Revie
Revie
net/publication/372188272
CITATIONS READS
0 31
1 author:
K.V. Vidyanandan
NTPC Limited
24 PUBLICATIONS 766 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by K.V. Vidyanandan on 07 July 2023.
Abstract—Power generation from renewable energy resource, such as wind and solar radiation, often takes place with
decentralized or distributed generation (DG) units. These units, generally located in remote locations, are not centrally
planned or dispatched, and are usually connected to distribution networks at low voltage (LV) or medium voltage (MV)
levels. In few cases, renewable based generation having large capacity implemented on a utility scale, are connected to the
transmission network. As a consequence, the power generation structure is moving from the large, centralized plants to a
mixed generation pool consisting of traditional synchronous machine based large plants and many smaller DG units. Most
of the renewable based generators have electrical characteristics that are different from the conventional directly
connected synchronous generators. Since a large group of DG technologies use power electronics converters for grid
connectivity, they introduce many technical issues related to power quality, stability and protection of the distribution
system. This paper presents some of the technical challenges that need to be addressed for the effective grid integration
of renewable energy systems (RES) based power generators so that eventually, our reliance on polluting and expensive
fossil fuel based power generation can be reduced.
Index Terms—Distributed Generation, Power Quality, Renewable Energy, Solar PV, Wind Turbines.
I. INTRODUCTION
R ENEWABLE energy share in the world power system is growing exponentially. During the past 50 years since 1965,
electricity generated from renewables has increased by more than 500%. In 2013, generation capacity based on RES
jumped more than 8%, accounting for over 56% of net additions [1]. By the end of 2013, the world renewable power
generation has reached 1560 GW, which is nearly 21.7% of the world's total electricity generation [2]. Hydro at 1000 GW
is the major electricity supplying renewable. Wind comes next at 319 GW, while solar photovoltaic is around 137 GW, and
solar thermal is around 326 GW. Annual growth rate of total renewables as of 2013 is 6.4% [3]. Global wind share is growing
at 20% per year whereas; solar PV is growing at about 60% per year. At present, wind share in the world energy mix is
around 2.5% and that of solar PV is around 1.1%. The world target, as per the goal set by the UN Sustainable Energy for All
initiative, is to double the share of renewables in the global energy mix by year 2030 [4].
As renewable energy become more reliable and economically feasible, there is a trend to interconnect RES based
generators to the grids to serve different purposes and offer more options to end-users. These include: a) Improving
availability and reliability of power supply, b) Peak load shaving, and c) Selling surplus power back to utilities. The increasing
share of renewable energy in the power systems will bring both positive and negative consequences to the existing system.
Some of the positive aspects include relief in line congestion, reliable power in remote locations, energy security, reduction
in pollution and global warming. However, the issues arising from renewable based power in grid is much more challenging
and thus needs more considerations.
Renewable energy sources have a much lower energy density than coal or oil, and hence, for capturing optimum energy
for practical applications, these units are geographically more dispersed. Hence, these generators cannot have very large
capacity as compared to conventional units. The rating of renewable generators typically vary from a few hundreds
kilowatts (kW) to few megawatts (MW) only. RES can be embedded into all types of electric networks, from small to large
capacity grids. However, due to the relatively small capacity and the remoteness from HV transmission lines, these
generators are usually connected to the power grid at the distribution level, normally at MV or LV level.
The integration of a RES into the power grid depends on a number of factors, both regulatory and technical. The
regulatory aspects include the percentage share of RES, location of point of common coupling (PCC), energy conversion
technology, the mix of generation technologies, and the size and characteristics of the network in which it is connected.
The technical aspects include the effect on system inertia, droop, power quality, working of network protection and stability
[5]-[8]. Integration of renewable based generation alters the power flows in distribution networks and changes the
traditional one way power flow from the high to the low voltage levels of the power system.
