SIMOTION D410-2 Manual
SIMOTION D410-2 Manual
Safety instructions 1
Description 2
SIMOTION
Operator control (hardware) 3
SIMOTION D410-2 4
Interfaces
Technical data 5
Manual
Dimension drawings 6
ESD guidelines B
Valid for
SIMOTION D410-2 DP and D410-2 DP/PN
as of version 5.2
03/2018
A5E33446720B
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified
personnel are those who, based on their training and experience, are capable of identifying risks and avoiding
potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in
this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
Scope
The SIMOTION D410-2 Manual describes the SIMOTION D410‑2 DP and
SIMOTION D410‑2 DP/PN control units.
Note
A separate SIMOTION D410 Manual is available for the SIMOTION D410 DP and SIMOTION
D410 PN control units.
Standards
The SIMOTION system was developed in accordance with ISO 9001 quality guidelines.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 3
Preface
SIMOTION Documentation
An overview of the SIMOTION documentation can be found in the SIMOTION Documentation
Overview document.
This documentation is included as electronic documentation in the scope of delivery of
SIMOTION SCOUT. It comprises ten documentation packages.
The following documentation packages are available for SIMOTION product version V5.2:
● SIMOTION Engineering System Handling
● SIMOTION System and Function Descriptions
● SIMOTION Service and Diagnostics
● SIMOTION IT
● SIMOTION Programming
● SIMOTION Programming - References
● SIMOTION C
● SIMOTION P
● SIMOTION D
● SIMOTION Supplementary Documentation
SIMOTION at a glance
We have compiled an overview page from our range of information about SIMOTION with the
most important information on frequently asked topics - which can be opened with only one
click.
Whether beginner or experienced SIMOTION user – the most important downloads, manuals,
tutorials, FAQs, application examples, etc. can be found at
https://support.industry.siemens.com/cs/ww/en/view/109480700
Additional information
Click the following link to find information on the following topics:
● Documentation overview
● Additional links to download documents
● Using documentation online (find and search manuals/information)
https://support.industry.siemens.com/cs/ww/en/view/109479653
SIMOTION D410-2
4 Manual, 03/2018, A5E33446720B
Preface
My Documentation Manager
Click the following link for information on how to compile documentation individually on the
basis of Siemens content and how to adapt it for the purpose of your own machine
documentation:
https://support.industry.siemens.com/My/ww/en/documentation
Training
Click the following link for information on SITRAIN - Siemens training courses for automation
products, systems and solutions:
http://www.siemens.com/sitrain
FAQs
Frequently Asked Questions can be found in SIMOTION Utilities & Applications, which are
included in the scope of delivery of SIMOTION SCOUT, and in the Service&Support pages in
Product Support:
https://support.industry.siemens.com/cs/de/en/ps/14505/faq
Technical support
Country-specific telephone numbers for technical support are provided on the Internet under
Contact:
https://support.industry.siemens.com/cs/ww/en/sc/2090
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 5
Preface
SIMOTION D410-2
6 Manual, 03/2018, A5E33446720B
Table of contents
Preface.........................................................................................................................................................3
1 Safety instructions......................................................................................................................................11
1.1 Fundamental safety instructions............................................................................................11
1.1.1 General safety instructions.....................................................................................................11
1.1.2 Safety instructions for electromagnetic fields (EMF)..............................................................14
1.1.3 Handling electrostatic sensitive devices (ESD)......................................................................14
1.1.4 Security information...............................................................................................................15
1.1.5 Danger to life due to software manipulation when using removable storage media..............15
1.1.6 Residual risks of power drive systems...................................................................................16
1.2 Specific safety information for SIMOTION D410-2................................................................17
2 Description..................................................................................................................................................19
2.1 System overview....................................................................................................................19
2.2 System components...............................................................................................................24
2.3 I/O integration.........................................................................................................................29
2.4 SIMOTION D410-2 DP representation...................................................................................30
2.5 SIMOTION D410-2 DP/PN drawing.......................................................................................32
2.6 Type plates.............................................................................................................................34
2.7 CompactFlash card................................................................................................................36
2.8 Data matrix code....................................................................................................................39
2.9 Licensing................................................................................................................................40
3 Operator control (hardware).......................................................................................................................41
3.1 Overview of operator control and display elements...............................................................41
3.2 Operator controls...................................................................................................................42
3.2.1 Service selector switch...........................................................................................................42
3.2.2 Mode selector switch..............................................................................................................43
3.2.3 DIAG button...........................................................................................................................45
3.2.4 RESET button........................................................................................................................46
3.2.5 Switch S5.0............................................................................................................................46
3.2.6 SIMOTION CompactFlash card.............................................................................................47
3.3 Error and status displays........................................................................................................48
4 Interfaces....................................................................................................................................................49
4.1 Overview of interfaces............................................................................................................49
4.2 DRIVE-CLiQ interface............................................................................................................50
4.3 PROFIBUS DP interfaces......................................................................................................53
4.4 PROFINET IO interface (SIMOTION D410-2 DP/PN only)....................................................55
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 7
Table of contents
SIMOTION D410-2
8 Manual, 03/2018, A5E33446720B
Table of contents
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 9
Table of contents
SIMOTION D410-2
10 Manual, 03/2018, A5E33446720B
Safety instructions 1
1.1 Fundamental safety instructions
DANGER
Danger to life due to live parts and other energy sources
Death or serious injury can result when live parts are touched.
● Only work on electrical devices when you are qualified for this job.
● Always observe the country-specific safety rules.
Generally, six steps apply when establishing safety:
1. Prepare for shutdown and notify all those who will be affected by the procedure.
2. Disconnect the machine from the supply.
– Switch off the machine.
– Wait until the discharge time specified on the warning labels has elapsed.
– Check that it really is in a no-voltage condition, from phase conductor to phase
conductor and phase conductor to protective conductor.
– Check whether the existing auxiliary supply circuits are de-energized.
– Ensure that the motors cannot move.
3. Identify all other dangerous energy sources, e.g. compressed air, hydraulic systems, or
water.
4. Isolate or neutralize all hazardous energy sources by closing switches, grounding or short-
circuiting or closing valves, for example.
5. Secure the energy sources against switching on again.
6. Ensure that the correct machine is completely interlocked.
After you have completed the work, restore the operational readiness in the inverse sequence.
WARNING
Danger to life from hazardous voltage when connecting an unsuitable power supply
Touching live components can result in death or severe injury.
● Only use power supplies that provide SELV (Safety Extra Low Voltage) or PELV
(Protective Extra Low Voltage) output voltages for all connections and terminals of the
electronics modules.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 11
Safety instructions
1.1 Fundamental safety instructions
WARNING
Danger to life from touching live parts on damaged devices
Improper handling of devices can result in damage.
For damaged devices, hazardous voltages can be present at the enclosure or at exposed
components; if touched, this can result in death or severe injury.
● Observe the limit values specified in the technical specifications during transport, storage,
and operation.
● Do not use damaged devices.
WARNING
Danger to life through electric shock due to unconnected cable shields
Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected
cable shields.
● As a minimum, connect cable shields and the cores of power cables that are not used
(e.g. brake cores) at one end at the grounded housing potential.
WARNING
Danger to life due to electric shock when not grounded
For missing or incorrectly implemented protective conductor connection for devices with
protection class I, high voltages can be present at open, exposed parts, which when touched,
can result in death or severe injury.
● Ground the device in compliance with the applicable regulations.
WARNING
Danger to life due to fire spreading if housing is inadequate
Fire and smoke development can cause severe personal injury or material damage.
● Install devices without a protective housing in a metal control cabinet (or protect the device
by another equivalent measure) in such a way that contact with fire inside and outside the
device is prevented.
● Ensure that smoke can only escape via controlled and monitored paths.
SIMOTION D410-2
12 Manual, 03/2018, A5E33446720B
Safety instructions
1.1 Fundamental safety instructions
WARNING
Danger to life from unexpected movement of machines when using mobile wireless devices
or mobile phones
Using mobile radios or mobile phones with a transmit power > 1 W closer than approx. 2 m
to the components may cause the devices to malfunction, influence the functional safety of
machines therefore putting people at risk or causing material damage.
● Switch off wireless devices or mobile phones in the immediate vicinity of the components.
WARNING
Danger to life due to fire if overheating occurs because of insufficient ventilation clearances
Inadequate ventilation clearances can cause overheating of components followed by fire and
smoke development. This can cause death or serious injury. This can also result in increased
downtime and reduced service life for devices/systems.
● Ensure compliance with the specified minimum clearance as ventilation clearance for the
respective component.
WARNING
Danger of an accident occurring due to missing or illegible warning labels
Missing or illegible warning labels can result in accidents involving death or serious injury.
● Check that the warning labels are complete based on the documentation.
● Attach any missing warning labels to the components, in the national language if
necessary.
● Replace illegible warning labels.
WARNING
Danger to life when safety functions are inactive
Safety functions that are inactive or that have not been adjusted accordingly can cause
operational faults on machines that could lead to serious injury or death.
● Observe the information in the appropriate product documentation before commissioning.
● Carry out a safety inspection for functions relevant to safety on the entire system, including
all safety-related components.
● Ensure that the safety functions used in your drives and automation tasks are adjusted
and activated through appropriate parameterizing.
● Perform a function test.
● Only put your plant into live operation once you have guaranteed that the functions relevant
to safety are running correctly.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 13
Safety instructions
1.1 Fundamental safety instructions
Note
Important safety notices for safety functions
If you want to use safety functions, you must observe the safety notices in the safety manuals.
WARNING
Danger to life from electromagnetic fields
Electromagnetic fields (EMF) are generated by the operation of electrical power equipment
such as transformers, converters or motors.
People with pacemakers or implants are at a special risk in the immediate vicinity of these
devices/systems.
● Ensure that the persons involved are the necessary distance away (minimum 2 m).
NOTICE
Damage through electric fields or electrostatic discharge
Electric fields or electrostatic discharge can cause malfunctions through damaged individual
components, integrated circuits, modules or devices.
● Only pack, store, transport and send electronic components, modules or devices in their
original packaging or in other suitable materials, e.g conductive foam rubber of aluminum
foil.
● Only touch components, modules and devices when you are grounded by one of the
following methods:
– Wearing an ESD wrist strap
– Wearing ESD shoes or ESD grounding straps in ESD areas with conductive flooring
● Only place electronic components, modules or devices on conductive surfaces (table with
ESD surface, conductive ESD foam, ESD packaging, ESD transport container).
SIMOTION D410-2
14 Manual, 03/2018, A5E33446720B
Safety instructions
1.1 Fundamental safety instructions
1.1.5 Danger to life due to software manipulation when using removable storage media
WARNING
Danger to life due to software manipulation when using removable storage media
The storage of files on removable storage media involves a high risk of infection, e.g. via
viruses or malware. Incorrect parameter assignment can cause machines to malfunction,
which can lead to injuries or death.
● Protect the files on removable storage media against harmful software through appropriate
protective measures, e.g. virus scanners.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 15
Safety instructions
1.1 Fundamental safety instructions
SIMOTION D410-2
16 Manual, 03/2018, A5E33446720B
Safety instructions
1.2 Specific safety information for SIMOTION D410-2
WARNING
Danger to life from hazardous voltage when connecting an unsuitable power supply
Only safety extra low voltage in accordance with EN/IEC 609501 may be connected at all
connectors and terminals.
WARNING
Danger to life from unexpected movement of machines on automatic restart
An automatic restart can be programmed for SIMOTION controllers. When the power returns,
the axes start automatically.
Make sure this presents no hazard to personnel or property.
NOTICE
Damage to the CompactFlash card from electrical fields or electrostatic discharge
The CompactFlash card is an ESD-sensitive component.
De-energize the SIMOTION D410‑2 device before inserting or removing the CompactFlash
card. The SIMOTION D410‑2 is in a de-energized state when all the LEDs are OFF.
Comply with the ESD rules.
NOTICE
Overheating if ventilation clearances are too small
Insufficient ventilation clearances result in overheating and therefore in more failures and a
shortened life of systems / devices.
Make sure the ventilation clearances of 50 mm are provided above and below the
components. The ventilation openings may not be covered by connecting cables.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 17
Safety instructions
1.2 Specific safety information for SIMOTION D410-2
SIMOTION D410-2
18 Manual, 03/2018, A5E33446720B
Description 2
2.1 System overview
SIMOTION D
SIMOTION D is a drive-based version of SIMOTION based on the SINAMICS S120 drive
family.
