Ik International 1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

TEST REPORT

ISSUED TO : M/S. I.K INTERNATIONAL


89/1.2 T.V TOWER AKRAMPUR
UNNAO (U.P)
Sample Identification No. : DW-230913/001
Test Report No. : GEL-2309/5933
ULR Number : TC-718623000008604F
Date of Issue : 16.09.2023
Testing Location : PERMANENT FACILITY
Sampling Method : IS:17614:2021
Type of Sample : DRINKING WATER
Sample Collection Date : 12.09.2023
Sample Collected by : GEL STAFF
Sample Quantity : 2.0 LTR + 500 ML
Sample Description : LIQUID
Sampling Location : R.O (OUTLET)
Date of Sample Receipt : 13.09.2023
Sample Condition : SEALED
Analysis Duration : 13.09.2023 To 16.09.2023
ANALYSIS RESULT
ORGANOLEPTIC & PHYSICAL PARAMETER
S. NO. PARAMETER UNIT TEST METHOD RESULT DRINKING WATER STANDARDS/LIMIT
(IS: 10500:2012) (RA 2018)
ACCEPTABLE LIMIT PERMISSIBLE LIMIT
1 Colour HZN IS:3025(Part 4): 2021 <5 5 (max.) 15 (max.)
2 Odour --- IS:3025 (Part 5): 2018 Agreeable Agreeable No relaxation
3 pH --- IS:3025 (Part 11): (RA 2022) 6.96 6.5-8.5 No relaxation

4 Turbidity NTU
IS:3025 (Part 10): 1984 (RA <1 1(max.) 5(max.)
2022)
5 Total Dissolved Solids (TDS) mg/L IS:3025 (Part 16): 2023 118 500 (max.) 2000 (max.)
GENERAL PARAMETER
S. NO. PARAMETER UNIT TEST METHOD RESULT DRINKING WATER STANDARDS/LIMIT
(IS: 10500:2012) (RA 2018)
ACCEPTABLE LIMIT PERMISSIBLE LIMIT
IS 3025 (Part 40): 1991 11.2
7 Calcium mg/L 75 (max.) 200 (max.)
(RA 2019)
IS 3025 (Part 32):1988 28.6
8 Chloride mg/L 250 (max.) 1000 (max.)
(RA 2019)
Fluoride (F ) IS 3025 (Part 60): SEC 0.03
9 mg/L 1.0 (max.) 1.5 (max.)
3:2022
10 Residual, Free Chlorine(RFC) mg/L IS 3025 (Part 26): 2021 N.D. 0.2 (min.) 1.0 (min.)
IS 3025 (Part 46):1994 5.7
11 Magnesium (Mg) mg/L 30 (max.) 100 (max.)
(RA 2019)
Sulphate (SO₄) IS 3025 (Part 24): SEC 9.5
12 mg/L 200 (max.) 400 (max.)
1:2022
N.D.: Not Detected. , BDL: Below Detection Limit.

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
Test Report No. : GEL-2309/5933
ULR Number: TC-718623000008604F
GENERAL PARAMETER
S. NO. PARAMETER UNIT TEST METHOD RESULT DRINKING WATER STANDARDS/LIMIT
(IS: 10500:2012) (RA 2018)
ACCEPTABLE LIMIT PERMISSIBLE LIMIT
IS 3025 Part 21:2009
13 Total Hardness mg/L 52 200 (max.) 600 (max.)
(RA:2019)
RESIDUE IN WATER (HEAVY METAL)
S. NO. PARAMETER UNIT TEST METHOD RESULT DRINKING WATER STANDARDS/LIMIT
(IS: 10500:2012) (RA 2018)
ACCEPTABLE LIMIT PERMISSIBLE LIMIT
IS 3025 (Part 53):2003
14 Iron (Fe) mg/L 0.08 1.0 (max.) No Relaxation
(RA:2019)
D: Not N.D.: Not Detected. , BDL: Below Detection Limit.

