TM0007-Uso e Installazione Perscab UK
TM0007-Uso e Installazione Perscab UK
TM0007-Uso e Installazione Perscab UK
MANUAL NO.TM0007
This document and the information that it contains are the property of
FENWAL Italia S.p.A.. Rights to duplicate or otherwise copy this document
and rights to disclose the document and the information that it contains to
others and the right to use the information contained therein may be acquired
only by written permission signed by a duly authorised officer of FENWAL
Italia S.p.A..
Page 2 of 36
AMENDMENT INCORPORATION RECORD
Amendment Brief Description of Content Name of Person
Number Incorporating
Amendment
1
10
Page 3 of 36
INDEX
Chapter Page
1 PRESENTATION ...................................................................................................................................... 5
2 FILE ............................................................................................................................................................... 6
3 RUN............................................................................................................................................................... 7
4 OPTIONS .................................................................................................................................................... 8
4.1 Communication Set ....................................................................................................................... 8
4.2 Set Debug .......................................................................................................................................... 9
4.3 Cards List ......................................................................................................................................... 10
5 ?.................................................................................................................................................................... 11
6 CONTROL PANEL CONFIGURATION ........................................................................................... 12
6.1 Heading ............................................................................................................................................. 12
6.2 Configuration ................................................................................................................................. 12
6.3 Company .......................................................................................................................................... 13
6.4 Network 485 .................................................................................................................................... 13
6.5 Zone Activation timing ............................................................................................................... 13
6.6 Area 2 Outputs Activation Timing ......................................................................................... 13
6.7 Analogue Sensor Calibration .................................................................................................. 13
6.8 LCD Backlight ................................................................................................................................ 13
6.9 Language ......................................................................................................................................... 13
6.10 Printer ............................................................................................................................................ 14
6.11 Area 2 events printing ............................................................................................................ 14
6.12 Host Computer .......................................................................................................................... 14
6.13 Panel Clock Setting ................................................................................................................. 14
7 ZONE CONFIGURATION .................................................................................................................... 15
7.1 Select area ....................................................................................................................................... 15
7.2 Area 1 [Safety] configuration .................................................................................................. 15
7.3 Zone Selection (Left button on Mouse) .............................................................................. 16
7.4 Zone Selection (Right button on Mouse) ........................................................................... 16
7.5 Zone Settings Change ................................................................................................................ 17
7.6 Modify zone sensors field......................................................................................................... 18
7.7 Modification of zone input field ............................................................................................. 21
7.8 Modification of zone actuators field .................................................................................... 23
7.9 Modification of zone associations field.............................................................................. 25
7.10 Preliminary zone check ......................................................................................................... 26
7.11 Area 2 [Security] configuration .......................................................................................... 26
7.12 Area 0 [Common entities] configuration ........................................................................ 26
8 HOLIDAYS ................................................................................................................................................ 26
9 TIME CODES ........................................................................................................................................... 26
10 REMOTE ASSOCIATIONS ............................................................................................................. 26
11 FOOTNOTE.......................................................................................................................................... 26
12 CHECK ................................................................................................................................................... 26
13 FILE GENERATING FOR… ............................................................................................................ 26
14 PROGRAMME INSTALLATION..................................................................................................... 26
14.1 Installation via CD-ROM or Floppy Disk ......................................................................... 26
Page 4 of 36
1 PRESENTATION
PERSCAB programming software is used for configuring 1019/1020 Control Panels or for
modifying existing programmes. It works with Windows 95/98 or Windows-nt operating
systems. Control Panel configuration is in three distinct phases:
1. Enter all settings relating to control panel programme.
2. Check data validity.
3. Transfer configuration file to control panel.
The same software can generate configuration files for both Series 1019 and 1020 Control
Panels. Below are the limitations adopted for configuration of 1020 panels.
• Configurations for 1020 panels can have a maximum of 40 zones only in area 1 (safety).
• Configurations for 1020 panels can accept the following types of cards only:
up to 4 ESP type cards, 1 DI card and 1 DO card.
• Admissible addresses are: 1-2-3-4 for ESP type cards, 5 for DI cards, and 6 for DO
cards.
• For DI/DO cards, only channels 1 to 8 are accepted.
NB: This programme utilises some parameters which are based on international settings of
the operational system. These parameters vary depending on the language used. Below is a
table showing recommended parameters for the two versions of the Perscab programme.
Do not utilize different international settings from the ones above, because the programme
has been tested only for international settings: standard Italian, UK English and USA
English.
