Sensor Parameter

This document contains settings for different parameters of a SEIMENS level transmitter. It lists 50 parameters such as operation mode, measurement response, units, empty and span levels, output function, temperature limits, damping filter settings, and echo lock parameters. The default and current settings are shown for 11 different configurations of the level transmitter identified by codes.

Uploaded by

Jisan Jisan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
50 views10 pages

Sensor Parameter

This document contains settings for different parameters of a SEIMENS level transmitter. It lists 50 parameters such as operation mode, measurement response, units, empty and span levels, output function, temperature limits, damping filter settings, and echo lock parameters. The default and current settings are shown for 11 different configurations of the level transmitter identified by codes.

Uploaded by

Jisan Jisan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 10

Level(micro wave) transmitter - SEIMENS : 7ML5221-2BA11 M LT114 11 M LT401 01 M LT403 01 M LT403 02 M LT403 71 M LT403 81 M LT404 01 M LT405 01

No. Parameter Unit Default Setting Setting Setting Setting Setting Setting Setting Setting
1 000 P000 Lock 1954 ← ← ← ← ← ← ← ←
2 001 P001 Operation 1(level)/2(Space)/3(distance) 1 1 1 1 1 1 1 1 1
3 002 P002 Material to be monitored --- --- --- 1 1 1 1 1 1 1 1
4 003 P003 Measurement Response 1(slow)/2(medium)/3(fast) 1 3 3 3 3 3 3 3 3
5 005 P005 Units 1(m)/2(cm)/3(mm)/4(ft)/5(inc) 1 3 3 3 3 3 3 3 3
6 006 P006 Empty (process empty level) mm 6.100 660.8 1374.1 2354.0 2354.4 1713.0 1656.7 896.4 1303.1
7 007 P007 Span (process full level) mm 5.725 347.5 1194.7 2040.8 1904.8 1348.4 1250.0 596.2 994.3
8 010 P010 Language 0/1/2/3/4 0 0 0 0 0 0 0 0 0
9 050 P050 Vessel (or Channel) Shape 0/1/2/3/4/5/6/7/8/9 0 0 0 0 0 0 0 0 0
10 051 P051 Maximum Volume m3 100 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0
11 052 P052 Vessel Dimension A 0.0 - - - - - - - -
12 053 P053 Vessel Dimension L 0.0 - - - - - - - -
13 054 P054 Level or Head Breakpoints mm 0.000 ← ← ← ← ← ← ← ←
14 055 P055 Volume or Flow Breakpoints 0.0000 ← ← ← ← ← ← ← ←
15 069 P069 Unlocked value 1954 ← ← ← ← ← ← ← ←
16 070 P070 Failsafe Timer min 100.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00
17 071 P071 Failsafe Material Level 1/2/3/4 3 HOLD HOLD HOLD HOLD HOLD HOLD HOLD HOLD
18 073 P073 Failsafe level mA 22.6 ← ← ← ← ← ← ← ←