With SIMOTION D, the SIMOTION PLC and motion control functionalities as well as the
SINAMICS S120 drive software run on shared control hardware.
SIMOTION D is available in two versions:
● SIMOTION D410-2 is a compact Control Unit predestined for single-axis applications.
● SIMOTION D4x5-2 is a Control Unit for multi-axis applications in the SINAMICS S120
booksize format.
The following performance variants of the SIMOTION D4x5-2 Control Units are offered:
Note
The SIMOTION D410-2 is described in this manual.
Separate manuals are available for the SIMOTION D4x5-2 and the SIMOTION D4x5 and
SIMOTION D410 predecessor modules.
SIMOTION D is an integral part of the Totally Integrated Automation (TIA) concept. TIA is
characterized by integrated data management, configuration, and communication for all
products and systems. Thus, an extensive toolbox of automation modules is also available for
the SIMOTION D410-2.
Note
In order to cover all variants of SIMOTION D in blocksize format, the product will be referred
to as "D410-2". Specific product designations will be used for information that applies only to
one product version, e.g. D410-2 DP/PN.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 19
Description
2.1 System overview
SIMOTION D410-2
Figure 2-1 SIMOTION D410-2 DP (pictured on left), SIMOTION D410-2 DP/PN (pictured on right)
SIMOTION D410-2
20 Manual, 03/2018, A5E33446720B
Description
2.1 System overview
'5,9(&/L4
3RZHU
352),%86'3
'5,9(&/L4
3RZHU
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 21
Description
2.1 System overview
Note
Path interpolation is supported as of V4.4.
Application
Combining a Power Module with SIMOTION D410-2 forms a compact single drive for machine
and plant engineering.
Applications include:
● Machine concepts with central drive (e.g. presses, printing and packaging machines, etc.)
● Modular machine concepts where the machine modules were broken down into single axes
● Single drives with high accuracy, stability and concentricity requirements (compared with
standard drives) in machine and industrial plant engineering
● Single drives for transport tasks (conveying, raising, lowering)
● Single drives with integrated PLC functionality and expanded motion control functionality
such as output cams or cams
● Drives without power recovery (wire drawing, extruding)
● Drive connections with high availability requirements (incoming supply failure may not
cause all axes to fail)
● Small multi-axis groupings (typically 2 to 3 axes) based on SINAMICS S110/120 blocksize.
Hardware components
As central hardware the SIMOTION D410-2 Control Unit is made up of the SIMOTION runtime
system and the SINAMICS drive control.
A range of additional SINAMICS S120 components, such as SMx encoder systems or Terminal
Modules can be connected via DRIVE‑CLiQ.
With a few exceptions (e.g. no BOP20 Basic Operator Panel, etc.), the drive control integrated
in SIMOTION D410-2 has the same control properties and performance features as the
SINAMICS S120 CU310-2 Control Unit.
SIMOTION D410-2
22 Manual, 03/2018, A5E33446720B
Description
2.1 System overview
Software components
The basic functionality of SIMOTION D is supplied on a CompactFlash card containing the
following:
● The SIMOTION runtime system with the following functions:
– Freely programmable runtime system (IEC 61131)
– Various runtime levels (tasks)
– PLC and arithmetic functionality
– Motion control functions
– Communication functions
● The SINAMICS S120 drive control with the following functions:
– Closed-loop current and torque control
– Closed-loop speed control
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 23
Description
2.2 System components
Overview
SIMOTION D410-2 communicates with the components of the automation landscape via the
following interfaces:
● PROFIBUS DP (D410-2 DP and D410-2 DP/PN)
● PROFINET IO (D410-2 DP/PN only)
● Ethernet
● DRIVE-CLiQ (DRIVE Component Link with IQ)
● Power Module interface (PM-IF)
SIMOTION D features a SINAMICS Integrated drive element. Communication with the
SINAMICS Integrated is via PROFIBUS mechanisms (DP Integrated), via PROFIdrive
telegrams.
Shorter cycle times and greater numbers of addresses for each node are achieved with the
"DP Integrated" compared to the "external PROFIBUS DP."
The most important components of the system and their functions are shown below.
Component Function
SIMOTION D410‑2 … is the central motion control module.
The module contains the programmable SIMOTION runtime of SIMO‐
TION D410‑2 and the SINAMICS S120 drive runtime software.
You can use the integrated high-speed I/Os (onboard I/Os) as:
● User-addressable process I/Os
● Homing inputs
● Fail-safe digital inputs
● Fail-safe digital output
● Inputs for measuring inputs
● Outputs for fast output cams
● Analog input
The measuring sockets can output any analog signals.
The DRIVE-CLiQ interface permits a fast connection to the SINAMICS drive
components.
System software The basic functionality of SIMOTION D410‑2 is supplied separately on a
CompactFlash Card containing the following:
● SIMOTION runtime (kernel)
● Drive software of SINAMICS S120
The CompactFlash card is not included in the scope of delivery.
Power supply (PS) … provides the electronic power supply for SIMOTION D410‑2 (e.g. SITOP
power supply).
SIMOTION D410-2
24 Manual, 03/2018, A5E33446720B
Description
2.2 System components
PROFIBUS DP
SIMOTION D410-2 can communicate with the following components via the PROFIBUS DP
interface.
Component Function
Programming device (PG/PC) … configures, assigns parameters, programs, and tests using the SIMOTION SCOUT En‐
gineering System (ES).
SIMATIC HMI device ... is used for operating and monitoring functions. This is not an essential requirement for
the operation of the SIMOTION D410-2.
Other controllers (e.g. SIMO‐ … e.g. higher-level controller (plant controller); modular machine concepts with multiple
TION or SIMATIC) controllers, distributed across individual machine modules.
Distributed I/O systems
SIMATIC ET 200MP Modular I/O system for cabinet installation and high channel densities in the SIMAT‐
IC S7‑1500 packaging system. SIMATIC ET 200MP permits the shortest bus cycle times
and fastest response time even with large volumes of data.
SIMATIC ET 200M Modular I/O system for cabinet installation and high channel densities in the SIMAT‐
IC S7‑300 packaging system.
SIMATIC ET 200SP Finely scalable I/O system for cabinet installation; ET 200SP features a single-cable and
multi-cable connection with push‑in terminals, compact dimensions, high performance, and
low part variety.
SIMATIC ET 200S Finely scalable I/O system for cabinet installation and particularly time-critical applications;
including motor starters, safety technology and individual grouping of load groups.
SIMATIC ET 200AL Modular, distributed I/O system with compact I/O modules in IP65/67; simple installation in
all mounting positions even in small spaces; front and transverse screw fastenings on flat
surfaces or on aluminum supporting channels; flexible connection to PROFINET or PRO‐
FIBUS or simple integration in SIMATIC ET 200SP.
SIMATIC ET 200pro Modular I/O system with IP65/IP67 degree of protection for machine-related applications
with no cabinet; with features such as more compact designs, integrated PROFIsafe safety
technology, PROFINET connection, and live module replacement.
SIMATIC ET 200eco I/O system with IP65/IP67 degree of protection for machine-related applications with no
cabinet, with a flexible and fast connection system in ECOFAST or M12.
Other PROFIBUS I/O
Gateways ● DP/AS-Interface Link 20E and DP/AS-Interface Link Advanced for the PROFIBUS DP
gateway to AS-Interface
● DP/DP coupler for connecting two PROFIBUS DP networks
Drive interfaces ● ADI4 (Analog Drive Interface for 4 axes) for the connection of drives with analog ±10 V
setpoint interface or for external encoders
● IM 174 (Interface Module for 4 axes) for the connection of drives with analog ±10 V
setpoint interface, external encoders or the connection of stepper drives with pulse/
direction interface
Drive units with PROFI‐ ... convert speed setpoints into signals for controlling the motor and supply the power re‐
BUS DP interface quired to operate the motors.
(e.g. CU310-2 DP) Can also be operated as an isochronous slave on the PROFIBUS DP.
Teleservice adapter Remote diagnostics
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 25
Description
2.2 System components
PROFINET IO
The SIMOTION D410‑2 DP/PN can communicate with the following components via the
onboard PROFINET IO interface.
Component Function
Programming device (PG/PC) … configures, assigns parameters, programs, and tests using the SIMO‐
TION SCOUT Engineering System (ES).
SIMATIC HMI device ... is used for operating and monitoring functions. This is not an essential require‐
ment for the operation of a Control Unit.
Other controllers (e.g. SIMOTION or SI‐ … e.g. higher-level controller (plant controller); modular machine concepts with
MATIC) multiple controllers, distributed across individual machine modules.
Master computer … communicates with other devices via UDP, TCP/IP.
Distributed I/O systems
SIMATIC ET 200MP Modular I/O system for cabinet installation and high channel densities in the SI‐
MATIC S7‑1500 packaging system. SIMATIC ET 200MP permits the shortest bus
cycle times and fastest response time even with large volumes of data. With the
time-based I/O, signals can be recorded or output to the precise µs.
SIMATIC ET 200M Modular I/O system for cabinet installation and high channel densities in the SI‐
MATIC S7-300 packaging system.
SIMATIC ET 200SP Finely scalable I/O system for cabinet installation; ET 200SP features a single-
cable and multi-cable connection with push‑in terminals, compact dimensions, high
performance, and low part variety. With the time-based I/O, signals can be recor‐
ded or output to the precise µs.
SIMATIC ET 200S Finely scalable I/O system for cabinet configuration and particularly time-critical
applications; including motor starters, safety technology and individual grouping
of load groups.
SIMATIC ET 200AL Modular, distributed I/O system with compact I/O modules in IP65/67; simple in‐
stallation in all mounting positions even in small spaces; front and transverse screw
fastenings on flat surfaces or on aluminum supporting channels; flexible connec‐
tion to PROFINET or PROFIBUS or simple integration in SIMATIC ET 200SP.
SIMATIC ET 200pro Modular I/O system with IP65/67 degree of protection for machine-related appli‐
cations with no cabinet; with features such as compact designs, integrated PRO‐
FIsafe safety technology, PROFINET IO connection and live module replacement.
SIMATIC ET 200eco PN Compact block I/O with IP65/66/67 degree of protection for cabinet-free usage in
machines with M12 connection method. Very rugged and resistant encapsulated
metal enclosure.
Other PROFINET IO I/O devices
Drive units with PROFINET IO interface ... convert speed setpoints into signals for controlling the motor and supply the
power required to operate the motors.
Gateways ● IE/AS-Interface link PN IO for the PROFINET IO gateway to AS-Interface
● PN/PN coupler for connecting two PROFINET IO networks
SIMOTION D410-2
26 Manual, 03/2018, A5E33446720B
Description
2.2 System components
Ethernet
The Control Unit can communicate with the following components via the Ethernet interfaces
or be embedded in an automation environment:
Component Function
Programming device (PG/PC) … configures, assigns parameters, programs, and tests using the SIMOTION SCOUT En‐
gineering System (ES).
Master computer … communicates with other devices via UDP, TCP/IP.
SIMATIC HMI device ... is used for operating and monitoring functions. This is not an essential requirement for
the operation of the SIMOTION D410‑2.
DRIVE-CLiQ
SIMOTION D410-2 can communicate via the DRIVE-CLiQ interface with the following
components:
Component Function
SINAMICS S120 AC DRIVE ... convert speed setpoints into signals for controlling the motor and supply the power re‐
drive units quired to operate the motors. The Power Module is connected via CUA31/CUA32. No more
(with CUA31/CUA32) than one Power Module can be connected. The chassis Power Module is connected via
DRIVE-CLiQ.
Note:
Components in booksize format are not supported!
TM15, TM17 High Feature Ter‐ The Terminal Modules TM15 and TM17 High Feature are used to implement measuring
minal Modules inputs inputs and output cam outputs. In addition, these Terminal Modules provide drive-
related digital I/Os with short signal delay times.
TM31 Terminal Module … enables terminal expansion via DRIVE-CLiQ (additional analog and digital I/Os).
TM41 Terminal Module … enables terminal expansion (analog and digital I/Os) and encoder simulation via DRIVE-
CLiQ. The TM41 can be connected to a real axis.
TM54F Terminal Module … enables terminal expansion (fail-safe digital inputs/outputs) for controlling the safe motion
monitoring functions of the integrated drive. A TM54F is not usually necessary because the
SIMOTION D410‑2 has 3 F‑DI and 1 F‑DO.