Page 5 of 36
2 FILE
Fig. 1
Fig. 2
Page 6 of 36
3 RUN
Fig. 3
Trasmission and Reception functions will be performed only if mod. bite-board 2000 dongle
key is inserted into LPT1 port on the computer.
Page 7 of 36
4 OPTIONS
Fig. 4
Connection: Indicates the type of connection between the programme and the panel. The
connection can be direct (Serial Port) or via Ethernet Link (TCP/IP). In both cases however
the connection can be made only with one Control Panel at a time. Therefore in case of
connections to more panels on the same link, the IP address will have to be changed.
Page 8 of 36
Parity Select type of parity.
Stop Bit Select number of stop bits.
Handshake Select type of data flow.
Modbus: Use these settings for configuration of Modbus options in MOD file.
Enable the outputs duplicated control in different zone This setting enable/disable the
outpus duplicated control in different zone.
NB:
if enabled it is not possible
if disabled it is possible
duplicate the outputs in different zone.
Page 9 of 36
4.3 Cards List
Selecting this option to display the cards list.
Besides selectiong from File menu Print option it is possible to print the cards list with
correspondent address.
Page 10 of 36
5 ?
Fig. 5
Page 11 of 36
6 CONTROL PANEL CONFIGURATION
On this page it is possible to view or change Control Panel configuration.
Fig. 6
6.1 Heading
This gives information relating to the customer and the type of control panel. Even though
the Control Panel does not use this information, it is stored in the binary configuration. This
data however is used for the headings on the two documentation files.
6.2 Configuration
These are the settings needed for configuration of the control panel hardware and some of
its operating options. In this section you can view the following:
Page 12 of 36
6.3 Company
In this window you can select the company name or logo which is displayed in bitmap
format.
6.9 Language
This setting cannot be changed as it indicates the control Panel communication language.
This parameter is identical to Perscab Language.
IT Italian language.
UK English language.
Page 13 of 36
6.10 Printer
In this window you set communication and printer functions if serial printer is connected to
Control Panel.
Disable Disable printer functions.
40 Columns Enable printer functions on 40 columns.
80 Columns Enable printer functions on 80 columns.
Baud Rate Select data transmission speed.
Parity Select type of parity.
Stop Bit Select number of stop bits.
Handshake Select type of data flow check
Mode By selecting “reduced” only alarm events are printed, by
selecting “complete” all events are printed.
Page 14 of 36
7 ZONE CONFIGURATION
For 1019 control panels the configuration structure is:
Area 0 (common entities) Area 1 (safety) Area 2 (security)
1 Zone consisting of: 300 zones consisting of: 300 zones consisting of:
99 sensors 99 sensors 99 sensors
99 inputs 99 inputs 99 inputs
99 actuators 99 actuators 99 actuators
99 associations 99 associations
As you can see the configuration is organised into three areas. Area 0 is where the common
entities are programmed. Area 1 consists of a variable number of zones between 1 and 300
relating to safety section. Area 2 consists of a variable number of zones between 1 and
300 relating to security section.
Each zone consists of 1-99 sensors, 1-99 inputs, 1-99 actuators, 1-99 associations. The
zone relating to area 0 has no associations.
As you can see in this case the configuration is organised into two areas. Area 0 is where
the common entities are programmed. Area 1 consists of a variable number of zones
between 1 and 40 relating to safety section. Each zone consists of 1-99 sensors, 1-99
inputs, 1-99 acuators, 1-99 associations. The zone relating to 0 has no associations.
Fig. 7
Page 15 of 36
7.3 Zone Selection (Left button on Mouse)
After selecting desired area you access the zone selection menu. From now on we will refer
only to management of area 1 zones, since management of area 2 zones is identical.
However management of area 0 is identical only to zone 1.
Fig. 8
Fig. 9
Page 16 of 36
7.5 Zone Settings Change
To change zone settings select a zone by pressing the left button on the mouse twice.
Fig. 10
Page 17 of 36
7.6 Modify zone sensors field
To access this field use the mouse to select each sensor
Fig. 11
Card: Indicates which type of card belongs to the sensor. Acceptable card types are: H3,
G3, A3, A5, A8, IDA, ESP, VIO, V2S, VAN. This field cannot be inputted manually via the
keypad, but must be selected from the list.
NB: Since 1019-IDA card is no longer produce, it cannot be covered by IMQ certification.
Address: Indicates physical address of the card. For all card types it is a three-digit number
between 1 and 126. It is possible to modify this parameter by typing in the number via the
keypad or using the arrow keys.
Page 18 of 36
Type: Indicates which device type the channel refers to. This name can vary depending on
the type of card. This parameter is applicable only to cards ESP/VIO/V2S/VAN. This field
too cannot be inputted manually via the keypad, but must be selected from the list.