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
.
Test Report No. : GEL-2309/5933
ULR Number: TC-718623000008604F
BACTERIOLOGICAL PARAMETER
REQUIREMENTS
S. No. Parameter Unit TEST METHOD RESULT
(IS: 10500:2012) (RA 2018)
IS:15185:2016 Shall not be detectable in 100ml
1 E.coli Per100ml Absent
(RA 2021) sample
IS:15185:2016 Shall not be detectable in 100ml
2 Total Coliform Per100ml Absent
(RA 2021) sample

(Checked By) MONICA SINGH


TANU CHAUDHARY (Microbiologist) (Authorized Signatory)
Note: 1. The results listed refer only to the tested samples and applicable PARAMETER.
2. The samples will be destroyed after 15 days of sampling.
3. This report cannot be used as evidence in the court of law and cannot be used in part or full in any media without prior permission.
4. Subject to Ghaziabad Jurisdiction only.
***END OF REPORT***
TEST REPORT
ISSUED TO : M/S. I.K INTERNATIONAL
89/1.2 T.V TOWER AKRAMPUR
UNNAO (U.P)
Sample Identification No. : SL-230913/001
Test Report No. : GEL-2309/5934
ULR Number : TC-718623000008605F
Date of Issue : 16.09.2023
Monitoring Method : GEL/SOP-01/SL
Monitoring Description : D.G. NOISE LEVEL
Instrument Used For Monitoring : NOISE METER
Monitoring Date : 13.09.2023
Monitored by : GEL STAFF
Monitoring Location : 1.0 METER AWAY FROM D. G. SET NO. 125 KVA

S. NO. PARAMETER RESULT UNIT


01. AVERAGE dB(A) (at open acoustic door position) 98.9
02. AVERAGE dB(A) (at closed acoustic door position) 73.7 dB(A)
03. AVERAGE dB(A) (insertion loss of the D.G. acoustic room/enclosure) 25.2

STANDARD
CPCB STANDARD AS PER FACTORIES LIMIT AS PER EPA
ACT – 1948

75 dB(A) 85 dB(A) Minimum insertion loss of 25 dB(A)

Remarks: 1. Average Noise Level is well within the limits as per CPCB and Factories Act – 1948

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
Note: 1. The results listed refer only to the tested samples and applicable PARAMETER.
2. The samples will be destroyed after 15 days of sampling.
3. This report cannot be used as evidence in the court of law and cannot be used in part or full in any media without prior permission.
4. Subject to Ghaziabad Jurisdiction only.
***END OF REPORT***
TEST REPORT
ISSUED TO : M/S. I.K INTERNATIONAL
89/1.2 T.V TOWER AKRAMPUR
UNNAO (U.P)
Sample Identification No. : SL-230913/002
Test Report No. : GEL-2309/5935
ULR Number : TC-718623000008606F
Date of Issue : 16.09.2023
Monitoring Method : GEL/SOP-01/SL
Monitoring Description : NOISE LEVEL
Instrument Used For Monitoring : NOISE METER
Monitoring Date : 13.09.2023
Monitored by : GEL STAFF
Monitoring Location : NEAR ELECTRICAL PANEL
Monitoring Duration : 10:32 HR To 10:42 HR

1 2 3 4 5 6 7 8 9 10

71.1 72.8 73.3 70.8 71.9 70.3 73.7 70.5 72.7 73.9

NOISE LEVEL STANDARD

MAXIMUM 73.9 CPCB STANDARD AS PER FACTORIES


dB(A)
SOUND LEVEL (FOR DAY TIME) ACT – 1948
MINIMUM dB(A) 70.3 INDUSTRIAL AREA 75 dB(A) 85 dB(A)
SOUND LEVEL
AVERAGE dB(A) 72.1 RESIDENTIAL AREA 55 dB(A)
VALUE
COMMERCIAL AREA 65 dB(A)
SILENCE ZONE 50 dB(A)

Remarks: 1. Average Noise Level is well within the limits as per CPCB and Factories Act – 1948

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
Note: 1. The results listed refer only to the tested samples and applicable PARAMETER.
2. The samples will be destroyed after 15 days of sampling.
3. This report cannot be used as evidence in the court of law and cannot be used in part or full in any media without prior permission.
4. Subject to Ghaziabad Jurisdiction only.
***END OF REPORT***
TEST REPORT
ISSUED TO : M/S. I.K INTERNATIONAL
89/1.2 T.V TOWER AKRAMPUR
UNNAO (U.P)
Sample Identification No. : L-230913/001
Test Report No. : GEL-2309/5936
ULR Number : TC-718623000008607F
Date of Issue : 16.09.2023
Monitoring Method : GEL/SOP-01/LUX
Monitoring Description : LUX LEVEL
Instrument Used For Monitoring : LUX METER
Monitoring Date : 13.09.2023
Monitored by : GEL STAFF
Monitoring Location : PRODUCTION LINE-01 NEAR ELECTRIC PANEL
Monitoring Time & Duration : 10:15 HR TO 10:25 HR

