Carel mC2SE User Manual Eng

Download as pdf or txt
Download as pdf or txt
You are on page 1of 52

µC2SE for process chiller

electronic control

User manual
IMPORTANT WARNINGS

ENGLISH
CAREL bases the development of its products on several years’ experience in the HVAC field, on
continuous investment in technological innovation of the product, on rigorous quality procedures and
processes with in-circuit and function tests on 100% of its production, on the most innovative production
technologies available on the market. CAREL and its branch offices/affiliates do not guarantee, in any
case, that all the aspects of the product and the software included in the product will respond to the
demands of the final application, even if the product is built according to state-of-the-art techniques. The
client (builder, developer or installer of the final equipment) assumes every responsibility and risk relating
to the configuration of the product in order to reach the expected results in relation to the specific final in-
stallation and/or equipment. CAREL in this case, through specific agreements, can intervene as consultant
for the positive result of the final start-up machine/application, but in no case can it be held responsible
for the positive working of the final equipment/apparatus.
The CAREL product is a state-of-the-art product, whose operation is specified in the technical documen-
tation supplied with the product or can be downloaded, even prior to purchase, from the website www .
carel. com.
Each CAREL product, in relation to its advanced technological level, needs a phase of definition / con-
figuration / programming / commissioning so that it can function at its best for the specific application.
The lack of such phase of study, as indicated in the manual, can cause the final product to malfunction of
which CAREL can not be held responsible.
Only qualified personnel can install or carry out technical assistance interventions on the product.
The final client must use the product only in the manner described in the documentation related to the
product itself.
Without excluding proper compliance with further warnings present in the manual, it is stressed that in
any case it is necessary, for each Product of CAREL:
• To avoid getting the electrical circuits wet. Rain, humidity and all types of liquids or condensation
contain corrosive mineral substances that can damage the electrical circuits. In any case, the product
should be used and stored in environments that respect the range of temperature and humidity
specified in the manual.
• Do not install the device in a particularly hot environment. Temperatures that are too high can shorten
the duration of the electronic devices, damaging them and distorting or melting the parts in plastic. In
any case, the product should be used and stored in environments that respect the range of temperatu-
re and humidity specified in the manual.
• Do not try to open the device in any way different than that indicated in the manual.
• Do not drop, hit or shake the device, because the internal circuits and mechanisms could suffer
irreparable damage.
• Do not use corrosive chemical products, aggressive solvents or detergents to clean the device.
• Do not use the product in application environments different than those specified in the technical
manual.
All the above reported suggestions are valid also for the control, serial unit, programming key or never-
theless for any other accessory in the product portfolio of CAREL.
CAREL adopts a policy of continuous development. Therefore, CAREL reserves the right to carry out
modifications and improvements on any product described in the present document without prior notice.
The technical data in the manual can undergo modifications without obligation to notice.
The liability of CAREL in relation to its own product is regulated by CAREL’s general contract conditions
edited on the website www .carel. com and/or by specific agreements with clients; in particular, within the
criteria consented by the applicable norm, in no way will CAREL, its employees or its branch offices/affi-
liates be responsible for possible lack of earnings or sales, loss of data and information, cost of substitute
goods or services, damage to things or persons, work interruptions, or possible direct, indirect, incidental,
patrimonial, of coverage, punitive, special or consequential in any way caused damages, be they con-
tractual, out-of-contract, or due to negligence or other responsibility originating from the installation, use
or inability of use of the product, even if CAREL or its branch offices/affiliates have been warned of the
possibility of damage.
Disposal of the product
In reference to European Community directive 2002/96/EC issued on 27 January 2003 and
the related national legislation, please note that:
1. we cannot be disposed of as municipal waste and such waste must be collected and
disposed of separately;
2. the public or private waste collection systems defined by local legislation must be used. In addition,
the equipment can be returned to the distributor at the end of its working life when buying new
equipment.
3. the equipment may contain hazardous substances: the improper use or incorrect disposal of such may
have negative effects on human health and on the environment;
4. the symbol (crossed-out wheeled bin) shown on the product or on the packaging and on the instruc-
tion sheet indicates that the equipment has been introduced onto the market after 13 August 2005 and
that it must be disposed of separately;
5. in the event of illegal disposal of electrical and electronic waste, the penalties are specified by local
waste disposal legislation.

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 3


ENGLISH

4 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


CONTENTS
1. INTRODUCTION 7

ENGLISH
1.1 General description ..............................................................................................................................7
1.2 User interface ........................................................................................................................................7

2. CONNECTIONS 9
2.1 General diagram ...................................................................................................................................9
2.2 Network layout .....................................................................................................................................9

3. APPLICATIONS 10
3.1 AIR/WATER chiller.................................................................................................................................10
3.2 WATER/WATER chiller .........................................................................................................................11

4. PARAMETERS 13
4.1 General parameters .............................................................................................................................13
4.2 Menu structure .....................................................................................................................................13
4.3 Parameter tables ..................................................................................................................................14

5. DESCRIPTION OF THE PARAMETERS 23

6. TABLE OF ALARMS 48

7. CONNECTIONS, ACCESSORIES AND OPTIONS 52


7.1 Connection diagram ..............................................................................................................................52
7.2 Expansion card .......................................................................................................................................53
7.3 EVD4*: Electronic expansion valve driver ........................................................................................53
7.4 Fan speed control board (code MCHRTF*).....................................................................................54
7.5 Fan ON/OFF control board (code CONVONOFF0) ......................................................................54
7.6 PWM to 0 to 10Vdc (or 4 to 20 mA)conversion board for fans ...............................................
(code CONV0/10A0)....................................................................................................................................54
7.7 Minimum and maximum fan speed calculation .............................................................................54
7.8 Programming key (code PSOPZKEYA0) ...........................................................................................55
7.9 RS485 serial options..............................................................................................................................56
7.10 Terminals ................................................................................................................................................56

8. DIMENSIONS 57

9. CODES 59

10. TECHNICAL SPECIFICATIONS AND SOFTWARE UPDATES 59


10.1 Technical specifications .....................................................................................................................59
10.2 Software updates................................................................................................................................60

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 5


ENGLISH

6 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


1. INTRODUCTION

ENGLISH
1.1 General description
The μC2SE is a compact CAREL electronic controller, the same size as a normal
thermostat, for the complete management of process chillers: it can control air-water
and water-water.

1.1.1 Main functions


• control of the water inlet and evaporator outlet temperature;
• defrost management by time and/or by temperature or pressure;
• fan speed control;
• complete alarm management;
• connection to serial line for supervision/telemaintenance;
• elimination of the expansion vessel.
- Driver function
• Management of electronic expansion valves.

1.1.2 Controlled devices


• compressor;
• condenser fans;
• water pumps for evaporator and/or condenser;
• antifreeze heater;
• alarm signal device.

1.1.3 Programming
CAREL offers the possibility to configure all the unit parameters not only from the
keypad on the front panel, but also using:
• a hardware key;
• a serial line.

1.2 User interface


1.2.1 Display I J
The display features 3 digits, with the display of the decimal point between -99.9 and
99.9.
Outside of this range of measurement, the value is automatically displayed without the
decimal (even if internally the unit still operates considering the decimal part). H
In normal operation, the value displayed corresponds to the temperature read by probe G
B1, that is, the evaporator water inlet temperature.
F
Fig. 1.a show the symbols present on the display and on the keypad and their meanings.

E D C B A L K

1.2.2 Symbols on the display Fig. 1.a


Display with 3 green digits (plus sign and decimal point), amber symbols and red alarm
symbols.

symbol colour meaning reference


with LED ON with LED flashing refrigerant
circuit
1; 2 amber compressor 1 and/or 2 ON start up request 1
1; 3 amber compressor 3 and/or 3 ON start up request 2
A amber at least one compressor ON 1/2
B amber pump ON start up request 1/2
C amber condenser fan ON 1/2
D amber defrost active defrost request 1/2
E amber heater ON 1/2
F red alarm active 1/2
G amber heat pump mode heat pump mode request 1/2
H amber chiller mode chiller mode request 1/2
Table 1.a

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 7


1.2.3 Functions associated with the buttons
button unit status button press
ENGLISH

I Loading default values press at power ON


Go up a sub-group inside the programming area, until exiting (saving changes to EEPROM) press once
In the event of alarms, mute the buzzer (if present) and deactivate the alarm relay press once
L Access the direct parameters press for 5 s
Select item inside the programming area and display value of direct parameters/confirm the changes to the parameters press once
I+L Program parameters afters entering password press for 5 s
J Select top item inside the programming area press once or press and hold
Increase value press once or press and hold
Switch from standby to chiller mode (P6=0) and vice versa press for 5 s
Provides immediate access to the condenser and evaporator pressure and temperature probes and DTE, DTC1-2 press once
K Select bottom item inside the programming area press once or press and hold
Decrease value press once or press and hold
Provides immediate access to the condenser and evaporator pressure and temperature probes and DTE, DTC1-2 press once
J+K Manual alarm reset press for 5 s
Immediately reset the hour counter (inside the programming area) press for 5 s
L+J Force manual defrost on both circuits press for 5 s
Table 1.b

1.2.4 Programming and saving the parameters


1. press “ “ and “ ” for 5 seconds;
2. the heating and cooling symbol and the figure “00” are displayed;
3. use “ ” and “ ” to set the password (page 28) and confirm by pressing “ ”;
4. use “ ” and “ ” to select the parameter menu (S-P) or levels (L-P) and then press “ ”;
5. use “ ” and “ ” to select the parameter group and then press “ ”;
6. use “ ” and “ “ to select the parameter and then press “ ”;
7. after making the changes to the parameter, press “ ” to confirm or “ ” to cancel the changes;
8. press “ ” to return to the previous menu;
9. to save the modifications, press “ ” repeatedly until reaching the main menu.
Note:
a. the parameters that have been modified without being confirmed using the “ ” button return to the
previous value;
b. if no operations are performed on the keypad for 60 seconds, the controller exits the parameter
modification menu by timeout and the changes are cancelled.

1.2.5. Keypad
The keypad is used to set the unit operating values (see Parameters/alarms - Keypad combinations)

8 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


2. CONNECTIONS

ENGLISH
2.1 General diagram

EVD*40*: MCH200002*: EVD*40*:


driver I/O expansion driver for
for electronic board for electronic
expansion µ2SE expansion
Optional board valve valve

PSOPZKEY*:
CONVONOFF*: programming key
PWM/digital
converter

CONV0/10A0*: PW/Modbus® RTU


PWM/analogic CAREL Supervisory
converter MCH200485*
NTC: temperature RS485
probes MCH2*T*:
serial card
terminal
MCHRTF**A0:
fan speed regulator SPKT: 0 to 5 V MCH2*TSV*: PW/Modbus® RTU
pres. transducer adapter CAREL Supervisory

Fig. 2.a

2.2 Network layout

EV driver

Fig. 2.b

EV driver EV driver
ESP.

Fig. 2.c
2
µC SE process chiller +030220416 - rel. 1.1 - 27.04.2010 9
3. APPLICATIONS
ENGLISH

3.1 AIR/WATER chiller

3.1.1 Single circuit

Key: 1
1 condernser fan overload 2
2 fan
3 condenser probe
4 flow switch 3
5 outlet evaporator probe
6 fan 4
7 antifreeze heater
8 inlet evaporator probe
9 compressor 1 5
10 high pressure
11 compressor overload
12 low pressure
13 water pump
14 compressor 2

6 7

13

10 11 12

14

Fig. 3.a.a

3.1.2 Two circuits, 2 condenser fan circuits and 2 evaporators

Key:
1 1 2 1
1 condenser fan overload 1 and 2
2 fan 1 and 2 1 2 4 2 2
3 condenser probe 1 and 2
4 flow switch 5
5 outlet temperature probe 1 3 2 3
6 evaporator 1 and 2
7 outlet evaporator probe 1 and 2 7 1
8 antefreeze heater 1 and 2
9 compressor 1
10 high pressure 1 and 2 2 7
11 compressor overload 1 and 2
12 low pressure 1and 2
13 inlet evaporator probe
14 compressor 2 1 6 8 8 6 2
1 2
15 water pump
16 compressor 3
17 compressor 4

9 16
13

10 1 1 11 12 1 12 11 10

15
14 17

Fig. 3.a.b

10 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


ENGLISH
3.1.3 Two circuits, 1 condenser fan circuit

Key:
1
1 3 2 3 1 condenser fan overload
2 fan
2 3 condenser probe 1 and 2
4 flow switch
5 outlet temperature probe
4 6 evaporator 1 and 2
7 outlet evaporator probe 1 and 2
8 antifreeze heater 1 and 2
5
9 compressor 1
10 high pressure 1 and 2
11 compressor overload 1 and 2
12 low pressure 1and 2
7 1 7 13 inlet evaporator probe
2
14 compressor 2
15 water pump
16 compressor 3
6 17 compressor 4
1 8 1 2 8 6 2

9 16

13
10 1 1 11 12 1 2 12 11 2 10 2

15
14 17

Fig. 3.a.c

3.2 WATER/WATER chiller


3.2.1 Single circuit
Key:
1 water condensing temperature probe
3 2 condensator
3 flow switch
4 outlet evaporator probe
1 4 5 evaporator
6 antifreeze heater
7 inlet evaporator probe
8 compressor 1
9 high pressure
2 10 compressor overload
11 low pressure
6 12 water pump
5 13 compressor 2

7
8

9 10 11 12

13

Fig. 3.b.a

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 11


3.2.2 Two circuits
ENGLISH

Key:
1 water condensing temperature probe 1 and 2
2 condensator 1 and 2 3
3 flow switch
4 outlet evaporator probe
5 evaporator 1 4 1
1 2
6 antifreeze heater 1 and 2
7 compressor 1
8 high pressure 1 and 2
9 compressor overload 1 and 2
10 low pressure 1 and 2
11 inlet evaporator probe 2 1 2
2
12 water pump
13 compressor 2
14 compressor 3 6
15 compressor 4
5

7 14

11

8 1 1 9 10 1 2 10 9 2 8 2
12

13 15

12

Fig. 3.b.b

3.2.3 Two circuits, 2 evaporators

Key:
1 water condensing temperature probe 1 and 2 3
2 condensator 1 and 2
3 flow switch 4
4 outlet temperature probe
5 outlet evaporator probe 1 and 2 1
6 antifreeze heater 1 and 2 1 1 2
7 evaporator 5 1 5
8 water pump 2
9 compressor 1
10 high pressure 1 and 2 2
11 compressor overload 1 and 2
2 1
2

12 low pressure 1 and 2


7 6 1 2 6 7
13 compressor 3 1 2
14 compressor 2
15 compressor 4
16 inlet evaporator pressure
9 13
16

10 1 1 11 12 1 2 12 11 2 10 2
8
14 15

Fig. 3.b.c

12 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


4. PARAMETERS

ENGLISH
4.1 General parameters
The parameters are divided into 4 different types, according to their level of access by the user (password)
and their function.
For each level, only the access to the parameters of the same or lower level can be set.
This means that through “factory” password, acessing the menù “levels” (L-P), it is possible to set the
desired level for each parameter.
• Factory parameters: Accessible with the 66 “Factory” password, allow the configuration of all the unit
parameters.
• Super User parameters: Accessible with the 11 “Super User” password, allow the configuration
of the Super User, User and Direct parameters.
• User parameters: Accessible with password 22, allow the configuration of the parameters that typically
can be set by the user (User parameters) and the Direct parameters, consequently relating to the options.
• Direct parameters: Accessible without password, this are used to read the probe measurements and
any data, by any user, without compromising the operation of the unit.

N.B.: The modifications to the parameters regarding the configuration of the unit (type, number of
compressors,...) must be performed with the controller in Standby. level level name password
_d_ direct no password
_U_ user 22
_S_ super user 11
_F_ factory 66
4.2 Menu structure

main menù F or 5”

Sa ve in the EEPROM And F or 5”

setting password

Or Or parameter level
parameter
values
parameters /*

parameters F-r*
parameters A*
probe settings
software
antifreeze

t* parameters

clock settings parameters b*

probes
parameters r*

regulation
parameters c*

parameters P* compressor

alarm

parameters D*

parameters H*
parameters F* defrost
unit setting

fan

parameter values F1 parameters F1 level value F1

Or
parameters Fn

Fig. 4.a
2
µC SE process chiller +030220416 - rel. 1.1 - 27.04.2010 13
4.3 Parameter tables
The following tables show of the parameters divided by type/family (e. g. compressor, probes, fans etc.).
ENGLISH

• Key to the parameter tables


Level (default)
S= super user
F= factory
D= direct
Visibility:
The visibility of some groups depends on the type of controller and the value of the parameters.
D= defrost (if D01=1)
F= fan (if F01=1)
L= low noise (if F15=1-3)
N= NTC probe (if /04-/08=2)
P= pressure (if /04-/08=3)
V= driver (if H08 =1-3)
X= expansion (if H08=2-3)
M= pump down (if D17=1)
W= watch (if the clock board is fitted)
- = always present
Supervisor variables:
R/W = supervisor read/write parameter
R= supervisor read-only parameter

4.3.1 Evaporator and condenser temperature and pressure values: (d*)


display parameter and description default min. max. UOM variat. default visibility supervis. Modbus variable
indicat. level variable type
dtE Current value of DTE D 0 0 - - 0 - 99 (R) 99 Analog
dC1 Current value of DTC1 D 0 0 - - 0 - 100 (R) 100 Analog
dC2 Current value of DTC2 D 0 0 - - 0 - 101 (R) 101 Analog
Tab. 4.a

