Saudi Arabia

LG Electronics
http://lge.com
http://partner.lge.com
http://lghvacstory.com

Copyright © 2022 LG Electronics. All rights reserved.


WHY
LG INVERTER
DIRECT DRIVE PACKAGE?

WORLD TOP LEVEL EFFICIENCY


7.5 ~25RT COOLING & HEATING
LG launches the world top level efficiency
Inverter Single package

CONVENIENCE
Direct drive fan motor
Easy set-up method (by ESP function)

ULTIMATE PERFORMANCE
Superior efficient ultimate inverter compressor
Applied BLDC motors for all fans
Superior level IEER 18.3 (25RT) & 19.0 (20RT)

2 3
LINE UP

DIRECT DRIVE INVERTER PACKAGE INVERTER PACKAGE


COOLING / HEATING Category COOLING ONLY
Category
380 ~ 415, 3, 50/60 230, 1, 60 400, 3, 60

Cooling Only
AK-C03620
3/4/5 AK-C04820
AK-C06020

Cooling &
Heating Cooling Only
AK-W110LH00
7.5 / 10 AK-W130LH00 7.5 / 10

AK-Q1209C02
AK-Q1509C02

Cooling &
Heating AK-W160LH00
Cooling Only
AK-W200LH00
12.5 / 15 12.5 / 15
AK-Q1509C02
AK-Q1809C02

Cooling & AK-W270LH00 Cooling Only


Heating AK-W320LH00 20 / 25

20/ 25
AK-Q2409C01
AK-Q3009C01

Economizer [PKEMD1CA0]

* Economizer can be used from 7.5 to 25 tons.

4 5
SUPERIOR EFFICIENCY ADVANCED KEY COMPONENTS FOR HIGH ENERGY EFFICIENCY
High energy efficiency with LG’s cutting-edge core components and Inverter leading technology.

Multi V inverter BLDC fan motor / New biomimetic fan


World Top level IEER compressor
Superior Partial Load Efficiency
Energy Savings with Linear Control
Superior Efficiency Cooling & Heating BLDC motor New biomimetic fan

Annual Energy Savings Estimation


Payback
Supply
Dual Sensing Control

Temperature Sensor Black Fin


Hydrophilic Film
+ Return (Water Flow)
Corrosion
LG Wide Louver Plus Fin Resistant Layer

Pressure Sensor

EXCELLENT PARTIAL LOAD EFFICIENCY


Inverter compressor maximizes energy efficiency through adjusting energy supply as required.

Energy saving concept comparison


Constant Speed Compressor

Supply of Energy
WASTE OF
ENERGY
Required Energy

100% Operation 100% Operation 100% Operation

09:00 12:00 14:00 16:00 18:00 Time

Inverter Compressor

Supply of Energy
Required Energy

Maximized
Energy
40% Operation 100% Operation 40% Operation Efficiency

09:00 12:00 14:00 16:00 18:00 Time

6 7
SUPERIOR EFFICIENCY

ANNUAL ENERGY SAVINGS SUPERIOR EFFICIENCY HEAT PUMP


Target low pressure will be adjusted according to cooling load. LG provides energy saving by preventing on/off New inverter single package provides both heating and cooling while saving energy.
operation with inverter technology.
CONVENTIONAL
19.3
25 - Superior initial investment cost by installing electric heater for heating

EER
- Superior electricity charges by auxiliary device
10.0
EER
93% 20

15

Additional Cost
10
35 °C 27.5 °C (About 5% of product price)

5
24.25 Power Input (kW)
48%
12.56 0 1.0
27.5 35 40 46 48 Max
Outdoor Temp. (°C)
Energy Efficiency1)
Outdoor Temp. (°C) 27.5 35 40 46 48
(W / W)
Unit (Cooling only) + Electric Heater 2)
EER 19.3 10.0 8.0 6.4 5.9

35 °C 27.5 °C Power Input (kW) 12.56 24.25 30.12 35.98 37.1 1) Energy efficiency is based on the following conditions :
※ Model : LG AK-Q300DC01 - Indoor Temp. 21.1°C (70°F) DB / 15.6°C (60°F) WB
- Outdoor Temp. 8.3°C (47°F) DB / 6.1°C (43°F) WB
2) Specification : 25kW / 460V / 3Ø / 60Hz

ELECTRICITY COST SAVING


During low Demand Periods, customers can save electricity costs because LG Inverter Compressors can match the
actual capacity needed without overcooling the spece. NEW INVERTER

- No additional investment due to no need for heater installation for heating


CONVENTIONAL (CONSTANT SPEED COMPRESSOR) LG SINGLE PACKAGE (INVERTER COMPRESSOR)
- Annual energy savings with superior efficiency heat pump system
- Wasted electricity cost with constant speed compressors - Electricity cost saving with inverter compressors

10 10
3.38
Capacity (RT)

Capacity (RT)

8 8

6 Constant Speed Comp. 6 Inverter Comp.


Cooling Load
with 4 4

Typical Number
2 2
of Visitors
0 0
0 5 10 15 20 24 0 5 10 15 20 24

Cooling Load (With typical number of visitors) Cooling Load (With typical number of visitors)
Energy Consumption Wasted Energy Energy Consumption

