Surge Protection Handbook
Surge Protection Handbook
Handbook
CONTENT
1. Introduction 3
2. Overvoltage sources 11
2.1 Atmosferic discharge - Lightning 11
2.1.1 Influence of lightning strikes on power lines 13
2.1.2 Electromagnetic couplings 14
2.1.3 Switching surges 15
2.2 Temporary overvoltages 17
2.3 Surges caused by different electrostatic discharges 18
4. Lightning protection 31
4.1 Standards 31
4.2 Need for lightning protection 31
4.3 Protection level and requirements for SPDs 34
4.4 Lightning protection system LPS 36
4.5 Lightning effects 42
4.6 Grounding 45
5. Surge protective devices 47
5.1 Surge protection elements 48
5.1.1 Classification of overvoltage protection elements 49
5.1.2 Overvoltage protection elements. Basic characteristics 50
5.1.2.1 Voltage switching components 52
5.1.2.2 Voltage limiting component 53
5.2 Characteristics of surge protective devices 55
5.2.1 Classification of SPDs 55
5.2.2 Electrical parameters of SPD 59
5.3 How to select proper value of back-up fuse 61
5.4 SPD selector 62
5.4.1 The expected types and levels of overvoltage impulses and currents 63
5.4.2 Characteristics of LV power supply system 65
5.4.3 Determining dielectric withstand category of protected devices 66
5.4.4 Determining protection level at the installation point of SPD 66
5.4.5 SPD selection 68
5.4.6 Installation of SPDs and analysis of its effect on the protection
provided by SPDs 69
6. Applications 72
6.1 Households 72
Surge Protection Handbook 3
1. Introduction
The following question is frequently asked: Why is surge protection required on
installations? To answer, we need to understand the nature and different sources of
overvoltages.
The role of a surge protective device (SPD) is to reduce the effects of these
overvoltages on a structure's internal distribution systems to the levels which the
interconnected electrical equipment can withstand.
Aging of an SPD results each time internal metal oxide varistor (MOV) is called upon,
to divert surge current and safely protect the downstream equipment. A MOV is rated
to withstand one surge of its maximum rated value (described Imax or Iimp) or many
surges of a lower operating value (described In).
In order to ensure safe behaviour at the end of its life cycle, SPD must be designed to
safely disconnect from the power system which it is protecting. This is the role of the
internal disconnector which every quality designed SPD shall contain. These devices
either disconnect or limit the current within the SPD during failure and help prevent
hazardous conditions (e.g. fires) from occurring. The SPD should also incorporate
some forms of disconnecting indication showing the user it is no longer providing
Surge Protection Handbook 5
The risks
To put this in perspective, the energy needed to cause failure to the typical integrated
electronics is less than one millionth of what could safely be sustained by discrete
technologies like the transistors and even more so in the past era of vacuum tube
technology. Moreover, increasingly polluted power distribution networks where
electrical disturbances, such as switching surges, lightning strikes, induced noise and
poor supply regulation, are all too common and we have a recipe for equipment
damage.
This damage may be all too obvious, as evident in catastrophic system failures, or
may show in more subtle mechanisms, such as accelerated component degradation,
reduced equipment life and lost or corruption of data. In extreme cases, such
overvoltage surges and transients can cause facility fires and risk to human life.
The process leading to the formation of the lightning discharge involves the
development of strong electric field strengths (measured in kV/m) between cloud and
ground as charge begins to separate between the upper and lower regions of the
cumulonimbus cloud mass. Eventually, this field reaches a point where a stepped
down-leader starts to propagate from the cloud towards the ground, causing the
localized electric field in which the wind turbine is located to escalate extremely
rapidly. At some point in this macro-time event, the electric field at points on the
ground and surrounding structures reaches the point where localized air breakdown
begins to occur. Any object which contributes to a magnification of this charge by
means of its geometrical shape, such as the tips of the turbine blades, will enhance
the launch of competing upward-streamers to intercept the rapidly approaching
down-leader. As the two meet, many hundreds of coulombs of charge are transferred
from the usually positively charged ground to the negatively charged cloud (negative
lightning), resulting in the spectacular return-stroke and subsequent rapid collapse of
the localized electric field.