4.3.2 Probe setting parameters: (/*)


display parameter and description default min. max. UOM variat. default visibility supervis. Modbus variable
indicat. level variable type
/01 Probe type B1 0= not present F 0 1 Flag 1 1 - 1 (R/W) 1 Digital
1= present
/02 Probe type B2 0= not present F 0 1 Flag 1 0 - 2 (R/W) 2 Digital
1= present
/03 Probe type B3 0= not present F 0 3 int 1 0 - 14 (R/W) 221 Integer
1= NTC Cond. Probe
2= NTC Out. Probe
3= differential control probe
/04 Probe type B4 0= not present F 0 4 int 1 0 - 15 (R/W) 222 Integer
1= ON/OFF (D.I)
2= NTC Out. Probe
3= ratiometric cond. Probe, 5 Vdc
4= differential control probe
/05 Probe type B5 0= not present F 0 1 Flag 1 0 X 3 (R/W) 3 Digital
1= present
/06 Probe type B6 0= not present F 0 1 Flag 1 0 X 4 (R/W) 4 Digital
1= present
/07 Probe type B7 0= not present F 0 3 int 1 0 X 16 (R/W) 223 Integer
1= NTC Cond. Probe
2= NTC Out. Probe
3= differential control probe
/08 Probe type B8 0= not present F 0 4 int 1 0 X 17 (R/W) 145 Integer
(expansion) 1= ON/OFF
2= NTC Out. Probe
3= ratiometric cond. Probe, 5 Vdc
4= differential control probe
NB. if more than one differential control probe
is configured, the priority is: B8, B7, B4, B3
/09 Min. value voltage input F 0 /10 0.01 Vdc 1 50 P 18 (R/W) 225 Integer
/10 Max. value voltage input F /09 500 0.01 Vdc 1 450 P 19 (R/W) 226 Integer
/11 Pressure min. value F 0 /12 bar 1 0 P 1 (R/W) 1 Analog
/12 Pressure max. value F /11 999 bar 1 345 P 2 (R/W) 2 Analog
/13 Probe B1 calibration F -12.0 12.0 °C/°F 0.1 0.0 - 3 (R/W) 3 Analog
/14 Probe B2 calibration F -12.0 12.0 °C/°F 0.1 0.0 - 4 (R/W) 4 Analog
/15 Probe B3 calibration F -12.0 12.0 °C/°F 0.1 0.0 - 5 (R/W) 5 Analog
/16 Probe B4 calibration F -12.0 12.0 °C/bar/°F 0.1 0.0 - 6 (R/W) 6 Analog
/17 Probe B5 calibration F -12.0 12.0 °C/°F 0.1 0.0 X 7 (R/W) 7 Analog
/18 Probe B6 calibration F -12.0 12.0 °C/°F 0.1 0.0 X 8 (R/W) 8 Analog
/19 Probe B7 calibration F -12.0 12.0 °C/°F 0.1 0.0 X 9 (R/W) 9 Analog
/20 Probe B8 calibration F -12.0 12.0 °C/bar/°F 0.1 0.0 X 10 (R/W) 10 Analog
/21 Digital filter U 1 15 - 1 4 - 20 (R/W) 227 Integer
/22 Input limitation U 1 15 - 1 8 - 21 (R/W) 228 Integer
/23 Unit of measure 0= °C U 0 1 Flag 1 0 - 5 (R/W) 5 Digital
1= °F
Table. 4.b

14 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


4.3.3 Antifreeze/support heater setting parameters (A*)
display parameter and description default min. max. UOM variat. default visibility supervis. Modbus variable
indicat. level variable type

ENGLISH
A01 Alarm set point antifreeze/low ambient temperature (air/air) U A07 A04 °C/°F 0.1 30 - 11 (R/W) 11 Analog
A02 Differential for antifreeze/low ambient temperature alarm (air/air) U 3 1220 °C °F 0.1 50 - 12 (R/W) 12 Analog
A03 Bypass time for antifreeze alarm/low ambient temp. when turning on the unit U 0 150 s 1 0 - 22 (R/W) 229 Integer
in heating mode
A05 Diff. for antifreeze heater/auxiliary heater U 3 500 °C/°F 0.1 10 - 14 (R/W) 14 Analog
A06 Auxiliary heater probe F 0 1 Flag 1 0 - 6 (R/W) 6 Digital
0= Control probe see (see Table 5.a)
1= Antifreeze probe see (see Table 5.a)
A07 Antifreeze alarm set point limit F -400 1760 °C °F 0.1 -400 - 15 (R/W) 15 Analog
A08 Auxiliary heater set point in heating mode U A01 r16 °C °F 0.1 250 AA 16 (R/W) 16 Analog
A08 Antifreeze/support heater set point differential U 0 200 °C °F 0.1 70 AR 78 (R/W) 78 Analog
A09 Auxiliary heater differential in heating mode U 3 500 °C/°F 0.1 30 - 17 (R/W) 17 Analog
A10 Antifreeze automatic start up U 0 3 1 0 - 23 (R/W) 230 Integer
0= disabled function
1= Heaters and pump on at the same time on A4/A8
2= Heaters and pump on indipendently on A4/A8
3= Heaters ON on A4/A8
A11 Auxiliary heater 2 set point in heating U A01 r16 °C/°F 0.1 250 AA 67 (R/W) 67 Analog
A11 Support heater 2 differential in heating U 0 200 °C/°F 0.1 70 AR 79 (R/W) 79 Analog
A14 Antifreeze alarm set point from EVD U A07 A04 °C/°F 0.1 30 - 82 (R/W) 82 Analog
Table 4.c
4.3.4 Probe reading parameters (b*)
display parameter and description default min. max. U.O.M. variat. default visibility supervis. Modbus variable
indicat. level variable type
b00 Config. of probe to be shown on the display U 0 11 N 1 0 - 24 (R/W) 231 integer
0= probe B1 1= probe B2
2= probe B3 3= probe B4
4= probe B5 5= probe B6
6= probe B7 7= probe B8
8= set point without compensation
9= dynamic set point with possible compensation
10= remote ON/OFF digital input status
11= µAD probe
b01 Value read by probe B1 D 0 0 °C /°F - 0 - 102 (R) 102 Analog
b02 Value read by probe B2 D 0 0 °C /°F - 0 - 103 (R) 103 Analog
b03 Value read by probe B3 D 0 0 °C /°F - 0 - 104 (R) 104 Analog
b04 Value read by probe B4 D 0 0 °C /°F/Dbar - 0 - 105 (R) 105 Analog
b05 Value read by probe B5 D 0 0 °C /°F - 0 X 106 (R) 106 Analog
b06 Value read by probe B6 D 0 0 °C /°F - 0 X 107 (R) 107 Analog
b07 Value read by probe B7 D 0 0 °C /°F - 0 X 108 (R) 108 Analog
b08 Value read by probe B8 D 0 0 °C /°F/Dbar - 0 X 109 (R) 109 Analog
b09 Driver 1 evaporator temperature D 0 0 °C /°F - 0 V 110 (R) 110 Analog
b10 Driver 1 evaporator pressure D 0 0 Dbar - 0 V 111 (R) 111 Analog
b11 Driver 1 superheating D 0 0 °C /°F - 0 V 112 (R) 112 Analog
b12 Driver 1 saturation temperature D 0 0 °C /°F - 0 V 113 (R) 113 Analog
b13 Driver 1 valve position D 0 1000 % - 0 V 114 (R) 114 Analog
b14 Driver 2 evaporator temperature D 0 0 °C /°F - 0 XV 115 (R) 115 Analog
b15 Driver 2 evaporator pressure D 0 0 Dbar - 0 XV 116 (R) 116 Analog
b16 Driver 2 superheating D 0 0 °C /°F - 0 XV 117 (R) 117 Analog
b17 Driver 2 saturation temperature D 0 0 °C /°F - 0 XV 118 (R) 118 Analog
b18 Driver 2 valve position D 0 1000 % - 0 XV 119 (R) 119 Analog
b19 Temp. probe at the outlet of the external coil c1 D 0 0 °C /°F - 0 V 120 (R) 120 Analog
b20 Temp. probe at the outlet of the external coil c12 D 0 0 °C /°F - 0 XV 121 (R) 121 Analog
Table 4.d
4.3.5 Compressor setting parameters (c*)
display parameter and description default min. max. U.O.M. variat. def. visib. supervis. Modbus variabile
indicat. level variable type
c01 Minimum on time U 0 999 s 1 60 - 25 (R/W) 232 Integer
c02 Minimum off time U 0 999 s 1 60 - 26 (R/W) 233 Integer
c03 Delay between 2 starts of the same compressor U 0 999 s 1 360 - 27 (R/W) 234 Integer
c04 Delay between starts of the 2 compressors U 0 999 s 1 10 - 28 (R/W) 235 Integer
c05 Delay between 2 shut-downs of the 2 compressors U 0 999 s 1 0 - 29 (R/W) 236 Integer
c06 Delay at start-up U 0 999 s 1 0 - 30 (R/W) 237 Integer
c07 Delay in switching on the compressor after switching on the pump/inlet U 0 999 s 1 20 - 31 (R/W) 238 Integer
fan (air/air)
c08 Delay in switching OFF the compressor after switching OFF the pump/ U 0 150 min 1 1 - 32 (R/W) 239 Integer
inlet fan (air/air)
c09 Maximum compressor operating time in tandem U 0 60 min 1 0 - 33 (R/W) 240 Integer
c10 Compressor 1 timer D 0 8000 100 hours - 0 - 122 (R) 122 Analog
c11 Compressor 2 timer D 0 8000 100 hours - 0 - 123 (R) 123 Analog
c12 Compressor 3 timer D 0 8000 100 hours - 0 - 124 (R) 124 Analog
c13 Compressor 4 timer D 0 8000 100 hours - 0 - 125 (R) 125 Analog
c14 Operation timer threshold U 0 100 100 hours 1 0 - 34 (R/W) 241 Integer
c15 Hour counter evaporator pump/fan 1 D 0 8000 100 hours - 0 - 126 (R) 126 Analog
c16 Hour counter condenser backup pump/fan 2 D 0 8000 100 hours - 0 - 127 (R) 127 Analog
c17 Minimum time between 2 pump starts U 0 150 min 1 30 - 35 (R/W) 242 Integer
c18 Minimum pump ON time U 0 15 min 1 3 - 36 (R/W) 243 Integer
Table 4.e

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 15


4.3.7 Fan setting parameters (F*)
ENGLISH

display parameter and description default min. max. U.O.M. variat. def. visibility supervis. Modbus variable
indicat. level variable type
F01 Enable Fan output F 0 1 Flag 1 0 - 10 (R/W) 10 Digital
0=not present
1=present
F02 Fan operating mode U 0 3 Int 1 0 F 48 (R/W) 255 Integer
0= always ON
1= depending ON the compressor (in parallel operation mode)
2= depending ON the compressors in ON/OFF control
3= depending ON the compressors in speed control mode
F03 Min. voltage threshold for Triac F 0 F04 step 1 35 F 49 (R/W) 256 Integer
F04 Max. voltage threshold for Triac F F03 100 step 1 75 F 50 (R/W) 257 Integer
F05 Speed temp. set point in Cooling mode U -400 1760 °C/°F 0.1 350 FN 24 (R/W) 24 Analog
Pressure value for min. speed Cooling U /11 /12 Dbar 0.1 130 FP 23 (R/W) 23 Analog
F06 Differential value for max. speed Cooling U 0 500 °C/°F 0.1 100 FN 26 (R/W) 26 Analog
Pressure value for max. speed Cooling U 0 300 Dbar 0.1 30 FP 25 (R/W) 25 Analog
F07 Fan shut-down differential in Cooling mode U 0 500 °C/°F 0.1 150 FN 28 (R/W) 28 Analog
Fan shut-down pressure in Cooling mode U 0 F05 Dbar 0.1 50 FP 27 (R/W) 27 Analog
F12 Triac impulse duration (fan start) F 0 10 s 1 2 F 52 (R/W) 259 Integer
F14 Fan with high condensing temperature when starting U 0 999 - 1 0 FN 91 (R/W) 298 Integer
F15 Low noise activation U 0 1 - 1 0 F 85 (R/W) 292 Integer
0= deactivated
1= activated in cooling
F16 Low noise diff. in cooling F 0 500 °C/°F/bar 0.1 0 L 35 (R/W) 35 Analog
Table 4.g

4.3.8 Unit setting parameters (H*)


display parameter and description default min. max. U.O.M. variat. def. visibility supervis. Modbus variable
indicat. level variable type
H01 Unit model F 2 4 Flag 2 2 - 54 (R/W) 261 Integer
2= air_water chiller
4= water_water chiller
H02 Number of condensers U 0 1 Flag 1 0 - 12 (R/W) 12 Digital
0=1 circuit; 1=2 circuits
H03 Number of evaporators F 0 1 Flag 1 0 - 13 (R/W) 13 Digital
0=1 evaporator; 1=2 evaporators
H04 Number of compressors per circuit F 0 5 Flag 1 0 - 55 (R/W) 262 Integer
0=1 comp. ON 1 circuit (single circuit)
1=2 comp. in tandem ON 1 circuit (single circuit)
2=1 comp. per circuit, 2 circuits (two circuits)
3=2 comp. in Tandem, 2 circuits (two circuits)
4=1 compressor and 1 Capacity step in one circuit
5=1 compressor and 1 capacity Step per circuit
H05 Pump/outlet fan (Air/Air) mode (output N2) F 0 3 Flag 1 1 - 56 (R/W) 263 Integer
0= absent
1= always ON
2= ON upon request of the controller
3= ON upon request of the controller and for set time
H06 Cooling/Heating digital input U 0 1 Flag 1 0 - 14 (R/W) 14 Digital
0= absent; 1= present
H07 ON/OFF digital input U 0 1 Flag 1 0 - 15 (R/W) 15 Digital
0= absent; 1= present
H08 µC2 network configuration F 0 7 Flag 1 4 - 57 (R/W) 264 Integer
0= µC2SE only
1= µC2SE + EVD
2= µC2SE + exp.
3= µC2SE + exp. + EVD
4= µC2SE + I/O
5= µC2SE + EVD + I/O
6= µC2SE + exp. + I/O
7= µC2SE + I/O + EVD + exp.
H09 Lock keypad U 0 1 Flag 1 1 - 16 (R/W) 16 Digital
0= disabled; 1= enabled
H10 Serial address U 1 200 - - 1 - 58 (R/W) 265 Integer
0= use as terminal
H11 Output modes (see Table 5.3 and following pag. 56) F 0 12 Int 1 0 - 59 (R/W) 266 Integer
H12 Capacity-control and reversing valve logic F 0 3 Flag 1 1 - 60 (R/W) 267 Integer
0= Both normally closed
1= Both normally open
2= Inversion valve normally open and capacity-control valve normally closed
3= Inversion valve normally closed and capacity-control valve normally open
H13 Activate pump down F 0 1 - 1 0 V 17 (R/W) 17 Digital
H14 Minimum pump down pressure F 0 500 Dbar 0.1 20 M 37(R/W) 37 Analog
H15 Maximum pump down time F 0 180 s 1 30 M 61 (R/W) 268 Integer
H21 Second pump function F 0 4 int 1 0 - 62 (R/W) 269 Integer
0= Disabled
1= Backup and weekly rotation
2= Backup and daily rotation
3= Condensing control on corresponding set point
4= Condensing control always on

16 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


display parameter and description default min. max. U.O.M. variat. def. visibility supervis. Modbus variable
indicat. level variable type
H22 Disable load default values F 0 1 Flag 1 0 - 18 (R/W) 18 Digital

ENGLISH
0= Function disabled
1= Function enabled
H23 Enable Modbus® F 0 1 Flag 1 0 - 11 (R/W) 11 Digital
H24 Set the mode of high temperature alarm F 0 3 Flag 1 0 - 124 (R/W) 331 Integer
0= no stop
1= high temperature stops compressor
2= low temperature stops compressor
3= high and low temperature stops
H25 Hot as bypass function enable F 0 1 Flag 1 0 - 25 (R/W) 25 Digital
0= disable; 1= enable
H26 Special stand by mode enable F 0 1 Flag 1 0 - 26 (R/W) 26 Digital
0= disable; 1= enable
Table 4.h

4.3.9 Firmware parameters (F-r*)


display parameter and description default min. max. U.O.M. variat. default visibility supervis. Modbus variable type
indicat. level variable
H99 Software version, Driver 2 D 0 999 Int - 14 - 1 (R) 208 Integer
H98 Software version, Driver 1 D 0 999 Int - 0 X 2 (R) 209 Integer
H97 Expansion software version D 0 999 Int - 0 V 3 (R) 210 Integer
H96 Software version (displayed when powering up the D 0 999 Int - 0 XV 4 (R) 211 Integer
instrument)
H95 I/O board software version D 0 999 Int - 0 - 149 (R) 356 Integer
Table 4.i

4.3.10 Alarm setting parameters (P*)


display parameter and description default min. max. U.O.M. variat. def. visibility supervis. Modbus variable
indicat. level variable type
P01 Flow switch alarm delay when starting the pump U 0 150 s 1 20 - 63 (R/W) 270 Integer
P02 Flow switch alarm delay during steady operation U 0 120 s 1 5 - 64 (R/W) 271 Integer
P03 Low pressure alarm delay at compressor start-up U 0 200 s 1 40 - 65 (R/W) 272 Integer
P04 Enable compressor capacity-control with high pressure U 0 3 Flag 1 0 P 66 (R/W) 273 Integer
0= capacity control deactivated
1= capacity-control with high pressure active
2= capacity-control with low pressure active
3= capacity-control with high and low pressure active
P05 Alarm reset F 0 6 Flag 1 0 - 67 (R/W) 274 Integer
0= HP1-2/LP1-2/A1-2/Lt manual
1= HP1-2/LP1-2/A1-2/Lt automatic
2= HP1-2/A1-2/Lt manual LP1-2 automatic
3= HP1-2 manual LP1-2/A1-2/Lt automatic
4= HP1-2/LP1-2 manual A1-2/Lt automatic
5= HP1-2/LP1-2 (thrice per hour) manual A1-2/Lt automatic
6= HP1-2/LP1-2 (thrice per hour) manual; A1-2/Lt manual
P07 Low pressure alarm with pressure probe: 0= Disabled; 1= Enabled F 0 1 Flag 1 0 P 68 (R/W) 275 Integer
P08 Digital input 1 selection F 0 23 Int 1 0 - 69 (R/W) 276 Integer
0= N 1=FL man. 2=FL auto. 3=TP man.
4=TP auto 5= TC1 man. 6= TC1 auto. 7= TC2 man.
8= TC2 auto. 9= Cool/heat 10= Cool/heat with 11= LA man.
delay
12= LA auto. 13= 2° Set 14= 2° Set timer 15= stop defrost c.1
16= stop 17= start 18= start defrost c.2 19= step 1
defrost c.2 defrost c.1
20 = step 2 21= step 3 22= step 4 23= remote ON/OFF
P09 Digital input 2 selection F 0 23 Int 1 0 - 70 (R/W) 277 Integer
P10 Digital input 6 selection F 0 23 Int 1 0 X 71 (R/W) 278 Integer
P11 Digital input 7 selection F 0 23 Int 1 0 X 72 (R/W) 279 Integer
P12 Digital input 10 selection F 0 23 Int 1 0 X 73 (R/W) 280 Integer
P13 Configuration of B4 as P8 if /4=1 (digital input) F 0 23 Int 1 0 - 74 (R/W) 281 Integer
P14 Configuration of B8 as /8=1 (digital input) F 0 23 Int 1 0 X 75 (R/W) 282 Integer
P15 Select low pressure alarm F 0 1 Flag 1 0 - 76 (R/W) 283 Integer
0= not active with compressor OFF
1= active with compressor OFF
P16 High temperature alarm set U -400 1760 °C/°F 0.1 280 AA 38 (R/W) 38 Analog
P17 High temperature alarm delay at start-up U 0 250 s 1 30 - 77 (R/W) 284 Integer
P18 High pressure alarm set from transducer F P33 999 Dbar 0.1 200 P 39 (R/W) 39 Analog
P19 System low temperature alarm set point U -400 1760 °C/°F 0.1 100 AA 40 (R/W) 40 Analog
P20 Enable system start-up protection: 0= Disabled; 1= Enabled U 0 1 Flag 1 0 - 20 (R/W) 20 Digital
P21 Alarm relay output logic: 0= normally de-activated; 1= normally activated F 0 1 - 1 0 - 8 (R/W) 8 Digital
P22 Low pressure alarm delay at start-up U 0 200 s 1 40 - 86 (R/W) 293 Integer
Compressor in heat pump
P23 Low pressure alarm delay at compressor start-up in defrost U 0 999 s 1 40 - 87 (R/W) 294 Integer
P24 Deactivate compressors with HP and LP capacity-control D 0 1 - 1 0 P 21 (R/W) 21 Digital
P25 Select digital output 2 F 0 11 Int 1 0 - 108 (R/W) 315 Integer
P26 Select digital output 3 F 0 11 Int 1 0 - 109 (R/W) 316 Integer
P27 Select digital output 4 F 0 11 Int 1 0 - 110 (R/W) 317 Integer
P28 Select digital output 5 F 0 11 Int 1 0 - 111 (R/W) 318 Integer
P29 Select digital output 7 F 0 12 Int 1 0 X 112 (R/W) 319 Integer
P30 Select digital output 8 F 0 12 Int 1 0 X 113 (R/W) 320 Integer
P31 Select digital output 9 F 0 12 Int 1 0 X 114 (R/W) 321 Integer
P32 Select digital output 10 F 0 12 Int 1 0 X 115 (R/W) 322 Integer