TM120 Terminal Module Four temperature sensors (KTY84‑130 or PTC) can be evaluated via the TM120 Terminal
Module. The temperature sensor inputs are safely electrically separated from the evaluation
electronics in the TM120 Temperature Module and are suitable for evaluating the temper‐
ature of special motors, e.g. 1FN linear motors and 1FW6 built-in torque motors.
TM150 Terminal Module The TM150 Terminal Module can be used to evaluate temperature sensors (KTY, PT100,
PT1000, PTC, and bimetal normally closed contact). This means, for example, that other
temperatures from the process can be measured in addition to the motor temperature.
Temperature sensors can be evaluated using a 2, 3 or 4‑wire system. Twelve temperature
sensors can be evaluated with 2‑wire evaluation and six temperature sensors with 3 and
4‑wire evaluation.
SMx Sensor Modules ... enable acquisition of encoder data from connected motors via DRIVE-CLiQ.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 27
Description
2.2 System components
Component Function
Motors with … allow simplified commissioning and diagnostics, as the motor and encoder type are iden‐
DRIVE-CLiQ interface tified automatically.
DMC20/DME20 … enables the number of DRIVE-CLiQ interfaces to be increased and the creation of a point-
DRIVE-CLiQ hub to-point topology.
Note
Please note that SIMOTION D410‑2 components in booksize format (Controller Extension,
Motor Modules, Line Modules, etc.) are not supported.
SIMOTION D410‑2 can only be used with the following Power Modules:
● PM340
● PM240-2 as of SIMOTION V4.4/SINAMICS V4.7
Other Power Modules are not supported by SINAMICS G120 (e.g. PM230).
Note
You will find detailed information on components in the SINAMICS S110/S120 family of
products in the SINAMICS S110/S120 manuals.
It is possible that older DRIVE‑CLiQ components can no longer be used with SIMOTION
D410‑2. You will find detailed information on this in the SIMOTION D410‑2 Commissioning
and Hardware Installation Manual in Section "Migration of SIMOTION D410 to
SIMOTION D410‑2" under "Permissible combinations".
SIMOTION D410-2
28 Manual, 03/2018, A5E33446720B
Description
2.3 I/O integration
Note
Note that not all modules in the ET 200 I/O family are approved for SIMOTION. Moreover,
system-related functional differences can come into play when these I/Os or I/O systems are
used on SIMOTION vs. on SIMATIC. For example, special process-control functions (e.g.
HART modules, etc.) are not supported by SIMOTION for the ET 200M distributed I/O system.
A detailed, regularly updated list of the I/O modules approved for use with SIMOTION, as well
as notes on their use, can be found at Internet address (https://support.industry.siemens.com/
cs/ww/en/view/11886029)
In addition to the I/O modules enabled for SIMOTION, in principle all certified standard
PROFIBUS slaves (DP-V0/DP-V1/DP-V2) and PROFINET IO devices with RT and IRT real-
time classes may be connected to SIMOTION D410-2. These modules are integrated using
the GSD file (PROFIBUS) or GSDML file (PROFINET) provided by the relevant device
manufacturer.
Note
Please note that in isolated cases, additional boundary conditions must be fulfilled in order to
integrate a module into SIMOTION. Thus, a few modules require "driver blocks" , e.g. in the
form of function blocks, that permit (or simplify) integration.
For modules enabled for SIMOTION (e.g. SIMATIC S7‑300 module FM 350‑1, etc.), these
driver blocks are part of the SIMOTION SCOUT engineering system command library.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 29
Description
2.4 SIMOTION D410-2 DP representation
View
The following figure shows a SIMOTION D410-2 DP with the interfaces and front elements.
;(1& &RQQHFWLRQIRU
(QFRGHULQWHUIDFH +7/77/66, SURWHFWLYHFRQGXFWRU
DQGLIUHTXLUHG
;'4 HTXLSRWHQWLDOERQGLQJ
'5,9(&/L4LQWHUIDFH 0 7RU[7
;'3 6FUHZW\SHVKLHOG
352),%86'3LQWHUIDFH VXSSRUW0 7RU[7
;'303,
352),%86'303,LQWHUIDFH /('GLVSOD\V
5'<
5816723
287!9
;
6)%)
(OHFWURQLFSRZHUVXSSO\
6ORWIRU&RPSDFW)ODVK
; FDUG
7HPSHUDWXUHVHQVRUFRQQHFWLRQ
IDLOVDIHGLJLWDOLQSXWV(3
WHUPLQDOV
;
,VRODWHGGLJLWDOLQSXWVIDVWGLJLWDO,2V
7\SHSODWH
%23LQWHUIDFH QR
; IXQFWLRQ
,VRODWHGGLJLWDOLQSXW
IDLOVDIHGLJLWDORXWSXW
5(6(7EXWWRQ
; 7770PHDVX
)DVWGLJLWDO,2VDQDORJLQSXW ULQJVRFNHWV
6HUYLFHVHOHFWRUVZLWFK
6
',3VZLWFKIRUDQDORJLQSXW
0RGHVHOHFWRUVZLWFK
;331,(
(WKHUQHWLQWHUIDFH ',$*EXWWRQ
Figure 2-4 Location of interfaces and front elements for SIMOTION D410-2 DP
The interface to the power module (PM) is located at the rear of the SIMOTION D410-2.
SIMOTION D410-2
30 Manual, 03/2018, A5E33446720B
Description
2.4 SIMOTION D410-2 DP representation
See also
Interfaces (Page 49)
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 31
Description
2.5 SIMOTION D410-2 DP/PN drawing
View
The following figure shows a SIMOTION D410-2 DP/PN with the interfaces and front elements.
;(1& &RQQHFWLRQIRU
(QFRGHULQWHUIDFH +7/77/66, SURWHFWLYHFRQGXFWRU
DQGLIUHTXLUHG
;'4 HTXLSRWHQWLDOERQGLQJ
'5,9(&/L4LQWHUIDFH 0 7RU[7
;33 6FUHZW\SHVKLHOG
352),1(7,2LQWHUIDFH VXSSRUW0 7RU[7
;'303, /('GLVSOD\V
352),%86'303,LQWHUIDFH 5'<
5816723
287!96<
;
6)%)
(OHFWURQLFSRZHUVXSSO\
; 6ORWIRU&RPSDFW)ODVK
7HPSHUDWXUHVHQVRUFRQQHFWLRQ FDUG
IDLOVDIHGLJLWDOLQSXWV(3WHUPLQDOV
;
,VRODWHGGLJLWDOLQSXWVIDVWGLJLWDO,2V 7\SHSODWH
%23LQWHUIDFH QR
IXQFWLRQ
;
,VRODWHGGLJLWDOLQSXW
5(6(7EXWWRQ
IDLOVDIHGLJLWDORXWSXW
; 7770PHDVX
)DVWGLJLWDO,2VDQDORJLQSXW ULQJVRFNHWV
6HUYLFHVHOHFWRUVZLWFK
6
',3VZLWFKIRUDQDORJLQSXW
0RGHVHOHFWRUVZLWFK
;331,( ',$*EXWWRQ
(WKHUQHWLQWHUIDFH
Figure 2-6 Location of interfaces and front elements for SIMOTION D410-2 DP/PN
The interface to the power module (PM) is located at the rear of the SIMOTION D410-2.
SIMOTION D410-2
32 Manual, 03/2018, A5E33446720B
Description
2.5 SIMOTION D410-2 DP/PN drawing
See also
Interfaces (Page 49)
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 33
Description
2.6 Type plates
$UWLFOHQXPEHU
'DWDPDWUL[FRGH
0RGXOHGHVLJQDWLRQ
+:SURGXFWYHUVLRQ
($&(XUDVLDQ&RQIRUPLW\ FXVWRPV
:HLJKW ZLWKRXWSDFNDJLQJ XQLRQRI5XVVLD%HODUXVDQG.D]DNKVWDQ
5&0 5HJXODWRU\&RPSOLDQFH0DUN
3URGXFWIDPLO\ SUHYLRXVO\&7LFNPDUNLQJIRU$XVWUDOLD
DQG1HZ=HDODQG
Figure 2-8 Rating plate using the SIMOTION D410-2 DP/PN as an example
Note
The information contained in each field of the rating plate on your actual Control Unit may differ
from that presented in this manual (for example, a later product version, approvals and marks
that have not yet been earned, etc. may be shown).
Depending on the rating plate, the HW version may be designated as "Version" or "FS"
(Function State). Older components are marked with C-Tick instead of RCM.
MAC addresses
A second rating plate for the MAC address of the Ethernet interface and the PROFINET
interface (D410‑2 DP/PN only) is attached to the front of the device.
'DWDPDWUL[FRGH
0RGXOHGHVLJQDWLRQ
$UWLFOHQXPEHU
(WKHUQHWLQWHUIDFH
0$&DGGUHVV;
352),1(7,2LQWHUIDFH
0$&DGGUHVV;
''331RQO\
6HULDOQXPEHU
+:SURGXFWYHUVLRQ
SIMOTION D410-2
34 Manual, 03/2018, A5E33446720B
Description
2.6 Type plates
Depending on the rating plate, the HW version may be designated as "Version" or "FS"
(Function State).
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 35
Description
2.7 CompactFlash card
Properties
The CF card is mandatory for operation of the SIMOTION D410‑2. The CF card must be
ordered as a separate component; it is not included in the SIMOTION D410‑2 scope of
delivery.
The SIMOTION Kernel (SIMOTION D410-2 firmware) and the software used to control the
drives (SINAMICS firmware) are contained on the CF card.
The CF card is used for:
● Backing up the technology packages and user data (programs, configuration data,
parameter assignments)
● Update (e.g. SIMOTION firmware update)
The licenses for the technology functions are linked to the serial number of the CF card. This
means the CF card can be inserted in different SIMOTION D410‑2s without having to change
the licenses.
The CF card is supplied in a bootable format with the latest SIMOTION Kernel and drive
software.
CF card
CF cards with different storage capactities are available for SIMOTION D410‑2.
At the time for going to press, these were:
● 1 GB CF, article number 6AU1400-1PA23-0AA0
● 1 GB CF, article number 6AU1400-1PA22-0AA0
You will find detailed information on the compatibility relationships for the CF card, boot loader
version, SIMOTION D hardware and SIMOTION firmware version in the software compatibility
list. You can find this list both in the documentation that comes with the
SIMOTION SCOUT DVD under \1_Important\Germany\Kompatibilitaet\… and on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/18857317).
SIMOTION D410-2
36 Manual, 03/2018, A5E33446720B
Description
2.7 CompactFlash card
0DUNLQJIRULQVHUWLRQGLUHFWLRQ
RIWKH&)FDUG
$UWLFOHQXPEHU
,GHQWLILHUIRU&)FDUGZLWK=RSWLRQ
/LVWRIWKH=RSWLRQV = 07
OLFHQVHVRQ&)FDUGDVGHOLYHUHG 6,027,21'963
3URGXFWDQGYHUVLRQGHVLJQDWLRQ
6,1$0,&69
FDUGFDSDFLW\ERRWORDGHUYHUVLRQ
+:VHULDOQXPEHU &)FDUG *%%RRWORDGHU9
8QLTXHQXPEHU
'DWHRIPDQXIDFWXUH
9HUVLRQ GLJLW 'DWDPDWUL[FRGH
LQFODUWLFOHQXPEHU
'HOLYHU\QRWHQXPEHU
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 37
Description
2.7 CompactFlash card
Note
Path interpolation is supported as of V4.4.
SINAMICS licenses
Selected SINAMICS licenses can be used with a SIMOTION D CF card. Only one relicensing
is possible. A prelicensing of SIMOTION D CF cards via Z options is not possible with
SINAMICS licenses.
Examples:
● SINAMICS S120 Advanced Position Control (APC)
Article no. 6SL3074-0AA05-0AA0
License for each drive (on CU, SINAMICS Integrated)
● SINAMICS S120 cogging torque compensation
Article no. 6SL3074-0AA15-0AA0
License for each drive (on CU, SINAMICS Integrated)
● SINAMICS Technology Extension "Vibration Extinction" (VIBX)
Article no. 6SL3077-0AA00-5AB0
License for a target device (CU, SINAMICS Integrated)
● SINAMICS DCB Extension
Article no. 6SL3077-0AA00-0AB0
License for a target device (CU, SINAMICS Integrated)
With SINAMICS licenses, underlicensing of SINAMICS Integrated is indicated by the flashing
SF LED on the SIMOTION D Control Unit. An entry is also made in the diagnostic buffer and
the underlicensing is displayed in the License dialog box of SIMOTION SCOUT. The licensing
is performed (as for SIMOTION licenses) via SIMOTION SCOUT or via the SIMOTION license
key on the CF card.
