Carbon Dioxide Transmitter CDT Mod 2000

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

CARBON DIOXIDE TRANSMITTERS

CDT-MOD-2000 Series

CO2
Multifunctional, wall mount CO2 transmitters for building auto-
mation systems that use Modbus serial communication protocol
The CDT-MOD-2000 series air quality transmitters are engineered
for building automation systems in the HVAC/R industry. The CDT-
MOD-2000 series measures carbon dioxide (CO2), utilizing the in-
dustry standard NDIR measurement principle, and temperature (T).
Optional relative humidity (rH) measurement is also available in the
same device. The CDT-MOD-2000 series devices have large touch-
screen display making the configuration of the device quick and
easy. Configuration is also possible via Modbus network.

The CDT-MOD-2000 series transmitters calibrate themselves au-


tomatically using ABC TM logic. The ABC TM logic requires that the
space in which the transmitter is used needs to to be unoccupied for
four hours per day so that the indoor CO2 concentration drops to
the outside level. CDT-MOD-2000-DC is a dual channel model with
a measuring channel and a reference channel that makes a continu-
ous comparison and the necessary adjustment accordingly. CDT-
MOD-2000-DC is also suitable for buildings that are continuously
occupied.

CDT-MOD-2000 series devices include:


• Separate field configurable Modbus output for each APPLICATIONS
measurement parameter (CO2, rH, T)
• Offset feature enabling field calibration for each measurement CDT-MOD-2000 series devices are commonly used to monitor:
parameter (CO2, rH, T) • CO2 and humidity levels in offices, public spaces, meeting
• One analog output for selected measurement: voltage (0/2–10 rooms and classrooms
V) or current (4–20 mA) • CO2 levels of return air in ventilation systems
• 2” x 3” touchscreen display • incoming air and return air humidity levels in ventilation system
• Optional relay output • humidity in various industrial applications
• temperatures in HVAC/R environment
• CDT-MOD-2000-DC series devices can also be used in
applications where there is a constant source of carbon dioxide
present (for example hospitals and greenhouses)

MODEL SUMMARY
CDT-MOD-2000 CDT-MOD-2000-rH

Description Model Product code Description Model Product code

Carbon dioxide transmitter for room with CDT-MOD-2000-D 301.001.004 Carbon dioxide and humidity transmitter CDT-MOD-2000-rH-D 301.003.004
Modbus configuration and display for room with Modbus configuration and
display

- with relay CDT-MOD- 301.001.005 - with relay CDT-MOD-2000-1R- 301.003.005


2000-1R-D rH-D

- with dual channel sensor CDT-MOD- 301.005.003 - with dual channel sensor CDT-MOD-2000-DC- 301.006.003
2000-DC-D rH-D

- with dual channel sensor and relay CDT-MOD-2000- 301.005.004 -with dual channel sensor and relay CDT-MOD-2000-DC- 301.006.004
DC-1R-D 1R-rH-D

Copyright HK Instruments 2020 www.hkinstruments.fi Datasheet Version 7.0 2020


CARBON DIOXIDE TRANSMITTERS
CDT-MOD-2000 Series
SPECIFICATIONS
Performance Physical Communication
Measurement ranges: Dimensions: Protocol: MODBUS over Serial Line
CO2: 400–2000 ppm Case: 99 x 90 x 32 mm Transmission Mode: RTU
Temperature: 0...50 °C Weight: Interface: RS485
Relative humidity: 0–100 % 150 g Byte format (11 bits) in RTU mode:
Accuracy: Mounting: Coding System: 8-bit binary
CO2: ±40 ppm + 2 % of reading, DC model: 75 ppm or 3 screw holes slotted, 3.8 mm Bits per Byte:
10 % of reading (whichever is greater) Materials: 1 start bit
Temperature: <0.5 ºC Case: ABS 8 data bits, least significant bit sent
Relative humidity: ±2...3 % at 0...50 °C and 10–90 % rH Protection standard: first
Total error band includes accuracy, hysteresis and IP20 1 bit for parity
temperature effect over 5...50 °C and 10–90% rH. Display (Optional): 1 stop bit
Touchscreen Baud rate: selectable in configuration
Technical Specifications Size: 77.4 x 52.4 mm Modbus address: 1−247 addresses selectable in
Media compatibility: Electrical connections: configuration menu
Dry air or non-aggressive gases Power supply:
Measuring units: 5-screw terminal block Conformance
ppm, °C and % rH (24 V, GND) Meets requirements for CE marking:
Measuring element: 0.2–1.5 mm2 (12–24 AWG) EMC Directive 2014/35/EU
CO2: Non-dispersive infrared (NDIR) Relay out: RoHS Directive 2011/65/EU
Temperature: Pt1000 3-screw terminal block LVD Directive 2014/35/EU
Relative humidity: Thermoset polymer capacitive (NC, COM, NO) WEEE Directive 2012/19/EU
sensing element 0.2–1.5 mm2 (12–24 AWG)
Calibration:
Automatic self-calibration ABC LogicTM or continuous Electrical
comparison (DC) Input:
Environment: 24 VAC or VDC, ±10 %
Operating temperature: 0...50 °C Current consumption: max 90 mA (at 24 V) +
Storage temperature: -20...70 °C 10 mA for each voltage output or 20 mA for
each current output COMPANY WITH
Humidity: 0 to 95 % rH, non condensing MANAGEMENT SYSTEM
Relay out:
SPDT Relay, 250 VAC / 30 VDC / 6 A CERTIFIED BY DNV GL RoHS 2
2011/65/EU

Adjustable switching point and hysteresis = ISO 9001 = ISO 14001 =


One analog output for selected media:
0/2–10 VDC, Load R minimum 1 kohm or
4–20 mA, maximum load 500 ohm

How to generate a model?


Example: Product series
CDT-MOD-
CDT2000 Carbon dioxide transmitter, analog configurations
2000-1R-D
CDT-MOD-2000 Carbon dioxide transmitter, Modbus configuration

Calibration

ABC logic™, Automatic Background Calibration

-DC Dual channel, for continuously occupied space

Mounting

Wall mount

Relay

-1R With relay

Without relay

Relative humidity sensor

-rH With relative humidity sensor

Without relative humidity sensor

Display

-D With display

Without display

Model CDT-MOD-2000 -1R -D

Copyright HK Instruments 2020 www.hkinstruments.fi Datasheet Version 7.0 2020