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 17


display parameter and description default min. max. U.O.M. variat. def. visibility supervis. Modbus variable
indicat. level variable type
P33 Low pressure alarm threshold F 0 P18 Dbar 0.1 10 P 76 (R/W) 76 Analog
ENGLISH

P34 Select digital input 5 F 0 23 Int 1 23 - 122 (R/W) 329 Integer


P35 Mute alarm with “mute“ button: 0= no; 1= yes F 0 1 - 1 0 - 23 (R/W) 23 Digital
P36 Type of high pressure alarm management F 0 1 - 1 0 - 24 (R/W) 24 Digital
0= always; 1= only if compressor active and 2 s after activation
P37 Select digital input 11 F 0 10 Int 1 0 - 138 (R/W) 345 Integer
P38 Select digital input 12 F 0 10 Int 1 0 - 139 (R/W) 346 Integer
P39 Select digital input 13 F 0 10 Int 1 0 - 140 (R/W) 347 Integer
P40 Select digital input 14 F 0 10 Int 1 0 - 141 (R/W) 348 Integer
P41 Select digital input 15 F 0 10 Int 1 0 - 142 (R/W) 349 Integer
P42 Select digital output 11 F 0 18 Int 1 0 - 143 (R/W) 350 Integer
P43 Select digital output 12 F 0 18 Int 1 0 - 144(R/W) 351 Integer
P44 Select digital output 13 F 0 18 Int 1 0 - 145 (R/W) 352 Integer
P45 Select digital output 14 F 0 18 Int 1 0 - 146 (R/W) 353 Integer
P46 Select digital output 15 F 0 18 Int 1 0 - 147 (R/W) 354 Integer
Table 4.i

4.3.11 Control setting parameters (r*)


display parameter and description default min. max. U.O.M. variat. def. visibility supervis. Modbus variable
indicat. level variable type
r01 Cooling set point D r13 r14 °C/°F 0.1 12.0 - 41 (R/W) 41 Analog
r02 Cooling differential D 1 500 °C/°F 0.1 30 - 42 (R/W) 42 Analog
r05 Compressor rotation F 0 3 Flag 1 0 - 78 (R/W) 285 Integer
0= disabled;
1= FIFO type
2= con controllo ore/hour control
3= direct relation between (D.I. and compressors D.O.)
r06 Type of compressor control F 0 4 Flag 1 0 - 79 (R/W) 286 Integer
0= proportional on inlet
1= proportional on inlet + dead zone
2= proportional on outlet
3= proportional on outlet + dead zone
4= time on outlet with dead zone
r07 Dead zone differential F 1 500 °C/°F 0.1 20 - 45 (R/W) 45 Analog
r08 Maximum control output activation time F 0 999 s 1 120 - 80 (R/W) 287 Integer
r09 Minimum control output activation time F 0 999 s 1 100 - 81 (R/W) 288 Integer
r10 Maximum control output deactivation time F 0 999 s 1 120 - 82 (R/W) 289 Integer
r11 Minimum control output deactivation time F 0 999 s 1 100 - 83 (R/W) 290 Integer
r12 Compressor deactivation differential F 0 500 °C/°F 0.1 20 - 46 (R/W) 46 Analog
r13 Minimum set point in Cooling U -400 r14 °C/°F 0.1 -400 - 47 (R/W) 47 Analog
r14 Max. Cooling set point U r13 1760 °C/°F 0.1 800 - 48 (R/W) 48 Analog
r17 Cooling compensation constant U -50 50 - 0.1 0 - 51 (R/W) 51 Analog
r18 Maximum distance from the set point U 3 200 °C/°F 0.1 3 - 52 (R/W) 52 Analog
r19 Start compensation temperature in cooling mode U -400 1760 °C/°F 0.1 300 - 53 (R/W) 53 Analog
r20 Start compensation temperature in heating mode U -400 1760 °C/°F 0.1 0 - 54 (R/W) 54 Analog
r21 Second cooling set point from external contact D r13 r14 °C/°F 0.1 120 - 55 (R/W) 55 Analog
r25 Outside temp set point to stop compressors D -400 800 °C/°F 0.1 -400 - 65 (R/W) 65 Analog
r27 Enable accumulation vessel suppression F 0 3 Flag 1 0 - 88 (R/W) 295 Integer
0= Disabled
1= Enabled in cool
2= Enabled in Heat
3= Always enabled
r28 Min. compressor running time for low load/damper travel time F 0 999 s 1 60 - 89 (R/W) 296 Integer
r29 Chiller low load differential/freecooling differential F 10 500 °C/°F 0.1 30 - 58 (R/W) 58 Analog
r30 Heat pump low load differential/freeheating differential F 10 500 °C/°F 0.1 30 - 59 (R/W) 59 Analog
r43 Heater set point F 0 7 - 1 7 - 121 (R/W) 328 Integer
0= A4, A8, A11, P16, P19 absolute values
1= A4, P16, P19 absolute value, A8 and A11 relative values
2= A8, A11, P16, P19 absolute values, A4 relative value
3= P16, P19 absolute values; A4, A8, A11 relative values
4= A4, A8, A11 absolute values; P16, P19 relative values
5= A4 absolute value, A8, A11, P16, P19 relative values
6= A8, A11 absolute values; A4, P16, P19 relative values
7= A4, A8, A11, P16, P19 relative values
r45 Maximum value of calculated set point in relative regulation D r46 1760 °C/°F 0.1 300 - 84 (R/W) 84 Analog
r46 Minimum value of calculated set point in relative regulation F -400 r45 °C/°F 0.1 100 - 85 (R/W) 85 Analog
r47 Set point for relative regulation D -400 1760 °C/°F 0.1 30 - 86 (R/W) 86 Analog
r48 Differential for relative regulation F 0 500 °C/°F 0.1 10 - 87 (R/W) 87 Analog
Table 4.k

18 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


4.3.12 Timer setting parameters (t*)
display parameter and description default min. max. U.M. variat. def. visibility supervis. Modbus variabile type

ENGLISH
indicat. level variable
t01 RTC hours U 0 23 h 1 0 W 129(R/W) 336 Integer
t02 RTC minutes U 0 59 min 1 0 W 130 (R/W) 337 Integer
t03 RTC day U 1 31 g 1 1 W 131 (R/W) 338 Integer
t04 RTC month U 1 12 mesi 1 1 W 132 (R/W) 339 Integer
t05 RTC year U 0 99 anni 1 6 W 133 (R/W) 340 Integer
t06 Start hours for 2nd set point in cooling U 0 23 h 1 0 W 92 (R/W) 299 Integer
t07 Start minutes for 2nd set point in cooling U 0 59 min 1 0 W 93 (R/W) 300 Integer
t08 End hours for 2nd set point in cooling U 0 23 h 1 0 W 94 (R/W) 301 Integer
t09 End minutes for 2nd set point in cooling U 0 59 min 1 0 W 95 (R/W) 302 Integer
t13 End minutes for 2nd set point in heating U 0 59 min 1 0 W 99 (R/W) 306 Integer
t14 Start hours for 2nd low-noise in cooling U 0 23 h 1 23 W 100 (R/W) 307 Integer
t15 Start minutes for 2nd low-noise in cooling U 0 59 min 1 0 W 101 (R/W) 308 Integer
t16 End hours for 2nd low-noise in cooling U 0 23 h 1 7 W 102 (R/W) 309 Integer
t17 End minutes for 2nd low-noise in cooling U 0 59 min 1 0 W 103 (R/W) 310 Integer
Table 4.l

4.3.13 Supervisor-only variables


display parameter and description default min. max. U.O.M variat. def. visibility supervis. Modbus variable
indicat. level variable type
- Show machine parameters (communication & SV CAREL) F 0 250 - 167 148 (R) 355 Integer
- Circuit 1 alarm D 0 1 - 0 41 (R) 41 Digital
- Circuit 2 alarm D 0 1 - 0 42 (R) 42 Digital
- EVD valve 1 alarm D 0 1 - 0 43 (R) 43 Digital
- EVD valve 2 alarm D 0 1 - 0 44 (R) 44 Digital
- General alarm D 0 1 - 0 45 (R) 45 Digital
- Probe alarm D 0 1 - 0 46 (R) 46 Digital
- Compressor warning D 0 1 - 0 47 (R) 47 Digital
- EVD 1 warning D 0 1 - 0 48 (R) 48 Digital
- EVD 2 warning D 0 1 - 0 49 (R) 49 Digital
- General warning D 0 1 - 0 50 (R) 50 Digital
- Temperature warning D 0 1 - 0 51 (R) 51 Digital
- Fan warning D 0 1 - 0 52 (R) 52 Digital
- DTE/DTC alarm D 0 1 - 0 77 (R) 77 Digital
- Digital input 1 D 0 1 - 0 53 (R) 53 Digital
- Digital input 2 D 0 1 - 0 54 (R) 54 Digital
- Digital input 3 D 0 1 - 0 55 (R) 55 Digital
- Digital input 4 D 0 1 - 0 56 (R) 56 Digital
- Digital input 5 D 0 1 - 0 57 (R) 57 Digital
- Digital input B4 D 0 1 - 0 58 (R) 58 Digital
- Digital input 1 D 0 1 1 0 59 (R/W) 59 Digital
- Digital input 2 D 0 1 1 0 60 (R/W) 60 Digital
- Digital input 3 D 0 1 1 0 61 (R/W) 61 Digital
- Digital input 4 D 0 1 1 0 62 (R/W) 62 Digital
- Digital input 5 D 0 1 1 0 63 (R/W) 63 Digital
- Standby/On status D 0 1 1 0 64 (R/W) 64 Digital
0= Standby
1= On
- Heating/Cooling status: D 0 1 1 1 65 (R/W) 65 Digital
0= Heating
1= Cooling
- Gain constant for probe 1 calibration F 0 8000 - 1000 5 (R) 212 Integer
- Gain constant for probe 2 calibration F 0 8000 - 1000 6 (R) 213 Integer
- Gain constant for probe 3 calibration F 0 8000 - 1000 7 (R) 214 Integer
- Gain constant for probe 4 calibration F 0 8000 - 1000 8 (R) 215 Integer
- Offset constant for pressure probe calibration F 0 16000 - 1000 150 (R) 357 Integer
- Offset constant for probe 1 calibration F -8000 8000 - 0 9 (R) 216 Integer
- Offset constant for probe 2 calibration F -8000 8000 - 0 10 (R) 217 Integer
- Offset constant for probe 3 calibration F -8000 8000 - 0 11 (R) 218 Integer
- Offset constant for probe 4 calibration F -8000 8000 - 0 12 (R) 219 Integer
- Gain constant for pressure probe calibration F -8000 8000 - 0 151 (R) 358 Integer
- Compressor 1 operating hours D 0 8000 - 0 152 (R) 359 Integer
- Compressor 2 operating hours D 0 8000 - 0 153 (R) 360 Integer
- Compressor 3 operating hours D 0 8000 - 0 154 (R) 361 Integer
- Compressor 4 operating hours D 0 8000 - 0 155 (R) 362 Integer
- Compressor pump operating hours D 0 8000 - 0 156 (R) 363 Integer
- Evaporator pump operating hours D 0 8000 - 0 157 (R) 364 Integer
- Digital input 6 D 0 1 - 0 66 (R) 66 Digital
- Digital input 7 D 0 1 - 0 67 (R) 67 Digital
- Digital input 8 D 0 1 - 0 68 (R) 68 Digital
- Digital input 9 D 0 1 - 0 69 (R) 69 Digital
- Digital input 10 D 0 1 - 0 70 (R) 70 Digital
- Digital input B8 D 0 1 - 0 71 (R) 71 Digital
- Digital output 6 D 0 1 1 0 72 (R/W) 72 Digital
- Digital output 7 D 0 1 1 0 73 (R/W) 73 Digital
- Digital output 8 D 0 1 1 0 74 (R/W) 74 Digital
- Digital output 9 D 0 1 1 0 75 (R/W) 75 Digital
- Digital output 10 D 0 1 1 0 76 (R/W) 76 Digital
- Digital input 11 D 0 1 - 0 80 (R) 80 Digital
- Digital input 12 D 0 1 - 0 81 (R) 81 Digital
- Digital input 13 D 0 1 - 0 82 (R) 82 Digital
- Digital input 14 D 0 1 - 0 83 (R) 83 Digital
- Digital input 15 D 0 1 - 0 84 (R) 84 Digital

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 19


4.3.13 Supervisor-only variables
display parameter and description default min. max. U.O.M variat. def. visibility supervis. Modbus variable
ENGLISH

indicat. level variable type


- Digital input B12 D 0 1 - 0 85 (R) 85 Digital
- Digital output 11 D 0 1 1 0 86 (R/W) 86 Digital
- Digital output 12 D 0 1 1 0 87 (R/W) 87 Digital
- Digital output 13 D 0 1 1 0 88 (R/W) 88 Digital
- Digital output 14 D 0 1 1 0 89 (R/W) 89 Digital
- Digital output 15 D 0 1 1 0 90 (R/W) 90 Digital
- Password to control outputs from the supervisor D 0 8000 1 0 13 (R/W) 220 Integer
- Defrost status D 0 255 - 0 134 (R) 341 Integer
- bit 0= Defrost circuit 1
- bit 1= Defrost circuit 2
- bit 2= Fan Defrost circuit 1
- bit 3= Fan Defrost circuit 2
- Controls from the UAD: D 0 1023 1 0 135 (R/W) 342 Integer
bit0= terminal status (0= not connected; 1= available)
bit2; bit1= mode set from µAD (00= AUTO; 01= cooling; 10=
heating)
bit3= enable dehumidification
bit4= enable humidification
bit5= terminal probe alarm
bit6= activate boiler output
bit7= 0= process mode active; 1= process mode disabled
- Signals to the µAD D 0 255 - 0 136 (R) 343 Integer
bit0= cool/heat request from uAD in progress
bit1= cool/heat request accepted from µAD (1= cooling; 0=
heating)
bit2= start fans
bit3= alarm active on µCH
bit4= RTC available on µCH2 SE
- DTE value saved in EEPROM D 0 0 - 0 98 (R) 98 Analog
- Internal set point compensated in the event of autotuning D 0 0 - 0 97 (R) 97 Analog
- Ambient set point (from µAD) D -400 1760 0,1 0 95 (R/W) 95 Analog
- Set point variation from µAM (µedronic) D -100 100 0,1 0 96 (R/W) 96 Analog
- Differential for the ambient set point D -100 100 0,1 0 94 (R/W) 94 Analog
- Controls by the µAD from save D 0 32767 1 0 - 137 (R/W) 344 Integer
- Active alarm signal: D 0 32767 1 0 - 128 (R/W) 335 Integer
bit0= probe alarm (E1,E2,E,E4,E5,E6,E7,E8)
bit1= high pressure alarm (HP1, HP2)
bit2= low pressure alarm (LP1, LP2)
bit3= flow switch alarm (FL)
bit4= expansion communication alarm (ESP)
bit5= EE2PROM alarm (EPB)
bit6= antifreeze alarm (A1, A2)
bit7= thermal overload alarm (TP, TP1, TP2)
bit8= hour counter alarm (H1, H2, H, H4)”
- Terminal humidity probe (per terminal µAD) D 0 1000 % 0,1 0 129 (R/W) 129 Analog
- Reset alarms D 0 1 1 0 78 (R/W) 78 Digital
- Digital input B D 0 1 - 0 79 (R) 79 Digital
- Compatibility with the test F 0 1 1 0 19 (R/W) 19 Digital
- Dummy digital F 0 0 - 0 22 (R) 22 Digital
- Dummy integer F 0 0 - 0 123 (R/W) 330 Integer
- Dummy analog F 0 0 - 0 133 (R) 133 Analog
Table 4.m

20 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


5. DESCRIPTION OF THE PARAMETERS

ENGLISH
To modify the parameters, see chapter 4 “Parameters.”
• Probe settings: parameters (/*) (see Table 4.a)
- Type of probe: from /01 to /08: enables the reading of the corresponding analogue input or sets the
function
• Functions of the probes

Type of unit Parameter H01 Temp. control Antifreeze probe Cond. temp. Press probe Antifreeze Cond. temp. Press. probe
probe 1st circuit probe 1st circuit probe probe 2nd circuit
1st circuit 2nd evaporator 2nd circuit
2= air/water Chiller B1/B2 single circuit B2 B3 B4 B6 B7 B8
(B1/B5 two circuits)
4= water/water Chiller B1/B2 single circuit B2 Not used Not used B6 Not used Not used
(B1/B5 two circuits)
11= Cooling-only air-air unit with electric heating B1 B2 (low outlet B3 B4 Not used B7 B8
temperature)
Table 5.a

- Min/max voltage and pressure values


From /09 to /12: sets the minimum/maximum voltage and pressure for the ratiometric signal.

- Probe calibration
From /13 to /20: calibrates the corresponding sensor (from B1 to B8).

- Digital filter
/21: Establishes the coefficient used in the digital filtering of the value measured. High values for this
parameter will eliminate any continuous disturbance at the analogue inputs (however decrease the
promptness of measurement). The recommended value is 4 (default).