Channel: Indicates the number of the device channel which the sensor being programmed
refers to. It is a variable number which depends on card type and, in case of V2S VAN
card, also on type of device. It is possible to change this parameter by typing in the number
or using the arrow keys.
Mode: Indicates operating mode for those sub-channels which are provided with two
operating modes (retained, non-retained) and is available only on the devices belonging to
ESP cards (all types), VIO type 8/DIN, V2S type 4/BIN and VAN type 1/AIN. It is a letter that
can assume only values R or N. This field cannot be entered via the keypad, but must be
selected from the list.
Logic: Indicates operating logic for those channels/sub-channels provided with two
opperating logics, i.e. NA or NC and is available only on the sub-channels belonging to VIO
cards type 8/DIN. They are two letters which can assume only NA or NC values. This field is
not inputted by the operator and must therefore be selected automatically. This field cannot
be entered via the keypad, but must be selected from the list.
Page 19 of 36
Sensitivity: Indicates sub-channels’ working sensitivity. These sub-channels are provided
with three different types of sensitivity. However this feature is available only on sub-
channels belonging to ESP cards and only for devices type ALG-E, AIE-E, ATG-E, ACA-E .
Admitted values are Low/Medium/High.
This field cannot be entered via the keypad, but must be selected from the list.
Units of measure: Indicates pre-alarm and alarm threshold levels for devices with two
programmable thresholds. This feature is available only on channels belonging to A3 and
A5 cards and on sub-channels belonging to VAN cards for devices type 1/AIN.
This measure is not directly used by the control panel, but the program, through adequate
conversion operations, obtains the 8-Bit numeric value relevant to pre-alarm and alarm
thresholds, which will be transmitted to the control panel. Cards type A3 and A5 accept only
Bit-type values. Cards VAN-1/VAN instead accept the following units of measure: mA,
%LEL, or PPM.
Pre-alarm: Indicates pre-alarm threshold level for devices with two programmable alarm
thresholds. It is available only on channels belonging to A3 and A5 cards and sub-channels
belonging to VAN cards and type 1/AIN devices. The values are inputted by the operator
and change according to the type of measure selected. If the value is not within the
permissible range for that particular unit of measure, it will not be accepted.
Alarm: Indicates alarm threshold level for devices with two programmable alarm thresholds.
It is available only on channels belonging to A3 and A5 cards, and sub-channels belonging
to VAN cards for type 1/AIN devices. The values are inputted by the operator and change
according to the type of measure selected. If the value is not within the permissible range for
that particular unit of measure, it will not be accepted. The pre-alarm and alarm values
allowed for the various units of measure are the following:
Page 20 of 36
7.7 Modification of zone input field
To access this field select the word “input” via the mouse.
Fig. 12
Card: Indicates the type of card the sensor belongs to. Admissible types are: H3, G3, A8,
IDA, ESP, VIO, V2S, DI. This field cannot be inputted manually, but must be selected from
the list.
Address: Indicates card physical address. For all card types it consists of a three-digit
number comprised between 1 and 126. It is possible to change this parameter via the
Page 21 of 36
numbers on the keypad or the arrow keys.
Type: Indicates the device type which the channel refers to. It is a variable name which
depends on the type of card. This parameter is available only on cards type ESP/VIO/V2S.
This field cannot be inputted manually, but must be selected from the list.
Channel: Indicates the channel number of the device which the sensor under examination
refers to. It is a variable number and depends on the type of card as well as, in case of
card V2S, on the type of device. It is possible to change this parameter via the numbers
on the keypad or the arrow keys.
Point: Indicates the sub-channel of a device. It is a variable one-digit number and depends
on the type of device. It is possible to change this parameter via the numbers on the
keypad or the arrow keys. Please refer to the table below showing types of devices, number
of channels and admissible points for each type of card in inputs field.
Mode: Indicates operational mode for those sub-channels with two working modes (i.e.
retained, non-retained) and is available only on devices belonging to ESP cards (all types):
VIO type 8/DIN, V2S type 4/BIN. It is a letter which can assume only value R or N. This
field cannot be inputted manually, but must be selected from the list.
Logic: Indicates the operational logic for those channels/sub-channels provided with two
operational logics (NA or NC) and is available only on sub-channels belonging to type 8/DIN
DI and VIO cards. It consists of two letters which can assume only NA or NC values. This
field is not inputted by the operator and must be selected automatically. This field cannot be
inputted manually, but must be selected from the list.