1 2 3 4 5 6 7 8 9 10

330 360 375 315 480 320 485 374 340 380

LUX LEVEL STANDARD


MAXIMUM LUX LEVEL 485

MINIMUM LUX LEVEL 315 300-700

AVERAGE VALUE 376

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
Note: 1. The results listed refer only to the tested samples and applicable PARAMETER.
2. The samples will be destroyed after 15 days of sampling.
3. This report cannot be used as evidence in the court of law and cannot be used in part or full in any media without prior permission.
4. Subject to Ghaziabad Jurisdiction only.
***END OF REPORT***
TEST REPORT
ISSUED TO : M/S. I.K INTERNATIONAL
89/1.2 T.V TOWER AKRAMPUR
UNNAO (U.P)
Sample Identification No. : L-230913/002
Test Report No. : GEL-2309/5937
ULR Number : TC-718623000008608F
Date of Issue : 16.09.2023
Monitoring Method : GEL/SOP-01/LUX
Monitoring Description : LUX LEVEL
Instrument Used For Monitoring : LUX METER
Monitoring Date : 13.09.2023
Monitored by : GEL STAFF
Monitoring Location : SAMPLE DEPARTMENT
Monitoring Time & Duration : 10:36 HR TO 10:46 HR

1 2 3 4 5 6 7 8 9 10

220 240 285 330 324 384 375 330 290 286

LUX LEVEL STANDARD


MAXIMUM LUX LEVEL 384

MINIMUM LUX LEVEL 220 300-700

AVERAGE VALUE 306

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
Note: 1. The results listed refer only to the tested samples and applicable PARAMETER.
2. The samples will be destroyed after 15 days of sampling.
3. This report cannot be used as evidence in the court of law and cannot be used in part or full in any media without prior permission.
4. Subject to Ghaziabad Jurisdiction only.
***END OF REPORT***
TEST REPORT
ISSUED TO : M/S. I.K INTERNATIONAL
89/1.2 T.V TOWER AKRAMPUR
UNNAO (U.P)
Sample Identification No. : L-230913/003
Test Report No. : GEL-2309/5938
ULR Number : TC-718623000008609F
Date of Issue : 16.09.2023
Monitoring Method : GEL/SOP-01/LUX
Monitoring Description : LUX LEVEL
Instrument Used For Monitoring : LUX METER
Monitoring Date : 13.09.2023
Monitored by : GEL STAFF
Monitoring Location : STORE LEATHER
Monitoring Time & Duration : 11:15 HR TO 11:25 HR

1 2 3 4 5 6 7 8 9 10

456 415 438 429 459 476 443 486 419 485

LUX LEVEL STANDARD


MAXIMUM LUX LEVEL 486

MINIMUM LUX LEVEL 415 300-700

AVERAGE VALUE 451

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
Note: 1. The results listed refer only to the tested samples and applicable PARAMETER.
2. The samples will be destroyed after 15 days of sampling.
3. This report cannot be used as evidence in the court of law and cannot be used in part or full in any media without prior permission.
4. Subject to Ghaziabad Jurisdiction only.
***END OF REPORT***
TEST REPORT
ISSUED TO : M/S. I.K INTERNATIONAL
89/1.2 T.V TOWER AKRAMPUR
UNNAO (U.P)
Sample Identification No. : L-230913/004
Test Report No. : GEL-2309/5939
ULR Number : TC-718623000008610F
Date of Issue : 16.09.2023
Monitoring Method : GEL/SOP-01/LUX
Monitoring Description : LUX LEVEL
Instrument Used For Monitoring : LUX METER
Monitoring Date : 13.09.2023
Monitored by : GEL STAFF
Monitoring Location : FINAL Q.C DEPARTMENT
Monitoring Time & Duration : 11: 30HR TO 11:42 HR