- Input limit
/22: Establishes the maximum variation that can be measured by the probes in one unit program cycle;
in practice, the maximum variations allowed in the measurement are between 0. 1 and 1.5 units (bars, °C
or °F, depending on the probe and the unit of measure) approximately every one second. Low values for
this parameter will limit the effect of impulsive disturbance. Recommended value 8 (default).

- Unit of measure
/23: Selects the unit of measure as degrees centigrade or Fahrenheit. When the parameter is modified,
the µC2SE automatically converts the values read by the NTC temperature probes B1, B2, B3 into the new
unit of measure; while all the other parameters set (set point, differential etc. ) remain unchanged.

• Antifreeze, auxiliary heater: parameters (A*) Example of antifreeze/outlet limit management


1
- Antifreeze alarm set point
A01: when probe B2 is installed on the coil represents the temperature (antifreeze set point) of the water
at the evaporator outlet below which an antifreeze alarm is activated; in this condition the compressors ON
corresponding to the circuit in question are stopped, while the pump remains on to decrease the
possibility of freezing. The alarm is reset manually (or automatically, depending on parameter P05) only OFF
when the water temperature returns within the operating limits (that is, above A01+A02). A1 A1+A2 2

Fig. 5.a.a
- Antifreeze alarm differential
A02: This represents the differential for the activation of the antifreeze alarm; the alarm condition cannot Key:
be reset until the temperature exceeds the set point + differential (A01+A02 or A14+A02). 1. freecooling or comp 2. probe B2

- Antifreeze alarm bypass time low room temperature from unit start in heating mode
A03: This represents the delay in the activation of the antifreeze alarm when starting the system.

- Auxiliary heater probe in heating


A06: This determines which probe is used for control the auxiliary heater. The meaning of the parameter
is the following:
A06 = 0 => Control probe see Table 5.a.a
A06 = 1 => Antifreeze probe see Table 5.a.a
Not valid if A10= 2

- Antifreeze alarm set point limit


A07: Establishes the minimum limit for setting the antifreeze alarm set point (A01).

- Heating (electrical heater or hot gas bypass) set point


A08: Represents the threshold below which the heating function is activated.
The set point in heating is compensated according to the following equation:
The heating function could be realized by electrical heater or hot gas bypass valve. The set point in
heating is compensated according to the following equation:
Set_heaters (heating) = A08 + (Compensated set point - Set point set)
A08 could both be absolute value or relative value to set point according to the parameter r43.

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 21


- Heating differential
A09: Represents the differential for the activation/deactivation of the heating function
ENGLISH

- Automatic switch-on
A10: This parameter is valid when the unit is in standby.
The operating mode switchover delay times are ignored.
A10=0: function not enabled
A10=1: heating function and pump are ON at the same time when the temperature is below A04
A10=2: heating function and compressor are ON at the same time when the temperature is below A04
(use for hot gas bypass)
A10=3: heating function automatically switches on whne the temperature is below A04

In this case, the display will be as follows:


• operating mode LED OFF;
• cooling heating flag not switched (not detected by the supervisor);
• antifreeze alarm A01 (remains active even at the end of the special operation if the unit was previously
ON, deactivated by manual reset or in standby).
A10=3: heaters ON based on the respective set point A04 and A08.
Do not use with H1= 6
- Antifreeze heater 2 set point in defrost/auxiliary in heating
A11: Heater 2 set point in heating, the control of the auxiliary heaters has been separated, each having its
own activation set point (see A08).
- Dirty filter signal set point (air/air units only)
A12: Set point for the dirty filter signal based on B1-B2, the deactivation differential is A05
• Valid in the following conditions:
• air-air units;
• B1 is configured;
• outlet limit active;
• freecooling not active;
• at least 1 compressor ON.
The warning is reset automatically in the following conditions:
• air-air units;
• B1 is configured;
• outlet limit active;
• freecooling not active.
- Outlet limit set point in freecooling conditions
A13: With freecooling active, and only when the compressors are off, this represents the outlet limit.
When the compressors are on, even if freecooling is active, the outlet limit alarm is bypassed and the
antifreeze alarm is used.
- Antifreeze alarm set point from EVD
A14: With the EVD connected in the tLAN, A14 represents the evaporation temperature (sent by the EVD)
below which the antifreeze alarm is activated; when the alarm is active, the compressors in the circuit
affected are switched off, while the pump remains on to reduce the possibility of freezing. Manual reset
(or automatic, depending on parameter P05), only occurs when the water temperature returns within the
operating limits (that it, exceeds A14+A02
• Probe readings: parameters (B*)
- Select probe to be shown on display.
b00: Sets the probe reading to be displayed.
0= probe B1
1= probe B2
2= probe B3
3= probe B4
4= probe B5
5= probe B6
6= probe B7
7= probe B8
8= set point without compensation
9= dynamic set point with possible compensation
10= remote ON/OFF digital input status
11= probe AD
For the list of parameter-probe associations see Table 4.d
Note: probes that are not present cannot be selected.

22 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


• Compressor settings: parameters (c*) ON
- Minimum ON time 1
c01: This establishes the time that the compressor must remain ON for when started, even if the stop OFF

ENGLISH
t
signal is sent. ON

Key: 2
OFF
1. signal; C2 t
2. compressor; 3
3. min. ON time-interval. Fig. 5.a.c
- Minimum OFF time
c02: This establishes the time that the compressor must remain OFF for when stopped, even if the start ON
signal is sent. The compressor LED flashes in this phase. 1
OFF
Key: t
ON
1. signal;
2. compressor; 2
OFF
3. min. OFF time-interval. C2 t

3
- Delay between 2 starts of the compressor
c03: This sets the minimum time that must elapse between two successive starts of the same compressor Fig. 5.a.d
(determines the maximum number of starts per hour for the compressor). The compressor LED flashes in this
phase. If by mistake the user enters a value lower than the sum of C01 + C02, this parameter will be ignored and
ON
only the times C01 and C02 will be considered.
1
Key: t
OFF
1. signal; ON
2. compressor; 2
3. min. time-interval between two ON routins. OFF
C2 t
3

Fig. 5.a.e

- Start delay between compressors


ON
c04: This sets the delay between the starts of the two compressors, so as to reduce the peak power input 1
and make the compressors start more smoothly. The compressor LED flashes in this phase. OFF
• In the event of capacity control, the delay c04 between compressor and valve becomes c04/2; ON
• In the event of defrost operation, the delay between compressor and compressor is 3 seconds, and 2
OFF
between compressor and valve is 2 seconds.
ON
3
Key: OFF
1. 1st signal; ON
2. 2nd signal; 4
3. 1st compressore; C4
OFF
4. 2nd compressor;
5. time delay between two compressors ON routines/time-delay of the capacity-controlled routine. 5

Fig. 5.a.f

- Stop delay between compressors ON


c05: This sets the stop delay between the compressors. 1
OFF

Key: ON
2
1. 2nd signal;
OFF
2. 1st signal; ON
3. 2nd compressor; 3
4. 1st compressore; OFF
5. time delay between two compressors OFF routines/time-delay before the capacity-controlled routine. ON
4
OFF
C5

- Delay on power-up (reset power supply) 5

c06: At power ON (when the controller is physically switched ON) the activation of all the outputs is delayed so Fig. 5.a.g
as to distribute the power input and protect the compressor against repeated starts in the event of frequent power
failures. This means that after the delay time, the controller will start to manage the outputs based on the other
times and the other normal functions.

- Compressor start delay from pump/outlet fan (air/air) ON. ON


c07: In cooling and heating operation, if the operation of the pump (outlet fan) is subject to the controller 1
(parameter H05=2), the compressor is started when required after the set time from the activation of the water OFF
t
pump (or outlet fan in air/air units). 2
If the pump/outlet fan is always ON (H05=1) and consequently does not depend on the control logic, the ON
compressor is started after the set time from when the unit starts. 3
OFF
C7 t
Key:
1. inlet fan; 4
2. pump;
Fig. 5.a.h
3. compressor;
4. time-delay between pump-inlet fan and compressor.

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 23


- Pump/outlet fan (air/air) start delay from compressor OFF
ON
1 c08: In cooling and heating operation, if the operation of the pump (outlet fan) is subject to the controller
(parameter H05=2), when the compressor is requested to stop, the control first stops the compressor and the
ENGLISH

OFF
t
2 pump (outlet fan).
ON If the pump/outlet fan is always ON (H05=1), it is only stopped in standby mode.
3
OFF Key:
C8 t
1. compressor;
4 2. pump;
3. inlet fan;
Fig. 5.a.i 4. time-delay between pump-inlet fan and compressor.

- Maximum tandem compressor operating time


c09: In the case of two compressors in tandem per circuit, one compressor should not operate for longer than
the time set for c09 while the other compressor in the circuit is OFF. This prevents the oil shared in common
from migrating over the allowed limit towards the active compressor, and consequently avoids damage when
inactive compressor next starts (FIFO logic) due to poor lubrication. As a result, compressor 1 (or 2) in circuit 1, if
requested to operate continuously, will actually stop OFF after the time c09 and hand over to compressor 2 (or 1)
that was previously OFF.
This function always considers the compressor times. Any value lower than the time set for c03 will be ignored, and
the compressors (if the above condition is satisfied) will switch over after the time c03.
When C9=0, the function is disabled (the compressors will not switch over).

- Hour counter compressor 1-2-3-4


c10, c11, c12, c13: These indicate the number of operating hours of compressor 1, 2, 3, 4, expressed in
hundreds of hours.
Pressing  and  together, when the hour counter is displayed, resets the hour counter and,
consequently, cancels any maintenance requests in progress.
c10= operating hours comp. 1
c11= operating hours comp. 2
c12= operating hours comp. 3
c13= operating hours comp. 4

- Compressor operating hour counter threshold


c14: This sets the number of compressors operating hours, expressed in hundreds of hours, above which
the maintenance request signal is sent.
c14= 0: function disabled.

- Evaporator pump/fan 1 hour counter


c15: This indicates the number of operating hours for the evaporator
pump or fan 1, expressed in hundreds of hours.
Pressing  and  together, when the hour counter is displayed, resets the hour counter and,
consequently, cancels any maintenance requests in progress.

- Condenser or backup pump/fan 2 hour counter


c16: This indicates the number of operating hours for the condenser pump (or backup) or fan 2,
expressed in hundreds of hours.
Pressing  and  together, when the hour counter is displayed, resets the hour counter and,
consequently, cancels any maintenance requests in progress.

- Minimum OFF time before the next pump/fan start


c17: The diagram below shows an example of the operation of the pump and with burst (active when
H05=3, see parameter H05).
The dashed areas on the compressor line indicate the pump-compressor and compressor-pump delay
times.
Burst mode is disabled in standby and during an alarm when the pump is OFF.
At power ON the delay c17 must elapse before burst can start.

- Minimum pump/fan ON time


c18: This represents the minimum time that the pump remains ON for, see Fig. 5.i (active with H05=3 see
parameter H05).

24 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


• Fan settings: parameters (F*)
- Fan output

ENGLISH
F01: Enables the operation of the fans.
F01=0: fans absent;
F01=1: fans present.
The PWM output (1 or 2, depending on the value of parameter H02) requires the presence of the optional
fan control cards (ON/OFF for the CONVONOFF module or speed variation for MCHRTF or FCS three-phase).

- Fan operating mode


F02: This establishes the operating logic for the fans:
F02=0: always ON at maximum speed, independently from the compressors. The fans are only switched
OFF when the unit is in standby.
F02=1: ON at maximum speed when at least one compressor in the corresponding circuit is ON (parallel
operation in each circuit).
F02=2: ON when the corresponding compressor is ON, with ON/OFF control based on the temperature/
pressure settings for the minimum and maximum speed (parameters F05-F06-F08 and F09). When
the compressors are stopped, the corresponding fans are also stopped, irrespective of the condensing
temperature/pressure.
Cooling ON/OFF Heating ON/OFF
1 1 Key:
100% 100%
1. speed %;
2. condensing temperature/pressure;
3. hysteresis.
F04 F04

0% 0%
F05 F08
2 2
F06 F09

Fig. 5.a.l

Cooling with speed control Heating with speed control

1 3 1 3
100 %
F05 F08

F04 F04

F03 F03

0% 0%
2 2
F07 F06 F09 F10

Fig. 5.a.m

F02=3: ON when the corresponding compressor is ON, with speed control. When the compressors are
stopped the corresponding fans are also stopped, irrespective of the condensing temperature/pressure.
With F02=3 and an NTC condenser probe, when the compressor starts the fans are started at maximum
speed for the time F11, irrespective of the temperature measured.
In the event of a condenser probe fault, the fans will be switched OFF.

- Minimum voltage threshold for Triac


F03: In the event of fan speed control, the optional phase cutting cards (MCHRTF*) are required, fitted
with a triac. The voltage delivered by the triac to the electric fan motor corresponding to the minimum
speed must be set. The set value does not correspond to the actual voltage in Volts applied, but rather to
an internal unit of calculation in the µC2SE.
If using FCS controllers, set this parameter to 0.
F03 = Represents the minimum threshold for the triac

- Maximum voltage threshold for Triac


F04: In the event of fan speed control, the optional phase cutting cards (MCHRTF*) are required, fitted
with a triac. The voltage delivered by the triac to the electric fan motor corresponding to the maximum
speed must be set. The set value does not correspond to the actual voltage in Volts applied, but rather to
an internal unit of calculation in the µC2SE.
If using FCS controllers, set this parameter to 100.
F04 = Represents the maximum threshold for the triac

- Temperature/pressure set point for minimum speed in cooling


F05: This represents the temperature or pressure below which the fans remain ON at minimum speed.
In the case of ON/OFF control, it represents the temperature or pressure below which the fans are
switched OFF (Fig. 5.a.k).

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 25


- Temperature/pressure differential for maximum speed in cooling
F06: This represents the temperature or pressure differential in reference to F05 above which the fans are
started at maximum speed; in the case of ON/OFF control, this represents the differential above which
ENGLISH

the fans are started (Fig. 5.a.k).

- Temperature/pressure differential for fans Off in cooling


F07: This represents the temperature or pressure differential in reference to F05 below which the fans
are stopped. The fans are started 1 °C “lower” when using NTC temperature probes, or 0. 5 bars if using
pressure probes. (Fig. 5.a.l)
If NTC temperature probes or pressure probes are used to control the condensing temperature/pressure,
there is an activation hysteresis of 1 °C or 0.5 bar respectively.

- Fan start time


F11: This establishes the operating time at maximum speed when the fans are started, so as to overcome
the mechanical inertia of the motor.
The same times are observed in reference to the start of the compressor (irrespective of the condensing
temperature/pressure), if NTC temperature probes are used on the condenser and speed control
is enabled, F02=3; this is done to bring forward the sudden increase in pressure (which does not
necessarily correspond to a likewise rapid increase in temperature in the area where the probe is located)
and consequently to improve control
F11=0: the function is disabled, that is, the fans are activated at the minimum speed and then controlled
based on the condensing temperature/pressure.

- Triac impulse duration


F12: This represents the duration in milliseconds for the impulse applied to the triac. For induction
motors, set the parameter to 2 (default). On the other hand, when using the CONVONOFF0,
CONV0/10A0 modules or FCS controllers, set the parameter to 0.

- Fan on time when starting in high condensing temp.


F14: establishes the time the fans are operated at maximum speed if starting with a high condensing
temperature.
F14 = 0: function disabled.
F14 > 0: fan on time (in seconds).
The function is operational only in chiller mode, if the probe on the condenser is a temperature sensor
and only for air-cooled units. When the first compressor in the circuit in question starts, it is assumed that
the temperature of the environment is close to the temperature of the condenser; if the value read by the
condenser probe is higher than the value of F05-F07, as well as starting the compressor, the fans in the
circuit in question are forced on at maximum speed for the time set by F14.

- Activate low noise


F15: This function moves the condensing pressure set point so as to lower the fan speed and
consequently reduce noise (specifically at night). If low noise is active in cooling, the condenser control
set points are increased by F16. If low noise is active in heating, the set points are reduced by F17.
F15= 0: Low noise deactivated.
F15= 1: Low noise activated in cooling.
F15= 2: Low noise activated in heating.
F15= 3: Low noise activated in cooling and heating.
N.B. The variation in the set point is not active during defrost

- Cooling set point differential


F16: Differential added to the condenser control set point when low noise is active (valid for both
temperature and pressure control).

• Unit settings: parameters: (H*)


- Unit model
H01: Used to select the type of unit being controlled:
H01= 2: AIR/WATER Chiller
H01= 4:WATER/WATER Chiller
(*) Note: Set H21= 4 (Condenser pump always on), if H02= 1 (Two condensers).

- Number of condenser fan circuits/water condensers


H02: This establishes the number of fan circuits present in the configurations with two circuits. With one
fan circuit (H02=0) the unit may have 1 or 2 refrigerant circuits:
• with one refrigerant circuit, the fans are exclusively controlled based on the pressure or temperature
read by the sensor in the first circuit;
• with two refrigerant circuits, the fans are controlled based on the higher temperature/pressure of the
two circuits. In heat pump mode, the output depends on the lower temperature or pressure.
The output used is Y1. Vice-versa, with 2 ventilation circuits (H02=1) each PWM output is independent
and depends on its own condenser probe (B3 or B4 for circuit 1 and B7 or B8 for circuit 2).

26 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


- Number of evaporators
H03: This establishes the number of evaporators present when there are 2 or 4 compressors, obviously
with 2 circuits (including the expansion). With one evaporator (H03=0), the management of the

ENGLISH
heaters and the antifreeze function is performed only on B2. Vice-versa, with 2 evaporators (H03=1)
antifreeze control will be performed using B2 and B6, while input B5 is used to control the water outlet
temperature.

- Number of compressors/circuits
H04: This establishes the number of compressors per circuit and the number of circuits. For further
details see Table 4.g.

- Evaporator pump/fan operating mode


H05: This establishes the operating mode for the evaporator water pump or the outlet fan (in air/air
units).
H05 = 0: pump disabled, (the flow switch alarm is ignored)
H05 = 1: always ON (the alarm is managed)
H05 = 2: ON when called by compressor (the alarm is managed)
H05 = 3: the pump will be started and stopped at regular intervals (independently from the compressors)
as per the Burst setting (see parameters c17 and c18).
H05= 4: follow hot keep or hot start in heating, always on in cooling
H05= 5: follow hot keep or hot start in heating, follow the compressors in cooling.
When the heating or cooling signal is received, first the evaporator pump/outlet fan starts (always ON),
and then the compressor, after the set times (c07, c08). The pump will not be stopped until all the
compressors are Off.

