Advantage Cooling Tower Catalouge

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

SUBJECT: WATER MAKE-UP REQUIREMENTS OF COOLING TOWERS FYI #262 12/07/2001

Evaporative cooling towers, like the Advantage Power Tower Series,


provide cooling by evaporating a small amount of the recirculated
process water flow. Approximately 1,000 BTUs are required to
evaporate .12 gallons of water. Therefore, every tower ton (15,000
BTH/hr) requires approximately 1.8 gallons of water evaporation, or
.03 gpm/ton.

As water evaporates in a cooling tower system, the water vapor


enters the atmosphere while any dissolved solids remain behind,
building concentration in the remaining water.

Most water treatment systems control this concentration by bleeding


off the high concentration water, which is made up by fresh city water
with a lower solid concentration. The amount of water that is bleed
off by the water treatment system is usually less than or equal to the
amount of water that evaporates.
Advantage Power Tower Series
Therefore, the maximum normal water make-up for a cooling tower Cooling Tower, Model TC-135F
system is .06 gpm/ton or about 2% of the nominal tower flow rate.

ADVANAGE TOWER MAXIMUM NOMINAL TOWER MAXIMUM WATER ADVANAGE


MODEL # CAPACITY EVAPORATION FLOW RATE MAKE-UP MODEL #
Power Tower Series expressed in TONS at design capacity (GPM) (GPM) at design capacity (GPM) Power Tower Series

TC-45F 45 1.35 135 2.7 TC-45F


TC-85F 85 2.55 255 5.1 TC-85F
TC-105F 105 3.15 315 6.3 TC-105F
TC-135F 135 4.05 405 8.1 TC-135F
TC-170F 170 5.10 510 10.2 TC-170F
TC-210F 210 6.30 630 12.6 TC-210F
TC-270F 270 8.10 810 16.2 TC-270F
TC-405F 405 12.15 1215 24.3 TC-405F
TC-540F 540 16.20 1620 32.4 TC-540F

Maximum includes
evaporation and bleed off

ADVANTAGE Engineering, Inc. 525 East Stop 18 Road Greenwood, IN 46142 317-887-0729 fax: 317-881-1277
web site: www.advantageengineering.com email: [email protected]
updated 12/07/2001 © 2001 Advantage Engineering, Inc.

You might also like