19 201 P201 mA Output Function 0(manual)/1(level)/ 1 1 1 1 1 1 1 1 1


2(Space)/3(Diatance)/4(volume)
20 210 P210 4 mA Setpoint (low output) mm 0.000 ← ← ← ← ← ← ← ←
21 211 P211 20 mA Setpoint (high output) mm 5.725 347.5 1194.7 2062.7 1927.1 1330.3 1246.6 596.2 994.3
22 212 P212 Minimum mA limit mA 3.800 ← ← ← ← ← ← ← ←
23 213 P213 Maximum mA limit mA 20.500 ← ← ← ← ← ← ← ←
24 214 P214 4 mA Output Trim --- --- --- ← ← ← ← ← ← ← ←
25 215 P215 20 mA Output Trim --- --- --- ← ← ← ← ← ← ← ←
26 300 P300 Temperature, transducer maximum ℃ -50 100 100 100 100 100 100 100 100
27 341 P341 RUN Time 0 260 260 260 260 260 260 260 260
28 342 P342 Power-On Resets 0 24 22 22 22 22 22 22 22
29 343 P343 Internal Temperature 1/2/3 1
346
30 650 P650 Offset Calibration mm
31 651 P651 Sound Velocity Calibration mm
32 652 P652 Offset Correction mm
33 653 P653 Velocity - - - - - - - -
34 654 P654 Sound Velocity at 20 oC
35 660 P660 Temperature source 1/2 1 ← ← ← ← ← ← ← ←
36 661 P661 Temperature fixed ℃ 20 ← ← ← ← ← ← ← ←
37 664 P664 Temperature
38 700 P700 Maximum Fill Rate m/min 1 ← ← ← ← ← ← ← ←
39 701 P701 Maximum Empty Rate m/min 1 ← ← ← ← ← ← ← ←
40 709 P709 Damping Filter sec 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000
41 711 P711 Echo Lock 0/1/2/3 2 ← ← ← ← ← ← ← ←
42 712 P712 Echo Lock Sampling 0.000 5:2 5:2 5:2 5:2 5:2 5:2 5:2 5:2
43 713 P713 Echo Lock Window mm 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
44 799 P799 Communications Control 0/1/2 1 ← ← ← ← ← ← ← ←
45 800 P800 Near Blanking mm 0.250 250.00 250.00 250.00 250.00 250.00 250.00 250.00 250.00
46 801 P801 Range Extension % 20.000 ← ← ← ← ← ← ← ←
47 804 P804 Confidence Threshold 10:5 ← ← ← ← ← ← ← ←
48 805 P805 Echo Confidence 34:0 36:0 36:0 36:0 36:0 36:0 36:0 36:0
49 806 P806 Echo Strength 84 86 86 86 86 86 86 86
50 807 P807 Noise -15,-15 -15,-15 -15,-15 -15,-15 -15,-15 -15,-15 -15,-15 -15,-15
51 820 P820 Algorithm 3/4/8/12 8 ← ← ← ← ← ← ← ←
52 825 P825 Echo marker % 50 ← ← ← ← ← ← ← ←
53 830 P830 TVT Type 1/2/3/4/5/6 1 ← ← ← ← ← ← ← ←
54 831 P831 TVT Shaper --- --- --- 0 0 0 0 0 0 0 0
55 832 P832 TVT Shaper Adjust --- --- --- 0 0 0 0 0 0 0 0
56 837 P837 Auto False-Echo Suppression 0/1/2, Only when tank empty 0 2=>1 2=>1 2=>1 2=>1 2=>1 2=>1 2=>1 2=>1
57 838 P838 Auto False-Echo Suppression Distance mm 1.000 160.8 874.1 1854.0 1854.4 1213.0 1156.7 396.4 803.1
58 839 P839 TVT Hover Level % 33 ← ← ← ← ← ← ← ←
59 900 P900 Software Revision Number 2.02 2.02 2.02 2.02 2.02 2.02 2.02 2.02
60 901 P901 Memory Test Idle Idle Idle Idle Idle Idle Idle Idle
61 911 P911 mA Output Value mA 4
62 912 P912 Temperature
63 920 P920 Reading Measurement mm
64 921 P921 Material Measurement mm
65 922 P922 Space Measurement mm
66 923 P923 Distance Measurement mm
67 924 P924 Volume (or Flow) Measurement - - - - - - - -
68 999 P999 Master Reset - - - - - - - -

1 / 10
Level(PT)

Level sensor - IFM : PI2798 M LT403 01 M LT403 02

No. Parameter Unit Default Setting Setting


25%
1 SP1 Switch-on point 1
VMR
23%
2 rP1 Switch-off point 1
VMR
• Switching signal for the pressure limits: hysteresis function [H ..] or
3 OU1 Configuration of output 1 window Hno
function [F ..], either normally open [. no] or normally closed [. nc].
• Switching signal for the pressure limits: hysteresis function [H ..] or
window
function [F ..], either normally open [. no] or normally closed [. nc] (only
4 OU2 Configuration of output 2 available for 3-wire operation). I I I
• Analogue signal for the current system pressure: 4...20 mA [I], 20...4
mA
[InEG].
75%
8 SP2 Switch-on point 2
VMR
73%
9 rP2 Switch-off point 2
VMR