SIMOTION D410-2
38 Manual, 03/2018, A5E33446720B
Description
2.8 Data matrix code
In addition to the "serial number", CF cards also have a "hardware serial number".
If licenses are purchased for licensed functions, a "license key" is generated from the hardware
serial number of the CF card and the serial number of the purchased licenses; such licenses
are valid only for the associated CF card.
The data required for the licensing can be read by a reader unit via the bar codes on the license
certificates (Certificate of License "CoL") and the 2D code on the CF card in order, for example,
to automate the licensing process.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 39
Description
2.9 Licensing
2.9 Licensing
Note
If you use more than one real axis with SIMOTION D410-2, you must license these additional
axes. The axis license with the highest functionality is covered by the inclusive license (a real
axis). The functionality has the following granularity: CAM > GEAR > POS.
Example:
You use two real axes: 1 POS, 1 CAM.
Because the CAM license has a higher value, and so inclusive, you only need to purchase
one POS license.
Licenses are required for runtime functions such as SIMOTION IT Virtual Machine. These
licenses can be pre-installed on a CompactFlash card (CF card) or ordered separately.
Additional references
For more information about license management, see the SIMOTION SCOUT Configuration
Manual. General information on the subject of licensing can be found in the SIMOTION PM
21 Catalog.
SIMOTION D410-2
40 Manual, 03/2018, A5E33446720B
Operator control (hardware) 3
3.1 Overview of operator control and display elements
The following figure shows the arrangement of the operator control and display elements on
the SIMOTION D410-2.
6ORWIRU
&RPSDFW)ODVKFDUG
/('GLVSOD\V /('GLVSOD\V
5'< 5'<
5816723 5816723
287!9 287!96<
6)%) 6)%)
5(6(7EXWWRQ
6HUYLFHVHOHFWRUVZLWFK
6ZLWFK6
0RGHVHOHFWRUVZLWFK
',$*EXWWRQ
Figure 3-1 Operator control and display elements: SIMOTION D410-2 DP (on the left), SIMOTION D410-2 DP/PN (on the
right)
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 41
Operator control (hardware)
3.2 Operator controls
Layout
SIMOTION D410-2 provides a service selector switch (SVC) behind the blanking cover in the
lower area of the front panel.
NOTICE
Damage from electrostatic discharge
The rotary switch can be destroyed by static electricity.
Operate the rotary switch only with an insulated screwdriver.
Comply with the ESD rules.
Function
The service selector switch is used to select service functions.
In "normal" operation, this switch must remain in the "0" position.
The following table shows the possible positions of the service selector switch. The service
selector switch positions are explained in the order in which they are arranged on the
SIMOTION D410-2. The service functions can generally be used in any set operating mode.
SIMOTION D410-2
42 Manual, 03/2018, A5E33446720B
Operator control (hardware)
3.2 Operator controls
Note
Alternatively, diagnostic data and non-volatile SIMOTION data can also be backed up via the
DIAG button. See Section DIAG button (Page 45).
Layout
SIMOTION D410-2 provides a mode switch (PLC) behind the blanking cover in the lower area
of the front panel.
NOTICE
Damage from electrostatic discharge
The rotary switch can be destroyed by static electricity.
Operate the rotary switch only with an insulated screwdriver.
Comply with the ESD rules.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 43
Operator control (hardware)
3.2 Operator controls
Function
The following table contains the possible mode switch positions and the associated operating
mode.
Note
In the "RUN" setting, you can also control the SIMOTION D410-2 operating mode from the
SIMOTION SCOUT engineering system. This means that it is not necessary to adjust the mode
switch to change the operating mode.
SIMOTION D410-2
44 Manual, 03/2018, A5E33446720B
Operator control (hardware)
3.2 Operator controls
Additional references
Detailed information
● For information on setting the operating modes, see the SIMOTION SCOUT Configuration
Manual.
● For device upgrade (device update tool), see Upgrading SIMOTION Devices Operating
Instructions.
Layout
The DIAG button is located on the SIMOTION D410‑2 behind the blanking cover on the
front.
Function
The diagnostic data and non-volatile SIMOTION data is backed up on the CompactFlash card
via the DIAG button. The DIAG button function therefore corresponds to the function of switch
position "D" of the Service selection switch.
The following options are available to backup the diagnostic data and the non-volatile
SIMOTION data:
● Backup during operation (in STOP/STOPU/RUN operating state)
A short pressing of the DIAG button suffices to initiate the backup of the data. The DIAG
button is therefore preferable to switch position "D" of the Service selection switch.
● Backup during the module startup
The DIAG button must be kept pressed until the boot process has completed. Since this
can take between 20 and 30 seconds, the switch position "D" of the Service selector switch
is preferable in this case.
Additional references
For detailed information on creating diagnostic data and backing up / restoring non-volatile
SIMOTION data, refer to the SIMOTION D410-2 Commissioning and Hardware Installation
Manual.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 45
Operator control (hardware)
3.2 Operator controls
Layout
The RESET button is located behind the blanking cover on the SIMOTION D410-2.
Function
The entire system is reset when the RESET button is pressed and a new power-up of the
system forced.
Layout
SIMOTION D410-2 provides the S5.0 switch behind the blanking cover in the lower area of
the front panel.
8 , 6
6
Function
The DIP switch is used for switching the analog input (X131 connector) as voltage or current
input.
Position Function
U The analog input is used as voltage input.
I The analog input is used as current input.
See also
Interface assignment (Page 62)
SIMOTION D410-2
46 Manual, 03/2018, A5E33446720B
Operator control (hardware)
3.2 Operator controls
Function
The SIMOTION Kernel (SIMOTION D410-2 firmware) and the software used to control the
drives (SINAMICS firmware) are contained on the CF card.
The CompactFlash card (CF card) is used to
● Backup technology packages and user data
● Update (e.g. SIMOTION firmware update)
NOTICE
Impermissible use of the CompactFlash card
The CF card of the SIMOTION D410-2 must not be used in a SIMOTION D410, D4x5 or
D4x5-2!
NOTICE
Elektrostatisch gefährdete Bauelemente
The CompactFlash card is an ESD-sensitive component.
De-energize the SIMOTION D410‑2 device before inserting or removing the CompactFlash
card. The SIMOTION D410‑2 is in a de-energized state when all the LEDs are OFF.
Comply with the ESD rules.
Additional information
For more information on writing and formatting the CF card, see the SIMOTION D410-2
Commissioning Manual.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 47
Operator control (hardware)
3.3 Error and status displays
Figure 3-7 LED displays: D410-2 DP (on the left), D410-2 DP/PN (on the right)
LED Meaning
D410-2 DP D410-2 DP/PN
RDY RDY Status indicator of the SINAMICS Integrated
RUN/STOP RUN/STOP SIMOTION D410-2 operating states
OUT>5V – Encoder current supply > 5 V (TTL/HTL)
– OUT>5V/SY Encoder current supply > 5 V (TTL/HTL)
Synchronization status (SY) of the onboard PROFINET IO in‐
terface (X150)
SF/BF: SF/BF: Group error / bus fault
Additional information
You can perform a detailed diagnosis with a PG/PC and the engineering system. For
information about diagnostics using LED displays, refer to the SIMOTION D410-2
Commissioning and Hardware Installation Manual, Section "Diagnostics using LED displays".
SIMOTION D410-2
48 Manual, 03/2018, A5E33446720B
Interfaces 4
4.1 Overview of interfaces
This section describes the interfaces of the SIMOTION D410‑2. Information on the
arrangement of the interfaces on the module can be found in Sections SIMOTION D410-2 DP
representation (Page 30) and SIMOTION D410-2 DP/PN drawing (Page 32).
Available interfaces
Non-usable interfaces
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 49
Interfaces
4.2 DRIVE-CLiQ interface
Properties
DRIVE-CLiQ has the following properties:
● Automatic detection of components by the Control Unit
● Independent expansion of components possible
● Standardized interfaces to all components
● Uniform diagnostics down to the components
● Complete service down to the components
● Mechanical parts are easy to use
For the DRIVE-CLiQ interface, 24 V / 450 mA are available to connect encoders and measuring
systems.
Interface characteristics
Characteristic Type
Connector type DRIVE-CLiQ connector
Maximum cable length 100 m
Data rate 100 Mbits
Connector type: RJ45 socket; blanking cover for DRIVE-CLiQ interface included in the scope of deliv‐
ery; blanking cover (50 pieces) Article number: 6SL3066-4CA00-0AA0)
Interface assignment
SIMOTION D410-2
50 Manual, 03/2018, A5E33446720B
Interfaces
4.2 DRIVE-CLiQ interface
Connectable devices
The following table contains the components that can communicate with SIMOTION D410-2
via the DRIVE-CLiQ interface. Note the max. number of nodes that can be connected to the
DRIVE-CLiQ!
Note
Note also the topology rules of the SINAMICS S120, see SINAMICS S120 Function Manual,
Chapter "Rules for wiring with DRIVE-CLiQ".
Additional information
For information on the components that can be connected via DRIVE-CLiQ (setup, connection,
configuration, etc.) see
● SINAMICS S120 Control Units and Additional System Components Manual
● SINAMICS S120 for AC Drives Manual
● SINAMICS S120 Commissioning Manual
● SINAMICS S120 Safety Integrated Function Manual
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 51
Interfaces
4.2 DRIVE-CLiQ interface
SIMOTION D410-2
52 Manual, 03/2018, A5E33446720B
Interfaces
4.3 PROFIBUS DP interfaces
Properties
SIMOTION D410-2 provides the following interfaces for connection on the PROFIBUS DP:
Interface characteristics
Characteristics Type
Connector type 9-pin sub D socket
Cable type PROFIBUS cable
Max. cable length 100 m at 12 Mbit/s
Max. data rate 12 Mbit/s
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 53
Interfaces
4.3 PROFIBUS DP interfaces
Connectable devices
The following devices can be connected to the PROFIBUS DP interfaces:
● PG/PC
● SIMATIC HMI devices
● SIMATIC controllers with PROFIBUS DP interface
● Distributed I/O
● Teleservice adapter
● Drive units with PROFIBUS DP interface (standard slaves)
Note
For remote diagnosis, a teleservice adapter can be connected to the PROFIBUS X21 or
X24 interface. A teleservice adapter can only be connected to one of the two interfaces.
The power supply for the teleservice adapter (terminals 2 and 7) can accept current loads
as high as 150 mA and is sustained short-circuit proof.
SIMOTION D410-2
54 Manual, 03/2018, A5E33446720B
Interfaces
4.4 PROFINET IO interface (SIMOTION D410-2 DP/PN only)
Properties
PROFINET is an open component-based industrial communication system using Ethernet for
distributed automation systems.
SIMOTION D410‑2 DP/PN has a PROFINET interface with two ports (X150 P1-P2) onboard.
The PROFINET interface supports operation of a SIMOTION D410‑2 DP/PN as an IO
controller and/or as an I device.
Interface characteristics
Characteristic Type
Connector type RJ45 socket connector
Cable type PROFINET
Maximum cable length 100 m
Minimum send cycle clock 0.25 ms
Autocrossing Yes
i.e. both crossed and uncrossed cables can be used
Dust protection filler plugs for seal‐ One filler plug contained in the D410‑2 scope of delivery
ing unused PROFINET ports Filler plugs (50 pcs) article number: 6SL3066‑4CA00‑0AA0
Interface assignment
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 55
Interfaces
4.4 PROFINET IO interface (SIMOTION D410-2 DP/PN only)
'LVSOD\
/,1.
'LVSOD\
$&7
Connectable devices
The following devices can be connected to the PROFINET IO interface:
● PG/PC programming devices (communication with SIMOTION SCOUT / STEP 7)
● SIMATIC HMI devices
● SIMATIC controllers with PROFINET interface
● Distributed I/O
● Drive units with PROFINET IO interface (standard devices)
The SIMOTION D410‑2 DP/PN then assumes the role of a PROFINET IO controller and can
offer the following functions:
● PROFINET IO controller, I-device (also controller and device simultaneously)
● Supports real-time classes of PROFINET IO:
– RT (real-time)
– IRT (isochronous real-time)
SIMOTION D410-2
56 Manual, 03/2018, A5E33446720B
Interfaces
4.4 PROFINET IO interface (SIMOTION D410-2 DP/PN only)
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 57
Interfaces
4.5 Encoder interface (HTL/TTL/SSI)
Interface characteristics
Characteristic Type
Encoder interface ● TTL or HTL incremental encoders (with adjustable
parameters)
● Absolute encoder SSI
Connector type 15-pin sub D connector
Measuring current via temperature sensor 2 mA
connection
NOTICE
Destruction of the encoder electronics
Operation of a 5 V encoder on the 24 V encoder supply may result in the destruction of its
electronic components!