10 10
Capacity (RT)

Capacity (RT)

Unit (Heat pump) Energy Efficiency1)


8 8 (W / W)
6 6
1) This result can be different depending on actual environment.
Cooling Load
4 4 (In regions with low load condition, the efficiency of H/P product is higher.)
with
Fewer Visitors 2 2

0 0
0 5 10 15 20 24 0 5 10 15 20 24

Cooling Load (With fewer visitors) Cooling Load (With fewer visitors)
Energy Consumption Wasted Energy Energy Consumption

8 9
SUPERIOR EFFICIENCY

ANNUAL ENERGY SAVINGS ESTIMATION PAYBACK ANNUAL ENERGY SAVINGS ESTIMATION PAYBACK
(KSA, RIYADH) (KSA, RIYADH) (KSA, DAMMAM) (KSA, DAMMAM)
Electricity consumption are expected to decline by 21% If you purchase the LG smart inverter, You can get back Electricity consumption are expected to decline by 21% If you purchase the LG smart inverter, You can get back
compared to on/off model. your investment cost after 1 year 10 months. compared to on/off model. your investment cost after 1 year 10 months.

Electricity Consumption Electricity Cost 13,092 $ (18%) Electricity Consumption Electricity Cost 13,148 $ (18%)
Currency (USD) Cost saving after 10 years Currency (USD) Cost saving after 10 years
96,356 80,000 97,135 80,000
On/Off Inverter 72,444 $ On/Off Inverter 72,822 $
kWh/year kWh/year
70,000 70,000
76,086 76,751
kWh/year 4,625 60,000 kWh/year 4,662 60,000
USD/year 3,652 1 Year 10 Months USD/year 3,684 1 Year 10 Months
50,000 50,000
USD/year 59,352 $ USD/year 59,674 $
40,000 40,000
21% 30,000
21% 30,000
Decrease Decrease
21% 20,000 21% 20,000
Decrease 10,000 Decrease 10,000

0 0
0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10
On/Off Inverter On/Off Inverter Years On/Off Inverter On/Off Inverter Years

▶ Electric charges : 0.048 USD/kWh ▶ Electric charges : 0.048 USD/kWh


(It may vary by region) (It may vary by region)

[Condition] [Condition]
- Capacity : 20RT Single Package - Capacity : 20RT Single Package
- Operation time : 24 hours - Operation time : 24 hours
- Cooling partial load and power consumption calculated based on yearly weather data (target indoor temperature : 24°C) - Cooling partial load and power consumption calculated based on yearly weather data (target indoor temperature : 24°C)
* This result can be different depending on actual environment * This result can be different depending on actual environment

ANNUAL ENERGY SAVINGS ESTIMATION PAYBACK


(KSA, JEDDAH) (KSA, JEDDAH)
Electricity consumption are expected to decline by 20% If you purchase the LG smart inverter, You can get back
compared to on/off model. your investment cost after 1 year 9 months.

Electricity Consumption Electricity Cost 14,075 $ (18%)


Currency (USD) Cost saving after 10 years
110,122 90,000
kWh/year On/Off Inverter 79,112 $
80,000
87,825
kWh/year 5,286 70,000
1 Year 9 Months
USD/year 4,216 60,000
USD/year 65,037 $
50,000
40,000
20%
Decrease 30,000
20% 20,000
Decrease 10,000
0
0 1 2 3 4 5 6 7 8 9 10
On/Off Inverter On/Off Inverter Years

▶ Electric charges : 0.048 USD/kWh


(It may vary by region)

[Condition]
- Capacity : 20RT Single Package
- Operation time : 24 hours
- Cooling partial load and power consumption calculated based on yearly weather data (target indoor temperature : 24°C)
* This result can be different depending on actual environment

10 11
SUPERIOR EFFICIENCY

APPLICATION – LG INVERTER PAYBACK APP DUAL SENSING CONTROL


You can easily simulate on mobile via payback app. (Install “LG SCAC / RAC Inverter Payback”)
Cooling load according to temperature change Cooling load according to humidity change

Latent heat load Sensible heat load Latent heat load Sensible heat load

Cooling Load Cooling Load Dual


Single sensing
Dual
sensing operation
sensing
operation operation
Dual
Sensing
Control

27°C 35°C 46°C 35°C (30%) 35°C (50%) 35°C (70%)


Temperature Temperature
(Humidity)
Dry condition
Dual sensing Control is a function that changes evaporation temperature according to temperature & humidity.

CONVETNTIONAL NEW INVERTER

- Excessive latent heat elimination regardless of humidity - Comfortable environment by making the room less dry
- Waste Energy to eliminate latent heat - Increased Seasonal Efficiency

DUAL SENSING CONTROL Dry


Summer
35°C 40% 2)
Dry
Summer
35°C 40% 2)
Comfort Comfort
New model can be operated by dual sensors for comfort and efficient operation. (Temperature & Humidity) 30% 70% 30% 70%
Te1) Te1) + α
Refrigerants Refrigerants
Why do we need dual sensing? Low High Low High

To provide a comfortable cooling and increase energy savings sensing both


1) Te : Evaporation Temperature 2) Temperature & humidity of outdoor
temperature and humidity is required.