Associated Actuator: Indicates the zone actuator associated with the input whose
activation logic is being checked by the control panel. It consists of a number comprised
between 1 and 99. This field is inputted manually by the operator. If the number is not within
the admissible range it will not be accepted. To disable this function put value 0. The time
delay for activation of the associated actuator is fixed at 10 seconds.
Page 22 of 36
7.8 Modification of zone actuators field
To access this field select the word “actuators” via the mouse.
Fig. 13
Card: Indicates the type of card the actuator belongs to. Admissible types are: H3, H8, DO,
IDA, ESP, VIO, V2S, VAN. This field cannot be inputted manually, but must be selected
from the list.
Address: Indicates card physical address. For all card types it consists of a three-digit
number comprised between 1 and 126. It is possible to change this parameter via the
numbers on the keypad or the arrow keys.
Page 23 of 36
Type: Indicates the device type which the channel refers to. It is a variable name which
depends on the type of card. This parameter is available only on cards type
ESP/VIO/V2S/VAN. This field cannot be inputted manually, but must be selected from the
list.
Channel: Indicates the channel number of the device which the sensor under examination
refers to. It is a variable number and depends on the type of card as well as, in case of
card V2S, on the type of device. It is possible to change this parameter via the numbers
on the keypad or the arrow keys.
Point: Indicates the sub-channel of a device. It is a variable one-digit number and depends
on the type of device. It is possible to change this parameter via the numbers on the
keypad or the arrow keys. Please refer to the table below showing types of devices, number
of channels and admissible points for each type of card in actuators field.
Note A: The addresses of actuators belonging to IDA cards must be greater than those of
the devices belonging to the same card described under sensor/input fields
Mode: Indicates actuator activation mode (Fixed, Periodic, Pulsed). It is a letter which can
assume only values F, P or I. This field cannot be inputted manually, but must be selected
from the list.
Periodic: Indicates time in seconds relating to actuator activation mode, if the actuator has
been programmed in Periodic or Pulsed mode. It is a three-digit number comprised
between 0 and 255. It is possible to change this parameter via the numbers on the keypad
or the arrow keys.
Sounder: Indicates if the actuator being in programmed is a sounder, in which case, it will
be activated by the control panel even following an evacuation command, and will be
disabled only following the Silence sounders command. Admissible values are Y and N.
This field cannot be inputted manually, but must be selected from the list.
Page 24 of 36
7.9 Modification of zone associations field
To access this field select the word Associations with the mouse
Fig. 14
Rule: Indicates the type of logic utilised by the association. Admissible values are: OR,
AND, or a number comprised between 1 and 9. This field cannot be inputted manually, but
must be selected from the list.
Page 25 of 36
Entity: Indicates the totality of entities which make up the rule. It consists of a series of
parameters subdivided into four characters. The first character indicates which status must
be assumed by the entity in order to meet the rule. The second character indicates the type
of entity on which the rule is executed; and the third character indicates if the field refers to
the current zone or the common zone in area 0. The fourth character indicates the row
number of the entity in the field which the rule refers to. Parameter groups can be spaced
with a comma up to a maximum of four, or a dash, up to a maximum of two. Entities
sequence can be typed in freely or selected via the help menu shown in Fig. 15 for sensors,
Fig. 16 for inputs, Fig. 17 for actuators, Fig. 18 for associations and Fig. 19 for associations
coming from the network.
Fig. 15
Fig. 16
Fig. 17
Page 26 of 36
Fig. 18
Fig. 19
Actuators-1: This field consists of a variable number of parameters from 1 to 6 and each
consists of two fields. They indicate which actuators are activated when a rule is satisfied.
The first field indicates if the actuator refers to the current zone or common zone; the
second field indicates the relevant line number comprised between 1 and 99. Actuators
sequence can be typed in freely or selected via the help menu shown in Fig. 20.
Page 27 of 36
Fig. 20
Delay: Indicates the delay in seconds for Actuators-1 activation, once the rule is satisfied. It
is a three-digit number comprised between 0 and 300. It is possible to change this
parameter via the numbers on the keypad or arrow keys.
Actuators-2: This field is identical to Actuators-1 field and allows the definition of another 6
actuators.
Delay: : Indicates the delay in seconds for Actuators-2 activation once the rule is satisfied. It
is a three-digit number comprised between 0 and 300. It is possible to change this
parameter via the numbers on the keypad or arrow keys.
Page 28 of 36
7.11 Area 2 [Security] configuration
With left mouse button select ‘+’ symbol near ‘Area 2 [Security]’ field.