The threat posed to exposed structures is not the only one caused due to direct
lightning interceptions, but there is also the rapidly collapsing electric field (in the
order of kV/ms) from nearby strikes. These changes in field serve to induce very large
voltage surges within the wiring and electrical components of the turbine which can
exceed the withstand level of these electrical systems and cause damage.
The cost of such damage can be extensive, particularly since wind farms are often
located offshore or in remote and difficult to access terrain, such as hilltops. It is for
this reason that lightning and surge protection has become a critical consideration in
Surge Protection Handbook 7
The growing interest in renewable energy generation has also lead to a proliferation
of photovoltaic panels in applications ranging from small residential installations to
large commercial “sun farms”. Such installations are located externally by their very
nature and thus particularly subject to the effects of lightning induced damage. As a
result, the use of SPDs on such panels is becoming increasingly important and new
standards, such as EN50539, are being developed to address the testing and
performance of SPDs intended for use in PV systems.
SPD manufacturers are only just starting to address these, somewhat more onerous
requirements. A number of innovative new disconnection designs have been
developed and patented.
Most of these use various mechanical shutters to extend the arc length while
disconnecting, thereby causing self-extinguishing even though a voltage zero-crossing
point is not present.
required modes of protection, form factor of the enclosure, types of status indication -
and the picture rapidly becomes complex.
Within the USA, it is mandatory that the National Electrical Code be followed (with a
few exceptions). This in turn requires that the SPD be “listed” for its application,
thereby making compliance with UL 1449 mandatory for an SPD manufacturer
wishing to sell its products in the US. Contrary to popular understanding, there are
many authorities which are authorized for testing in accordance with UL1449
standard. Obviously, Underwriters Laboratories Inc. is one of them, but there are also
others, such as Canadian Standards Authority (CSA mark) and Intertek Services (ETI
mark), etc. These are broadly called NRTL (nationally recognized test laboratories) in
the USA.
The situation with IEC is different. An SPD manufacturer may still sell its product,
even if it does not comply with the relevant IEC standard, and even if the country of
manufacturer is an international signatory to the IEC. However, this is not the case at
CENELEC levels where European norms, such as EN 61643-11, are called up by the
mandatory LV Directives. This said, aspects of this “mandatory” situation are still not
fully enacted and it is to remain so until a specific law is imposed to regulate it.
Other developing countries, such as China and India are actively developing their own
national standards and regulations governing the installation of SPDs. Most of these
draw up their requirements and carry out tests in accordance with existing IEC
standards.
The 35 mm DIN standards for enclosures have found wide acceptance in panel
boards for such devices as miniature circuit breakers (MCBs) and SPDs, making them
ideal for power. Not only are most IEC based SPDs available in this industry standard
package for easy mounting, but inherent to this packaging is the comforting fact that
such an SPD must incorporate safe disconnection. In other words, it is not relying on
its enclosure alone for safety.
International standards such as the IEC 62305 series on Lightning Protection and the
IEC 61643 series on Surge Protection, categorize SPDs into various test classes
associated with the electrical exposure of the location in which they are intended to
be installed.
For example, an SPD tested to test Class I is intended to be installed where it is likely
to carry direct or partial lightning current, while an SPD tested to test Class II is
intended to be installed where overvoltage protection of electronic systems from the
effects of induced lightning currents is required. SPDs tested to Class III are generally
installed at the end-use equipment such as power outlets, or for data and signal line
protection.
Surge Protection Handbook 9
Conclusions
The electrical environment in which today's sensitive electronic systems are required
to operate is becoming increasingly polluted by electrical disturbances, such as
voltage surges and transients. At the same time, the susceptibility of these systems
to failure has increased as the use of micro-controlled based electronics has
proliferated into even the simplest consumer appliances.
This situation is driving the need for effective surge protection at competitive cost.
Iskra Zaščite is the leading designer and OEM manufacturer of surge protective
devices. It is at the forefront of many new and patented technological advances and
actively participates in various international standards setting committees dealing
with surge protection, including IEC, Cenelec, UL and IEEE.