Wet condition
In wet summer season, the system senses the high humidity level and increases operating ratio to decrease humidity level rapidly for
making room condition in comfort zone.

CONVETNTIONAL NEW INVERTER


Humidity Sensor
- High humidity condition is not considered by only sensing - Comfortable environment
the room temperature - With quick latent heat elimination by sensing humidity
- General latent heat elimination regardless of humidity - At higher humidity, the compressor runs more powerfully

Wet Wet
35°C 85% 2) 35°C 85% 2)
Summer Summer

Temp.(°C)

Temp.(°C)
Te1) Te1) - α
Refrigerants Refrigerants
Target Target

Time Time

1) Te : Evaporation Temperature 2) Temperature & humidity of outdoor

12 13
CONVENIENCE DIRECT DRIVE FAN MOTOR
Easy maintenance
Beltless direct drive system is easy to maintain and cost effective.

CONVENTIONAL NEW INVERTER


Direct Drive Fan Motor
- Motor alignment, pulley and belt adjustment are required - No need to adjust pulley and belt periodically
Enhanced Structure - Grease periodically - No need to grease periodically
Sliding Type Filter - High cost of replacement and repair with large number of parts - Low cost of replacement and repair with fewer parts

Pulley V belt Pulley

No additional parts
Additional parts
(Reduced parts and labor costs)

Easy installation
By applying a high static pressure motor, It has wide E.S.P coverage and easy to set the air volume.

CONVENTIONAL NEW INVERTER

- It is necessary to change the pulley and motor to change airflow - Set RPM by simple touch on remote control to change airflow

Simple setup

High 140

※ ESP setting is available through wired remote controller.


- Standard Ⅱ (PREMTB100/10)
Pulley change Turn adjust Motor change
- Standard Ⅲ (PREMTB001/01)
(Variable pulley)
- Simple controller (PQRCUC2W)

※ Motor operation range (Based on 9,400 CFM) ※ Motor operation range (Based on 9,200 CFM)

Standard Medium High High

0.1 0.4 0.5 1.0 1.1 1.4 0 in.Aq Largest 10HP BLDC Motor 2.0 in.Aq
in.Aq in.Aq in.Aq in.Aq in.Aq in.Aq

14 15
CONVENIENCE

SLIDING TYPE FILTER ENHANCED STRUCTURE


Easy maintenance and extended product life with sliding type filter. The pre-filter is easy to clean with water and 3 Way fork lift holes easy to carry the product in various places and pop nut structure increases screw wear reliability.
replaceable 2 inch filter can also be installed.

3 Way Fork Lift Holes Pop Nut with Improved Wear

Easy Sliding Sliding Easy Cleaning


Filter Rack with Water

Filter Rack

Replaceable
2 inch Filter1)

1) Specification : 25 x 20 (in.) x 6 (EA)


※ When 2 inch filter is applied, Static pressure drops by 0.142 in.Aq.

16 17
RELIABILITY ULTIMATE INVERTER COMPRESSOR
By applying world class technology of Multi V, superior efficient and reliable operation has been achieved.
18 years of inverter technology applied to LG new single package.

CONVENTIONAL NEW COMPRESSOR


Ultimate Inverter Compressor
- Inner bearing type - Increased durability and reliability with outer bearing type
Protection for Voltage Fluctuation - Low speed operation with unstable structure - Superior speed operation with reduction of bearing load and
vibration
Black Fin

1
3 3
3 3
2
2

EXTREME 6.8 HP 9.6 HP

DURABILITY 1 1 Material : PTFE1) 1 1 Material : PEEK2)


1 2 Structure : Inner Bearing 1 2 Structure : Outer Bearing
2 2
3 Supporter 3 Supporter

1) PTFE : Polytetra fluoro ethylene


2) PEEK : Polyether ether ketone
※ Conventional : JBA068MAC (6.8 HP) x 2EA in product
New inverter : JBA096MAC (9.6 HP) x 2EA in product

PROTECTION FOR VOLTAGE FLUCTUATION


Below low voltage limit, inverter compressor reduces frequency (Hz) and boost DC voltage, over high voltage limit,
cuts off the relay to prevent damage of DC capacitor. And inverter is able to operate at a wider voltage range than
constant speed model.
Constant LG Inverter
No loss of capacity
Low & High Automatic detection
No protection logic
Voltage detection and blocking
Operable Range
CT (Current transformer) Inverter Control
On/Off operation
current limit without stopping

Automatic detection
DC peak detection No need
and blocking Continuous
Operation Range
N phase reverse wiring
No detection Automatic detection
(3 phase only)

Missing phase detection


No detection Automatic detection
(3 phase only)
391 414 460 506 529
(-15%) (-10%) (Rated) (+10%) (+15%)
Voltage
Product ※ The allowable operation range is ±10% of rated voltage (460V).
Protection ※ This result can be different depending on actual environment.