Make sure that you can operate the connected encoder on a 24 V power supply (e.g. HTL
encoder). This setting can be set in the expert list of the drive in parameter p0400 and in the
following parameters.
SIMOTION D410-2
58 Manual, 03/2018, A5E33446720B
Interfaces
4.5 Encoder interface (HTL/TTL/SSI)
Interface assignment
For Pin 1 / Pin 8: The associated temperature channel (T1) can be assigned parameters as an individual
channel or together in combination with the second temperature channel (T2) at interface X120.
(For parameterization, see the SINAMICS S120 Commissioning Manual).
For Pin 6 / Pin 9: At an encoder supply of 5 V, the voltage drops on the encoder supply cables are recorded
and compensated by means of the sense cables. For this purpose, the sensor supply is corrected on the
SIMOTION D410-2.
NOTICE
Motor overheating due to an incorrectly connected KTY temperature sensor
A sensor connected with the incorrect polarity cannot detect the motor overheating.
Connect the KTY temperature sensor with the correct polarity.
For more information on the temperature sensors and how to use them, see the SINAMICS
S120 Commissioning Manual, in Chapter Temperature sensors for SINAMICS components.
Note
There are two ways of connecting the temperature sensor:
1. Via X120, terminal 1 and 2
2. Via X23, pins 1 and 8
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 59
Interfaces
4.5 Encoder interface (HTL/TTL/SSI)
Note
We recommend that bipolar encoders are used
When using unipolar encoders, the unused negative track signals can either be connected or
connected to ground. This results in different switching thresholds.
Note
Prefabricated cable for 5 V - TTL encoder
If a 5 V - TTL encoder (6FX encoder) is used, the connecting cable 6FX8002-2CR00-... must
be used.
SIMOTION D410-2
60 Manual, 03/2018, A5E33446720B
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
4.6.1 Properties
The onboard I/Os (Onboard I/Os) of the SIMOTION D410-2 are assigned to the SINAMICS
Integrated. An appropriate configuration allows the I/Os also to be used by SIMOTION.
Digital I/Os
The digital I/Os at the X120, X121 and X130, X131 connectors are provided for the connection
of sensors and actuators.
Following types of digital I/Os are available on the SIMOTION D410-2:
● Three fail-safe electrically-isolated digital inputs (F-DI)
(can be used alternatively as six standard digital inputs, DI 17 can also be used as EP
terminal)
● One fail-safe electrically-isolated digital output (F-DO)
(can be used alternatively as one standard digital output)
● Five electrically-isolated digital inputs (DI)
● Eight high-speed non-isolated digital I/Os (DI/DO)
Assignment of the I/Os to functions can be parameterized as required. Special functions (e.g.
input of measuring input and output for output cam) can also be assigned to the I/Os.
Note
For optimal noise immunity of the digital inputs, the use of shielded cables is necessary if they
are to be used as
● Inputs of measuring inputs or
● Inputs for equivalent zero mark
Analog input
The analog input at connector X131 can be parameterized as voltage or current input.
Switching between the voltage or current input using a DIP switch, refer to Switch S5.0
(Page 46).
Features Type
Connector type (X120, X121) 12-pin spring-loaded terminal
Connector type (X130, X131) 8-pin spring-loaded terminal
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 61
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
Features Type
Connectable cable types and conductor cross-sec‐
tions
Rigid 0.2 mm² … 1.5 mm²
Flexible 0.2 mm² … 1.5 mm²
Flexible, with wire-end ferrule without plastic 0.25 mm² … 1.5 mm²
sleeve
Flexible, with wire-end ferrule with plastic 0.25 mm² … 0.75 mm²
sleeve
AWG / kcmil 24 … 16
Stripped length 10 mm
Tool Screwdriver 0.4 x 2.0 mm
Max. cable length 30 m
Note
To prevent an incorrect connection, the X120, X121, X130 and X131 connectors are supplied
coded. The terminal and pin numbers are also inscribed on the connectors.
SIMOTION D410-2
62 Manual, 03/2018, A5E33446720B
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
X120
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 63
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
Note
Using the "STO" safety function via the Power Module terminals for the PM240-2 (FSD, FSE
and FSF). With enabled Safety Integrated functions of the D410-2, a simultaneously active
STO function via Power Module terminals results in error messages being output (e.g. fault
F30600, reason 1005).
● Deactivate the function "STO via Power Module terminals" by setting both the DIP switches
for the interface STO_A/STO_B to the "0" position. Further information, see SINAMICS
S120 Manual for AC Drives, section Power Modules Blocksize (PM240-2)
The X120 interface has a connection for the motor temperature sensor.
You can use the temperature sensor connection to connect the temperature sensing via
KTY84‑1C130 (special temperature sensor) or PTC (positive temperature coefficient). The
temperature sensing provides thermal motor protection by detecting critical motor conditions.
SIMOTION D410-2
64 Manual, 03/2018, A5E33446720B
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
For more information on "thermal motor protection", see the SINAMICS S120 Commissioning
Manual.
NOTICE
Motor overheating due to an incorrectly connected KTY temperature sensor
A sensor connected with the incorrect polarity cannot detect the motor overheating.
Connect the KTY temperature sensor with the correct polarity.
For more information on the temperature sensors and how to use them, see the SINAMICS
S120 Commissioning Manual, Section Temperature sensors for SINAMICS components.
The maximum length of the temperature sensor cable is 300 m. The cables must be shielded.
For cable lengths >100 m, cables with a cross-section of ≥1 mm² must be used.
DANGER
Danger to life from electric shock due to insufficient safety isolation
Only temperature sensors that meet the safety isolation specifications stipulated in EN
61800-5-1 may be connected to terminals "+Temp" and "-Temp".
Use a Sensor Module External (SME120 or SME125) or Terminal Module TM120 if safe
electrical separation cannot be guaranteed (for linear motors or third-party motors, for
example).
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 65
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
X121
Note
An open input is interpreted as "low".
The use of the digital inputs (DI 0 ... DI 3) requires terminal M2 be connected. This is achieved
by:
● Providing the reference ground of the digital inputs, or
● a jumper to terminal M. This removes the electrical isolation for these digital inputs.
SIMOTION D410-2
66 Manual, 03/2018, A5E33446720B
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
X130
Note
An open input is interpreted as "low".
Note
If M1 or M2 is connected with M, the electrical isolation no longer exists.
If the digital output (DO 16) cannot be set by the signal source despite being set, an alarm
A03507 (digital output not set) is issued. This alarm can also parameterized as a fault.
The possible cause may be missing power supply (X130.6) or a short-circuit. For further details,
see the SINAMICS S120/S150 List Manual, Section List of faults and alarms.
Note
If the 24 V supply is briefly interrupted, the digital output is deactivated until the interruption
has been rectified.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 67
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
X131
NOTICE
Incorrect results of analog-to-digital conversion due to impermissible input voltage
The common mode range must not be violated.
Makes sure that the analog input voltage signals can have a maximum voltage of ±12 V with
respect to the reference potential. If the range is infringed, incorrect results may occur during
analog/digital conversion.
Note
A 24 V supply voltage must be connected to terminal X124 for the digital outputs to be used.
If momentary interruptions in the voltage occur in the 24 V supply, the digital outputs are
deactivated until the interruption has been rectified.
If a digital output (DO 8 … DO 15) is parameterized and the external 24 V power supply is not
connected (or the level is too low), the alarm A03506 will be issued. This alarm can also be
parameterized as a fault.
For further details, see the SINAMICS S120/S150 List Manual, Section List of faults and alarms.
See also
SIMOTION D410-2 DP connection examples (Page 71)
SIMOTION D410-2 DP/PN connection examples (Page 75)
SIMOTION D410-2
68 Manual, 03/2018, A5E33446720B
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
Note
The following safety functions are available for SIMOTION D410-2:
● Safety Integrated Basic Functions via the EP terminals
● Safety Integrated Extended and Advanced Functions via onboard I/Os (3 F-DI and 1 F-DO)
● Safety Integrated Extended and Advanced Functions with TM54F
● Safety Integrated Basic and Extended/Advanced Functions via secure communication from
"PROFIsafe on PROFIBUS"
Control (F logic) is via a SIMATIC F-CPU which is connected to PROFIsafe via PROFIBUS
(not SCOUT TIA).
● Safety Integrated Basic and Extended/Advanced Functions via secure communication from
"PROFIsafe on PROFINET" (only for SIMOTION D410-2 DP/PN)
Control (F logic) is via a SIMATIC F-CPU which is connected to PROFIsafe via PROFINET
(e.g. an S7-1500 F-CPU).
For further information on Safety Integrated, see the SINAMICS S120 Safety Integrated
Function Manual.
EP terminal
The pulse inhibit function (EP) is only available when Integrated Basic Functions are enabled.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 69
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
Note
An open input is interpreted as "low".
For the DI 22 digital input to function correctly, the coupled reference potential (DI 22-) must
be connected. The following options are available:
● Connect the coupled reference potential of the digital input to M1, M2 or M.
This assigns the input to the potential of the associated pin.
● Create a bridge between terminal M and terminal M1 or M2.
Caution: This will cancel the electrical isolation for this digital input!
Note
An additional external electronics power supply via terminal X124 is required in two cases:
● If the digital outputs DO 8 to DO 15 are in use, the power supply needs to be connected to
X124.
● The Power Module provides the electronics power supply of the SIMOTION D410-2. If the
SIMOTION D410-2 needs to remain functional when the Power Module is switched off,
X124 must be used for the electronics power supply.
Additional references
For information on configuring the digital I/Os as freely addressable I/Os, inputs of measuring
inputs or outputs of output cams, see the SIMOTION D410-2 Commissioning and Hardware
Installation Manual.
SIMOTION D410-2
70 Manual, 03/2018, A5E33446720B
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
For information on the configuration and function of the measuring input and output cam
technology objects, refer to the SIMOTION Output Cams and Measuring Inputs Function
Manual.