The main objective of a power system network is to efficiently deliver reliable electricity to the consumer. System
frequency and node voltage are the two important parameters which guarantee the stable operation of the grid. It is a
known fact that more the number of generators participating in system frequency and voltage regulation functions, more
smoothened frequency and voltage excursions result after system events. Currently, renewable systems, including wind
turbine generators (WTG) and solar PV systems, do not participate in system frequency and voltage regulation functions.
This is mainly due to the facts that majority of the RES (e.g. wind and solar PV) are highly intermittent and fluctuating type
of resources. Due to technical limitations, RES based units do not increase or decrease their active/reactive power outputs
when the frequency/voltage deviates from the respective nominal values. Since frequency and voltage stability in the
1
power grid is essential for maintaining security and stability of the supply, this inadequacy of the RES will pose a limit to
the level of penetration of these technologies into the existing system.
The standard practice generally followed with RES is to disconnect them during contingencies and reconnect when
normalcy is restored. The active/reactive power support required by the system during that period is usually provided by
conventional units. This is tolerable as long as RES share is low. However, with the increasing share of RES, they must also
contribute to frequency and voltage regulation exactly like traditional units. Besides, the practice of disconnecting RES
during system contingencies is no longer permitted as this will aggravate the situation because of loss of more power.
The focus of this work is to highlight the technical issues and challenges associated in the grid integration of renewables
such as wind farm and solar PV farm (or a solar park). The rest of the paper is organized as follows: overview of renewable
energy technologies are discussed in Section II, power generation from renewable resources is presented in Section III,
issues with grid integration of renewables is covered in Section IV and conclusions are presented in Section V.
Fig. 2a. Working of a PV cell. Fig. 2b. I-V and power curves. Fig. 2c. PV based power generation.
5
Flicker is a periodic or aperiodic fluctuation in system voltage that can lead to noticeable changes in light output. Slow
fluctuating periodic flickers, in the 0.5–30 Hz range, are considered to be noticeable by humans. In case of PV systems;
flicker is resulted due to the power variations caused by passing clouds. In case of WTGs, flicker is caused by fluctuations
in the output power due to wind speed variations, wind shear, and the tower shadow effects. Variable-speed WTGs have
shown better performance related to flicker emission in comparison with fixed-speed WTGs.
Harmonics are sinusoidal voltages and currents with frequencies that are integral multiplies of the fundamental
frequency (50/60 Hz). Harmonics are associated with the distortion of fundamental sine wave and are produced by non-
linearity of electrical equipments. Harmonics results in increased currents, power losses and overheating in equipments
leading to premature ageing of devices. Service life reduction of equipment has been reported as 32.5% for single-phase
machines, 18% for three-phase machines and 5% for transformers. Harmonics may also lead to flickering in displays and
lighting, spurious tripping of circuit breakers, malfunctioning of sensitive equipments etc.
PQ problems can be mitigated by two ways, either from the customer side or from the utility side. The first approach,
known as load conditioning, ensures that the connected equipment is less sensitive to power supply disturbances, allowing
the operation even under significant voltage distortions. The second solution is by installing line conditioning systems that
suppress or offset the PQ related disturbances. Energy storage systems (flywheels, super-capacitors etc.), and other devices
such as constant voltage transformers, harmonic filters, noise filters, surge suppressors, isolation transformers etc. are
used for the mitigation of specific PQ problems. Recently, many FACTS (Flexible AC Transmission System) devices such as
DVR (Dynamic Voltage Restorer), STATCOM (Static Compensator), DSTATCOM (Distribution-STATCOM), SSSC (Static Series
Synchronous Compensator), SVC (Static Var Compensator), TCSC (Thyristor Controlled Series Compensator), and UPFC
(Unified Power Flow Controller) etc. are also being used for PQ mitigation.
d. Voltage Ride-Through (VRT) Capability
DFIG based wind turbines are the main technology used in wind generation systems. These WTGs are very sensitive to
the voltage variations in the connected grid. During abnormal voltage conditions, continuous operation of DFIGs may lead
to destructive over currents in the rotor winding or large over-voltages in the dc-link capacitor. Identical situations also
arise with converters used in PV systems.