- Cooling/heating digital input


H06: Establishes whether the cooling/heating selection from digital input is enabled. see parameters P08,
P09, P10, P11, P12 and P13). The open status places the unit in cooling operation, vice-versa, in heating.
D-IN Open = Cooling
D-IN Closed = Heating

- ON/OFF digital input


H07: Establishes whether the ON/OFF selection from digital input is enabled or disabled. If the selection
is enabled (H07= 1), the “open” status switches the unit Off, while in the “closed” status, the unit may be
OFF or ON, as controlled by the keypad.
This parameter is not valid for condensing units.

- µC2SE network configuration


H08: Establishes the layout of the tLan network.
0= µC2SE only
1= µC2SE + valve
2= µC2SE + exp.
3= µC2SE + exp. + valve
4= µC2SE + I/O
5= µC2SE + valve + I/O
6= µC2SE + exp. + I/O
7= µC2SE + I/O + valve + valve

- Enable keypad
H09: Used to disable the modification of the DIRECT and USER parameters from the keypad. The
value of the parameters can always be displayed. The enable/disable cooling, heating and reset counter
functions are also available.
Values:
0: keypad disabled
1: keypad enabled (default)

- Serial address
H10: Establishes the address of the instrument for the serial connection, via an optional board, to a PC
for supervision and/or telemaintenance.

- Selection map outputs


H11: This parameter is used to arbitrarily associate some digital outputs to the devices on the unit.
H11= 0: standard (default); for units with one compressor per circuit (H04=0, 2).
H11= 1: For cooling only units with two compressors (H01=0, 2, 4, 7, 9 and H04=1, 3, 5)
H11= 2: The outputs of the expansion follow the same logic for the 2nd circuit. For H01= 1, 3, 5, 6, 8, 10
and H04= 1, 3, 5
H11= 3: The outputs of the expansion follow the same logic for the 2nd circuit. For H01= 1, 3, 5, 6, 8, 10
and H04= 1, 3, 5
H11= 4: For H01= 1, 3, 5, 6, 8, 10 and H04= 0, 1
H11= 5: For cooling only units with two compressors (H01= 0, 2, 4, 7, 9, and H04= 0)
H11= 6: 1 compressor per circuit, heat pump
H11= 7: 1 compressor per circuit, cooling only, solution 1
H11= 8: 1 compressor per circuit, cooling only, solution 2
H11= 9: 2 compressors per circuit, heat pump
H11= 10: 2 compressors per circuit, cooling only, solution 1
H11= 11: 2 compressors per circuit, cooling only, solution 2

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 27


H11= 12:
associated device
ENGLISH

outputs H11=0 H11= 1 H11= 2 H11= 3 H11= 4 H11= 5


C1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1
C2 heater 1 heater 1 heater 1 reversing valve 1 reversing valve 1 heater 1
C3 Pump/evaporator (fan) (on Pump/evaporator (fan) (on Pump/evaporator (fan) (on Pump/evaporator (fan) (on evaporator pump Pump/evaporator (fan) (on
air/air units) air/air units) air/air units) air/air units) air/air units)
C4 reversing valve 1 Compressor 2 (or capacity Compressor 2 (or capacity Compressor 2 (or capacity Compressor 2 (or capacity condenser fan 1
control comp. 1) control comp. 1) control comp. 1) control comp. 1)
C5 alarm alarm reversing valve 1 alarm alarm alarm
C6 compressor 2 compressor 3 compressor 3 compressor 3 not used compressor 2
C7 heater 2 heater 2 heater 2 reversing valve 2 heater 1 heater 2
C8 Condenser pump/backup Condenser pump/backup Condenser pump/backup Condenser pump/backup Condenser pump/backup Condenser pump/backup
C9 reversing valve 2 Compressor 4 (or capacity Compressor 4 (or capacity Compressor 4 (or capacity not used condenser fan 2
control comp. 2) control comp. 2) control comp. 2)
C10 Warning Warning reversing valve 2 Warning Warning Warning

associated device
outputs H11= 6 H11= 7 H11= 8 H11= 9 H11= 10 H11= 11 H11= 12
C1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1
C2 1 step heater 1 step heater 1 step heater compressor 2 compressor 2 compressor 2 P25
C3 outlet fan outlet fan outlet fan outlet fan outlet fan outlet fan P26
C4 reversing valve 1 2 step heater condenser fan 1 reversing valve 1 heating step 1 heating step 1 P27
C5 alarm alarm alarm alarm alarm alarm P28
C6 compressor 3 compressor 3 compressor 3 compressor 3 compressor 3 compressor 3 compressore 3
C7 2 step heater P29 2 step heater compressor 4 P29
C8 open freecooling/ open freecooling open freecooling open freecooling/ open freecooling/ open freecooling/ P30
freeheating freeheating freeheating freeheating
C9 reversing valve 2 humidifier (ON/OFF) condenser fan 2 1 step heater heating step 2 humidifier P31
C10 close freecooling/ close freecooling close freecooling close freecooling/ close freecooling/ close freecooling/ P32
freeheating freeheating freeheating freeheating

Parameters P25 to P28 can have the following meanings:


0 = no function associated with the relay
1 = compressor 2
2 = Heater 1
3 = Reversing valve 1
4 = Pump/inside fan
5 = Open freecooling/freeheating
6 = Close freecooling/freeheating
7 = Humidifier
8 = Condenser fan 1 on/off
9 = Heater 2
10 = Alarm
10 = Boiler contact

Parameters P29 to P32 can have the following meanings:


0 = no function associated with the relay
1 = compressor 4
2 = Heater 2
3 = Reversing valve 2
4 = Pump/inside fan 2nd evaporator
5 = Open freecooling/freeheating
6 = Close freecooling/freeheating
7 = Humidifier
8 = Condenser fan 2 on/off
9 = Warning
10 = Condenser pump/Backup
11 = Heater 1

28 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


- Capacity-control logic
H12: Specifies the logic for the activation of the capacity-control steps for the compressors and the 4-way
reversing valve.

ENGLISH
H12 = 0: 4-way reversing valve and capacity-control normally energised
H12 = 1: 4-way reversing valve and capacity-control normally de-energised. Default value.
H12 = 2: 4-way reversing valve normally de-energised and capacity-control normally energised
H12 = 3: 4-way reversing valve normally energised and capacity-control normally de-energised.
Note: in the event of capacity-control, the rotation between compressor and corresponding valve is disabled.
FIFO or time logic can be used between the 2 circuits to optimise the starts or the operating hours of the
2 compressors (1 per circuit).

- Enable pump down


H13: This function allows the unit to be stopped while avoiding the possible formation of liquid refrigerant
inside the evaporator.
When the only active compressor is called to stop, the expansion valve is closed so as to depressurise the
circuit.
Valid only when the driver is installed, as the driver pressure probe is used.

- Minimum pumpdown pressure


H14: Limit pressure below which the compressor is deactivated.

- Maximum pumpdown time


H15: Maximum time after which the compressor is deactivated.

- Function of the second pump


H21: This parameter defines how the output dedicated to the second pump must be managed.
H21= 0: the second pump is disabled.
H21= 1: the second pump is used only as a backup.
If the flow switch and corresponding alarm are activated, the pumps are switched over:
• if the alarm passes, a warning is shown on the display and the warning relay is activated, while the
unit continues to operate with the Backup pump. When the next alarm is activated the pumps will be
switched over.
• if the alarm remains active even with the second pump on for longer than the time set for P1, the
generic alarm is generated and the unit is switched OFF.
H21= 2: the second pump represents a backup pump. The two pumps are never used at the same time
but each 24 hours, are switched over. In the event of flow alarms, the logic is the same as for setting 1.
After being switched over due to the flow alarm, the 24-hour timer is set to zero.
H21= 3: the second pump is used as an ON/OFF device in the same way as the condenser fan (which in
this case is not present), in ON/OFF mode, with the same settings (in fact in this case the pump replaces
the fan, including the symbol).
H21= 4: the second pump is used for the condenser but is always ON. In this case the pump symbol is
not managed.
Note: In the event of flow alarms with automatic reset, 10 attempts are made to restart the pump every
90 seconds, for a maximum time of P02; after the 10 attempts, the alarm becomes manual reset. With the
second pump, the attempt consists in switching over the pump that is on, with the same logic.
- Disable load default values
H22: If this parameter is set to 1, it disables the possibility of restoring the default parameters using the
PRG button at power ON.
- select supervisor protocol
H23: establishes the protocol used for the connection to the supervisor from the serial board RS485
H23 = 0: CAREL protocol (baud rate 19200,…)
H23 = 1: Modbus protocol
- High/Low temperature alarm mode
H24: determines when HT/LT alarm appears, whether the compressor stops
H24 = 0: compressor doesn’t stop
H24 = 1: compressor stops when HT alarm appears
H24 = 2: compressor stops when LT alarm appears
H24 = 3: compressor stops when HT or LT alarm appear
- Enable hot gas bypass function
H25: determines whether the hot gas bypass function is enabled
H25 = 0: disable
H25 = 1: enable
- Enable special standby function
H26: determines whether the special stanby function is enabled
H25 = 0: disable
H25 = 1: enable
When this function is enable, if during STAND BY mode the temperature B1 drops below r3 the unit
switches on the heating mode (electrical heater or hot gas bypass).

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 29


• Alarm settings: parameters (P*)
- Flow switch alarm delay when starting pump
ENGLISH

P01: Establishes a delay in the recognition of the flow switch alarm when starting the pump (this allows the
flow-rate to stabilise). In the event of alarms, the compressors are stopped immediately, ignoring the times.
- Flow switch alarm delay in steady operation
P02: Establishes a delay in the recognition of the flow switch alarm in steady operation, so as to filter any
variations in flow-rate or air bubbles present in the water circuit. In the event of alarms, the compressors
are stopped immediately, ignoring the times.
- Low pressure alarm delay at compressor start
P03: Establishes a delay in the recognition of the low pressure alarm when the compressor starts, so as
to allow stable operating conditions to be reached. This delay is also counted when reversing the 4-way
valve in the refrigerant circuit.
Part load in low pressure - Part load in high pressure and low pressure in heat pump
P04: enable or disable the part load operation of the circuit in high pressure.
The function is valid if the unit is fitted with tandem or capacity controlled compressors and pressure
all LP
transducers. In the event of high pressure alarms, that is, for values over P18 (hysteresis 0.5 bar), the
controller deactivates a load step in the circuit in question and waits 10 seconds. After this interval, if the
alarm is still active, the unit is stopped, otherwise it continues to operate in part load mode. In this situation,
the display shows the message PH1 and/or PH2, depending on the circuit. This condition remains active
parz LP until the pressure falls below the value corresponding to the maximum speed of the condenser fans
pressure
1 bar 1,5 bar 2 bar F08-F09 (F05+F06). Below this value, the unit reactivates the load step that had previously been deactivated.
P04=0: capacity control not activated
Fig. 5.b.b P04=1: capacity control activated for high pressure
P04=2: capacity control activated for low pressure
P04=3: capacity control activated for high and low pressure
With the unit operating in heat pump mode, due to low outside temperatures or the load the pressure may
fall and stop the unit due to the low pressure alarm. If the circuit has 2 compressor steps and the pressure
remains below the value of one bar for the time P22, the circuit can operate at part load. This capacity
control is not activated when the alarm comes from the digital input. In the event of low pressure, the
controller deactivates one step and if the pressure does not return above the threshold in 10 seconds, the
alarm is activated and the circuit is stopped. This function is valid for all units with pressure transducers.

- Alarm reset
P05: Enables automatic reset for all those alarms that normally feature manual reset (high pressure, low
pressure, flow switch/antifreeze) as per the following table:
P05= 0: (default) high pressure, low pressure and antifreeze (low temperature) with manual reset;
P05= 1: all the alarms with automatic reset;
P05= 2: high pressure and antifreeze (low temperature) manual, low pressure automatic;
P05= 3: high pressure manual, low pressure and antifreeze (low temperature) automatic;
*: the high and low pressure alarms are managed in the P05= 4: high and low pressure manual, antifreeze (low temperature) automatic;
same way both for the transducers and the pressure switches P05= 5: high and low pressure manual after the third activation in one hour*, antifreeze (low temperature)
(digital input); if the unit is in standby the count (3 times in automatic;
one hour) is reset. P05= 6: high and low pressure manual after the third activation in one hour*, antifreeze (low temperature) manual.

- Low pressure alarm with pressure probes


P07: P07=0: this function is disabled.
P07=1: if in heat pump mode the evaporator (external exchanger) pressure is less than 1 bar (and if the
presence of the condenser pressure probe is enabled), the low pressure alarm is activated (while still
considering the delay P03).
Note: P07=1 the LP digital inputs in heat pump are ignored.

- Select digital input ID1


P08= 0: none;
P08= 1: flow switch with manual reset (normally closed);
P08= 2: flow switch with automatic reset (N.C.);
P08= 3: general thermal overload with manual reset (N.C.);
P08= 4: general thermal overload with automatic reset (N.C.);
P08= 5: thermal overload circuit 1 with manual reset (N.C.);
P08= 6: thermal overload circuit 1 with automatic reset (N.C.);
P08= 7: thermal overload circuit 2 with manual reset (N.C.);
P08= 8: thermal overload circuit 2 with automatic reset (N.C.);
P08= 9: cooling/heating (open = Cooling, closed = Heating) if H06= 1;
P08= 10: cooling/heating with delays d12 and d13 (open = Cooling, closed = Heating) if H06= 1;
P08= 11: alarm signal with manual reset (N.C.);
P08= 12: alarm signal with automatic reset (N.C.);
P08= 13: second set point from external contact (cooling and heating), (normally open);
P08= 14: second cooling set point from external contact and heating from time band (N.O.);
P08= 15: end defrost from external contact circuit 1 (N.C.);
note 1: if P08 is set to 10, the change in state considers the P08= 16: end defrost from external contact circuit 2 (N.C.);
times d12 and d13, and respects the compressor protection P08= 17: end defrost from external contact circuit 1 (N.C.);
times, both from the digital input and the keypad. P08= 18: end defrost from external contact circuit 2 (N.C.);
note 2: if the digital input is used to switch the unit ON/OFF P08= 19: condenser step 1 (N.O.);
or change the operating mode, these functions are disabled P08= 20: condenser step 2 (N.O.);
on the keypad. P08= 21: condenser step 3 (N.O.);
note 3: ID5 for the condensing unit with reverse cycle has P08= 22: condenser step 4 (N.O.);
the function of cooling/heating changeover P08= 23: remote ON/OFF.
30 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010
- Select digital inputs ID2, ID6, ID7, ID10, ID5
P09, P10, P11, P12, P34: Configuration of digital inputs ID2, ID6, ID7, ID10, and ID5 respectively (as per
the table above for digital input ID1).

ENGLISH
Note: Cooling/heating (9, 10) cannot be set on P10, P11, P12, and P14.

- Select input B4 if /04 = 1


P13: If input B4 is used as ON/OFF (/04 = 1) the same options are valid as for P08.

- Select input B8 if /08 = 1


P14: If input B8 is used as ON/OFF (/08 = 1) the same options are valid as for P08.

- Select low pressure alarm


P15: Used to select whether the low pressure alarm is detected when the compressor is OFF (P15=1) or
alternatively only when the compressor is ON (P15=0, default).
When the compressor starts the alarm is in any case ignored for the time P03.

- High temperature/high system start-up temperature alarm delay


P16: Represents the high temperature alarm threshold detected by probe B1; the differential is set at 2
°C and the alarm is reset automatically (the alarm relay is activated, signal only, and the message “Ht” is
shown). When starting the system, this alarm is ignored for the time P17. If the system start-up protection
is enabled (see parameter P20) and the alarm is activated, the time P17 is ignored and the alarm has no
hysteresis.

- High temperature alarm delay on power-up


P17: High temperature alarm delay when the control is switched on (power ON), from the remote ON/
OFF contact or from the keypad.
- High pressure alarm from transducer set point
P18: Sets the value beyond which the high pressure alarm is generated. Each circuit will be managed by
its own transducer.
P18= 0: the function is disabled.
For all other values greater than 3.0, due to the hysteresis (3 bars), the alarm is managed according to the
set value.
- Low temperature alarm set point
P19: Represents a threshold for the low temperature (measured by probe B1) alarm, the differential is set
at 2 °C and it is reset automatically (the alarm relay is activated and the disply shows the message “Lt”)
- System start-up protection for high/low temperature
P20: If set to 1, this parameter enables the system protection function when starting, both at power ON
and when switching ON from Standby.
For values of B1 greater than the set point P19, an alarm is activated and the unit is not started (display
“AHt”).
The alarm is reset automatically.
P20=0: the function is not enabled.
- Low pressure alarm waiting time in heat pump
P22: Delay in generating the low pressure alarm in heat pump mode
If the pressure remains below 1 bar for the time p22 and the circuit has 2 compressor steps, the circuit
can operate at part load (see P04). This preventive capacity control function remains active until the
pressure rises above F08-F09.
- Low pressure alarm waiting time during defrost
P23: Delay in generating the low pressure alarm in heat pump mode during defrost
- Deactivate compressors in capacity control for HP and LP
P24: Decide which compressor must be stopped in each circuit during capacity control
P24= 0 stops compressors 1 and 3
P24= 1 stops compressors 2 and 4
- Low pressure alarm set point from transducer
P33: : Sets the value beyond which the low pressure alarm is generated when the unit is operating in
heat pump mode. Each circuit will be managed according to its own transducer.
P33= 0 the function is disabled.
- Mute alarm relay using “PRg/mute” button
P35=0 the PRG/mute button does not alter the status of the relay, if the alarm is active and in progress.
P35=1 the PRG/mute button alters the status of the relay even if the alarm is active and in progress, as if
it were a buzzer or a siren.
- High pressure alarm management
P36: the parameter is used to consider the high pressure alarm even when the compressor is off or
consider it only when the compressor is on, depending on whether the pressure switch is directly
connected to the digital input on the controller or via another circuit.
P36=0: high pressure alarm always considered (pressure switch connected directly to the digital input).
P36=1: high pressure alarm considered 2 seconds after starting the compressor.

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 31


- Definition of DI11 to DI15
P37: selection of digital input 11 (input 1 I/O board)
P38: selection of digital input 12 (input 1 I/O board)
ENGLISH

P39: selection of digital input 13 (input 1 I/O board)


P40: selection of digital input 14 (input 1 I/O board)
P41: selection of digital input 15 (input 1 I/O board)

Each parameter can be:


0= not connected
1= alarm Ad1
2= alarm Ad2
3= alarm Ad3
4= alarm Ad4
5= alarm Ad5
6= warning Ad1
7= warning Ad2
8= warning Ad3
9= warning Ad4
10= warning Ad5

Note: all alarms stop the unit. THe alarm relay will be activated. All warning activate the warning relay.