18 19
RELIABILITY

BLACK FIN
The black coating with enhanced complex resin is applied for strong protection from various corrosive external Black Fin‘s performance of corrosion resistance is improved based on Conventional Fin.
conditions such as salt contamination and air pollution including fumes from factories. This improvement in durability
prolongs the product’s lifespan and lowers both the operational and maintenance costs.

Longer Lifespan, Lower Maintenance Costs SST (Salt Spray Test)


Test Process Test Result (0.05% Area of defects compared to initial)

1,000%
10,000
hours

Hydrophilic Film (Water Flow) Fog1)


(35°C, 24hr)
The Hydrophilic coating minimizes moisture buildup on the fin. 1,000
hours
Corrosion Resistant Layer Process
The Black coating provides strong protection from corrosion. Repeated Conventional Fin Black Fin
LG Wide Louver Plus Fin

Test process is conducted according to ISO 9227.


1) Salty water concentration : NaCl aqueous solution (5%)

100% copper material


to prevent corrosion &
refrigerant leakage

CCT (Cyclic Corrosion Test)


Test Process Test Result (0.05% Area of defects compared to initial)

600%
3,000
Fog1) Dry Wet2) hours
(35°C, 2hr) (70°C, 2hr) (50°C, 2hr)

500
Process hours
Repeated Conventional Fin Black Fin

Test process is conducted according to ISO 14933.


1) Salty water concentration : NaCl aqueous solution (5%)
※ Verification of corrosion resistance performance. 2) Deionized water
※ Black Fin is applied for Cooling & Heating model only. ※ Dry condition changed : 60°C, 4hr → 70°C, 2hr
100% copper material
to prevent corrosion &
refrigerant leakage

20 21
CUSTOMIZED CONTROL

NEW DESIGN REMOTE CONTROLLER DESIGN 3rd PARTY BMS SYSTEM COMPATIBILITY
LG Individual Controller provides intuitive GUI with color LCD and touch type interface button. LG Inverter Single Package can be connected with gateway products for different protocols such as Modbus, BACnet
and LonWorks. And gateway product offers self diagnosis interface thanks to smart GUI included.
Standard III LG HAVC System LG BMS Gateway BMS System
Controller Individual

4.3” Color Display & Touch Button Yearly Schedule

ACP 5
Multi V ACP Lonworks
LG Protocol BMS Protocol

Single / Multi
AC Smart 5

ERV

5” Touch screen Touch Push


Button Button
Single Package
Self Diagnosis
Premium Standard III Standard II
1) ACP 5 (BACnet IP/Modbus TCP) : PACP5A000
(PREMTA000) (PREMTB100) (PREMTB001)
ACP LonWorks (Modbus) Interface : PLNWKB000

※ Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

GROUP CONTROL ECONOMIZER (MODEL : PKEMD1CA0)


Group Control allows the user to control the operation of multiple units at once. This is the appropriate solution to Provides outside air to a room to save energy and improve the air quality indoors.
control a big area as a one zone.
FUNCTION SPECIFICATIONS
Appealing Design
Max. 16 unit
- Differential Enthalpy Control - Economizer Size : 1,149 x 743 x 597
Connections available
- Includes Outdoor Air Rain Hood - Filter Efficiency : MERV6
- Washable 1” Stainless Filter - Filter Size : 925 x 508 x 25
- Motorized 2-Position and Manual Operation Available - Damper Opening Size : 930 x 510
-D  amper Operation with Wired Remote Controller
- AMCA Certified Low Leak Air Damper
- Easy maintenance

Conventional New

Controller & Installation Cost Saving

Save

22 23
CUSTOMIZED CONTROL

LOW NOISE OPERATION EASY SCHEDULING


The Low-Noise Operation is possible regardless of the time where noise sensitive areas. Instead of installer setting, Schedule function allows customers to arrange the operation setting of equipment according to their desired
the low noise operation is set by a building manager easily. schedule. Customers easily schedule daily, weekly, monthly, yearly plan with a calendar, also an exception date
enables patterned schedule.
Conventional ACP / AC Smart ACP EZ Touch
Outdoor Unit setting only

Load Only outdoor unit dip switch


setting is possible.

Premium R/C Standard III R/C


Sound level Off (Basic time) Low-noise operation time

On
09:00 13:00 18:00 21:00 0:00 09:00
Highest Start End
outdoor temp.

New Inverter
Standard III wired Remote Controller setting possible
2 SET POINT CONTROL
Auto Changeover can manage room temperature with changing Heating / Cooling mode and Compressor-off
automatically. With setting heating and cooling set temperature just one time, comfortable condition will continue at
all times. It is also possible to reduce the energy use by broadening the set temperature gap of cooling and heating.