10
Surge Protection Handbook 11
2. Overvoltage sources
2.1 Atmospheric discharge - Lightning
During storms, powerful electrical currents flow between clouds and ground. The
consequence of these discharge currents is the induction of overvoltages and surges
in metallic elements of buildings, power supply and communication lines due to the
electromagnetic coupling. Overvoltage can also be generated by a direct strike which
is more dangerous than indirect strike. Direct strike may result in explosion, fire, or
total destruction of the struck object. In order to minimize damage risk due to
lightning surges, it is important to describe the transient characteristics of such
pulses, that could cause a partial or total collapse of distribution network or electrical
system (power, communication, etc.).
The first parameter of the lightning strike is maximum magnitude of the current. This
value cannot be exactly predicted. It appears in the range between several tens of kA
and 200 kA. The probability of amplitude discharge intensity is statistically described
in Figure 2.
The highest probability of current magnitude is in the range between 10 and 30 kA.
Waveforms used for testing surge protection devices have a long tradition of using
unidirectional waves, particularly a 1.2/50 µs voltage impulse and an 8/20 µs or
10/350 µs current impulse (Figures 3a, 3b, 3c).
In Figure 3, the value 8/20 µs or 10/350 µs refers to the 8 or 10 µs rise time of the
surge, and the 20 or 350 µs fall time. The latter value defines the time for the voltage
to reach half of its peak value.
This rapid raise of current at the beginning of pulse causes strong magnetic field,
creating dangerous levels of induced voltages. Therefore, an important factor is a
rate of current rise. This parameter is usually expressed in kA/µs. This data is
required for voltage determination on the protected device that includes inductance.
The distance between protective device and object or device should be as short as
possible.
Surge Protection Handbook 13
If the aim of design is to provide protection for a direct and indirect stroke to the
building, the correct selection of surge protection devices also requires knowledge of
lightning charge:
(2-1)
(2-2)
The amount of dissipated energy is related to the switching surge waveform, its
magnitude, the system impedance, circuit topology, the characteristics of surge
protection device, and the number of strikes. The selected equipment should have an
energy capability greater than the energy related to the expected switching surges on
the system.
Overhead power lines are distributed on wide geographical area and are thus very
likely to be affected by lightning. Different atmospheric discharges in the vicinity of
lines cause the induction of overvoltage along the power line. In that case,
transmission line itself acts as a widespread antenna. The power line network is
primarily designed for transmission of electrical energy but it is also the media for
transmission of overvoltage through the network. The power lines therefore suffer
different consequences caused by atmospheric discharges. A lightning strike can
generate transient overvoltage on an overhead line by:
direct strike to the overhead shield wire or tower, which then flashes over to the
phase conductor,
strike a several hundred meters away from the power line (indirect strike), which
also induces overvoltage on the power line.
The overvoltage impulses caused by direct or indirect strikes travel from the point of
14 Overvoltage sources
impact through the whole network. These impulses can be transferred also through
transformers from higher to lower levels of a network where they present another
source of overvoltage disturbances.
Galvanic connection causes the most dangerous overvoltage and arises at juncture of
two wires with different operating voltages or electrical arc appearance between such
wires.
The example is a stick between communication and power cables (Figure 4a).
Overvoltage from one network to another can also be transferred if there exists
capacitive coupling between two networks (Figure 4b), or in the case of parasitic
capacitance in the transformer, which will transfer overvoltage from high voltage side
to low voltage side in the case of unbalance on the high voltage side. The most
common coupling between two networks is inductive coupling. It is well known
according to the Faraday's law that magnetic field varying in time will induce voltage in
the loop inside that field. If magnetic field corresponds to the transient current with
the high rate of change, transient overvoltage will be induced in such loop (Figure 4c).
c
b
230/380 V
Should lightning strike into the air terminal, lightning current IL flows through down
conductor to the earth. Induced voltage in the installation loops causes different
disturbances, i.e. faults that can even lead to a fire. If the loop is at the horizontal
distance c from the down conductor, and loop dimensions are a and b as in Figure 5,
the induced voltage V equals:
For instance, for the square loop 10x10 m, 1 m away from the conductor, mutual
inductance M equals 4.8 H and, under assumption di/dt = 40 kA/s, induced voltage
amounts to 192 kV.
t [ms]
t [ms]
Higher overvoltage can appear due to switching inductive loads, such as inductors,
transformers, motors as well as capacitive loads. Interruption of short-circuit currents
also causes high overvoltage. As with circuit breaker caused overvoltage, here also
the peak is correlated with the power-frequency voltage value in the moment of
switching operation.