- Definition of DO11 to DO15


P42: selection of digital output 11 (output 1 I/O board)
P43: selection of digital output 12 (output 1 I/O board)
P44: selection of digital output 13 (output 1 I/O board)
P45: selection of digital output 14 (output 1 I/O board)
P46: selection of digital output 15 (output 1 I/O board)

Each parameter can be:


0= not connected
1= Ad1
2= Ad2
3= Ad3
4= Ad4
5= Ad5
6= HP1
7= HP2
8= LP1
9= LP2
10= TC1
11= TC2
12= FL
13= LT
14= HT
15= ALT
16= AHT
17= TP
18= FLB

• Control settings: parameters (r*)


- Cooling set point
r01: between r13 and r14
r02: cooling differential value of DTE when the unit is first started (autotuning enabled)
- Compressor rotation
r05: The rotation of the compressors allows the operating hours to be balanced either statistically, using
FIFO logic, or absolutely, by counting the effective operating hours. Settings:
r05=0: rotation disabled; The customer can use compressors with different power ratings according
to the desired logic or manage the capacity-control functions. The compressors are started/stopped in
proportional mode.
r05=1: rotation with FIFO logic (first ON, first OFF, and vice-versa first OFF, first ON); in this mode the
operating hours are optimised together with the number of starts, even if the compressor safety times are
always respected.
r05=2: rotation with control of operating hours; in this way the compressors will have the same operating
hours, as the compressor with the least operating hours is always started first, again observing the safety
times. This does not however consider FIFO logic and does not optimise the starts and stops. In the case of
capacity controlled compressors (1 per circuit), FIFO logic or timed operation will refer to the actual circuit
and not the compressor valves. If, for example, when capacity is required from circuit 1, compressor 1 starts
first, capacity controlled (not at full capacity), and then the valve is managed as a second step, so that the
compressor will work at maximum efficiency. If less capacity is required, the second step will be deactivated
first, and then the compressor. There is no rotation between the compressor and the valve. If extra capacity is
required, the second circuit will start with compressor 2 and then, if required, the valve is operated.

32 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


When stopping, the valve is managed first and then the actual compressor as a whole. Both FIFO logic
and timed operation will involve either one circuit or the other. The activation and deactivation of the valves
are not subject to timers, but rather only a hysteresis that is equal to the set point and the differential of

ENGLISH
the step (in fact the valve performs the same function as a hermetic compressor).
r05=3: direct correspondence between the digital inputs and the compressor relays (condensing units
only).

- Type of compressor control


r06: This parameter is used to set the logic for maintaining the set point:
r06= 0: proportional on inlet ON
r06= 1: proportional on inlet + dead zone (see Dead zone, below)
r06= 2: proportional on outlet
r06= 3: proportional on outlet with dead zone
r06= 4: on outlet by time with dead zone (see timed outlet temperature control)
DEAD ZONE
The dead zone essentially shifts the proportional band from the set
point by the value set for the parameter r07.This parameter is valid in
all configurations if enabled (for r070: dead zone set and enabled).
Key Figure 5.b.c: OFF r01 r01+r07+r02/4 r01+r07+r02*3/4
r06: enable the dead zone (enabled if r06=1 or 3) r01+r07 r01+r07+r02/2 r01+r07+r02
r07: dead zone
r01: cooling set point Fig. 5.b.c
r02: cooling differential

In chiller (cooling) mode, the dead zone moves the cooling proportional band above the set point by the
value r07.

Outlet temperature control by time r06 = 4


This type of control is based on the need to maintain the outlet temperature as constant as possible,
despite the load being variable or the reduced inertia of the system.
The logic has the aim of keeping the temperature inside the dead zone.
If outside the zone, the compressors will be activated with the logic described below, so as to return
inside the dead zone, neither too quickly (using an integral or derivative), nor too slowly, with fixed time
logic. There are two logical times involved: the activation time and deactivation time.

- Dead zone differential


r07: (see dead zone)

- Activation delay at lower limit of r07 (if r06 = 4)


r08: The value set is used in the control algorithm (see timed outlet temperature control) as the
maximum time (at the start of the differential) for the activation of the compressors.

- Activation delay at upper limit of r07 (if r06 = 4)


r09: The value set is used in the control algorithm (see timed outlet temperature control) as the
minimum time (at the end of the differential) for the activation of the compressors.
Activation time (cooling) r10
activation time
The activation time is not a set parameter, but rather the combination of two set parameters, that is, r08
and r09. When the temperature leaves the dead zone, the activation time is equal to r08, while at the end
time

of the differential r02 the activation time is equal to r09.


Inside the differential r02, the activation time varies linearly between r08 and r09.
This means that as the temperature moves away from the set point, the times are reduced and the r11
esponse of the process becomes more dynamic.
temperature
- Deactivation delay at upper limit of r12 (if r06 = 4) r03 r03+r12
r10: The value set is used in the control algorithm (see timed outlet temperature control) as the dead zone comp. act. differential
maximum time (at the set point) for the deactivation of the compressors.
Fig. 5.b.e
- Deactivation delay at lower limit of r12 (if r06 = 4)
r11: The value set for this parameter is used in the control algorithm (see timed outlet temperature
control) as the minimum time (at the end of the deactivation differential) for the deactivation of the
compressors.

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 33


- Compressor deactivation differential (if r06 = 4)
r01
r12: This represents the temperature differential for the deactivation of the compressors, according to the
deactivation time procedure described in “Deactivation time”.
ENGLISH

time
Deactivation time (cooling) Fig. 5.b.f
In the same way as for the activation time, the deactivation time also varies between a maximum value,
set for the parameter r10 and corresponding to the set point temperature, and a minimum, set for the
r01 parameter r11 corresponding to the end of the differential for the deactivation of the compressors, set by
the parameter r12.
temperature
A1 A4 r01-r12 compressor
Below this value, the deactivation time will be equal to the minimum set until reaching the temperature
compressor deactivation time A04, after which all the compressors will be switched OFF, irrespective of the times. As the temperature
stop
moves away from the set point, the response of the process becomes more dynamic.
Fig. 5.b.f

- Minimum Cooling set point


r13: Establishes the minimum limit for setting the Cooling set point.

- Maximum Cooling set point


r14: Establishes the maximum limit for setting the Cooling set point.

- Cooling compensation constant (chiller mode):


50
r17: Sets the coefficient that controls the cooling compensation algorithm. In cooling mode, if r17 is
3 positive, the set point increases as the outside temperature increases (measured by the outside probe); if
40 on the other hand r17 is negative the set point decreases as the outside temperature increases.
4 This difference in the set point from the set value can have a maximum absolute value equal to the
1
30
setting of r18. The values for the parameters shown on the graph are: r17=±2, r01=25, r19=32 and r18=5).
5 r18
Key:
6 r18
1. temperature;
20
7
2. time;
3. external temperature (probe B3/B4);
10 4. comp. start temperature (r19);
2 5. positive compensation (r17= 2);
Fig. 5.b.i 6. set point (r1);
7. negative compensation (r17=-2).

Example of compressor deactivation due to outside - Maximum deviation from the set point
temperature r18: Indicates the maximum deviation from the set point beyond which compensation is stopped
1 (maximum and minimum limits in reference to the set point).
ON

- Start compensation temperature in cooling (outside probe)


r19: Sets the temperature (measured by the outside probe) above which the compensation function
r25 r25+1 °C 2
starts (cooling), value between -40T80 °C.
Fig. 5.b.l
- Start compensation temperature in heating (outside probe)
r20: Sets the temperature (measured by the outside probe) below which the compensation function
starts (heating), the value must be between -40T80 °C.

- Second cooling set point from external contact


r21: Represents the alternative to r01 if an associated digital input is closed (see parameter P08), between
r13 and r14.

- Outside temperature set point to stop compressors


r25: To avoid energy efficiency lower than electrical heating, the compressors are stopped if the outside
temperature falls below r25, the differential to start them again is set to 1 degree. The heaters can then be
activated according to the corresponding set point.
Setting 25 to “-40” (default value) disabled the function.

- Buffer tank suppression (low load)


r27: The low load condition is determined when only one compressor is started and then is stopped after
operating for less than the time set for parameter r28.
The settings are:
r27=0: the function is disabled;
r27=1: enabled only in chiller mode;
r27=2: enabled only in heat pump mode;
r27=3: enabled in chiller and heat pump modes.

- Minimum compressor on time to determine low load condition


r28: This parameter represents the minimum compressor on time below which the low load condition is
determined. Whenever the compressor stops, the controller analyses the load status.
If already in low load condition, the time considered by the controller for the analysis becomes “r28 x r29:
r02” in chiller mode, or “r28 x r30 : r04” in heat pump mode.
This parameter also has the meaning of damper travel time when freecooling/heating is enabled.
When the sum of the opening times reaches 2*damper travel time, the damper is no longer moved. The
sum is reset when the damper is closing. Operation is the same in closing.
34 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010
- Differential during the low load condition in chiller mode
r29: This parameter represents the new differential considered by the controller in chiller mode during
the low load condition.

ENGLISH
Specifically, r02 is replaced by r29.
This also has the meaning of freecooling differential.

- Differential during the low load condition in heat pump mode


r30: This parameter represents the new differential considered by the controller in heat pump mode
during the low load condition.
Specifically, r04 is replaced by r30.
This also has the meaning of freeheating differential.

1 2 Key:
on on 1. chiller;
2. chiller in low load;
off off 5. temperature.
r01 r01 + r02 5 r01 r01 + r29 5
Fig. 5.b.m
- Electric heater set point relationship
r43: defines the relationship between the absolute set point, considered as the activation threshold for
the electric heaters, and the relative set point, that is, the activation threshold for the electric heaters
referred to a working set point (set point sent by µAD, r01 or r04 or from time band) depending on the
various applications and the mode, cooling or heating, and more precisely:
r43= 0 A4, A8, A11, P16, P19 absolute values
r43= 1 A4, P16, P19 absolute values; A8, A11 relative values
r43= 2 A8, A11, P16, P19 absolute values; A4 relative value
r43= 3 P16, P19 absolute values; A4, A8, A11 relative values
r43= 4 A4, A8, A11 absolute values; P16, P19 relative values
r43= 5 A4 absolute value; A8, A11, P16, P19 relative values
r43=6 A8, A11 absolute values; A4, P16, P19 relative values
r43=7 A4, A8, A11, P16, P19 relative values
- Maximum value of calculated set point in relative regulation
r45: for the relative set point function, there is a maximum limit. When the control works in relative
mode, the set point calculated is lmited by r45.

- Minimum value of calculated set point in relative regulation


r46: for the relative set point function, there is a minimum limit. When the control works in relative mode,
the set point calculated is lmited by r46.

• Firmware parameters: (F-r*)


These parameters cannot be set (display only:
H95: software version of I/O board;
H96-H97: software version of Driver 1, 2;
H98: software version of the expansion;
H99: software version of the µC2SE controller.
Functions available with the clock board
The alarm log is only active and operative if the clock board is fitted. The terminal shows whether the
clock board is fitted by displaying the following parameters:
- RTC hours
t01: RTC hours
- RTC minutes
t02: RTC minutes
- RTC day
t03: RTC day
- RTC month
t04: RTC month

- RTC year
t05: RTC year

The alarms are only shown on the local display.


The controller saves the significant events that stop (alarms) or limit (warnings) the operation of the unit.
Up to 25 events can be saved, highlighting:
— Event code;
— Start hours;
— Start minutes;
— Start day;
— Start month;
— End hours;
— End minutes;
— End day;
— End month.

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 35


The log is accessed by pressing PRG+SEL for 5s and entering the password 44.
The alarms saved are complete, as they include both the start and end of the event.
The alarms can be deleted individually by pressing UP and DOWN for 5s when the desired event is
ENGLISH

displayed. If there are no alarms saved, “noH” is displayed. The table shows the possible alarms that can
be saved:
SV Display Type SV Display Type SV Display Type
All. Circ. 1 HP1 High pressure circuit 1 All. Sonde E4* Probe B4 alarm OFF SH1 EVD1 overheat alarm
All Circ. 2 HP2 High pressure circuit 2 All. Sonde E5 Probe B5 alarm All. Evd 2 SH2 EVD2 overheat alarm
All. Circ. 1 LP1 Low pressure circuit 1 All. Sonde E6 Probe B6 alarm All. Evd 1 EP1 EEPROM error EVD 1
All Circ. 2 LP2 Low pressure circuit 2 All. Sonde E7* Probe B7 alarm7 All. Evd 2 EP2 EEPROM error EVD 2
All. Gen. TP General thermal overload All. Sonde E8* Probe B8 alarm All. Evd 1 ES1 Probe error EVD 1
All. Circ. 1 tC1 Thermal overload circuit 1 All. Gen. ESP Expansion error All. Evd 2 ES2 Probe error EVD 2
All. cir. 2 tC2 Thermal overload circuit 2 All. Circ. 1 A1 Frost alarm circ. 1 All. Evd 1 EU1 Valve open error EVD 1 start
All. Gen FL Flow switch alarm All. Circ. 2 A2 Frost alarm circ. 2 All. Evd 2 EU2 Valve open error EVD 2 start
All. Sonde E1 Probe B1 alarm All. Gen. EHS High power supply voltage All. Evd 1 Eb1 EVD 1 battery alarm
All. Sonde E2 Probe B2 alarm All. Evd 1 Ed1 EVD1 tLAN error All. Evd 2 Eb2 EVD 2 battery alarm
All. Sonde E3* Probe B3 alarm All. Evd 2 Ed2 EVD2 tLAN error All. Sonda µAD Et uAD terminal probe alarm

- Start hours for 2nd set point in cooling


t06 (I92): Hour when the second cooling set point starts(r21).
- Start minutes for 2nd set point in cooling
t07 (I93): Minutes when the second cooling set point starts (r21).
- End hours for 2nd set point in cooling
t08 (I94): Hour when the second cooling set point stops (r21).
- End minutes for 2nd set point in cooling
t09 (I95): Minutes when the second cooling set point stops (r21).
If a digital input is configured as the second set point from external contact (e.g. p08 = 13) the time bands
are ignored. If a digital input is configured as the second cooling set point from external contact and
heating set point from time band (e.g. p08 = 14), the cooling time bands are ignored.
The second set point from external contact input has priority over the second cooling set point from
external contact and heating set point from time band.
- Start hours for low noise in cooling
t14: Start hours for low noise in cooling
- Start minutes for low noise in cooling
t15: Start minutes for low noise in cooling
- End hours for low noise in cooling
t16: End hours for low noise in cooling
- End minutes for low noise in cooling
t17: End minutes for low noise in cooling

36 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


6. TABLE OF ALARMS

ENGLISH
Key to the table of alarms:
*: if the probe is set for the compensation function, in the event of probe faults, the unit continues to operate.
ON*: if the expansion card is not present.
EVD 1= EVD400 connected to µC2SE (1st circ.)
EVD 2= EVD400 connected to the expansion (2nd circ.)

alarm alarm type resetting Compressor pump fan heater Valve alarm warning superv. superv. variab. variab.
display variable description type
IO Communication error with Automatic OFF OFF OFF OFF OFF OFF - - Signal on display Digital
I/O board
HP1 High pressure Depends on P05 OFF C1-2 - ON(60”) - - ON - 41 (R) Circuit 1 alarm Digital
HP2 High pressure Depends on P05 OFF C3-4 - ON(60”) - - ON - 42 (R) Circuit 2 alarm Digital
LP1 Low pressure Depends on P05 OFF C1-2 - OFF 1 - - ON - 41 (R) Circuit 1 alarm Digital
LP2 Low pressure Depends on P05 OFF C3-4 - OFF 2 - - ON - 42 (R) Circuit 2 alarm Digital
TP General overload Depends on P08 OFF OFF OFF - - ON - 45 (R) General warning Digital
tC1 Circuit 1 overload Depends on P08 OFF C1-2 - OFF 1 - - ON - 41 (R) Circuit 1 alarm Digital
tC2 Circuit 2 overload Depends on P08 OFF C3-4 - OFF 2 - - ON - 42 (R) Circuit 2 alarm Digital
LA advice Depends on P08 - - - - - ON* ON 50 (R) General advice Digital
FL Flow controller alarm Depends on P08 OFF OFF OFF - - ON - 45 (R) General alarm Digital
FLb Backup pump warning Automatic - - - - - - ON 50 (R) General advice Digital
E1 Probe B1 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E2 Probe B2 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E3* Probe B3 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E4* Probe B4 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E5 Probe B5 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E6 Probe B6 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E7* Probe B7 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E8* Probe B8 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
Hc1-4 Hour warning C1-4 Automatic - - - - - - ON 47 (R) Compressor advice Digital
EPr EEPROM error during Automatic - - - - - - ON 50 (R) General advice Digital
operation
EPb EEPROM error at the start-up Automatic OFF OFF OFF OFF OFF OFF OFF 45 (R) General alarm Digital
ESP Expansion Error Automatic OFF OFF OFF OFF OFF ON - 45 (R) General alarm Digital
EL1-2 Zero cross Automatic - - 100% - - ON* ON 52 (R) Fan advice Digital
dF1-2 Defrosting error Automatic - - - - - - ON 50 (R) General warning Digital
d1-2 Defrost on circuit in - - - - - - - - - Signal on display -
question
A1 Frost alarm circ. 1 Depends on P05 OFF C1-2 - OFF 1 - - ON - 41 (R) Circuit 1 alarm Digital
A2 Frost alarm circ. 2 Depends on P05 OFF C3-4 - OFF 2 - - ON - 42 (R) Circuit 2 alarm Digital
Ht High temperature Automatic - - - - - ON* ON 51 (R) Temperature advice Digital
Lt Low ambient temp. Depends on P05 - - - - - ON* ON 51 (R) Temperature advice Digital
AHt High temperature at the Automatic OFF - OFF OFF - - ON 50 (R) General warning Digital
start-up
ALt Low temperature at the Automatic OFF - OFF OFF - - ON 50 (R) General warning Digital
start-up
ELS Low supply voltage Automatic - - - - - - ON 50 (R) General warning Digital
EHS High supply voltage Automatic OFF OFF OFF OFF OFF OFF OFF 45 (R) General alarm Digital
Ed1 EVD 1 tLAN error Automatic OFF C1-2 - OFF - - ON - 43 (R) EVD 1 warning Digital
Ed2 EVD 2 tLAN error Automatic OFF C3-4 - OFF - - ON - 44 (R) EVD 2 warning Digital
SH1 EVD 1 superheat alarm - OFF C1-2 - OFF- - - ON - 43 (R) EVD 1 warning Digital
SH2 EVD 2 superheat alarm - OFF C3-4 - OFF- - - ON - 44 (R) EVD 2 warning Digital
nO1 MOP 1 warning Automatic - - - - - - ON 48 (R) EVD 1 advice Digital
nO2 MOP 2 warning Automatic - - - - - - ON 49 (R) EVD 2 advice Digital
LO1 LOP 1 warning Automatic - - - - - - ON 48 (R) EVD 1 advice Digital
LO2 LOP 1 warning Automatic - - - - - - ON 49 (R) EVD 2 advice Digital
HA1 High inlet temperature Automatic - - - - - - ON 48 (R) EVD 1 advice Digital
warning circ.1
HA2 High inlet temperature Automatic - - - - - - ON 49 (R) EVD 2 advice Digital
warning circ. 2
EP1 EVD 1 Eeprom error Automatic OFF C1-2 - OFF- - - ON - 43 (R) EVD 1 warning Digital
EP2 EVD 2 Eeprom error Automatic OFF C3-4 - OFF- - - ON - 44 (R) EVD 2 warning Digital
ES1 EVD 1 probe error Automatic OFF C1-2 - OFF- - - ON - 43 (R) EVD 1 warning Digital
ES2 EVD 2 probe error Automatic OFF C3-4 - OFF- - - ON - 44 (R) EVD 2 warning Digital
EU1 Open valve EVD 1 error at Automatic OFF C1-2 - OFF - - ON - 43 (R) EVD 1 warning Digital
the start-up
EU2 Open valve EVD 2 error at Automatic OFF C3-4 - OFF - - ON - 44 (R) EVD 2 warning Digital
the start-up
Eb1 EVD 1 battery alarm Automatic OFF C1-2 - OFF - - ON - 43 (R) EVD 1 warning Digital
Eb2 EVD 2 battery alarm Automatic OFF C3-4 - OFF - - ON - 44 (R) EVD 2 warning Digital
L Low load warning Automatic - - - - - - - - Signal on display -
Ed1 tLan EVD 1 communication Automatic OFF C1-2 - OFF - - ON - 43 (R) EVD 1 warning Digital
error
Ed2 tLan EVD 2 communication Automatic OFF C3-4 - OFF - - ON - 44 (R) EVD 2 warning Digital
error
PH1 Low pressure circ. 1 warning - - - - - - - - - Signal on display -
PH2 Low pressure circ. 2 warning - - - - - - - - - Signal on display
SUL low outlet temperature - - - - - - - - - Signal on display
warning
Table 6.a
Note: The warning relay differs from the alarm relay as it is only activated for warnings, that is, signals only, which
have no direct effect on the operation of the unit, and the display does not show the alarm symbol (bell).
N.B. The alarm relating to the circuit with the fault must not interact with the operation of the other
circuit, as long as the condenser is not shared in common.