$GGLWLRQDO $GGLWLRQDO
H[WHUQDO,2VXSSO\ H[WHUQDO,2VXSSO\
9 9
9 0 9 0
;
9
9 9
0
; ; 6 6 6 6
',
6 6 6 6 6 6 ',
', ',
', ',
9
M1
', 0
', ','2 6 6 6 6
','2
0 0
',
', ','2
','2
0 0
0 + + + +
9
9
6 ; ;
', ','2 6 6 6 6
0 ','2
0
','2
','2
0
0
9 + + + +
'2
+
0
;3LQDQG;3LQFDQEHSDUDPHWHUL]HGDVLQSXWRURXWSXW
Figure 4-2 Example of circuits for the DI/DO without Safety Integrated functions
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 71
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
9
([W 0 ([W
9 9
(QFRGHULQWHUIDFH
'5,9(&/L4VRFNHW
;
9
9
0
0
0
0
; ;
9
', ','2
',
', ','2
0 0
0 ','2
','2
0
9 0
'2 '2 $,
''3
8VHVKLHOGHGFDEOHIRUPRWRUWHPSHUDWXUHVHQVRULQSXW
',LVXVHGDV(3WHUPLQDOZLWK6DIHW\,QWHJUDWHGEDVLFIXQFWLRQV
-XPSHURSHQHOHFWULFDOLVRODWLRQIRUGLJLWDOLQSXWV ',
8VHVKLHOGHGFDEOHVIRUIDVWLQSXWV
&DQEHSDUDPHWHUL]HGLQGLYLGXDOO\DVLQSXWRURXWSXW
8VHVKLHOGHGFDEOHIRUDQDORJLQSXW
0HPRU\FDUG 5HTXLUHGIRUVXSSO\RIWKHGLJLWDORXWSXWV'2WR'2
'2KDVQRIXQFWLRQIRUDSSOLFDWLRQVZLWKRXWVDIHW\IXQFWLRQ
Figure 4-3 Connection example of SIMOTION D410-2 DP without Safety Integrated functions
SIMOTION D410-2
72 Manual, 03/2018, A5E33446720B
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
9
([W 0 ([W
9 9
(QFRGHULQWHUIDFH
'5,9(&/L4VRFNHW
;
9
9
0
0
0
0
; ;
9
', ','2
',
', ','2
0 0
0 ','2
','2
0
)'2
9 0
'2 $,
''3
8VHVKLHOGHGFDEOHIRUPRWRUWHPSHUDWXUHVHQVRULQSXW
7KHLQYHUVLRQFDQEHSDUDPHWHUL]HG
-XPSHURSHQHOHFWULFDOLVRODWLRQIRUGLJLWDOLQSXWV ',
8VHVKLHOGHGFDEOHVIRUIDVWLQSXWV
&DQEHSDUDPHWHUL]HGLQGLYLGXDOO\DVLQSXWRURXWSXW
8VHVKLHOGHGFDEOHIRUDQDORJLQSXW
0HPRU\FDUG 5HTXLUHGIRUVXSSO\RIWKHGLJLWDORXWSXWV'2WR'2
$,DVYROWDJHLQSXW
Figure 4-4 Connection example of SIMOTION D410-2 DP with Safety Integrated Extended and Advanced Functions
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 73
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
$GGLWLRQDO $GGLWLRQDO
([WHUQDO,2VXSSO\ ([WHUQDO,2VXSSO\
9 9
9 0 9 0
9
6ZLFKLQJWR3 ;
9
SRWHQWLDO 9
6ZLWFKLQJWR1 0
SRWHQWLDO
; ; S0 S1 S2 S3
0 ',
',
9 ',
9 )', ',
9
0
6ZLFKLQJWR3 ','2 6 6 6 6
)',
SRWHQWLDO 0 ','2
0
6ZLFKLQJWR3 ','2
)',
SRWHQWLDO ','2
0
0 + + + +
0
9
M1 ; ;
','2 6 6 6 6
24 V1 ','2
0
','2
0 ','2
0
9 + + + +
)'2
([DPSOHRIFRQQHFWLQJDVDIHW\FRQWUROOHUZLWKRXWSXWVVZLWFKLQJWR3DQG1SRWHQWLDO
([DPSOHRIFRQQHFWLQJDVDIHW\FRQWUROOHUZLWKWZRRXWSXWVVZLWFKLQJWR3SRWHQWLDO
Figure 4-5 Example of circuits for the F-DI and F-DO with Safety Integrated Extended and Advanced Functions
SIMOTION D410-2
74 Manual, 03/2018, A5E33446720B
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
$GGLWLRQDO $GGLWLRQDO
H[WHUQDO,2VXSSO\ H[WHUQDO,2VXSSO\
9 9
9 0 9 0
;
9
9 9
0
; ; 6 6 6 6
',
6 6 6 6 6 6 ',
', ',
', ',
9
M1
', 0
', ','2 6 6 6 6
','2
0 0
',
', ','2
','2
0 0
0 + + + +
9
9
6 ; ;
', ','2 6 6 6 6
0 ','2
0
','2
','2
0
0
9 + + + +
'2
+
0
;3LQDQG;3LQFDQEHSDUDPHWHUL]HGDVLQSXWRURXWSXW
Figure 4-6 Example of circuits for the DI/DO without Safety Integrated Extended and Advanced Functions
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 75
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
9
([W 0 ([W
9 9
(QFRGHULQWHUIDFH
'5,9(&/L4VRFNHW
;
9
9
0
0
0
0
; ;
9
', ','2
',
', ','2
0 0
0 ','2
','2
0
9 0
'2 '2 $,
''331
8VHVKLHOGHGFDEOHIRUPRWRUWHPSHUDWXUHVHQVRULQSXW
',LVXVHGDV(3WHUPLQDOZLWK6DIHW\,QWHJUDWHGEDVLFIXQFWLRQV
-XPSHURSHQHOHFWULFDOLVRODWLRQIRUGLJLWDOLQSXWV ',
8VHVKLHOGHGFDEOHVIRUIDVWLQSXWV
&DQEHSDUDPHWHUL]HGLQGLYLGXDOO\DVLQSXWRURXWSXW
8VHVKLHOGHGFDEOHIRUDQDORJLQSXW
0HPRU\FDUG 5HTXLUHGIRUVXSSO\RIWKHGLJLWDORXWSXWV'2WR'2
'2KDVQRIXQFWLRQIRUDSSOLFDWLRQVZLWKRXWVDIHW\IXQFWLRQ
Figure 4-7 Connection example of SIMOTION D410-2 DP/PN without Safety Integrated Extended and Advanced Functions
SIMOTION D410-2
76 Manual, 03/2018, A5E33446720B
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
9
([W 0 ([W
9 9
(QFRGHULQWHUIDFH
'5,9(&/L4VRFNHW
;
9
9
0
0
0
0
; ;
9
', ','2
',
', ','2
0 0
0 ','2
','2
0
)'2
9 0
'2 $,
s9
''331
'2 $,
8VHVKLHOGHGFDEOHIRUPRWRUWHPSHUDWXUHVHQVRULQSXW
7KHLQYHUVLRQFDQEHSDUDPHWHUL]HG
-XPSHURSHQHOHFWULFDOLVRODWLRQIRUGLJLWDOLQSXWV ',
8VHVKLHOGHGFDEOHVIRUIDVWLQSXWV
&DQEHSDUDPHWHUL]HGLQGLYLGXDOO\DVLQSXWRURXWSXW
8VHVKLHOGHGFDEOHIRUDQDORJLQSXW
0HPRU\FDUG 5HTXLUHGIRUVXSSO\RIWKHGLJLWDORXWSXWV'2WR'2
$,DVYROWDJHLQSXW
Figure 4-8 Connection example of SIMOTION D410-2 DP/PN with Safety Integrated Extended and Advanced Functions
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 77
Interfaces
4.6 Digital I/Os / temperature sensor / analog input
$GGLWLRQDO $GGLWLRQDO
([WHUQDO,2VXSSO\ ([WHUQDO,2VXSSO\
9 9
9 0 9 0
9
6ZLFKLQJWR3 ;
9
SRWHQWLDO 9
6ZLWFKLQJWR1 0
SRWHQWLDO
; ; S0 S1 S2 S3
0 ',
',
9 ',
9 )', ',
9
0
6ZLFKLQJWR3 ','2 6 6 6 6
)',
SRWHQWLDO 0 ','2
0
6ZLFKLQJWR3 ','2
)',
SRWHQWLDO ','2
0
0 + + + +
0
9
M1 ; ;
','2 6 6 6 6
24 V1 ','2
0
','2
0 ','2
0
9 + + + +
)'2
([DPSOHRIFRQQHFWLQJDVDIHW\FRQWUROOHUZLWKRXWSXWVVZLWFKLQJWR3DQG1SRWHQWLDO
([DPSOHRIFRQQHFWLQJDVDIHW\FRQWUROOHUZLWKWZRRXWSXWVVZLWFKLQJWR3SRWHQWLDO
Figure 4-9 Example of circuits for the F-DI and F-DO with Safety Integrated Extended and Advanced Functions
SIMOTION D410-2
78 Manual, 03/2018, A5E33446720B
Interfaces
4.7 Power supply
Note
When using external power supplies (e.g. SITOP), the ground potential must be connected
with the protective ground terminal (PELV).
Note
Ground potential and housing (PE) are connected internally with low impedance.
Interface characteristics
Features Type
Connector type 4-way screw-type terminal
Connectable cable types and conductor cross-sec‐
tions
Rigid 0.2 mm² … 2.5 mm²
Flexible 0.2 mm² … 2.5 mm²
Flexible, with wire-end ferrule without plastic 0.2 mm² … 2.5 mm²
sleeve
Flexible, with wire-end ferrule with plastic 0.2 mm² … 1.5 mm²
sleeve
AWG / kcmil 22 … 12
Stripped length 6 … 7 mm
Tool Screwdriver 0.5 x 3 mm (M2.5)
Tightening torque 0.4 to 0.5 Nm
Max. current carrying capacity, incl. loop-through 20 A (15 A per UL/CSA)
Max. cable length 10 m
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 79
Interfaces
4.7 Power supply
Interface assignments
Note
The power supply terminal strip must be screwed on tightly using a flat-bladed screwdriver.
Note
The 24 V is looped through via the 24 V connector. In this case, pin 1 is jumpered with pin 2,
and pin 3 is jumpered with pin 4 in the connector. The maximum current can be limited through
the current carrying capacity of the cable. The current carrying capacity of the cable depends,
for example, on the type of cable installation (cable duct, laying on a cable rack, etc.).
SIMOTION D410-2
80 Manual, 03/2018, A5E33446720B
Interfaces
4.8 Ethernet interface
Properties
SIMOTION D410-2 has an X127 interface for connection to Industrial Ethernet.
Industrial Ethernet is a communication network with a transmission rate of 10/100 Mbit/s.
SIMOTION D410-2 offers the following functions via the Ethernet interface:
● PROFINET basic services (e.g. DCP, LLDP, SNMP)
Although these PROFINET basic services provide uniform functions for the address
assignment and diagnostics, they do not provide PROFINET IO communication for the
connection of drives or I/O modules, for example.
● Communication with STEP 7 and SIMOTION SCOUT
● Communication between SIMOTION and SIMATIC NET OPC
The "SIMATIC NET SOFTNET-S7 (S7-OPC server)" software must be installed on the PG/
PC for this function.
● Connection of HMI systems
● Communication with other devices over TCP/IP or UDP communication
● IT communication (e.g. via SIMOTION IT OPC XML‑DA)
For further information on the software packages, see the SIMOTION PM 21 Catalog.
Interface characteristics
Characteristic Type
Connector type RJ45 socket connector
Cable type Industrial Ethernet cable
Maximum cable 100 m
length
Autocrossing Yes, i.e. both crossed and uncrossed cables can be used
Blanking cover for Ethernet interface included in the scope of delivery;
blanking cover (50 units), article number: 6SL3066‑4CA00‑0AA0
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 81
Interfaces
4.8 Ethernet interface
Interface assignment
Note
The MAC address is on a printed label visible from the front.
SIMOTION D410-2
82 Manual, 03/2018, A5E33446720B
Interfaces
4.9 Measuring sockets
Properties
The T0 - T2 measuring sockets are used to output analog signals. Any interconnectable signal
can be output via SINAMICS on every measuring socket on the control unit.
Note
The measuring sockets are suited for multiple-spring wire connectors with a diameter of 2 mm.
Interface characteristics
Characteristic Type
Connector type 2 mm sockets
Voltage 0 V to 5 V
Resolution 8-bit
Load current max. 3 mA
Sustained short-circuit proof
Reference potential is M terminal
Interface assignment
7
Note
The test sockets are provided as a support to commissioning and diagnostics; they must not
be connected for normal operation.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 83
Interfaces
4.10 Power Module Interface
Figure 4-10 SIMOTION D410-2 interface to the Power Module interface (PM-IF)
Note
SIMOTION D410-2 can only be connected to a SINAMICS Power Module in blocksize format
via the Power Module interface. A Power Module in chassis format must be connected via the
DRIVE‑CLiQ interface (see SIMOTION D410-2 Commissioning and Hardware Installation
Manual).
A SIMOTION D410-2 cannot be operated with SINAMICS G120 (PM2x0) Power Modules.
Booksize Motor Modules can likewise not be connected.
SIMOTION D410-2
84 Manual, 03/2018, A5E33446720B
Technical data 5
5.1 Shipping and storage conditions
The following conditions apply to modules that are shipped and stored in the original
packaging.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 85
Technical data
5.2 Ambient conditions
Conditions of use
SIMOTION D410-2 is designed for use in stationary, weather-protected locations.
SIMOTION D410-2 meets the conditions of use for Class 3C3 according to
DIN EN 60721‑3‑3:1995 (operating locations with high traffic densities and in the immediate
vicinity of industrial equipment with chemical emissions).
Use prohibition
Without additional measures, SIMOTION D410-2 must not be used in
● Locations with a high percentage of ionizing radiation
● Locations with extreme operating conditions, e.g.
– Dust accumulation
– Corrosive vapors or gases
● Installations requiring special monitoring such as:
– Elevator installations
– Electrical systems in particularly hazardous rooms
An additional measure for using SIMOTION D410-2 can, for example, be installation in
cabinets.