In the initial periods of renewable grid integration, for the safety reasons; during abnormal voltage periods, converter
based generators used to be disconnected from the faulty system. However, with the increasing renewable penetration,
such practices are not more permitted and therefore, wind and PV generators should remain in service during grid events.
To enable wind and PV systems stay connected during abnormal voltage conditions, they need a voltage ride through
capability [20], [21]. VRT capability helps to produce reactive power in an effort to stabilize the grid. Without VRT capability,
DRs must trip for voltage deviations more than ± 10%.
Faults in the power grid result in voltage depression over a large area, both during the fault and during post-fault
dynamic behavior. In conventional system with synchronous generators, field forcing will help to keep the unit in
synchronism. As this feature is not available in distributed generators, terminal voltage will dip severely during faults. If
one unit trips due to under-voltage, that will trigger cascade tripping of other units, which in turn may lead to a bulk grid
event that stresses the grid further. To avoid this, DRs should not get isolated from the network during low system voltage
levels. Such requirements are called Low Voltage Ride Through (LVRT) capability.
During the post-fault period, high voltages may occur over a wide area due to dynamic backswing. These voltage
variations at the transmission level tend to propagate to the distribution systems to which DRs are connected. Over-voltage
may also arise due to load shedding or unbalanced faults. The magnitude and duration of high voltage will depend on the
fault scenario. To support the system during the short periods of such over-voltages, the DRs should not get isolated. This
requirement is called High Voltage Ride Through (HVRT) capability.
In many countries, LVRT capabilities are now mandatory for grid integration of DRs. Fig. 6a shows LVRT and HVRT
requirements as per IEEE Std. 1547, and LVRT requirement specified by few renewable rich countries, including India.
As per IEEE Std. 1547, grid connected wind and PV plants are expected to remain online and ride-through zero-voltage
faults, i.e. 100% drop in voltage, for up to 150 ms. The no-trip zone is set by voltage recovery for up to 2 s. The HVRT
requirement is 140% for 150 ms and 120% for 2 s. In India, wind plants connected to buses at 66 kV and above, ride-through
is 85% drop in voltage for up to 300 ms and voltage recovery is for up to 3 s [22]. These generators are required to maximize
reactive power till the time voltage starts recovering or for 300 ms, which ever time is lower.
There are two methods to enhance LVRT capability of induction generators based wind turbines during faults: a) by
reducing input to wind turbine and b) by increasing output of WTG. Turbine mechanical input can be reduced by blade
pitch control. The generator output can be increased by using switched capacitors, SVC, STATCOM, Unified Power Quality
Conditioner (UPQC), DVR, and series braking resistor etc. In case of DFIG based WTGs, LVRT capability can also be improved
by using active crowbar and series antiparallel thyristors.
Fig. 6a. Voltage ride through Fig. 6b. VAR capability of wind Fig. 6c. Freq. profile with increased wind
requirements of DRs. turbine generators. share in absence of droop and inertia.
f. Frequency Regulation Capability
Conventional synchronous generators possess two key qualities which are very essential in controlling the grid
frequency. These are: a) system inertia and b) speed droop.
Inertia is the property of a body to oppose any change in its motion. Inertia of the power system is proportional to the
amount of rotating masses in the system [13]. It determines the rate of change of frequency (ROCOF) following a load
event. The larger the system inertia, the less is the ROCOF following a power imbalance. The initial turbine governor action
immediately following a load event, known as primary control, establishes the active power balance between generation
and demand by using a proportional control action, known as droop, arrests the frequency deviations due to the change
in load. The droop parameter in the governor control loop allows multiple units to share common loads.