Indoor temperature (°C)

Load Can be easily activated in the Cooling Set


Cooling Mode (Comp. Off) (18 ~ 30°C)
remote controller. +0.5°C
Scheduled setting available
Sound level
-0.5°C

Low-noise operation
Fan Mode (Comp. Off) * Dead Band
On
Off
+0.5°C
09:00 13:00 18:00 09:00
Start End -0.5°C Heating Set
※ Low-Noise Operation requires Standard III wired Remote Controller. (18 ~ 30°C)
Heating Mode (Comp. On)

Summer Autumn Winter Spring


※ 2 Set point Control requires Standard III or Premium wired remote Controller.
- Model : PREMTB100 (Standard III), PREMTA000 / PREMTA000A / PREMTA000B (Premium)
* Minimum temperature gap : Setting value (0 ~ 5°C)

24 25
SPECIFICATION

COOLING ONLY COOLING ONLY

1 Phase 220 ~ 240V 50Hz 3 Phase, 400V 60Hz


1 Phase 220V 60Hz

Category 3 4 5 Category 7.5 10

Model Name - AK-C03620 AK-C04820 AK-C06020 Model Name - AK-Q0909C01 AK-Q1209C02

kW kW
10.26 13.50 17.25 26.4 36.6
(Rated) (Rated)
Net Capacity Net Capacity
Btu/h Btu/h
35,000 46,500 59,200 90,000 125,000
(Rated) (Rated)
Cooling Capacity Cooling Capacity
kW kW
10.55 14.07 17.58 27.5 38.4
(Rated) (Rated)
Gross Capacity Gross Capacity
Btu/h Btu/h
36,000 48,000 60,000 94,000 131,000
(Rated) (Rated)

Power Input Cooling kW 2.69 3.86 5.10 Power Input Cooling kW 7.50 10.60
EER Btu/Wh 13.00 12.05 11.60 EER Btu/Wh 12.0 11.8
SEER Btu/Wh 18.0 17.0 17.0 SEER Btu/Wh
Power Supply V, Ø, Hz 230, 1, 60 230, 1, 60 230, 1, 60 Power Supply V, Ø, Hz 400, 3, 60 400, 3, 60
Running Current Cooling Rated A 11.7 16.9 22.5 Running Current Cooling Rated A 11.8 16.3
Wiring Connections Power Supply Cable (Included Earth) No. x mm 2 3C × 4.0 3C × 4.0 3C × 4.0 Wiring Connections Power Supply Cable (Included Earth) No. x mm 2 4C × 8.4 4C × 8.4
WxHxD mm 1,280 × 1,065 × 1,110 1,280 × 1,065 × 1,110 1,280 × 1,065 × 1,110 WxHxD mm 2,250 × 1,106 × 1,130 2,230 × 1,237 × 1,958
Dimensions 50-13/32 × 41-29/32 50-13/32 × 41-29/32 50-13/32 × 41-29/32 Dimensions
WxHxD inch WxHxD inch 88-19/32 × 43-17/32 × 44-1/2 87-25/32 × 48-11/16 × 77-3/32
× 43-23/32 × 43-23/32 × 43-23/32

Net Weight kg (lbs) 174 (384) 174 (384) 174 (384) Net Weight kg (lbs) 343 (756) 530 (1,168)

Compressor Type - Twin Rotary Twin Rotary Twin Rotary Compressor Type - HSS DC SCROLL HSS DC SCROLL
(#1, A Cycle) Motor Output W x No. 4,000 x 1 4,000 x 1 4,000 x 1 (#1, A Cycle) Motor Output W x No. 5,300 × 1 5,300 × 1

Compressor Type - Compressor Type -


(#2, B Cycle) Motor Output W x No. (#2, B Cycle) Motor Output W x No.
Type - R410A R410A R410A Type - R410A R410A
Precharged Amount (A-circuit) g 3,600 3,600 3,600 Precharged Amount (A-circuit) g 6900.0 13000.0
Refrigerant Refrigerant
Precharged Amount (B-circuit) Precharged Amount (B-circuit)
Control - EEV EEV EEV Control - EEV EEV
Type - FVC68D FVC68D FVC68D Type - FVC68D FVC68D
Refrigerant Oil Refrigerant Oil
Charged Volume cc x No. 1,300 x 1 1,300 x 1 1,300 x 1 Charged Volume cc x No. 1,200 × 1 1,200 × 1
Type - Centrifugal Blower Fan Centrifugal Blower Fan Centrifugal Blower Fan Type - Sirocco Fan Sirocco Fan
Diameter mm (inch) Direct Direct Direct Diameter mm (inch) Belt Belt
Indoor Side Fan Indoor Side Fan
Nominal m3 /min 34.0 45.3 49.8 Nominal m3 /min 85.0 113.3
Air Flow Rate Air Flow Rate
Nominal ft 3 /min 1,200 1,600 1,760 Nominal ft 3 /min 3,000 4,000
Dehumidification Rate ℓ/h 2.23 3.47 5.58 Dehumidification Rate ℓ/h 9.9 13.8

Outdoor Side Gold fin / Gold fin / Gold fin / Outdoor Side Gold fin / Gold fin /
Fin Type - Fin Type -
Heat Exchanger Wide Louver plus Wide Louver plus Wide Louver plus Heat Exchanger Wide Louver plus Wide Louver plus