The shape of the overvoltage wave is a ringing wave. Rate of voltage rise is usually in
the order of a few kV/µs, while the transient can then last from µs to ms.
The time duration of switching surges is much longer than lightning surge duration,
but voltage peak is significantly weaker. The peak is determined by response of the
low-voltage installation, inductance and capacitance of a circuit, type of switching
(on/off, circuit breaker or fuse) and load types.
Surge Protection Handbook 17
In the case of resistive load, switching currents are in the order of rated equipment
value. When inductive/capacitive load is switched on/off, high frequency oscillations
appear. Oscillating voltage is superimposed with rated voltage of the system and total
voltage represents the stress to the equipment connected to the power supply
system. Overvoltage caused by switching on load side is higher than overvoltage on
the line side.
The presence of capacitor banks for the power factor correction is also a cause of
capacitor-switching surges. These capacitor banks are typically installed on a
medium-voltage side. Capacitor-switching overvoltage is frequently below double
value of the system normal voltage (Figure 7).
Fuse operation in power supply network initiates overvoltage, which takes somewhat
triangular wave shape. This overvoltage is less frequent than the one caused by
switching operations.
The first letter indicates the connection between earth and power supply equipment
(generator or transformer)
I : no point is connected with earth (isolation), except perhaps via a high impedance
The second letter indicates the connection between earth and the electrical device
being supplied
3.1 TN system
In TN earthing system, one of the points in the generator or transformer, is connected
with earth, usually the star point in a three-phase system. The body of the electrical
device is connected via this earth connection to the transformer.
The conductor, that connects the exposed metallic parts of the consumer, is called
protective earth (PE). The conductor that connects to the star point in a three-phase
system, or carries the return current in a single-phase system, is called neutral (N). It
is to be distinguished among three variants of TN system:
22 Earthing and network topology
TN-S: PE and N are separate conductors that are connected together only near the
power source
TN-C-S: part of the system uses a combined PEN conductor; at a certain point it is
split up into separate PE and N lines. The combined PEN conductor typically
occurs between the substation and the entry point into the building, and
separates the service head.
In TN-C system, combined PE and N conductors (PEN) are used from the transformer
neutral point to the consuming device. An example of a typical TN-C system is
presented in Figure 9.
The neutral current and the earth-fault current flows via the same return path to the
earthed neutral point of the power transformer. Usage of a single conductor for both
currents reduces the cost of an additional conductor needed for separate N and PE
connections.
The separate protective earth (PE) and neutral (N) conductors from transformer to
consuming device are used in TN-S system. The PE conductor is connected to the
neutral conductor at the neutral point of the power transformer (Figure 10). The
neutral current and the earth-fault current use separate conductive paths.
Surge Protection Handbook 23
Exposed conductive parts are connected to the PE conductor for the conduction of
earth-fault current. Separated PE and N conductors allow successful application of
residual-current circuit breakers.
This system represents combination of the above defined TN-C and TN-S systems. TN-
C-S system has a separate N and separate PE conductor, as well as their combination
as PEN conductor (Figure 11). PEN conductor is used for the connection between
power supply transformer and service-entrance point of the building. After this point,
separate N and PE conductors are utilized. As in the TN-S system, separate N and PE
conductors inside the building allow usage of successful application of residual-
current circuit breakers.
3.2 TT system
In TT earthing system, the protective earth connection of the consumer is provided by
a local connection to earth, independently of any connection at the generator.
The greatest advantage of the TT earthing system is that it is clear of high and low
frequency noises coming through neutral wire from various electrical appliances
connected to it. This is why, TT has always been prefered for special applications like
telecommunication sites benefiting from interference free earthing. Additionally, TT
does not pose the risk of broken neutral.