For optimizing the energy conversion efficiency, most of the wind farms use variable speed WTG technologies. In order
to prevent the reproduction of wind speed variation as frequency variation in the grid, variable speed WTGs use back-to-
back ac-dc-ac power electronic converters for the grid connection. The intermediate dc bus in the converter creates an
electrical decoupling between the machine and the grid. Because of this ac-dc-ac decoupling, the wind turbines, though
they are very heavy, appear lighter to the system. Thus the increasing presence of WEC systems in the power system will
reduce the effects of conventional synchronous generators that supply the major portion of the active power needed in
the grid. The entire system will then behave as a lighter system. A lighter system will experience larger changes in the
frequency even for small mismatches in the supply and demand.
The increasing penetration of wind and solar energy in the power grid increases the equivalent droop parameter of the
system. The increase in droop value translates into a weaker system, less responsive to load changes and consequently,
more frequency excursions result after every system event. Since the droop parameter is incorporated in the primary speed
control loop of a prime-mover governor, increase in the droop value will reduce the overall frequency control capability of
the generating unit. Fig. 6 c represents the system frequency profile after a small increase in load, in absence of inertia and
droop [23].
Another requirement for a generating unit to take part in frequency regulation is the availability of sufficient reserve
generation margin to meet the sudden increase in load demand or tripping of some generators. Traditionally, variable
speed WTGs and solar PV systems always operate at the maximum power point tracking (MPPT) curve so as to capture
optimum energy from the resource. This leaves no power reserve for frequency regulation needs. Thus, these generators
provide very little or no support to the system frequency regulation [24].
g. Protection Issues
The major protection issues related to the grid connection of distributed resources are: a) change of short circuit levels,
b) reverse power flow, c) lack of sustained fault current, d) blinding of protection and e) islanding.
8
V. CONCLUSION
Increased environmental awareness and energy security concerns have pushed renewable energy systems towards the
top of the power generation program. Among various renewable resources, wind and solar PV systems show exponential
growth rate during the past many years and are capable for grid integration. Due to the low energy density of wind and
sunlight, as compared to traditional fuels, power generation from these resources usually takes place in a distributed
manner. Integration of RES based distributed generation into the power system can be done at either the transmission
level or the distribution level, depending on the scale of generation. However, due to the proximity to distribution system
in remote areas where majority of the RES based generators are installed, they are normally connected to the grid at the
distribution level. Due to the variable and intermittent nature of the renewable resource, the generation technology used
in these units is different from the conventional units. The frequency of the power generated by these units will not be
normally at the standard system frequency and hence, a large group of DG technologies use power electronics converters
for grid connectivity. The decoupling of machine dynamics from the system dynamics by the power electronics devices
introduces several technical issues. This paper reviewed some of the technical challenges that need to be addressed for
the effective grid integration of renewable energy based distributed generators. The major concerns in interconnection of
renewable energy generation at the distribution level are related to voltage control, power quality and protection.
REFERENCES
[1] Renewables 2014 Global Status Report, Renewable Energy Policy Network for the 21st Century (REN21).
http://www.ren21.net/Portals/0/documents/Resources/GSR/2014/GSR2014_KeyFindings_low%20res.pdf
[2] http://www.bp.com/content/dam/bp/excel/Energy-Economics/statistical-review-2014/BP-
Statistical_Review_of_world_energy_2014_workbook.xlsx
[3] BP Energy Outlook 2035, January 2014. http://www.bp.com/content/dam/bp/pdf/Energy-economics/Energy-
Outlook/Energy_Outlook_2035_booklet.pdf
[4] http://www.se4all.org/resources/fact-sheets/
[5] G. Lalor, A. Mullane and M. O’Malley, “Frequency control and wind turbine technologies”, IEEE Trans. Power Sys., vol. 20, No. 4, pp. 1905-1913,
November, 2005.
[6] G. Ramtharan, J.B. Ekanayake and N. Jenkins, “Frequency support from doubly fed induction generator wind turbines”, IET Renew. Power Gen., pp.
3-9, March, 2007.