Note
The components must be protected against conductive contamination, e.g. by installing them
in a control cabinet with degree of protection IP54 according to IEC 60529 or NEMA 12.
If conductive contamination can be excluded at the installation site, a lower degree of cabinet
protection may be permitted.
SIMOTION D410-2
86 Manual, 03/2018, A5E33446720B
Technical data
5.2 Ambient conditions
Note
Observe the fields of application of the Power Modules along with their derating. Refer to
SINAMICS S120 for AC Drives Manual.
Vibration reduction
If SIMOTION D410-2 is subjected to larger shocks or vibrations, you must use suitable
measures to reduce the acceleration or the amplitude.
We recommend installation on shock-absorbing material (e.g. rubber-metal vibration dampers).
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 87
Technical data
5.2 Ambient conditions
Other data
SIMOTION D410-2
88 Manual, 03/2018, A5E33446720B
Technical data
5.3 System data, connection values, dimensions and weight
Memory
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 89
Technical data
5.3 System data, connection values, dimensions and weight
Note
The memory sizes may be increased for the current version after the time for going to press
for the documentation. The latest values can be found at Internet address (https://
support.industry.siemens.com/cs/ww/en/view/18857317)
CompactFlash card
Mounting plate
SIMOTION D410-2
90 Manual, 03/2018, A5E33446720B
Technical data
5.4 Interfaces and performance features
Table 5-7 Maximum number of axes and minimum cycles for SIMOTION D410-2
5.4.2 Communication
Interfaces
DRIVE-CLiQ interface 1
Ethernet interface 1
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 91
Technical data
5.4 Interfaces and performance features
Address space
Logical address space: Logical addresses can be assigned in STEP 7 within this space.
Physical address space: Address space with assigned data.
The address space contains all the logical addresses, i.e. also diagnostic addresses, I-device,
etc.
SIMOTION D410-2
92 Manual, 03/2018, A5E33446720B
Technical data
5.4 Interfaces and performance features
Number of slaves/devices
Digital inputs
Number of inputs 5
Input voltage
● Rated value ● 24 VDC
● For signal "1" ● 15 … 30 V
● For signal "0" 2)
● -3 … +5 V
Electrical isolation 1) Yes (via optocoupler)
Current consumption typical at 1 signal level 3.5 mA at 24 V
5 mA at 24 V 3)
Input delay, typical (hardware)
● Signal "0" → "1" ● 50 μs
● Signal "1" → "0" ● 150 μs
Permissible quiescent current 2 mA
Protection Protected against polarity reversal
1)
Reference potential for DI 0 ... DI 3 is terminal M2 (X121, X130),
reference potential for DI 22+ is terminal DI 22- (X130)
2)
The digital inputs are protected against polarity reversal up to -30 V
3)
Up to and including hardware version "C" for D410-2 DP or "B" for D410-2 DP/PN
Digital inputs/outputs
Table 5-13 Technical data regarding the digital inputs/outputs with adjustable parameters
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 93
Technical data
5.4 Interfaces and performance features
Input voltage
● Rated value ● 24 VDC
● For signal "1" ● 15 … 30 V
● For signal "0" 2)
● -3 V … +5 V
Galvanic isolation No
Current consumption typical at 1 signal level 3.5 mA at 24 V
5 mA at 24 V 3)
Input delay, typ. (hardware):
● Signal "0" → "1" ● 5 μs
● Signal "1" → "0" ● 50 μs
Measuring input input, resolution 1 µs
Measuring input input, reproducibility Typ. 5 µs
If used as an output
Rated load voltage, permissible range 24 VDC, 20.4 ... 28.8 V
Galvanic isolation No
Current load, max. 500 mA per output
Residual current, max. 2 mA
Output delay time,
typ./max. (hardware) 1) ● 150 μs / 400 μs
● Signal "0" → "1" ● 75 μs / 100 μs
● Signal "1" → "0"
Output cam output, resolution Typ. 125 µs
Output cam output, reproducibility Typ. 125 µs
Switching frequency of the outputs, max.
● With resistive load ● 4 kHz
● With inductive load ● 0.5 Hz
● With lamp load (max. 5 W) ● 10 Hz
Protection Short circuit, ground fault and overload proof
Automatic restart after overload tripping
1)
Data for: Vcc = 24 V; load 48 Ω; high ("1") = 90% Vout; low ("0") = 10% Vout
2)
The digital inputs are protected against polarity reversal up to -30 V
3)
Up to and including hardware version "C" for D410-2 DP or "B" for D410-2 DP/PN
SIMOTION D410-2
94 Manual, 03/2018, A5E33446720B
Technical data
5.4 Interfaces and performance features
The max. achievable switching frequency can also be limited by the CU parameter p0799[0]
(sampling time of the inputs/outputs of the CU) or p2048 (PROFIdrive PZD sampling time).
Reproducibility
The reproducibility at the measuring input input depends on the edge steepness of the
measurement signal.
Generally, the following is valid: The steeper the edges of the input signal are, the easier it is
to reproduce the measurement results.
Sloping signals are achieved by switching the signal level to "active". This is typically with rising
edges as the signal here is "actively" switched to HIGH by the digital output (example: Output
of a TM17 module: Rising edge).
Falling edges typically have less edge steepness (signal level that falls slowly), as the signal
level is "not actively" forced to LOW (example: Output of a TM17 module: Falling edge).
Recommendation: Where the connected components do not have special output drivers, the
recommendation is to use the rising edges for measurements.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 95
Technical data
5.4 Interfaces and performance features
Analog input
Number of inputs 1
Galvanic isolation No
Common-mode range -12 … +12 V
Integration time / conversion time (per channel)
● Parameters can be assigned Yes
● Integration time ≥ 62.5 µs
Operational limit (across temperature range, in
relation to the end value of the measuring range
in the input range)
● Voltage input ±0.65%
● Current input ±1.1%
Basic error limit (operational limit at 25° C, in re‐
lation to the end value of the measuring range in
the input range)
● Voltage input ±0.5%
● Current input ±0.5%
Linearity error (with reference to the input range) ±0.05%
Repeatability (in steady state at 25° C, with refer‐ ±0.05%
ence to input range)
When used as analog voltage input
Input voltage range -10 … +10 V
Resolution 12-bit + sign (based on ± 11 V)1)
Input resistance (Ri) > 100 kΩ
Temperature error (with reference to the input ±0.005%
range)
When used as analog current input
Input current range -20 … +20 mA
Resolution 11-bit + sign (based on ± 22 mA)1)
Input resistance (Ri) 250 Ω
SIMOTION D410-2
96 Manual, 03/2018, A5E33446720B
Technical data
5.4 Interfaces and performance features
0D[FDEOHOHQJWK>P@
66,EDXGUDWH>N+]@
Figure 5-1 Maximum cable length depending on the SSI baud rate for SSI encoders
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 97
Technical data
5.4 Interfaces and performance features
Note
The CUA32 control unit adapter also provides an encoder interface for an HTL, TTL or SSI
encoder.
The technical data of the CUA32 adapter module can be found in the SINAMICS S120 AC
Drive Manual.
SIMOTION D410-2
98 Manual, 03/2018, A5E33446720B
Technical data
5.5 Clock
5.5 Clock
Properties Meaning
Type Hardware clock (integrated "real-time clock")
Default setting when delivered DT#1992-01-01-00:00:00
Maximum deviation per day ±5 s
for supply voltage switched on and switched off at
0° to 55° C
Backup time At least 5 days (at 0 to 55° C)
Charging time 1h
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 99
Technical data
5.6 Certificates, approvals, declarations of conformity
SIMOTION D410-2
100 Manual, 03/2018, A5E33446720B
Dimension drawings 6
6.1 SIMOTION D410-2 DP dimension drawing
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 101
Dimension drawings
6.1 SIMOTION D410-2 DP dimension drawing
Note
Overheating if ventilation clearances are too small
Insufficient ventilation clearances result in overheating and therefore in more failures and a
shortened service life of the component.
Maintain 50 mm ventilation clearances above and below the component.
SIMOTION D410-2
102 Manual, 03/2018, A5E33446720B
Dimension drawings
6.2 SIMOTION D410-2 DP/PN dimension drawing
Note
Overheating if ventilation clearances are too small
Insufficient ventilation clearances result in overheating and therefore in more failures and a
shortened service life of the component.
Maintain 50 mm ventilation clearances above and below the component.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 103
Dimension drawings
6.3 Mounting plate dimension drawing
$
0RXQWLQJZLWK
VFUHZV
0RU0
%
%
SIMOTION D410-2
104 Manual, 03/2018, A5E33446720B
Dimension drawings
6.4 CAD data, dimension drawings, and circuit-diagram macros
Circuit-diagram macros
EPLAN circuit-diagram macros are available for the SIMOTION D410-2. The macros assist
you when creating circuit diagrams.
The EPLAN circuit diagram macros can be ordered at the following Internet addresses:
● Drive Technology Configurator Industry Mall (http://www.siemens.com/dt-configurator)
● CAx Download Manager (https://support.industry.siemens.com/my/ww/en/
CAxOnline#CAxOnline)
● Product support Support (https://support.industry.siemens.com/cs/ww/en/view/31622426)
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 105
Dimension drawings
6.4 CAD data, dimension drawings, and circuit-diagram macros
SIMOTION D410-2
106 Manual, 03/2018, A5E33446720B
Spare parts / accessories 7
7.1 Available spare parts and accessories
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 107
Spare parts / accessories
7.1 Available spare parts and accessories
Reference
You can find order data information for other SINAMICS drive components, such as Line
Modules, Motor Modules, DRIVE-CLiQ cables, etc. in Catalog SIMOTION PM 21.
Note
The procedure for replacing the SIMOTION D410‑2 fan is described in the
SIMOTION D410‑2 Commissioning and Hardware Installation Manual.
Spares On Web
Spares On Web is an information system that enables you to find out which spare parts are
available for your device. For information, visit the following Internet address (https://
www.sow.siemens.com).
In order to view the spare parts, you require the article number and the serial number of the
module.
Both numbers can be found on the rating plate on the module or the packaging label.
SIMOTION D410-2
108 Manual, 03/2018, A5E33446720B
Spare parts / accessories
7.2 TM31 terminal module
Characteristics
The TM31 Terminal Module allows you to expand the number of available digital I/Os as well
as the number of analog I/Os within a drive system. The TM31 is connected via DRIVE-CLiQ.
It has 2 DRIVE-CLiQ interfaces for this.
Interfaces
The TM31 contains the following terminals:
Interface Quantity
Digital inputs 8
Bidirectional inputs/outputs 4
Relay outputs with changeover contact 2
Analog inputs 2
Analog outputs 2
Temperature sensor input (KTY84-130 or PTC) 1
NOTICE
Overheating if ventilation clearances are too small
Insufficient ventilation clearances result in overheating and therefore in more failures and a
shortened life of the component.
Maintain 50 mm ventilation clearances above and below the component.
Additional references
For further information on the TM31 Terminal Module, see the SIMOTION D410-2
Commissioning and Hardware Installation Manual.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 109
Spare parts / accessories
7.3 TM41 terminal module
Characteristics
The TM41 Terminal Module can be used to expand the number of digital I/Os and analog
inputs within a drive system. In addition, it enables the use of the TTL output for encoder
simulation. The TM41 is connected via DRIVE-CLiQ.
Interfaces
The TM41 contains the following terminals:
Type Quantity
Digital inputs 4
Digital I/Os 4
Analog inputs 1
TTL encoder output 1
NOTICE
Overheating if ventilation clearances are too small
Insufficient ventilation clearances result in overheating and therefore in more failures and a
shortened life of the component.
Maintain 50 mm ventilation clearances above and below the component.
Additional references
For further information on the TM41 Terminal Module, see the SIMOTION D410-2
Commissioning and Hardware Installation Manual.
SIMOTION D410-2
110 Manual, 03/2018, A5E33446720B
Spare parts / accessories
7.4 TM54F terminal module
Characteristics
The TM54F Terminal Module is a terminal expansion module for snapping on to a DIN EN
60715 mounting rail. The TM54F offers safe digital inputs and outputs for control of Safety
Integrated functions of SINAMICS.
A SIMOTION D410‑2 can be assigned exactly one TM54F which is connected via DRIVE-CLiQ.
The TM54F Terminal Module is an alternative to using Safety Integrated functions via the
onboard terminals (F‑DI, F‑DO) or via PROFIsafe.