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 37


IO: communication error with I/O board
If the control loses communication with I/O board, all of the system will be inhibited to prevent the unit being
damaged. The alarm relay will be activated and the message will be visible on the display with fixed red LED.
ENGLISH

HP1: High pressure circuit 1


The alarm is detected irrespective of the status of the pump and the compressors. The compressors
corresponding to circuit 1 are immediately stopped (ignoring the set protection times), the buzzer and
alarm relay are activated, and the display starts flashing.
The fans corresponding to the condenser in circuit 1 are activated at maximum speed for 60 s, so as
to oppose the alarm situation, after which they are switched OFF. This alarm may also be generated
when the high pressure limit is exceeded (valid only when the pressure transducer is fitted) set by the
parameter P18, which to be enabled must be greater than 3.0 bars, due to the corresponding hysteresis.

HP2: High pressure circuit 2


As for HP1 but relating to circuit 2.

LP1: Low pressure circuit 1


The alarm depends on P15, P7 and P3.
P15= 0, P07= 0: the alarm is detected only if the compressors in circuit 1 are ON, and after the time P03
from when the compressors started, otherwise it is immediate.
P15= 1, P07= 0: the alarm is detected even if the compressors in circuit 1 are off, after the time P03.
P15= 0, P07= 1: the alarm is detected only if the compressors in circuit 1 are ON, and after the time P03
from when the compressors started, otherwise it is immediate, and if in heat pump mode, is activated for
pressure values less than 1 bar.
P15= 1, P07= 1: the alarm is detected also if the compressors in circuit 1 are Off, after the time P03, and if in
heat pump mode, is activated for pressure values lower then 1 bar. The hysteresis for this alarm is 1 bar.

LP2: Low pressure circuit 2


As for LP1 but relating to circuit 2.

PH1: Compressor part load circuit 1


Indicates the part load of circuit 1 due to high pressure. This situation is signalled by the message “PH1”
on the display the activation of the warning relay.

PH2: Compressor part load circuit 2


As for PC1, but for circuit 2.

tP: General thermal overload


The alarm is detected irrespective of the status of the pump and the compressors. The compressors, the
pumps and fans stop (without observing the protection times) or are inhibited from starting, the alarm
relay is activated, the display flashes the corresponding message, and the LED flashes. It can be reset
either manually or automatically (see par. P08, P09, P10, P11, P12, P13).

tC1: Thermal overload circuit 1


As for tP but relating to circuit 1

tC2: Thermal overload circuit 2


As for tC1 but relating to circuit 2.

LA: generic warning


This represents a generic warning that appears on the display, from digital input, without modifying the
operation of the unit. With the 1st circuit module only, the alarm relay is activated, while with the
expansion card the warning relay can be used.

FL: flow alarm


This alarm is detected only if the pump is ON (excluding the delays when starting P01 and in steady
operation P02), irrespective of the status of the compressor. All of the outputs are disabled: pump,
compressor (without observing the OFF times), condenser fan, and the buzzer sounds, the alarm relay is
activated and the display flashes.
The presence of the utility water pump must be enabled (H50). It can be reset either manually or
automatically (see P08, P09, P10, P11, P12, P13).

FLb: Backup pump warning


The warning activates the warning relay and displays the message “FLb”; reset is manual. This indicates
the operation of the backup pump (if present) due to a probable fault on the main pump, suggesting that
maintenance is required. If the flow alarm features automatic reset, the controller will make 10 attempts
to re-start the pumps, after which the FL alarm will replace FLb. If the flow alarm features manual reset,
when first activated the controller will display the alarm FLb, switching over the pumps; when activated
again the FL alarm will replace FLb.

E1 to E8: probe error detected even when the unit is in Standby


The presence of a probe alarm causes the deactivation of the compressor, the condenser fans, the pump
(outlet fan in AIR/AIR units) and the heaters (so as to avoid fires in the air/air units); the buzzer and alarm
relay are activated, and the display starts flashing.
If the probe has a compensation function, the unit will continue a operate correctly, with the exception of
the corresponding function, and the warning relay will be activated and a message shown on the display,
from E1 to E8 for probes from B1 to B8.

38 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


Hc1 to Hc4: compressor operating hour limit exceeded warning
When the number of operating hours for the compressor exceeds the maintenance threshold (as default
equal to zero, and consequently the function is disabled), the maintenance request signal is activated.

ENGLISH
The buzzer and the alarm relay are not activated, however the warning relay is activated (with the
expansion card fitted).

Epr, EPb: EEPROM error


A problem has occurred when saving the parameters to the unit’s non-volatile memory (EEPROM); in the
event of an Epr error, the µC2SE continues to perform the control functions with the data present in the
volatile memory (RAM), where there is a physical copy of all of the data. After the first power failure the
configuration will be lost.
The buzzer and the alarm relay are not activated. If the occurs when starting the unit, “EPb”, the controller
will not operate.

ESP: communication error with expansion card


If the controller loses communication with the expansion card, the entire system will be stopped to avoid
adversely affecting the unit. The alarm relay is activated and the display will show the message, with the
red LED on steady.

EL1-2: warning, zero crossing error circuit 1-2


If the controller detects errors in the power supply, control may be lost over the fan speed. In this case,
the display will show a warning, and the fans will be controlled at maximum speed. The alarm is reset
automatically, so as to not affect the operation of the unit. If the expansion card is used, the warning relay
is activate)

dF1-2: warning, end defrost circuit 1-2 due to maximum time


If the defrost ends after the maximum time when end defrost by temperature or from external contact
has been selected, the unit displays the text dF1 for circuit 1 or dF2 for circuit 2. The message is cancelled
using the delete alarm procedure or when the next correct defrost cycle is completed. The buzzer and the
alarm relay are not activated. If the expansion card is used, the warning relay is activated (if used).

A1: antifreeze alarm outlet limit circuit 1


The alarm is only detected in water chillers (H01= 2, 3, 4, 5 or 6) by the evaporator water outlet
probe (B2/B6) or, if the electronic expansion driver (EVD) is connected to the tLAN, based on the
evaporation temperature sent by the driver. The evaporator water outlet temperature is compared
against the threshold A01, while the evaporation temperature is compared against the threshold A14. The
compressors in circuit 1 and the condenser fans in circuit 1 are immediately stopped, the buzzer and
alarm relay are activated, and the display starts flashing. If the µC2SE is in Standby, the alarm condition is
not detected, and only the heaters are managed. Reset depends on parameter P5:
1. in the event of automatic reset, the unit restarts automatically if the temperature is above the value
A01+A02 or A14+A02.
2. in the event of manual reset, the unit can restart manually even if the alarm is active.
After the time A03, if the alarm persists the unit will stop again.
For air/air units the parameter becomes the antifreeze-outlet limit alarm set point. If the outlet limit is
active, the freecooling damper is forced closed and the message SUL is shown on the display.

A2: antifreeze alarm circuit 2


As for A1 but relating to circuit 2

Ht: high temperature warning


This alarm is activated when the threshold is exceeded (read by B1), set for the parameter P16. It is
delayed at power ON by the parameter P17 and causes the activation of the alarm relay and the buzzer,
without deactivating the outputs. It is reset automatically when conditions that caused the alarm are no
longer present.

Lt: low temperature warning


For direct expansion units (H01=0, 1) the alarm is used to measure a low room temperature using probe
B1 or B2 (depending on par. A06).
The alarm may be reset manually or automatically, and depends on the parameter P05. If the expansion
is present, the corresponding relay is activated; in the event of µC2SE module only, the alarm relay will be
used.

AHt: high temperature warning when starting the system


The advice does not activate the relay, and displays the message “AHt”.

ALt: low temperature warning when starting the system


The advice does not activate the relay, and displays the message “ALt”.

ELS/EHS: warning, low/high power supply alarm


If the power supply voltage is too low or too high, the corresponding message is displayed. In these
cases, the correct operation of the µC2SE is no longer guaranteed. In the low voltage conditions only the
requests to deactivate the loads are effected. Any start-up requests remain pending. The high voltage
condition involves the deactivation of all the energised relays.

L: Low load warning


The warning does not activate the relay and displays the message “ L ”; reset is automatic.

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 39


D1: defrost signal circuit 1
When the defrost is on circuit 1, the display shows the message D1.
ENGLISH

D2: defrost signal circuit 2


When the defrost is on circuit 2, the display shows the message D2.

Driver
All the driver alarms on the µC2SE that stop the unit feature automatic reset. Consequently, the possibility
to select the automatic resetting of the entire system must be selected for the drivers by setting the
corresponding parameters. The µC2SE can send the Go Ahead command according to the normal
procedure for resetting the alarms from the keypad.

Ed1: tLan communication error with Driver 1


The alarm is generated after a fixed time (5 s) from when the µC2SE loses contact with Driver 1. In this
case, circuit 1 is disabled for safety reasons.

Ed2: tLan communication error with Driver 2 (expansion card)


As for Ed1, but relating to driver 2.

SH1: low superheat alarm circuit 1


The low superheat alarm for circuit 1, after a fixed time (5 s), inhibits the circuit 1 for safety reasons.
The risk is that the compressors will flood.

SH2: low superheat alarm circuit 2


As for SH1, but relating to driver 2

nO1: MOP warning (maximum operating pressure) circuit 1


The warning appears on the display and, if the expansion card is fitted, the corresponding relay is
activated.

nO2: MOP warning (maximum operating pressure) circuit 2


The warning appears on the display and, if the expansion card is fitted, the corresponding relay is
activated.

LO1: LOP warning (lowest operating pressure) circuit


The warning appears on the display and, if the expansion card is fitted, the corresponding relay is
activated.

LO2: LOP warning (lowest operating pressure) circuit 2


As for LO1, but relating to driver 2

HA1: high evaporator temperature warning circuit 1


The warning appears on the display and, if the expansion card is fitted, the corresponding relay is
activated.

HA2: high evaporator temperature warning circuit 2


As for HA1, but relating to driver 2.

EP1: EEPROM error driver 1


The circuit 1 is disabled for safety reasons, as the status of Driver 1 is not known.

EP2: EEPROM error driver 2


As for EP1, but relating to driver 2.

ES1: probe error driver 1


The circuit 1 is disabled for safety reasons, as the status of Driver 1 is not known.

ES2: probe error driver 2


As for ES1, but relating to driver 2.

EU1: EVD 1 error, valve open when starting


If when starting the system the Driver detects that the valve is still open, an alarm is sent to the µC2SE that
stops the compressors and the fans in the corresponding circuit.

EU2: EVD 2 error, valve open when starting


As for EU1, but relating to EVD 2.

Eb1: EVD 1 battery alarm


The EVD 1 battery alarm stops the compressors from starting so as to prevent the risk of liquid returning
to circuit 1, and disables the corresponding fans.

Eb2: EVD 2 battery alarm


The EVD 2 battery alarm stops the compressors from starting so as to avoid the risk of liquid returning to
circuit 2, and disables the corresponding fans.

40 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


7. CONNECTIONS, ACCESSORIES AND OPTIONS

ENGLISH
7.1 Connection diagram
Below is the connection diagram for the µC2SE.
Panel version
N
Line
L

AUX10
AUX9
AUX8

AUX7

AUX6
No6 C6/7C6/7C8/9 x C10

No7 No8 No9 C8/9 x No10


Tx/Rx GND

Top

I/O

Bottom
GND Tx/Rx GND B8 V+
G0 B5 B6 B7 ID10 ID8 ID6

G GND GND Y2 GND ID9 ID7

pressure
P probe

N L
Line
EV Driver

EV driver ESP EV driver

Expansion N
board Line
EV Driver L
tLAN
AUX4
AUX3

AUX2

AUX5
No1 C1/2 C1/2 C3/4 x C5

No2 No3 No4 C3/4 x No5


Tx/Rx GND

GND B4 V+
G0 B1 B2 B3 ID5 ID3 ID1 Key/SPV
G GND GND Y1 GND ID4 ID2

pressure
P probe

To program key
RS485
option

N L
Line To serial link
Fig. 7.a
I/O layout
µC2SE Description
B1 Programmable I/O
B2 Programmable I/O
B3 Programmable I/O
B4 (universal) Programmable I/O
ID1* Programmable I/O (*= Any of the options for P08 can be selected (see Table 5.11))
ID2* Programmable I/O (*= Any of the options for P08 can be selected (see Table 5.11))
ID3 Programmable I/O
ID4 Programmable I/O
ID5 Programmable I/O
Y1 Programmable I/O
C1/2-NO1 Programmable I/O
C1/2-NO2 Programmable I/O
C3/4-NO3 Programmable I/O
C3/4-NO4 Programmable I/O
C5-NO5 Programmable I/O
Table 7.a
Expansion Description
B5 Programmable I/O
B6 Programmable I/O
B7 Programmable I/O
B8 (universal) Programmable I/O
ID6** Programmable I/O (**= Any of the options for P08 can be selected, except for E/I and E/I delay.)
ID7** Programmable I/O (**= Any of the options for P08 can be selected, except for E/I and E/I delay.)
ID8 Programmable I/O
ID9 Programmable I/O
ID10
Y2 Programmable I/O
C6/7-NO6 Programmable I/O
C6/7-NO7 Programmable I/O
C8/9-NO8 Programmable I/O
C8/9-NO9 Programmable I/O
C10-NO10 Programmable I/O
Table 7.b
µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 41
7.2 Expansion card
This device allows the µC2SE to manage the second refrigerant circuit on chillers, heat pumps and
ENGLISH

condensing units with up to 4 hermetic compressors.


The following figure shows the connection diagram for the µC2SE expansion card, code MCH200002*.

EV Driver N
EV driver Line
L

No6 C6/7 C6/7 C8/9 x C10

No7 No8 No9 C8/9 x No10


Tx/Rx GND

Top
Expansion board

Bottom
GND Tx/Rx GND B8 V+
G0 B5 B6 B7 ID10 ID8 ID6

outlet probe
G GND GND Y GND ID9 ID7

cond. probe

inlet probe

remote ON/OFF
multi funct.

multi funct.

high press.
pressure

low press.
P probe

temperature
probe

digital
input
t-LAN
N L
Line

Fig. 7.b

NOTE: The expansion features two LEDs on the main board (to see these, remove the top or bottom
door), which display its status by the following messages:

ON Flashing
green LED Board powered Board powered and serial communication with µC2SE in progress
red LED 1 flash: Probe fault alarm
2 flashes: Zero crossing alarm (mains frequency not detected)
3 flashes: Serial communication alarm with EVD
4 flashes: Serial communication alarm with µC2SE
Table 7.c
The alarms are displayed in sequence and are separated from each other by pauses.

7.3 EVD4*: Electronic expansion valve driver


This device is used to control electronic expansion valves. The device is connected to the µC2SE via a
tLAN serial line. The condensing pressure probe must be connected to the µC2SE, which then sends the
reading to the driver.
Nota: for all other information on the connections, refer to the EVD4* driver manual.

1 GND 2 COM NO PHOENIX¡


PHOENIX¡ GMSTB 2,5/2 ST
MC1,5/3-ST-3,81 3 GND 4

EEV driver

FCSER00000

MOLEX¡ Mini-Fit G Vbat DI1 S4V S3 S2 S1


538-39-01-2140 MOLEX¡ Mini-Fit
G0 GND DI2 S4I Vr1 Vr2 OC GNX RT+ RT- 538-39-01-2060

Fig. 7.c

42 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


7.4 Fan speed control board (code MCHRTF*)
The phase cutting boards (code MCHRTF****) are used to control the speed of the condenser fans. 1

ENGLISH
IMPORTANT: The power supply to the µC2SE (G and G0) and the MCHRTF**** board must be in 2 GND Y
phase. If, for example, the power supply to the µC2SE system is three-phase, make sure that the - +
primary of the transformer supplying the µC2SE board is connected to the same phase that
is connected to terminals N and L on the speed control board; therefore, do not use
380 Vac/24 Vac transformers to supply the controller if the phase and neutral are used to directly
power the speed control boards.
Connect the earth terminal (where envisaged) to the earth in the electrical panel.
Key:
1. to µchiller;
2. earth;
3. to motor.
LOAD LINE
3. al motore.