1 2 3 4 5 6 7 8 9 10

428 480 462 458 469 436 452 477 484 482

LUX LEVEL STANDARD


MAXIMUM LUX LEVEL 484

MINIMUM LUX LEVEL 428 300-700

AVERAGE VALUE 462.8

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
Note: 1. The results listed refer only to the tested samples and applicable PARAMETER.
2. The samples will be destroyed after 15 days of sampling.
3. This report cannot be used as evidence in the court of law and cannot be used in part or full in any media without prior permission.
4. Subject to Ghaziabad Jurisdiction only.
***END OF REPORT***
TEST REPORT
ISSUED TO : M/S. I.K INTERNATIONAL
89/1.2 T.V TOWER AKRAMPUR
UNNAO (U.P)
Sample Identification No. : L-230913/005
Test Report No. : GEL-2309/5940
ULR Number : TC-718623000008611F
Date of Issue : 16.09.2023
Monitoring Method : GEL/SOP-01/LUX
Monitoring Description : LUX LEVEL
Instrument Used For Monitoring : LUX METER
Monitoring Date : 13.09.2023
Monitored by : GEL STAFF
Monitoring Location : PRODUCTION LINE -02 ADJACENT TO FINAL QC
Monitoring Time & Duration : 11: 35HR TO 11:46 HR

1 2 3 4 5 6 7 8 9 10

553 468 481 514 439 489 458 536 474 477

LUX LEVEL STANDARD


MAXIMUM LUX LEVEL 553

MINIMUM LUX LEVEL 439 300-700

AVERAGE VALUE 489

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
Note: 1. The results listed refer only to the tested samples and applicable PARAMETER.
2. The samples will be destroyed after 15 days of sampling.
3. This report cannot be used as evidence in the court of law and cannot be used in part or full in any media without prior permission.
4. Subject to Ghaziabad Jurisdiction only.
***END OF REPORT***
TEST REPORT
ISSUED TO : M/S. I.K INTERNATIONAL
89/1.2 T.V TOWER AKRAMPUR
UNNAO (U.P)
Sample Identification No. : L-230913/006
Test Report No. : GEL-2309/5941
ULR Number : TC-718623000008612F
Date of Issue : 16.09.2023
Monitoring Method : GEL/SOP-01/LUX
Monitoring Description : LUX LEVEL
Instrument Used For Monitoring : LUX METER
Monitoring Date : 13.09.2023
Monitored by : GEL STAFF
Monitoring Location : MACHINE ROOM
Monitoring Time & Duration : 11:40 HR TO 11:50 HR

1 2 3 4 5 6 7 8 9 10

521 526 578 545 565 582 548 542 532 532

LUX LEVEL STANDARD


MAXIMUM LUX LEVEL 582

MINIMUM LUX LEVEL 521 300-700

AVERAGE VALUE 547.1

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
Note: 1. The results listed refer only to the tested samples and applicable PARAMETER.
2. The samples will be destroyed after 15 days of sampling.
3. This report cannot be used as evidence in the court of law and cannot be used in part or full in any media without prior permission.
4. Subject to Ghaziabad Jurisdiction only.
***END OF REPORT***
TEST REPORT
ISSUED TO : M/S. I.K INTERNATIONAL
89/1.2 T.V TOWER AKRAMPUR
UNNAO (U.P)
Sample Identification No. : L-230913/007
Test Report No. : GEL-2309/5942
ULR Number : TC-718623000008613F
Date of Issue : 16.09.2023
Monitoring Method : GEL/SOP-01/LUX
Monitoring Description : LUX LEVEL
Instrument Used For Monitoring : LUX METER
Monitoring Date : 13.09.2023
Monitored by : GEL STAFF
Monitoring Location : STORE FITTING
Monitoring Time & Duration : 11:45 HR TO 11:55 HR