Interfaces
Type Quantity
Fail-safe digital outputs (F‑DO) 1)
4
Fail-safe digital inputs (F‑DI) 2)
10
Sensor power supplies, can be made dynamic 3), 4) 2
Sensor power supply, cannot be made dynamic 3) 1
Digital inputs for testing the F‑DO during test stop 4
1)
A fail-safe digital output consists of a P/M-switching output as well as a digital input for reading back
the switching state.
2)
A fail-safe digital input consists of two digital inputs.
3)
Sensors: Fail-safe devices for commanding and detecting, such as emergency stop pushbuttons and
safety locks as well as position switches and light arrays / light curtains.
4)
Dynamic response: The sensor power supply is switched on and off during test stop for testing the
sensors, the cable routing, and the evaluation electronics of TM54F.
NOTICE
Overheating if ventilation clearances are too small
Insufficient ventilation clearances result in overheating and therefore in more failures and a
shortened life of the component.
Maintain 50 mm ventilation clearances above and below the component.
Additional references
You find detailed information on the TM54F Terminal Module in the SINAMICS S120 Safety
Integrated Function Manual.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 111
Spare parts / accessories
7.4 TM54F terminal module
See also
DRIVE-CLiQ interface (Page 50)
SIMOTION D410-2
112 Manual, 03/2018, A5E33446720B
Spare parts / accessories
7.5 TM15 and TM17 High Feature terminal modules
Characteristics
The TM15 and TM17 High Feature Terminal Modules are used to implement inputs of
measuring inputs and outputs of output cams for SIMOTION D. In addition, these Terminal
Modules provide drive-related digital I/Os with short signal delay times. TM15 and TM17 High
Feature are connected by means of DRIVE-CLiQ.
TM15
Each of the 24 electrically isolated digital I/Os can be parameterized channel-by-channel as
a digital input (DI), digital output (DO), a measuring input input, or an output cam output.
TM15 DI/DO
Each of the 24 isolated digital I/Os can be configured on a channel-specific basis as a digital
input (DI) or digital output (DO). The digital I/Os can be interconnected using BICO technology
and thus used from the drive side as well. Unlike the TM15, measuring input inputs and cam
outputs are not available with the TM15 DI/DO.
Note
The module hardware for TM15 and TM15 DI/DO is identical. A distinction is only made by the
addition of the component in the SIMOTION SCOUT project navigator using "Inserting I/O
component".
NOTICE
Overheating if ventilation clearances are too small
Insufficient ventilation clearances result in overheating and therefore in more failures and a
shortened life of the component.
Maintain 50 mm ventilation clearances above and below the component.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 113
Spare parts / accessories
7.5 TM15 and TM17 High Feature terminal modules
Additional references
Detailed information about the TM15 and TM17 High Feature can be found in the SIMOTION
Terminal Modules TM15 / TM17 High Feature Commissioning Manual.
SIMOTION D410-2
114 Manual, 03/2018, A5E33446720B
Spare parts / accessories
7.6 CUA31/CUA32 control unit adapter
Properties
You can connect a Power Module in blocksize format to the DRIVE-CLiQ interface using the
CUA31 adapter module. The CUA32 adapter module also provides an encoder interface for
an HTL, TTL or SSI encoder.
Interfaces
NOTICE
Overheating if ventilation clearances are too small
Insufficient ventilation clearances result in overheating and therefore in more failures and a
shortened life of the component.
Maintain 50 mm ventilation clearances above and below the component.
Additional references
You will find more information on the CUA31/CUA32 Control Unit Adapter in the
SINAMICS S120 AC Drive Manual.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 115
Spare parts / accessories
7.7 DMC20/DME20 DRIVE-CLiQ hub
Characteristics
The DMC20 and DME20 DRIVE‑CLiQ hub modules are used to implement point-to-point
distribution of a DRIVE‑CLiQ line.
● DMC20 is the hub for the control cabinet configuration
● DME20 is the hub for use without a control cabinet (IP67 degree of protection).
The modules are particularly well suited to applications that require DRIVE-CLiQ link nodes
to be removed in groups without interrupting the DRIVE-CLiQ link and therefore the data
exchange.
The DMC20/DME20 is also used with a SIMOTION D410‑2 when a second encoder is
required. As an SMx Sensor Module and a motor with DRIVE-CLiQ interface only have one
DRIVE-CLiQ interface, a DMC20/DME20 must be used for a second encoder via DRIVE-CLiQ.
If a CUA31/CUA32 is used, the DMC20/DME20 is not required. Alternatively, a second encoder
can also be connected via the X23 interface on the SIMOTION D410‑2.
NOTICE
Overheating if ventilation clearances are too small
Insufficient ventilation clearances result in overheating and therefore in more failures and a
shortened life of the component.
Maintain 50 mm ventilation clearances above and below the component. The ventilation
openings may not be covered by connecting cables.
Additional references
You will find detailed information about the DMC20/DME20 in the SINAMICS S120 Control
Units and Additional System Components Manual.
SIMOTION D410-2
116 Manual, 03/2018, A5E33446720B
Standards and approvals A
A.1 General rules
CE marking
Our products satisfy the requirements and protection objectives of the EC Directives and comply with
the harmonized European standards (EN).
Electromagnetic compatibility
Standards for EMC are satisfied if the EMC Installation Guideline is observed.
SIMOTION products are designed for industrial use in accordance with product standard DIN
EN 61800‑3, Category C2.
cULus approval
Listed component mark for United States and the Canada Underwriters Laboratories (UL) according to
Standard UL 508, File E164110, File E115352, File E85972.
You can find further information on the respective device on the Internet at http://
database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm Enter the first seven
characters of the article number at Keyword. Then click Search.
Korea certification
Declaration of conformity
The current Declaration of conformity is available on the Internet at Declaration of conformity
(https://support.industry.siemens.com/cs/ww/en/ps/14506/cert)).
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 117
Standards and approvals
A.1 General rules
SIMOTION D410-2 satisfies the requirement of the standard AS/NZS CISPR 16.
or
Marking with RCM (Regulatory Compliance Mark) or C-Tick with older components.
SIMOTION D410-2
118 Manual, 03/2018, A5E33446720B
Standards and approvals
A.2 Device-specific information
Note
The product standard EN 61800-3 describes the EMC requirements placed on "Variable-speed
drive systems". As such, it defines different limits depending on the location of the drive system.
SINAMICS S120 power units are designed for use in the second environment. The term second
environment refers to all locations outside residential areas. These are basically industrial
areas which are supplied from the medium-voltage line supply via their own transformers.
It is essential to follow the installation instructions in the SINAMICS S120 Manuals in order to
ensure compliance with emitted interference and immunity values.
The same installation instructions apply for the SIMOTION D410-2 Control Unit as for the
SINAMICS S120 CU310-2 Control Unit with regard to EMC.
For further information on this topic also refer to the SIMOTION PM 21 Catalog as well as the
SINAMICS Function Manuals.
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 119
Standards and approvals
A.2 Device-specific information
SIMOTION D410-2
120 Manual, 03/2018, A5E33446720B
ESD guidelines B
B.1 ESD definition
NOTICE
Damage caused by electric fields or electrostatic discharge
Electric fields or electrostatic discharge can result in malfunctions as a result of damaged
individual parts, integrated circuits, modules or devices.
● Only pack, store, transport and send electronic components, modules or devices in their
original packaging or in other suitable materials, e.g conductive foam rubber or aluminum
foil.
● Only touch components, modules and devices if you are first grounded by applying one
of the following measures:
– Wearing an ESD wrist strap
– Wearing ESD shoes or ESD grounding straps in ESD areas with conductive flooring
● Only place electronic components, modules or devices on conductive surfaces (table with
ESD surface, conductive ESD foam, ESD packaging, ESD transport container).
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 121
ESD guidelines
B.2 Electrostatic charging of individuals
9ROWDJHLQN9
N9 6\QWKHWLFPDWHULDO
:RRO
$QWLVWDWLFPDWHULDOHJZRRGRUFRQFUHWH
5HODWLYHDLUKXPLGLW\LQ
SIMOTION D410-2
122 Manual, 03/2018, A5E33446720B
ESD guidelines
B.3 Basic measures for protection against discharge of static electricity
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 123
ESD guidelines
B.3 Basic measures for protection against discharge of static electricity
SIMOTION D410-2
124 Manual, 03/2018, A5E33446720B
Index
without Safety Integrated Extended Functions, 75
without Safety Integrated functions, 71
A cULus approval, 117
Accessories, 107
CUA31/CUA32, 115
DMC20 DRIVE-CLiQ hub module, 116
D
DME20 DRIVE-CLiQ hub module, 116 Declaration of conformity, 117
TM15, 113 DIAG button, 45
TM15 DI/DO, 113 Diagnostic buffer, 89
TM17 High Feature, 113 Digital I/Os, 61
TM31, 109 Bidirectional, 70
TM41, 110 Connection examples, 75
TM54F, 111 Fail-safe, 69
Address space, 92 Digital inputs/outputs
Ambient conditions Connection examples, 71
Climatic, 86 Technical data, 93
Mechanical, 86 Dimension drawing, 105
Analog input, 61 Mounting plate, 104
SIMOTION D410-2 DP, 101
SIMOTION D410-2 DP/PN, 103
B Dimensions, 89
Display elements, 41
Backup
DMC20
Non-volatile data, 89
Characteristics, 116
DMC20 (hub)
Characteristics, 116
C DME20
CAD data, 105 Characteristics, 116
CE marking, 117 DME20 hub
CF card Characteristics, 116
Slot, 47 DRIVE-CLiQ
CF card, 37 Connectable devices, 51
Data matrix code, 39 Interface, 50
Licenses, 37 Interface assignment, 50
Properties, 36 Interface characteristics, 50
Rating plate, 37
Technical data, 90
Circuit-diagram macro, 105 E
Clock, 99
Electrical connection values, 89
Component
Electromagnetic compatibility, 117
on DRIVE-CLiQ, 27
EMC directives, 117
on Ethernet, 27
Encoder interface, 58
on PROFIBUS, 25
Interface assignment, 59
on PROFINET, 26
Interface characteristics, 58
Conditions of use, 86
ESD guideline, 121
Connection examples
Ethernet
with Safety Integrated Extended/Advanced
Connectable devices, 81
Functions, 73, 77
Interface, 81
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 125
Index
G O
Guideline Operator controls, 41
ESD, 121 DIAG button, 45
Mode switch, 43
RESET button, 46
H Service selector switch, 42
Switch S5.0, 46
Hardware components, 22
P
I
Performance
I/O systems
Motion Control, 91
PROFINET, 26
PLC, 91
Interface assignment
PLC and motion control
X120, 63
SIMOTION D410-2 DP performance, 91
X121, 66
SIMOTION D410-2 DP/PN performance, 91
X130, 67
Possible applications, 22
X131, 68
PROFIBUS DP interface
Interfaces, 49
Assignment, 53
Analog input (X131), 61
PROFINET IO interface
Digital I/Os, 61
Assignment, 55
DRIVE-CLiQ (X100), 50
Encoder interface (X23), 58
Ethernet (X127), 81
Measuring socket, 83
R
Power Module Interface, 84 Rating plate
Power supply, 79 CF card, 37
PROFIBUS DP, 25, 53 SIMOTION D410-2, 34
PROFINET, 26 Real-time clock, 99
PROFINET IO, 55 References, 4
Temperature sensor connection (X120), 64 RESET button, 46
Runtime licenses, 37
L
LED displays, 48
S
Licenses Safety instructions, 17
Runtime, 37 Service selector switch, 42
Licensing, 40 Shipping conditions, 85
Software components, 23
Spare parts, 107
M Storage conditions, 85
MAC address, 34
Measuring socket, 83
Memory
T
SIMOTION D410-2, 89 Technical data
Mode switch, 43 Address space, 92
Mounting plate Analog input, 96
Data, 90 CF card, 90
Clock, 99
SIMOTION D410-2
126 Manual, 03/2018, A5E33446720B
Index
Communication, 91
Digital inputs/outputs, 93
Encoder interface, 97
Mounting plate, 90
SIMOTION D410-2 memory, 89
Temperature sensor connection, 64
Terminal Module
TM15, 113
TM15 DI/DO, 113
TM17 High Feature, 113
TM31, 109
TM41, 110
TM54F, 111
U
UL certification, 117
W
Weight, 89
SIMOTION D410-2
Manual, 03/2018, A5E33446720B 127
Index
SIMOTION D410-2