3 220 Vac

Fig. 7.d

to µchiller

7.5 Fan ON/OFF control board (code CONVONOFF0) 24 Vac Y GND

The relay boards (code CONVONOFF0) are used for the ON/OFF management of the condenser fans.
1 2 3 4
The control relay has a switchable power rating of 10 A at 250 Vac in AC1 (1/3 HP inductive).

5 6 7 8

No Com Nc
Fig. 7.e

to µchiller
7.6 PWM to 0 to 10Vdc (or 4 to 20 mA)conversion board for fans 24 Vac Y GND
(code CONV0/10A0)
The CONV0/10A0 boards convert the PWM signal at terminal Y on the µC2SE to a standard 0 to 10 Vdc (or 1 2 3 4
4 to 20 mA) signal. The FCS series three-phase controllers can be connected to the µC2SE without using
this module.

5 6 7 8

G0 0-10V G0 4-20mA
Fig. 7.f

7.7 Minimum and maximum fan speed calculation - +

This procedure should only be performed when the fan speed control boards are sued (code MCHRTF*).
it must be stressed that if the ON/OFF modules (code CONVONOFF0) or alternatively the PWM to 0 to
10 V converters (code CONV0/10A0) are used, parameter F03 should be set to zero, and parameter F04
to the maximum value.
Given the different types of motors existing on the market, the user must be able to set the voltages
supplied by the electronic board corresponding to the minimum and maximum speeds. In this regard
(and if the default values are not suitable), proceed as follows:
• set parameter F02= 3 and set F03 and F04 to zero; LOAD LINE
• the condenser control set point (evaporator in HP mode) has been modified to take the output signal L N N L
to the maximum value (PWM);
• increase F04 until the fan operates at a sufficient speed (make sure that, after having stopped it, it can
rotate freely when released);
• “copy” this value to parameter F03; this sets the voltage for the minimum speed;
• connect a voltmeter (set for AC, 250V) between the two “L” terminals (the two external contacts);
Vac?
• increase F04 until the voltage stabilises at around 2 Vac (inductive motors) or 1.6, 1.7 Vac (capacitive
motors). Once the value has been found, it will be evident that even when increasing F04 the voltage
no longer decreases. In any case do not increase F04 further so as to avoid damaging the motor;
• restore the correct condenser set point (evaporator in HP mode).

The operation is now completed. Fig. 7.g

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 43


7.8 Programming key (code PSOPZKEYA0)
The programming keys PSOPZKEY00 and PSOPZKEYA0 for CAREL controllers are used for copying the
ENGLISH

complete set parameters for µC2SE.


The keys must be connected to the connector (4 pin AMP) fitted on the controllers, and can work with
the instruments ON or OFF, as indicated in the operating instructions for the specific controller.
The two main functions (upload/download) that can be selected through two dip-switches (which are
placed under the battery cover). They are:
• Loading to the key the parameters of a controller (UPLOAD);
• Copying from the key to one or more controllers (DOWNLOAD).
Warning: the copying of the parameters is allowed only between instruments with the same code.
Data loading operation to the key is always allowed. To make identification of the key easier CAREL has
inserted a label on which you can describe the loaded programming or the machine to which you are
Fig. 7.h Fig. 7.i referring.
IMPORTANT NOTE: the key can be used only with controllers µC2SE that have the same Firmware
version.

UPLOAD - copying the parameters from an instrument to the key:


• open the rear hatch of the key and place the two dip-switches in the OFF position (see Fig. 7.j.a). Close
the hatch;
• connect the key to the connector of the instrument;
• press the button on the key and keep it pressed, checking the LED signal sequence: at first it is red,
after a few seconds it becomes green;
• if the sequence of signals is as indicated above, the copying operation has been completed correctly
(green LED ON), the button can be released and the key disconnected from the instrument; in case of
different signals: if the green LED doesn’t turn on or if there are some flashes, there’s a problem. Refer
to the corresponding table for the meaning of the signals.
Fig. 7.j.a

DOWNLOAD - copying the parameters from the key to the instrument:


• open the rear hatch of the key and place the dip-switch n. 1 in the OFF position and the dip-switch n.
2 in the ON position (see Fig. 7.j.b). Close the hatch;
• connect the key to the connector of the instrument;
• press the button on the key and keep it pressed, checking the LED signal sequence: at first it is red,
after a few seconds it becomes green;
• if the sequence of signals is as indicated above, the copying operation has been completed correctly
(green LED ON), the button can be released; after a few seconds the LED turns off and the key can be
disconnected from the instrument;
• in case of different signals: if the green LED doesn’t turn on or if there are some flashes there’s a
problem. Refer to the corresponding table for the meaning of the signals.
The operation takes maximum 10 seconds to complete. If after this period the completed operation signal
Fig. 7.j.b hasn’t yet appeared, i.e. the green LED ON, try releasing and pressing the button again. In the event of
flashes, refer to the corresponding table for the meaning of the signals.

LED signal error meaning and solution


red LED flashing Flat batteries at the The batteries are flat, the copying cannot be carried out.
beginning of the Replace the battery (only on PSOPZKEY00).
copying
green LED Flat batteries at the end The copying operation has been carried out correctly but at the end
flashing of the copying (only on of the operation the voltage of the batteries is low.
PSOPZKEY00) It is advisable to replace the batteries.
Alternate red/ Not compatible The setup of the parameters cannot be copied since the model of
green LED instrument the connected parameters is not compatible. Such error happens
flashing only with the DOWNLOAD function, check the controller code and
(orange signal) make the copy only on compatible codes.
red and green Copying error Error in the copied data. Repeat the operation; if the problem
LEDs ON persists, check the batteries and the connections of the key.
red LED always Data transmission error The copying operation hasn’t been completed because of serious
ON data transmission or copying errors. Repeat the operation, if the
problem persists, check the batteries and the connections of the key.
LEDs OFF Batteries disconnected Check the batteries (for the PSOPZKEY00)
Power supply not Check the power supply (for the PSOPZKEYA0)
connected
Table 7.d

Technical specifications
Power supply to the - Use three 1.5 V 190 mA batteries (Duracell D357H or equivalent)
PSOPZKEY00 - Maximum current supplied 50 mA max.
Power supply to the - switching power supply:
PSOPZKEYA0 Input 100 to 240 V~; (-10%, +10%); 50/60 Hz; 90 mA. Output: 5 Vdc; 650 mA
Operating conditions 0T50°C r.H. <90% non-condensing
Storage conditions -20T70°C r.H. <90% non-condensing
Case Plastic, dimensions 42x105x18 mm including prod and connector Figs. 1 and 2
Table 7.e
(Here we have dealt only with the base functions of the instrument. For the remaining specific functions, see the
manual of the instrument that is being used).

44 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


7.9 RS485 serial options
RS485 serial option for µC2SE panel version (code MCH2004850)

ENGLISH
The MCH2004850 serial option is used to connect the µC2SE controller to a supervisor network via a
standard RS485 serial line.
This option uses the input normally associated with the programming key, which has the dual function of
key connector/serial communication port.

Fig. 7.k

7.10 Terminals
The µC²SE features the following user interfaces:

Remote terminal
The remote terminal allows the complete configuration of the µC2SE from a remote position. The buttons
and indications on the display faithfully reproduce the µC2SE user interface. In addition, PlantVisor can be
connected to the remote terminal using the special accessory.

Product code:
MCH200TP00 for panel installation
MCH200TW00 for built-in assembly

For further information see the instruction sheet +050001065.


Fig. 7.l
µAD
µAD is the µC2SE room terminal.
This terminal, fitted with built-in temperature and humidity probes, controls the temperature-humidity
conditions in the environment where its is installed, interacting with the units controlled by the µC2SE.
The µAD can be used to set time bands, the temperature and humidity set point, switch the system on/off
and change operating mode simply and intuitively.
Product code:
ADMA001000: with NTC probe
ADMB001010: with NTC probe, RTC and buzzer
ADMG001010: with NTC and humidity probe, RTC and buzzer
ADMH001010: with NTC and humidity probe, RTC, buzzer and backlighting

For further information see the instruction sheet +05000750 and the manual +030220465.
Fig. 7.m
µAM
µAM is the µArea controller compatible with the µC2SE.
This can control up to 10 fan coils (fitted with the e-droFAN electronic controller). By analysing the
temperature-humidity conditions in the different rooms, µAM optimises the temperature of the water
produced by the chiller/HP, improving power consumption, performance and comfort.

In addition, the µAM centralises the data, such as set point, heat/cool mode and on/off for the individual
fan coil and the entire system, including time bands.

Product code:
ADEC001010: with NTC probe, RTC, buzzer and backlighting
ADEH001010: cwith NTC and humidity probe, RTC, buzzer and backlighting Fig. 7.n

For further information see the instruction sheet +050000740 and the manual +030220460.

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 45


8. DIMENSIONS
ENGLISH

The following are the mechanical dimensions of each component in the µC2SE controller; all the values
are expressed in millimetres.

Note: the dimensions include the free connectors inserted.

MCH20000* µC2SE panel mounting version

33
75 64
74

drilling template
comp 71x29 mm
x100
PRG

Sel

panel mounting
overall dimensions 91,5x36x5 mm

Fig. 8.a

CONVONOFF0 and CONV0/10 A modules Expansion board for µC2SE


110
44
88

Expansio
n board

Expansion board

DIN rail mounting

11
36 60
70 60
Fig. 8.c Fig. 8.b

RS485 serial card: codeMCH2004850


24

5 75 5
31 3 56 85
59

Fig. 8.d

46 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


MCHRTF series single-phase speed controllers

ENGLISH
Model A (component side) B C D E
MCHRTF04C0 43 100 40 50 107
MCHRTF08C0 75 100 58 82 107
MCHRTF12C0 75 100 58 82 107
Note: the version with screw teminals code MCHRTF*D0 is available on request
Table 8.a

D D
A C A C

8 e 12 A B E 4A B E

Fig. 8.e

Model
MCHRTF10C0
Table 8.b

90
3 74.5 12.5 64
19
19

35.5
84
50

Ø4
29.5
15

3 74.5 12.5

Fig. 8.f

µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 47


9. CODES
ENGLISH

Description Code
µC2SE single circuit, 2 compressors, panel mounting MCH2000050
µC2SE single circuit, 2 compressors, panel mounting (20 pcs. multiple package) MCH2000051
µC2SE expansion board for 2nd. circuit maximum 4 compressors MCH2000020
µC2SE expansion board for 2nd. circuit maximum 4 compressors (10 pcs. multiple package) MCH2000021
RS485 optional board for µC2SE panel version MCH2004850
Programming key for µC2SE PSOPZKEY00
ON/OFF fan card (only screw terminals) CONVONOFF0
PWM - 0 to 10 V fan card (only screw terminals) CONV0/10A0
Temperature probes for regulation or condensation control NTC***WP00
***depending on the length (015= 1.5 m, 030= 3 m, 060=6 m)
Pressure probes for condensing pressure control SPK*R*
** depending on the pressure (13= 150 PSI, 23= 75 PSI, 33= 500 PSI)
Connectors kit for code MCH2000001 (multiple package 20 pcs) MCH2CON001
Connectors kit for code MCH2000001 (multiple package 10 pcs) MCH2CON021
Minifit connectors kit + 1 meter length for code MCH2** MCHSMLCAB0
Minifit connectors kit + 2 meter length for code MCH2** MCHSMLCAB2
Minifit connectors kit + 3 meter length for code MCH2** MCHSMLCAB3
Remote terminal for MCH20000** for panel installation MCH200TP0* MCH200TP0*
Remote terminal for MCH20000** for wall-mounting MCH200TW0* MCH200TW0*
Supervisor serial connection kit for remote terminal MCH200TSV0
Fan speed PWM 4 A/230 Vac MCHRTF04C0
Fan speed PWM 8 A/230 Vac MCHRTF08C0
Fan speed PWM 12 A/230 Vac MCHRTF12C0
Fan speed PWM 10 A/230 Vac 1 Pc. Nor. Ind. MCHRTF10C0
Fan speed PWM 10 A/230 Vac 10 Pc. Nor. Ind. MCHRTF10C1
Table 9.a

10. TECHNICAL SPECIFICATIONS AND SOFTWARE UPDATES


10.1 Technical specifications
Electrical specifications
In the following specifications “Group A” defines the grouping of the following outputs: valve, pump,
compressor, heater.
Power supply 24 Vac, range +10/–15 %; 50/60 Hz
Maximum power input: 3W
Fuse (compulsory) in series with the power supply to the µC2SE: 315mAT
300
12 pin connector Max. current 2 A for each relay output, extendable to 3 A for one single output
200 Relays Max current at 250 Vac: EN60730: resistive: 3A, Inductive: 2A cos =0.4 60,000
120 Vac
cycles
100 250 Vac 30 Vdc UL: Resistive: 3A, 1 FLA, 6 LRA cos =0.4 30,000 cycles
number of operations (x 104)

AC 120 V cosø =0.7 For further information refer to the characteristics shown in Figure 10.a
50 Minimum interval between communications (each relay): 12 s (the manufacturer
30 AC 250 V cosø =0.7 of the unit that the device is integrated into must ensure the correct configuration
20
so as to respond to this specification
10 Type of microswitching: 1 C
Insulation between relays in group A: functional
30 Vdc Insulation between the relays in group A and the very low voltage parts:
5
3
120 Vac cosø =0.4 reinforced
2 250 Vac cosø =0.4 Insulation between relays in group A and the signal relays: primary
30 Vdc Insulation between the signal relays and the very low voltage parts: reinforced
1
0 1 2 3 4 5 Insulation between the relays and the front panel: reinforced
Digital inputs Electrical standard: voltage-free contacts
current on contacts (A)
Closing current to earth: 5 mA
Maximum closing resistance: 50 W
Fig. 10.a Analogue inputs B1, B2, B3, B4: NTC CAREL temperature probes (10 kW at 25 °C)
The response time depends on the component used, typical value 90 s
B4: NTC temp. probes (10 kW at 25 °C) or CAREL 0 to 5 V ratiometric pressure
probes SPKT00**R*
Fan output Control signal for CAREL modules MCHRTF****, CONVONOFF* and
CONV0/10A*
Phase width modulation (settable width) or modulation of the duty cycle
No-load voltage: 5V ± 10%
Short-circuit current: 30 mA
Minimum output load: 1 kW
Front panel index of protection IP55
Storage conditions -10T70 °C – humidity 80 % rH non-condensing
Operating conditions -10T55 °C – humidity <90 % rH non-condensing
Degree of pollution Normal
Cat. of resist. to heat and fire D (RU94 V0)
PTI of the insulating materials All the insulating materials have PTI250 V
Software class and structure A
Period of electric stress across Long
insulating parts
Homologations CE/RU (File EI98839 sez.16)
Table10.a
Nota: all the relays must have the common terminals (C1/2, C3/4, C6/7, C8/9) connected together.

48 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010


Functional characteristics
Resolution of the analogue inputs Temperature probes: range -40T80 °C, 0.1 °C
Temperature measurement error Range -20T20 °C, ±0.5 °C (excluding probe)

ENGLISH
Range -40T80 °C, ±1.5 °C (excluding probe)
Pressure measurement error The % error with a voltage reading with a range of input from 0.5 to 4.5
is ± 2% (excluding probe).
The error in the converted value may vary according to the settings of
parameters /9, /10, /11, /12
Table 10.b
Characteristics of the connectors
The connectors may be purchased using CAREL code (MCHCON0***) or from the manufacturer Molex®
Molex® codes of the connector Number of pins
39-01-2120 12
39-01-2140 14
Table 10.c
Max. number of insertion/removal cycles for the connectors: 25 cycles
Code of the contacts according to the cross-section of the connection cables to the 12- and 14-pin
connectors (use the special Molex® tool code 69008-0724 for crimping
Molex® code of the contact Cross-section of cables allowed
39-00-0077 AWG16 (1,308 mm2)
39-00-0038 AWG18-24 (0,823...0,205 mm2)
39-00-0046 AWG22-28 (0,324...0,081 mm2)
Table 10.d
In addition, the pre-wired kits MCHSMLC*** are also available
WARNINGS
• If one transformer is used to supply both the µC2SE and the accessories, all the G0 terminals on the
various controllers or the various boards must be connected to the same terminal on the secondary,
and all the G terminals to the other terminal on the secondary, so as to avoid damaging the
instrument;
• For use in residential environments, use shielded cable (two wires + shield earthed at both ends, AWG
20-22) for the tLAN connections (EN 55014-1).
• Avoid short-circuits between V+ and GND so as to not damage the instrument;
• Perform all the maintenance and installation operations when the unit is not connected to the power
supply;
• Separate the power cables (relay outputs) from the cables corresponding to the probes, digital inputs
and serial line;
• Use a transformer dedicated exclusively to the electronic controllers for the power supply.
Protection against electric shock and maintenance warnings
The system made up of the control board (MCH200003*) and the other optional boards (MCH200002*,
MCH200485*, MCHRTF****, CONVONOFF*, CONV0/10A*, EVD000040*) represents a control device to
be integrated into class 1 or class 2 appliances.
The class of protection against electric shock depends on how the control device is integrated into the
unit built by the manufacturer.
Disconnect power before working on the board during assembly, maintenance and replacement.
The protection against short circuits must be guaranteed by the manufacturer of the appliance that the
controller will be fitted on.
Maximum length of the NTC/ratiometric probe
NTC/ratiometric probe connection cables 10 m
digital input connection cables 10 m
power output connection cables 5m
fan control output connection cables 5m
power cables 3m
Table 10.e
10.2 Software updates
10.2.1 Notes for version 1.1
First release.
10.2.2 Notes for version 1.2
Optimised use of the programming key.
10.2.3 Notes for version 1.3
Implemented direct current operation.
Use EXP. version 1.5 or higher.
10.2.4 Notes for version 1.4
Implemented a differential relating to the working set point for electric heaters in air- and water-source
units. Implemented cooling only air-source unit with electrical heaters operating in heating mode only.
Implemented new logic for the activation of the alarm relays.
Implemented new logic for the management of the high pressure alarm.
Implemented management of minimum damper opening.
Implemented damper inactivity time in freecooling or freeheating mode.
Optimised management of damper closing for minimum outlet temperature limit.
Implemented alarm reset from µAD.
10.2.5 Notes for version 1.6
Improved Modbus communication with supervisory system
10.2.6 Notes for version 1.7
Implemented second antifreeze set point (A14)
µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 49
Notes:
CAREL reserves the right to modify the features of its products without prior notice
µC2SE chiller process +030220416 - rel. 1.1 - 27.04.2010

Agenzia/Agency:

CAREL S.p.A.
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
Tel. (+39) 049.9716611 - Fax (+39) 049.9716600
e-mail: carel @ carel. com - www .carel. com

You might also like