17 COF Calibration offset 0.0

0%
13 ASP Analogue start point measured value at which 4 mA is provided (20 mA if [OU2] = [InEG]). 11.6 11.6
VMR

100%
14 AEP Analogue end point measured value at which 20 mA is provided (4 mA if [OU2] = [InEG]). 210.1 200.5
VMR

bAr
11 Uni Display unit mbar mbar
/ mbAr

- Pressure in the unit set in [Uni].


12 SELd Display mode P P% P%
- Pressure in % of the set scaling of the analogue output.

18 dS1 Switch-on delay for the output 1 0.0

19 dr1 Switch-off delay for the output 1 0.0

20 dS2 Switch-on delay for the output 2 only active if [OU2] = [Hnc], [Hno], [Fnc] or [Fno]. 0.0

21 dr2 Switch-off delay for the output 2 only active if [OU2] = [Hnc], [Hno], [Fnc] or [Fno]. 0.0

22 FOU1 Behaviour of output 1 in case of an internal fault. OU

23 FOU2 Behaviour of output 2 in case of an internal fault. OU

24 P-n Output polarity (output 1) pnp

25 dAP Damping for the switching output (OU1) 0.06

26 dAA Damping for the analogue output (OU2) 0.03 5.00 5.00

27 diS Setting of the display d2 rd3 rd3

29 CP1 Calibration point 1 0.00

30 CP2 Calibration point 2 0.00


Temperature sensor - Hydac : ABZMT-1X/0300MS/E3-T4-K24 M TH404 01 M TH405 01

No. Parameter Unit Default Setting Setting


1 t.uni Determining the temperature unit C C C
2 r.ou1 tenp
3 r.ou2 tenp
4 r.ou3 tenp
5 r.ou4 tenp
6 diS Setting the display's update rate FASt FASt FASt
7 Loc Activating / deactivating the key lock 000 000 000
8 rES Restoring the factory settings (reset)
9 sp1 Switching point for OUT 1 decC 50 20 20
10 rp1 Switch-back point for OUT 1 decC 45 20 20
Time period in seconds during which the
11 dS1 signal must be continuously available for the sec 0 0 0
switching output to respond.
12 dr1 Delay of the switch-back signal for OUT 1 sec 0 0 0
13 ou1 Test possibility for the switching output Hno Hno Hno
14 sp2 Switching point for OUT 2 decC 60 60 60
15 rp2 Switch-back point for OUT 2 decC 55 60 60
Time period in seconds during which the
16 dS2 signal must be continuously available for the sec 0 0 0
switching output to respond.
17 dr2 Delay of the switch-back signal for OUT 2 sec 0 0 0
18 ou2 Test possibility for the switching output Hno Hno Hno
19 sp3 Switching point for OUT 3 decC 70 40 40
20 rp3 Switch-back point for OUT 3 decC 65 40 40
Time period in seconds during which the
21 dS3 signal must be continuously available for the sec 0 0 0
switching output to respond.
22 dr3 Delay of the switch-back signal for OUT 3 sec 0 0 0
23 ou3 Test possibility for the switching output Hno Hno Hno
24 sp4 Switching point for OUT 4 decC 80 50 50
25 rp4 Switch-back point for OUT 4 decC 75 50 50
Time period in seconds during which the
26 dS4 signal must be continuously available for the sec 0 0 0
switching output to respond.
27 dr4 Delay of the switch-back signal for OUT 4 sec 0 0 0
28 ou4 Test possibility for the switching output Hno Hno Hno
29 LEd1

3/10
LT setting

7ML5221
(SIEMENS)

Sensor No Equip Volume(L)


