DD2003
DD2003
Product characteristics
MONITOR
FR-1
Housing for DIN rail mounting
2 relay outputs
2 transistor outputs
Analogue output
0/4...20 mA
programmable
Test function without external frequency
Key function
Application
Application single pulse evaluation system with µprocessor for frequency; rotational speed;
speed and machine cycles
Switching function 2 switch points for monitoring overspeed/underspeed and acceptable range
Electrical data
Nominal voltage [V] 110...240 AC (50...60 Hz) / 27 DC (typ. 24 DC)
Voltage tolerance [%] -20...+10
Power consumption [VA] 5 (3 W)
Inputs
Inputs pnp/npn; NAMUR (24 V)
auxiliary supply: typ. 24 V DC / 15 mA; short-circuit protected
threshold pnp: > 12 V on; < 5 V off
threshold npn: > 15 V off; < 8 V on
input frequency (max): 5 kHz (corresponds to min. pulse length / space 0.1 ms)
Outputs
Relay
Contact rating 6 A (250 V AC); B300, R300
Transistor
Transistor outputs pnp; external supply
switching voltage/current: 24 V DC / max. 15 mA; short-circuit protected
DD2003
MONITOR/FR-1 /110-240VAC/DC Evaluation systems, power supplies
analogue
Analogue output 0/4...20 mA
Max. load [Ω] 500
limitation: 20.5 mA; accuracy: 1 % (of the final value)
Measuring / setting range
Setting range [pulses/min.] 1...60000 (0.1...1000 Hz)
Accuracy / deviations
Measuring error [% of the final value] <1
Environment
Ambient temperature [°C] -20...60
Storage temperature [°C] -25...80
Max. relative air humidity [%] 75 (35°C)
Protection housing / terminals IP 50 / IP 20
Tests / approvals
EMC EN 61010 : 2001
EMC 89/336/EEC
EN 61000-6-3 : 2007
EN 61000-6-2 : 2005
Mechanical data
Housing materials plastics
Weight [kg] 0.364
Displays / operating elements
Input pulses LED yellow
Output status indication LED green (lights when the relay is energised / the transistor is closed)
Function display LED LCD display; 7/14-segment
Electrical connection
Connection dual-chamber terminals 2 x 2.5 mm² (2 x AWG 14)
Wiring
1: DC Supply voltage (L-)
2: DC Supply voltage (L+)
3: supply transistor outputs (L+)
4: sensor signal pnp
5: DC Sensor supply (L+)
6: DC Sensor supply (L-)
7: AC Supply voltage (L1)
8: AC Supply voltage (N)
9: n.c.
10: sensor signal npn
11: n.c.
12: n.c.
13: Relay 1 (common)
14: Relay 1 (normally open)
15: Relay 1 (normally closed)
16: transistor output 1 pnp
17: Reset 1 pnp
18: Reset 2 pnp
19: Relay 2 (common)
20: Relay 2 (normally open)
21: Relay 2 (normally closed)
22: analogue output (+)
23: analogue output (-)
24: transistor output 2 pnp
Remarks
DD2003
MONITOR/FR-1 /110-240VAC/DC Evaluation systems, power supplies