1 2 3 4 5 6 7 8 9 10

462 482 499 532 517 498 478 536 472 493

LUX LEVEL STANDARD


MAXIMUM LUX LEVEL 536

MINIMUM LUX LEVEL 462 300-700

AVERAGE VALUE 497

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
Note: 1. The results listed refer only to the tested samples and applicable PARAMETER.
2. The samples will be destroyed after 15 days of sampling.
3. This report cannot be used as evidence in the court of law and cannot be used in part or full in any media without prior permission.
4. Subject to Ghaziabad Jurisdiction only.
***END OF REPORT***
TEST REPORT
ISSUED TO : M/S. I.K INTERNATIONAL
89/1.2 T.V TOWER AKRAMPUR
UNNAO (U.P)
Sample Identification No. : AA-230913/001
Test Report No. : GEL-2309/5943
ULR Number : TC-718623000008614F
Date of Issue : 16.09.2023
Sampling Method : GEL/SOP-01/AA
Testing Location : PERMANENT FACILITY
Sample Description : AMBIENT AIR
Sampling Duration : 12.09.2023 TO 13.09.2023
Sample Collected by : Gel staff
Instrument Used For Sampling : RDS WITH GASEOUS ATTACHMENT + CO ANALYSER
Sampling Location : NEAR MAIN GATE
Sample Collection Date : 13.09.2023
Ambient Temperature (K) : 306
Weather Condition : SUNNY
Date of Sample Receipt : 13.09.2023
Sample Condition : SEALED
Analysis Duration : 13.09.2023 To 16.09.2023
ANALYSIS RESULTS
S. No. PARAMETER UNIT RESULTS *LIMIT TEST METHOD
1. Particulate Matter (Size <10 µm) [µg/m3] 86 100* IS:5182(part-23):2006 (RA:2022)
2. Sulphur Dioxide (as SO2) [µg/m3] 16.7 80* IS:5182(part-2):2001 (RA :2022)
3. Nitrogen Dioxide (as NO2) [µg/m3] 36.2 80* IS:5182(part-6):2006 (RA :2022)
4. Carbon Monoxide (CO) [mg/m3] 0.76 4** IS:5182(part-10):1999 (RA:2019)
*CPCB’S specification for Ambient Air Quality for 24 hours.
**CPCB’S specification for Ambient Air Quality for 1.0 hours.

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
Note: 1. The results listed refer only to the tested samples and applicable PARAMETER.
2. The samples will be destroyed after 15 days of sampling.
3. This report cannot be used as evidence in the court of law and cannot be used in part or full in any media without prior permission.
4. Subject to Ghaziabad Jurisdiction only.
***END OF REPORT***
TEST REPORT
ISSUED TO : M/S. I.K INTERNATIONAL
89/1.2 T.V TOWER AKRAMPUR
UNNAO (U.P)
Sample Identification No. : SE-230913/001
Test Report No. : GEL-2309/5944
ULR Number : TC-718623000008615F
Date of Issue : 16.09.2023
Sampling Method : GEL/SOP-01/SE
Testing Location : PERMANENT FACILITY
Monitoring Description : STACK EMISSION FROM: D.G. SET - 125 KVA
Sample Collection Date : 12.09.2023
Instrument Used For Sampling : STACK SAMPLER
Sampling Duration : 3600 sec
Sample Collected by : GEL STAFF
Sampling Location : PORT HOLE
Date of Sample Receipt : 13.09.2023
Sample Condition : SEALED
Analysis Duration : 13.09.2023 To 16.09.2023
SAMPLE SOURCE DETAILS
Type & Consumption of Fuels : H.S.D- 15.0 -16.0 Ltr/Hr (APPROX)
Stack Height (From Ground level) : 4.5 meter
Stack Height (From Roof level) : -
Stack Diameter (at Port Hole) : 125 mm
Stack Temperature (K) : 432
Ambient Temperature (K) : 304
Average Velocity [m/sec.] : 14.7
Flow Rate of SPM [LPM] : 22.0
Flow Rate of Gases [LPM] : 2.4
Quantity of emission(m3/Hr) : 649.09
ANALYSIS RESULT
S No. PARAMETERS Unit RESULTS *LIMIT TEST METHOD

0.13
1. PARTICULATE MATTER [g/kw-hr] 0.2 IS:11255(part-1): 1985 (RA:2019)
1.32
2. OXIDES OF NITROGEN [g/kw-hr] IS:11255(part-7):2005 (RA:2022)
4.0
0.54
3. HYDROCARBON [g/kw-hr] GEL/SOP-HC/SE
1.05
4. CARBON MONOXIDE [g/kw-hr] 3.5 IS:13270:1992 (RA:2019)
*CPCB’S Emission Standard for Diesel Generator Sets (Engine rating <800 KW)

(Checked By) ARVIND KUMAR


INTEKHAB KHAN (Technical Manager) (Authorized Signatory)
Note: 1. The results listed refer only to the tested samples and applicable parameters.
2. The samples will be destroyed after 15 days of sampling.
3. This report cannot be used as evidence in the court of law and cannot be used in part or full in any media without prior permission.
4. Subject to Ghaziabad Jurisdiction only.
***END OF REPORT***

You might also like