Fan Type - Propeller Propeller Propeller Fan Type - Propeller Propeller


Outdoor Side Fan Outdoor Side Fan
Motor Type - BLDC BLDC BLDC Motor Type - BLDC BLDC
Sound Pressure Level Cooling Rated dB(A) 75 75 75 Sound Pressure Level Cooling Rated dB(A) 70 75
Drain Connection Size - NPT 3/4 NPT 3/4 NPT 3/4 Drain Connection Size - Male PT 3/4" Female NPT 1"

Operation Range Operation Range


Cooling Min. ~ Max. °C DB (°F DB) -5 (23.0) ~ 54 (129.2) -5 (23.0) ~ 54 (129.2) -5 (23.0) ~ 54 (129.2) Cooling Min. ~ Max. °C DB (°F DB) -5 ~ 54 (23.0~129.2) -5 ~ 54 (23.0~129.2)
(Outdoor Temperature) (Outdoor Temperature)

26 27
SPECIFICATION

COOLING ONLY COOLING ONLY

3 Phase, 400V 60Hz 3 Phase, 400V 60Hz

Category 12.5 15 Category 20 25

Model Name - AK-Q1509C02 AK-Q1809C02 Model Name - AK-Q2409C01 AK-Q3009C01

kW kW
40 52.5 70.6 80.9
(Rated) (Rated)
Net Capacity Net Capacity
Btu/h Btu/h
136,000 180,000 241,000 276,000
(Rated) (Rated)
Cooling Capacity Cooling Capacity
kW kW
41.5 54.2 73.6 85
(Rated) (Rated)
Gross Capacity Gross Capacity
Btu/h Btu/h
141,800 185,100 251,100 290,000
(Rated) (Rated)

Power Input Cooling kW 11.70 15.50 Power Input Cooling kW 21.50 26.20
EER Btu/Wh 11.6 11.6 EER Btu/Wh 11.2 10.5
SEER Btu/Wh SEER Btu/Wh
Power Supply V, Ø, Hz 400, 3, 60 400, 3, 60 Power Supply V, Ø, Hz 400, 3, 60 400, 3, 60
Running Current Cooling Rated A 18.1 24.0 Running Current Cooling Rated A 34.0 42.0
Wiring Connections Power Supply Cable (Included Earth) No. x mm 2 4C × 8.4 4C × 8.4 Wiring Connections Power Supply Cable (Included Earth) No. x mm 2 4C × 13.3 4C × 13.3
WxHxD mm 2,230 × 1,237 × 1,958 2,230 × 1,242 × 3,520 WxHxD mm 2,230 × 1,242 × 3,520 2,230 × 1,242 × 3,520
Dimensions Dimensions
WxHxD inch 87-25/32 × 48-11/16 × 77-3/32 87-25/32 × 48-29/32 × 138-19/32 WxHxD inch 87-25/32×48-29/32×138-19/32 87-25/32×48-29/32×138-19/32

Net Weight kg (lbs) 530 (1,168) 885 (1,951) Net Weight kg (lbs) 950 (2,094) 950 (2,094)

Compressor Type - HSS DC SCROLL HSS DC SCROLL Compressor Type - HSS DC SCROLL HSS DC SCROLL
(#1, A Cycle) Motor Output W x No. 5,300 × 1 4,200 × 1 (#1, A Cycle) Motor Output W x No. 5,300 × 1 5,300 × 1

Compressor Type - HSS DC SCROLL Compressor Type - HSS DC SCROLL HSS DC SCROLL
(#2, B Cycle) Motor Output W x No. 4,200 × 1 (#2, B Cycle) Motor Output W x No. 5,300 × 1 5,300 × 1
Type - R410A R410A Type - R410A R410A
Precharged Amount (A-circuit) g 13000.0 9000.0 Precharged Amount (A-circuit) g 12000.0 12000.0
Refrigerant Refrigerant
Precharged Amount (B-circuit) 9000.0 Precharged Amount (B-circuit) 12000.0 12000.0
Control - EEV EEV Control - EEV EEV
Type - FVC68D FVC68D Type - FVC68D FVC68D
Refrigerant Oil Refrigerant Oil
Charged Volume cc x No. 1,200 × 1 1,200 × 1 Charged Volume cc x No. 1,400 × 1 1,400 × 1
Type - Sirocco Fan Sirocco Fan Type - Sirocco Fan Sirocco Fan
Diameter mm (inch) Belt Belt Diameter mm (inch) Belt Belt
Indoor Side Fan Indoor Side Fan
Nominal m3 /min 141.6 169.9 Nominal m3 /min 226.5 283.2
Air Flow Rate Air Flow Rate
Nominal ft 3 /min 5,000 6,000 Nominal ft 3 /min 8,000 10,000
Dehumidification Rate ℓ/h 15.6 20.7 Dehumidification Rate ℓ/h 26.18 29.82

Outdoor Side Gold fin / Gold fin / Outdoor Side Gold fin / Gold fin /
Fin Type - Fin Type -
Heat Exchanger Wide Louver plus Wide Louver plus Heat Exchanger Wide Louver plus Wide Louver plus