M LT114 11 CPC Hyd 100% 275
275L HH
天板~側面天:20 H 250
L 120
LL
0% 0

M LT401 01 OIL Lube 100% 5000


5,000L HH
H 4500
L 2500
LL 1500
0% 0

M LT403 01 Coolant Main Tank(Clean) 100% 50000


50,000L HH
H 45000
L 25000
LL 15000
0% 0

M LT403 02 Coolant Main Tank(Dirty) 100% 20000


20,000L HH
H 18000
L 10000
LL 6000
0% 0

M LT403 71 DI (MIXING) Tank 100% 5000


5,000L HH
H 5000
L 3000
LL
0% 0
M LT403 81 Mill Wash Tank 100% 10000
10,000L HH
H 10000
L 3000
LL 2000
0% 0

M LT404 01 AGC Hyd 100% 1650


1,650L HH
天板~側面天:20 H 1500
L 750
LL 500
0% 0

M LT405 01 AUX Hyd 100% 3300


3,300L HH
天板~側面天:20 H 3000
L 1700
LL 800
0% 0
%表記(参考) Liquid Level from bottom(h1) Liquid Level from sensor top Z mm
100.0% 347.459538555532 512.240461444468 313.3
0.0% 0.0 859.7 660.8
90.9% 315.9 543.8 344.9
43.6% 151.6 708.1 509.2
0.0% 0.0 859.7 660.8
0.0% 0.0 859.7 660.8

100.0% 1194.743130227 378.256869772999 179.4


-1.0% -12.5 1585.5 1386.6
90.0% 1075.3 497.7 298.8
50.0% 597.4 975.6 776.7
30.0% 358.4 1214.6 1015.7
0.0% 0.0 1573.0 1374.1

100.0% 2040.81632653061 490.183673469388 291.3


-1.2% -25.0 2556.0 2357.1
90.0% 1836.7 694.3 495.4
50.0% 1020.4 1510.6 1311.7
30.0% 612.2 1918.8 1719.9
0.0% 0.0 2531.0 2332.1
-5.9%
100.0% 1904.76190476191 626.238095238095 427.3
-1.3% -25.0 2556.0 2357.1
90.0% 1714.3 816.7 617.8
50.0% 952.4 1578.6 1379.7
30.0% 571.4 1959.6 1760.7
0.0% 0.0 2531.0 2332.1
-6.2%
100.0% 1348.43581445523 581.564185544768 382.7
-0.9% -12.5 1942.5 1743.6
100.0% 1348.4 581.6 382.7
60.0% 809.1 1120.9 922.0
0.0% 0.0 1930.0 1731.1
0.0% 0.0 1930.0 1731.1
100.0% 1250 609 410.1
0.0% 0.0 1859.0 1660.1
100.0% 1250.0 609.0 410.1
30.0% 375.0 1484.0 1285.1
20.0% 250.0 1609.0 1410.1
0.0% 0.0 1859.0 1660.1

100.0% 596.214781804512 499.085218195488 300.2


-1.6% -9.7 1105.0 906.1
90.9% 542.0 553.3 354.4
45.5% 271.0 824.3 625.4
30.3% 180.7 914.6 715.7
0.0% 0.0 1095.3 896.4

100.0% 994.267322846722 507.732677153278 308.8


-1.8% -17.5 1519.5 1320.6
90.9% 903.9 598.1 399.2
51.5% 512.2 989.8 790.9
24.2% 241.0 1261.0 1062.1
0.0% 0.0 1502.0 1303.1
Water
Z mm Density 990
密度
Density 密度 9710.6037

3% 9684.0651

Ignore this volume


(=ΔV, approx 1~2%)
Little

347.5

1194.7
mBar
2050 210.1

1845 190.3
1025 110.9
615 71.2
2040.8 0 11.6
Inst -120
1950 200.5

780 1755 181.6


975 106.0
585 68.3
1904.8 0 11.6
-120
H=100%

1348.4
H=100%

1250.0

596.2

994.3
at 60 deg
Rolling oil VG46 VG220 unit
900 867 897.5 kg/m3
8825.985 8505.27 8804.475 N/m3

You might also like