[7] J. Ekanayake and N. Jenkins, “Comparison onctionf the response of doubly fed and fixed-speed induction generator wind turbines to changes in
network frequency”, IEEE Trans. Energy Conv., vol. 19, No. 4, pp. 800-803, December, 2004.
[8] J. Morren, S. W. H. de Haan, and W. L. Kling, “Wind turbines emulating inertia and supporting primary frequency control”, IEEE Trans. Power Sys.,
vol. 21, No. 1, pp. 433-434, February, 2006.
[9] T. Ackermann, Wind power in power systems, Wiley, 2005.
[10] IEEE Std. 519-2014, IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems.
[11] IEEE Std. 1547.2-2008, Application Guide for IEEE 1547 Standard for Interconnecting Distributed Resources with Electric Power Systems.
[12] IEEE Std.1547.4-2011: IEEE Guide for Design, Operation, and Integration of Distributed Resource Island Systems with Electric Power Systems.
[13] P. Kundur, Power system stability and control, McGraw Hill, 1994
[14] J. Earnest, Wind Power Technology, PHI, New Delhi, 2014.
[15] V. Gevorgian and S. Booth, “Review of PREPA Technical Requirements for Interconnecting Wind and Solar Generation”, NREL Technical Report,
NREL/TP-5D00-57089, November 2013. http://www.nrel.gov/docs/fy14osti/57089.pdf
[16] N. Jenkins, R. Allan, P. Crossley, D. Kirchen, and G. Strbac, Embedded Generation, IEE Power and Engineering Series 31, Institution of Electrical
Engineers, London, 2000.
[17] L. Freris and David Infield, Renewable Energy in Power Systems, John Wiley, 2008.
[18] S. Lundberg, "Electrical limiting factors for wind energy installations", Chalmers University of Technology, Göteborg, Sweden, 2000.
http://webfiles.portal.chalmers.se/et/MSc/LundbergStefanMSc.pdf
[19] IEEE Std. 1159-2009, IEEE Recommended Practice for Monitoring Electric Power Quality.
[20] M. Mohseni, M. A.S. Masoum, and S. M. Islam, “Low and high voltage ride-through of DFIG wind turbines using hybrid current controlled
converters”, Electric Power Systems Research, pp. 1456–1465, vol. 81, no. 7, July 2011.
[21] R. Walling, A. Ellis, and S. Gonzalez, “Implementation of Voltage and Frequency Ride-Through Requirements in Distributed Energy Resources
Interconnection Standards”, Sandia National Laboratories Technical Report 2014-3122, California, April 2014. http://energy.sandia.gov/wp/wp-
content/gallery/uploads/SAND-2014-3122-VFRT_Paper_April-2014.pdf
[22] Large Scale Grid Integration of Renewable Energy Sources - Way Forward, Central Electricity Authority, India, Nov. 2013.
http://www.cea.nic.in/reports/powersystems/large_scale_grid_integ.pdf
[23] K. V. Vidyanandan and N. Senroy, “Issues in the grid frequency regulation with increased penetration of wind energy systems”, IEEE Students
Conference on Engineering and Systems (SCES 2012), pp. 1-6, MNNIT, Allahabad, U. P., India. 16-18, Mar. 2012.
[24] K. V. Vidyanandan, Frequency Regulation in Microgrids, Ph.D. Thesis, Dept. of Electrical Engineering, IIT-Delhi, India, 2013.
Dr. K.V. Vidyanandan received the M. Tech. (Power Generation Technology) and Ph. D. (Electrical
Engineering) from the Indian Institute of Technology (IIT), Delhi, India. He is a Faculty Member at the
Power Management Institute (PMI), NTPC Ltd., NOIDA. His research interests include Wind and Solar
PV Energy Systems, Energy Storage, Microgrids, and Frequency Regulation.
E-mail: [email protected]
Citation:
K. V. Vidyanandan, “Issues in the Grid Integration of Renewable Energy Systems”, International Power Plant O&M
Conference, pp. 1-9, New Delhi, India, 13-15 Feb. 2015.