Fan Type - Propeller Propeller Fan Type - Propeller Propeller


Outdoor Side Fan Outdoor Side Fan
Motor Type - BLDC BLDC Motor Type - BLDC BLDC
Sound Pressure Level Cooling Rated dB(A) 75 85 Sound Pressure Level Cooling Rated dB(A) 85 85
Drain Connection Size - Female NPT 1" Female NPT 1" Drain Connection Size - Female NPT 1" Female NPT 1"

Operation Range Operation Range


Cooling Min. ~ Max. °C DB (°F DB) -5 ~ 54 (23.0~129.2) -5 ~ 54 (23.0~129.2) Cooling Min. ~ Max. °C DB (°F DB) -5 ~ 54 (23.0~129.2) -5 ~ 54 (23.0~129.2)
(Outdoor Temperature) (Outdoor Temperature)

28 29
SPECIFICATION

COOLING & HEATING COOLING & HEATING

3 Phase, 380 ~ 415V, 50/60Hz 3 Phase, 380 ~ 415V, 50/60Hz

Nominal Capacity (Rated/Max) RT 7.5/10 10/11 15/18 Nominal Capacity (Rated/Max) RT 20/26 23/29

Model Name - AK-W110LH00 AK-W130LH00 AK-W200LH00 Model Name - AK-W270LH00 AK-W320LH00

kW kW
26.4 / 34.6 34.3 / 38.1 51.0 / 64.5 70.0 / 90.3 81.0 / 101.1
(Rated/Max) (Rated/Max)
Net Capacity Net Capacity
Btu/h Btu/h
90,000 / 118,000 117,000 / 130,000 174,000 / 220,000 240,000 / 308,000 276,000 / 345,000
(Rated/Max) (Rated/Max)
Cooling Capacity Cooling Capacity
kW kW
27.0 / 35.2 35.2 / 39.0 52.6 / 66.1 72.3 / 92.3 83.6 / 103.8
(Rated/Max) (Rated/Max)
Gross Capacity Gross Capacity
Btu/h Btu/h
91,960 / 119,960 120,000 / 133,000 179,500 / 225,500 246,900 / 314,900 285,200 / 354,200
(Rated/Max) (Rated/Max)

Power Input Cooling kW 7.37 / 15.0 10.08 / 15.5 15.26 / 30.00 Power Input Cooling kW 21.3 / 32.1 26.0 / 39.2
EER Btu/Wh 12.2 11.6 11.4 EER Btu/Wh 11.3 10.6
SEER Btu/Wh 20 19 18.5 SEER Btu/Wh 19.0 18.3
Power Supply V, Ø, Hz 380~415, 3, 50/60 380~415, 3, 50/60 380~415, 3, 50/60 Power Supply V, Ø, Hz 380~415, 3, 50/60 380~415, 3, 50/60
Running Current Cooling Rated A 11.8 15.9 23.4 Running Current Cooling Rated A 33.0 40.0
Wiring Connections Power Supply Cable (Included Earth) No. x mm 2 4C × 13.3 4C × 13.3 4C × 21.2 Wiring Connections Power Supply Cable (Included Earth) No. x mm 2 4C × 33.6 4C × 33.6
WxHxD mm 1,130 × 1,242 × 2,250 1,130 × 1,242 × 2,250 2,230 × 1,242 × 2,400 WxHxD mm 2,230 × 1,242 × 3,520 2,230 × 1,242 × 3,520
Dimensions 44-1/2 × 48-29/32 44-1/2 × 48-29/32 87-25/32 × 48-29/32 Dimensions
WxHxD inch WxHxD inch 87-25/32 × 48-29/32 × 138-19/32 87-25/32 × 48-29/32 × 138-19/32
× 88-19/32 × 88-19/32 × 94-1/2

Net Weight kg (lbs) 440 (970) 440 (970) 705 (1,554) Net Weight kg (lbs) 915 (2,017) 915 (2,017)

Compressor Type - HSS DC SCROLL HSS DC SCROLL HSS DC SCROLL Compressor Type - HSS DC SCROLL HSS DC SCROLL
(#1, A Cycle) Motor Output W x No. 5,500 x 1 5,500 x 1 5,300 x 1 (#1, A Cycle) Motor Output W x No. 5,500 × 1 5,500 × 1

Compressor Type - HSS DC SCROLL Compressor Type - HSS DC SCROLL HSS DC SCROLL
(#2, B Cycle) Motor Output W x No. 5,300 x 1 (#2, B Cycle) Motor Output W x No. 5,500 × 1 5,500 × 1
Type - R410A R410A R410A Type - R410A R410A
Precharged Amount (A-circuit) g 9000 9000 5200.0 Precharged Amount (A-circuit) g 9000.0 9000.0
Refrigerant Refrigerant
Precharged Amount (B-circuit) 5200.0 Precharged Amount (B-circuit) 9000.0 9000.0
Control - EEV EEV EEV Control - EEV EEV
Type - FW68D FW68D FW68D Type - FW68D FW68D
Refrigerant Oil Refrigerant Oil
Charged Volume cc x No. 1,500 x 1 1,500 x 1 1,200 x 1 Charged Volume cc x No. 1,500 × 1 1,500 × 1
Type - Plug Fan Plug Fan Plug Fan Type - Plug Fan Plug Fan
Diameter mm (inch) Direct Direct Direct Diameter mm (inch) Direct Direct
Indoor Side Fan Indoor Side Fan
Nominal m3 /min 85 113 170 Nominal m3 /min 227 261
Air Flow Rate Air Flow Rate
Nominal ft 3 /min 3,000 4,000 6,000 Nominal ft 3 /min 8,000 9,200
Dehumidification Rate ℓ/h 9.1 12.1 18.1 Dehumidification Rate ℓ/h 24.1 30.1

