DeltaV M-Series Virtual IO Module 2 (2013)
DeltaV M-Series Virtual IO Module 2 (2013)
The M-series Virtual I/O Module 2 provides DeltaV™ I/O simulation and a high speed Ethernet I/O device integration platform
www. DeltaV.com
DeltaV Product Data Sheet
January 2013 – Page 2 M-series Virtual I/O Module 2
Benefits Automatic updates. Simulation I/O driver updates for
the VIM2 are included with the MiMiC software
Non-Intrusive DeltaV I/O simulation. Use the VIM2 releases. Updates are quick and easy over the
in conjunction with the MYNAH Technologies’ MiMiC simulation network.
Simulation Software to simulate your DeltaV M-Series
I/O and digital bus field devices. Seamless Ethernet I/O integration. When used with
the MYNAH Ethernet I/O drivers, the VIM2 is seen by
Supports DeltaV I/O modules. Provides completely the DeltaV M-series controller as four DeltaV Serial
non-intrusive simulation of all DeltaV M-series I/O Cards. Commissioned VIM2s are auto-sensed by the
Modules. Supports autosensing of I/O and accurate DeltaV controller as DeltaV Serial Cards.
testing of controller loading. DeltaV configuration can
be fully tested without modifying the control Configured in DeltaV Explorer. Serial dataset
strategies. configuration used for Ethernet I/O integration is done
in the DeltaV Explorer in the same manner as a
Digital bus support. Provides simulation of all DeltaV Serial Card. Ethernet I/O signals can be used
DeltaV Digital Busses and Foundation Fieldbus in DeltaV Control Modules, displayed on DeltaV
function blocks. Supports Foundation Fieldbus control Operate graphics and stored in the DeltaV
in the field configuration testing. Continuous Historian.
Powerful simulation solution. Provides full Intuitive setup. The VIMNet Explorer application
simulation of up to 64 DeltaV I/O modules per provides plug-n-play capability making setup of the
controller. Simulation execution is fast and efficient; VIM2 easy and intuitive. Graphical, drag-n-drop,
the DeltaV controller thinks it’s talking with real IO. functionality makes setting up multiple VIM2s almost
effortless. VIMNet Explorer is integrated with DeltaV
Powerful integration solution. Use the VIM2 in Explorer to make setup of the VIM2 easy and intuitive.
conjunction with the MYNAH Ethernet I/O drivers to
integrate your DeltaV system with your Ethernet I/O device Modular, flexible packaging. The VIM2 mounts in the
networks. same manner as the DeltaV controller. It mounts in the
controller slot of a DeltaV 2-wide horizontal or 4-wide
Large device capacity. Each VIM emulates four vertical carrier and uses a standard DeltaV Power Supply.
DeltaV Serial Cards and support up to 128 Serial The advanced design of the VIM2 will provide years of
Card Datasets of information from 32 network devices uninterrupted use.
in simplex installations and 16 devices in redundant
installations. Communication over the Ethernet I/O
device network is fast and efficient.
The I/O simulation driver is provided with the VIM2 The VIMNet Explorer software installation file for the VIM2
hardware, pre-loaded in the VIM2. The MiMiC Simulation is available on a DeltaV v12 and later workstation and on
Software must be purchased separately from MYNAH the DeltaV v12 and later software installation DVD. The
Technologies. Technical support for the MiMiC Simulation VIMNet Explorer software installation file is also provided
Software and I/O simulation driver is provided by MYNAH with the purchase of a MYNAH Ethernet I/O driver.
Technologies.
VIM Redundancy. Two VIM2s can be setup as a
Ethernet I/O Integration When used with the MYNAH redundant pair for installations that require backup
Ethernet I/O drivers, the VIM2 can communicate with Ethernet I/O networks. Each VIM2 will be installed on its
high-speed Ethernet networks over Modbus TCP or own 2-wide carrier, with its own power supply to the left of
Ethernet/IP. When the VIM2 is configured with the the DeltaV Controller.
appropriate Ethernet I/O driver, the DeltaV Controller auto-
senses a commissioned VIM2 as four DeltaV Serial Cards. The active and standby VIM2s monitor each other with a
In simplex installations these cards will be sensed in continuous status command using the redundancy link
slots 57-60 or 61-64. cable supplied with each redundant pair. The active VIM2
In redundant installations the redundant pairs will be communicates over the network to the Industrial Ethernet
sensed in slots 57 to 64. device and the standby sends an intermittent signal to the
device to maintain communication integrity.
Configuration of the I/O signals from the commissioned
VIM2 is done in the DeltaV Explorer in the same manner The Ethernet I/O drivers are not provided with the VIM2
as a DeltaV Serial Card. hardware; they must be purchased separately from
MYNAH Technologies. Technical support for the Ethernet
I/O drivers is provided by MYNAH Technologies.
DeltaV Product Data Sheet
January 2013 – Page 4 M-series Virtual I/O Module 2
The DeltaV system with M-series VIM2 and Ethernet I/O integration (simplex VIM2 and DeltaV controller shown)
DeltaV Product Data Sheet
January 2013 – Page 5 M-series Virtual I/O Module 2
Supported Industrial Ethernet DeltaV Licensing Guidelines
Protocols DeltaV Software Licensing Requirements (DST count) will
Modbus TCP/IP The VIM2 with the Modbus TCP/IP be impacted by DeltaV Module configuration use of VIM2
registers in the same way as Serial Card registers. The
Master Driver supports the following Modbus
following guidelines can be applied:
communications protocol function codes to read and write
values to and from a Modbus slave device, as specified by
the Modbus Application Protocol Specification from A DeltaV Serial Card data set can contain up to 100
Modbus-IDA.org. values (a value can be any Boolean, 8-bit or 16-bit
number), and up to16 data sets are supported by
each of the 2 ports on the serial card. If the data set
The VIM2 Modbus TCP/IP Driver supports the following
registers are configured as floating point or 32-bit
Modbus function codes:
values, then the maximum value is 50. However, the
serial device, in general, limits the total capacity of the
Code 1 - Read Coil Status interface.
Code 2 - Read Input Status Each data set counts as one DST as long as a single
Code 3 - Read Holding Registers module references all values in the data set. If
Code 4 - Read Input Registers multiple modules reference values in a data set, then
Code 5 - Force Single Coil the DST count for the data set is equal to the number
Code 6 - Preset Single Register of modules referencing the data set.
Code 8 - Diagnostic Loop Back Test Values used in modules containing control function
Code 15 - Force Multiple Coils blocks will be counted as Control DSTs.
Code 16 - Preset Multiple Registers Values referenced only in graphics or a history
collection count as SCADA values, not DSTs.
The VIM2 can function as both a Modbus TCP/IP master
and slave simultaneously. Master or slave mode is set at
the virtual port level. In master-only mode, this driver can
communicate with a maximum of 32 slave devices.
Systems that use both master and slave mode can
communicate with a maximum of 16 slaves and 16
masters at the same time. The master and slave capability
is available in simplex implementations only. In redundant
applications, only master mode is supported.
M-series VIM2
DeltaV Product Data Sheet
January 2013 – Page 6 M-series Virtual I/O Module 2
Hardware Specifications
Specifications for the M-series Virtual I/O Module 2
Power requirement Supplied by System Power Supply, either through the 4-wide vertical (only
for simplex setups) or the 2-wide horizontal Power/Controller Carrier.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be
construed as warrantees or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed
by our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such products at any time
without notice.