Tech Note - Abseiling Loads
Tech Note - Abseiling Loads
FYI
Peter Mueller
Associate
All,
Happy New Year!
We would agree with Peter’s concerns. If a rope access solution is being explored, we recommend the specialist façade access and maintenance consultants WSP are engaged to do a full review. There are
critical items to consider such as below which WSP would be able to give more detailed advice on:
1. The 15kN lateral point load that the fixing point (not 150kg) would need to accommodate in line with IRATA guidance for safety loads
2. Not less than 6kN point load on the parapet for safety-load condition (parapet can deform permanently but cannot fall off)
3. Not less than 1kN vertical point point load on the parapet at each rope. Under this load the parapet must not be deformed or damaged
4. Impact loads on the elevations from rope access operatives. These will exceed those applied by the BMU as the operatives do not wear ‘buffers’.
See notes below which were provided by the access consultant on another project:
If the BMU is not operating to the speeds predicted there may be some work WSP could carry out with the BMU contractor to review the operational parameters.
Regards,
Colman
Colman Billings
It is the recipients' responsibility to virus scan the electronic communications entering their computer systems and in that regard Billings Design Associates Limited take no responsibility for loss, modification or corruption of data or consequential losses due to
same.
Colm, I'm afraid GHA must raise the below concerns - we don't think this is a viable approach. Abseiling has never been envisaged in the building's maintenance strategy andas such the roof design
and especially the cantilevering edge was not considered / checked for adequate robustness for abseiling operations.
From a PD point of view we must advise that the BMU has been designed as the safest way to access the tower facades and should be used for the various maintenance tasks including
cleaning. If windspeeds don't allow the BMU to operate is it then safe for an abseiler to clean the building?
Bruno is correct the plinths in question are wrapped with the waterproofing and insulation - see screen shot below
The upstand board where the waterproofing (green hatched line) is applied to is I recall a PIR type insulation board with 10mm cemetitious topping - and would appear to GHA too brittle to
withstand a robe slung around it and would be likely to be damaged including the waterproofing.
Re the roof parameter including the parapet edge - the area beyond the balustrade was not intended for regular maintenance access, it's a lightweight bolt on cassette system with far less
load capacity compared to the main concrete slab. See screen shot below we don't think a mobile frame / 'roof jockey system' / davit arm could be brought safely into position beyond the
safety balustrade hence robe and abseiler's feet would then impact on the parapet edge coping which is made of 3mm aluminium sheet only and from our point of view highly likely to get
damaged. If you attempted to protect - then how would the protection be secured from been blown off the roof?
Apologies if these are not favourable comments - but please consider before proceeding with this.
Kind regards
Peter
Peter Mueller
Associate
We are struggling to use the BMU in certain locations and it was taking far too long due to the max allowable wind speed the BMU can operate in.
The ropes will fit above the insulation so it shouldn’t effect the waterproofing.
If you are happy that the plinths can support the 150kg load we will proceed on this basis.
KR,
Colm O’ Connor
S&C Project Manager
07736274402
Ballymore Group
Wardian
163 Marsh Wall
London E14 9TJ
I’ve cc’d Peter as this is likely to damage the insulation/waterproofing, @Peter Mueller would you be able to comment?
Regards
Bruno
As we don’t have any fall protection anchor points on the roof we are reviewing the option of strapping the ropes around the RC plinths on the roof.
Could you please help us and check if these can safely take a maximum imposed lateral load of 150kgs.
KR,
Colm O’ Connor
S&C Project Manager
07736274402
Ballymore Group
Wardian
163 Marsh Wall
London E14 9TJ
This email is sent on behalf of Ballymore Development Management Limited (reg.#08874050) and Ballymore Construction Services Limited (reg.#09066749), companies registered in England and Wales, with offices at 161 Marsh Wall, London E14 9SJ. The
name "BALLYMORE" and the Ballymore logos are registered trade-marks of Ballymore Properties and used by the companies under licence. The contents of this e-mail and any attachments are confidential to the intended recipient. If you are not the intended
recipient, please (i) do not use or publish its contents, and (ii) contact the sender and then remove it from your system. You may not copy, forward, use or disclose the contents of this email to anybody else if you are not the intended recipient. Emails are not
secure and may contain viruses. The companies may monitor traffic data and also the content of email for the purposes of security and staff training.
NOTICE: This communication and any attachments ("this message") may contain information which is privileged, confidential, proprietary or otherwise subject to restricted disclosure under applicable law. This message is for the sole use of the intended recipient(s). Any unauthorized use,
disclosure, viewing, copying, alteration, dissemination or distribution of, or reliance on, this message is strictly prohibited. If you have received this message in error, or you are not an authorized or intended recipient, please notify the sender immediately by replying to this message, delete
this message and all copies from your e-mail system and destroy any printed copies.
-LAEmHhHzdJzBlTWfa4Hgs7pbKl
Glenn Howells Architects Limited are committed to protecting and safeguarding your personal data. As part of this commitment, we have updated our privacy policy to meet standards of the new General Data Protection Regulation (GDPR). You can view our privacy policy here https://glennhowells.co.uk/privacy-policy/
This email is intended solely for the named recipients only. It may contain privileged and/or confidential information. If you are not one of the intended recipients, please notify the sender immediately, and destroy this e-mail; you must not copy distribute or take any action in reliance upon it.
All digital drawing information should be checked against issued hard copy for completeness and accuracy.
Whilst all efforts are made to safeguard inbound and outbound e-mails, Glenn Howells Architects Limited cannot guarantee that attachments are Virus-free.