Outdoor Side Black fin / Black fin / Black fin / Outdoor Side Black fin / Black fin /
Fin Type - Fin Type -
Heat Exchanger Wide Louver plus Wide Louver plus Wide Louver plus Heat Exchanger Wide Louver plus Wide Louver plus

Fan Type - Propeller Propeller Propeller Fan Type - Propeller Propeller


Outdoor Side Fan Outdoor Side Fan
Motor Type - BLDC BLDC BLDC Motor Type - BLDC BLDC
Sound Pressure Level Cooling Rated dB(A) 80 80 80 Sound Pressure Level Cooling Rated dB(A) 77 77
Drain Connection Size - Male NPT 3/4" Male NPT 3/4" Male NPT 1" Drain Connection Size - Male NPT 1" Male NPT 1"

Operation Range Operation Range


Cooling Min. ~ Max. °C DB (°F DB) -5 ~ 54 (23.0~129.2) -5 ~ 54 (23.0~129.2) -5 ~ 54 (23.0~129.2) Cooling Min. ~ Max. °C DB (°F DB) -5 ~ 54 (23.0 ~ 129.2) -5 ~ 54 (23.0 ~ 129.2)
(Outdoor Temperature) (Outdoor Temperature)

* In case of Heatpump model, AHRI certification program is limited up to 20RT model. so, LG will provide LG laboratory test report of 25RT model. * In case of Heatpump model, AHRI certification program is limited up to 20RT model. so, LG will provide LG laboratory test report of 25RT model.

30 31
ADDITIONAL LINE UP

COOLING ONLY

3 Phase, 380 ~ 415V, 60Hz

Norminal Capacity RT 30

Model Name - AK-C3609H00


Cooling Capacity @ T1* Btu/h 350,000
Power Consumption @ T1* W 34,400
EER @ T1* - 10.15
Cooling Capacity @ T3** Btu/h 294,000
Power Consumption @ T3** W 38,800
EER @ T3** Btu/Wh 7.55
Nominal Air Flow CFM 12,000
External Static Pressure Inch H 2 O g 0.5*
Power Supply V / Ph / Hz 380-400 / 3 / 60
Type - R410A
The Largest Capacity Single Package
Precharged Amount kg 32.0
Refrigerant
Standard Circuit NOS 2
Control - TXV
Type - Centrifugal

STANDARD FEATURES Blower


Drive - Belt Drive
Dia x Width Inch 18” x 18” - Twin
• Refrigerant : R410A. Quantity - 1
Power Supply V / Ph / Hz 380-400 / 3 / 60
• Power Supply : 380-415V / 3PH / 60Hz. Type - Induction
• Factory Wired with Single Point Power Input. Evaporator Blower Motor Quantity - 1
HP - 10
• Constant Scroll Compressor. IP - IP55
• High Pressure & Low Pressure Safety Switches. Air Filter Type - Disposable Air Filter
Type - Corrugated Al Fin with Inner grooved copper coil
• Power Controller, High / Low Voltage, Phase Loss / Reversal Protection. Coil Tube Dia / No of row / FPI - 3/8” / 4 / 15
• All units are provided with ON-Delay timers for Anti-short cycling. Face Area SQ.FT 17.22
Type - Propeller / Direct Driven
• Internal Motor Protection for 3Ø Indoor & Outdoor motors. Fan Quantity - 6

• All Units are designed to operate with 24V Universal Thermostat. Dia of Fan Inch 26”
Type - Corrugated Al Fin with Inner grooved copper coil
• Thermal Expansion Valve Tube Dia / No of row / FPI - 3/8” / 3 / 15 3/8” / 4 / 15

• Condenser Fans are Propeller type Direct Driven, draw through Vertical Discharge with fan guard mounted to Coil Number of Coils - 4
Condenser Face Area / Coil SQ.FT 23.24
the Panel. Total Face Area SQ.FT 46.48

• Condenser & Evaporator Coils made of Copper tubes and Aluminum fins. Power Supply V / Ph / Hz 208-230 / 1 / 60
HP - 0.75
• Weather resistant steel cabinet, qualified for 1,000 Hours of Salt Spray test. Fan Motor IP - IP20

• 2’’ Disposable Air Filter. Motor RPM - 1,130


Motor Type - ECM
• Anti Corrosion Heresite Treatment on condenser coil HEX Condensate Drain Size Inch 1”

• Hydrophilic coating on Evaporator HEX Length mm 3,945


Dimensions Width mm 2,150
• IP 55 Class F for Blower Motor Height mm 2,075
Unit Weight kg 2,020

32 33