can control not more than eight 40 W fluorescent tubes at the same time..
2-2.4 Representation of One and multi positional control of lamps schematically and on the
Architectural plan
Depending on the size of a room and the requirement of a client, the number of lamps in a given
room can be controlled from one or more positions .Usually for small sized room, the lamps are
However, for long hall especially the one with two or more entrances or exits, the normal
practice is to control the lights from more than one position. The switches that are employed to
control the lights in such long halls may be either two-way or two-way and intermediate
switches. Figure 2.14 shows the control of fluorescent tubes from two and three points
respectively.
Fig 2.14 Control of lamps from multi-positions (two-way and intermediate)
The Figures 2.14 show how multi positional controls of lamps are represented on an architectural
plan. The corresponding schematic diagrams for the switching and circuit connections of the
With one way switching the lamps can be switched on and off only from one position.
With two way switches the lamps are controlled from two positions such that when the lamp is
switched on from one end of a room and then the original position of the switch at the other end
of the room is changed, the lamps will go off. The lamps can be switched on again by bringing
either the latter switch or the first switch to its original position..
The same switching principle can be applied to a two way and intermediate switches, except that
in this case the lamps can be controlled from three positions in the same way as was explained
Fig 2.15
Fig 2.15 (cont’d)
As its name implies, a ring connection of socket outlets is one which forms a closed ring; it starts
at one of the ways of a distribution board, runs to a number of socket outlets one after another,
and returns to the distribution board it started from. This is illustrated in Figure 2.16.
The advantage of this arrangement is that current can flow from the fuse way to the socket
outlets along both halves of the ring, so that at any one point the cable carries only part of the
rating. The fuse carries the sum of the currents in the two halves of the ring and will blow when
the current in one part of the ring is about half the fusing current of the fuse. A ring circuit with
socket outlets for 13A fused plugs cabled in 2.5mm2 PVC cable and protected by a fuse or circuit
breaker rated at 30A or 32A can serve any number of outlets but the floor area covered must not
A circuit which runs only from the fuse way to the outlets it serves without returning to the fuse
is called a radial circuit. A radial circuit for this type of outlet can serve a floor area of 50m 2 if it
is cabled in 4mm2 cables and protected by a 30 / 32A HRC fuse or circuit breaker. If it is cabled
in 2.5mm2 cable and protected by any type of fuse or circuit breaker rated at 20A, it is restricted
to a floor area of 20m2. In either case there can be any number of outlets within this area
The human body when shoeless wet and covered in moisture from condensing bath water is most
vulnerable to electric shock. In those instances the body resistance is greatly reduced. Bathrooms
containing a bath and / or shower shall not have any main socket or make provision for main
portable equipment. However, it is permissible to install in bathroom a shaver supply unit and or
a shaver light unit and totally enclosed luminaries and to have normal access to the insulated
cord of a cord switch all within a reach of a person using a bath or shower. All other mains
switches, controls or equipment are out of normal reach. Metal work and other conductive parts
in bathroom must be bonded to prevent dangerous fault voltage existing during earth fault.
Pushbutton Switch
Momentary switch - normally open
(N.O)
Pushbutton Switch
Momentary switch - normally closed
(N.C)
DIP Switch DIP switch is used for onboard configuration
SPST Relay
Relay open / close connection by an electromagnet
SPDT Relay
Ground Symbols
Earth Ground Used for zero potential reference and electrical shock protection.
Digital / Common
Ground
Resistor Symbols
Resistor (IEEE)
Resistor reduces the current flow.
Resistor (IEC)
Potentiometer (IEEE)
Adjustable resistor - has 3 terminals.
Potentiometer (IEC)
Variable Resistor /
Rheostat (IEEE)
Adjustable resistor - has 2 terminals.
Variable Resistor /
Rheostat (IEC)
Photoresistor / Light
dependent resistor Photo-resistor - change resistance with light intensity change
(LDR)
Capacitor Symbols
Capacitor
Capacitor is used to store electric charge. It acts as short circuit
with AC and open circuit with DC.
Capacitor
Variable Inductor
Ammeter Measures electric current. Has near zero resistance. Connected serially.
Diode Diode allows current flow in one direction only (left to right).
Allows current flow in one direction, but also can flow in the reverse
Zener Diode
direction when above breakdown voltage
A semiconductor diode with a low forward voltage drop and a very fast
switching action. When current flows through a diode there is a small
voltage drop across the diode terminals. A normal silicon diode has a
voltage drop between 0.6–1.7 volts, while a Schottky diode voltage
Schottky Diode
drop is between approximately 0.15–0.45 volts. This lower voltage
drop can provide higher switching speed and better system efficiency.
Tunnel Diode
Transistor Symbols
NPN Bipolar
Allows current flow when high potential at base (middle)
Transistor
PNP Bipolar Transistor Allows current flow when low potential at base (middle)
Made from 2 bipolar transistors. Has total gain of the product of each
Darlington Transistor
gain.
Misc. Symbols
Bus
Bus
Optocoupler / Opto-
Optocoupler isolates onnection to other board
isolator
Analog-to-digital
Converts analog signal to digital numbers
converter (ADC)
Digital-to-Analog
Converts digital numbers to analog signal
converter (DAC)
Antenna Symbols
Antenna / aerial
Transmits & receives radio waves
Antenna / aerial
Multiplexer / Mux 2 to
1
Connects the output to selected input line.
Multiplexer / Mux 4 to
1
Demultiplexer /
Connects selected output to the input line.
Demux 1 to 4