Area 2 programming is practically identical to that of Area 1, except for:
• In inputs/sensors field, admissible card types are only those with supervised lines in
accordance with regulations for security panels Level 2. In particular these cards are:
V2S-A8-IDA. The input types used by these cards are non-latching.
• In actuators filed admissible cards are: H8-DO-IDA-V2S.
• Programmable outputs must not be fixed or periodic, otherwise IMQ mark will be
invalidated.
• Rules refered to Alarm state are active also with Tamper state. If you need to activate
outputs with zone disable you must define them in Common zone.
Page 29 of 36
8 HOLIDAYS
By selecting this option you access the holidays definition page.
In this phase it is possible to select up to a maximum of 30 days defined as holidays during
current year, as shown in the figure below:
Fig. 21
Page 30 of 36
9 TIME CODES
In this phase it is possible to define/change 10 categories of time codes as shows in figure
22 below.
Fig. 22
Beginning Time: Indicates beginning of current time band in format: hours/minutes. This
parameter can be changed by typing in the numbers or via the arrow keys.
Page 31 of 36
Modify Beginning Time: : Indicates beginning of current time band valid for one machine
cycle in format: hours/minutes. (Temporary modification). This parameter can be changed
by typing in the numbers or via the arrow keys.
End Time: Indicates the end of the current time band in format: hours/minutes. This
parameter can be changed by typing in the numbers or via the arrow keys.
Modify End Time: : Indicates the end of current time band valid for one machine cycle in
format: hours/minutes. (Temporary modification). This parameter can be changed by typing
in the numbers or via the arrow keys.
Validity: Indicates valid days in current time band. Admissible values are: Monday,
Tuesday, Wednesday, Thursday, Friday, Saturday, Sunday, Weekday, Workday, Weekend,
Holiday. This field cannot be inputted manually, but must be selected from the list.
Type: Indicates the type of activity performed by the control panel when the time band
under examination is active. This field cannot be inputted manually, but must be selected
from the list. Admissible types are:
• Liv-1: Isolates/deisolates the zones associated with this time band on level one.
If a zone is isolated on level 1, entities status variations are indicated on control panel,
but rules are not carried out; therefore no outputs activations will be performed in
isolated zones on this level.
• Liv-2: Isolates/deisolates the zones associated with this time band on level two.
If a zone is isolated on level 2, no entities status variations will be indicated except for
Tamper events.
• Temperature Mode: (Sets Series ESP type ACA combined detectors in “only
temperature” working mode.
• Combined Mode: (Sets Series ESP type ACA combined detectors in “smoke +
temperature” working mode).
Time Setting Forewarning: Gives prior indication of time available before each category
setting (0-60 minutes). This parameter can be changed by typing in the numbers or via the
arrow keys.
During setting forewarning period it is possible to delay the relevant zone activation time by
one hour. During each panel cycle a maximum of three zone activation delays can be
performed; therefore each category setting (zone activation) can be delayed by maximum
three hours.
Page 32 of 36
10 REMOTE ASSOCIATIONS
In this phase you can define/change up to a maximum of 999 remote associations which
will then be sent to the other control panels in the communication network, as shown in Fig.
23.
Fig. 23
Page 33 of 36
Remote Association Name: 19-character field, modifiable at will.
Identifier: Indicates the control panel identifier present on the network, which the remote
association refers to and consists of a number between 1 and 999. This parameter can be
changed by typing in the numbers or via the arrow keys.
Area: Indicates the area which the remote association refers to. This field cannot be
inputted manually, but must be selected from the list.
Zone No. : Indicates the zone number which the remote association refers to and consists
of a number tetween 1 and 300. This parameter can be changed by typing in the numbers
or via the arrow keys.
Association No.: Indicates the association number which the remote association refers to
and consists of a number tetween 1 and 99. This parameter can be changed by typing in the
numbers or via the arrow keys.
Page 34 of 36
11 FOOTNOTE
On the last line of the main screen page you can find some information concerning the
configuration file.
1019: Indicates the type of control panel which has been selected for that type of
configuration and can assume values 1019 or 1020.
dd/mm/yy hh:mm : Indicates the date and time when the last saving of the active file has
been performed.
12 CHECK
In this phase the programme checks data validity, the following window will be shown:
The presence of this type of inconsistency will be clearly indicated to the operator so that he
can make the necessary changes.
Page 35 of 36
14 PROGRAMME INSTALLATION
In the table below are listed the minimum technical requirements needed for installing the
configuration software on the computer.
Note-A: To view the Use Manual on line your computer must be equipped with
ACROBAT READER Version 4 or superior.
Fig. 24
Page 36 of 36