In pre-RCD era, TT earthing system was unattractive for general use because of its
slim capability of accepting high currents in short circuit (in comparison with TN
systems). But as residual current devices mitigate this disadvantage, the use of TT
earthing systems is becoming more popular in premises where all AC power circuits
are RCD protected.
3.3 IT system
In an IT network, the distribution system has no connection to earth at all or it only
has high impedance connection.
Table 1: Temporary overvoltage for different types of neutral earthing, fault type and fault
location [adopted from IEC 61643-11 Ed 1]
3.6.1 TN network
For SPD connected between L and PE, the general rule for dealing with maximal
temporary overvoltage is Utov = 335V. SPD itself can be exposed to this phenomenon
for a longer period.
A solution is to increase nominal voltage of SPD to 335 V (in this case SPD is not
subjected to Utov), or disconnect it from live conductor via thermal disconnector, but
in such case SPD is out of order.
IK F
R= 0
U
IK=
3.Z
3.6.2 TT network
F
L
N
SPD
RE
IK
U SPD
F I
SPD
However, this is not a reasonable solution because RCD has relatively low dielectric
strength and can suffer mechanical damage in case of atmospheric discharges.
These damages can have serious influence on RCD operation and are not visible,
making operator unable to know if it is still functioning.
Connection 4+0 is allowed only in the case when SPD is connected downstream of
RCD.
L1 L1
L2 L2
L3 L3
N
Figure 18: TT system - connection 3+1 Figure 19: TT system - connection 4+0
Surge Protection Handbook 29
F
L1
L2
L3
RE , I K
If short circuit and impulse overvoltage happen in the system at the same time, Ik
(short circuit current) starts flowing through gas discharge tube (GDT). That is the
reason why GDT should be able to extinguish the follow-up current and at the same
time preventing allowing touch voltage endangering human life.
L1 L1
L2 L2
L3 L3
N
PEN
PE
Figure 21: TN-C SPD (3+0) Figure 22: TN-S SPD (4+0)
L1 L1 I
L2 L2
L3 L3
N RCD
PE
PE
L1
L2
L3
PEN
Reference:
1. IEC 61643-1 Surge protective devices connected to low voltage power distribution systems-
requirements and test
2. IEC 61643-12 Surge protective devices connected to low voltage power distribution
systems- selection and application principles
3. CEI IEC 60364-5-53 Electrical installation of buildings- Part 5-53: Selection and erection of
electrical equipment isolation, switching and control
4. IEC PAS 60099-7 Surge arresters- Part 7: Glossary of terms and definitions from IEC
publications 60099-4, 60099-4, 60099-6, 61643-1, 61643-12, 61643-21, 61643-311,
61643-321, 61643-331 and 61643-341
5. IEC 61000-4-5: Electromagnetic compatibility (EMC) Part 4-5: Testing and measurement
techniques - Surge immunity test
6. IEC 62305-1 Protection against lightning- Part 1: General principles
7. IEC 62305-2 Protection against lightning- Part 2: Risk management
8. IEC 62305-3 Protection against lightning- Part 3: Physical damage to structures and life
hazard
9. IEC 62305-4 Protection against lightning- Part 4: Electrical and electronic systems within
structures
10. IEC 61312-1 Protection against lightning electromagnetic impulse (LEMP)- Part 1: General
principle
11. IEC 61312-2 Protection against lightning electromagnetic impulse (LEMP)- Part 2: Shielding
of structures, bonding inside structures and earthing
12. IEC 61312-3 Protection against lightning electromagnetic impulse (LEMP)- Part 3:
Requirements of surge protection devices
13. IEC 61312-4 Protection against lightning electromagnetic impulse (LEMP)- Part 4:
Protection of equipment in existing structures
Surge Protection Handbook 31
4. Lightning protection
4.1 Standards
Lightning protection covers the fields of interception systems, down conductors,
grounding, potential equalisation or isolation. In the following standards the complete
procedure of design drawings is defined, from the calculations to the use of
materials.
IEC 62305 - 4: 2010 Protection against lightning Part 4: Electrical and electronic
systems within structures
To reduce the loss due to lightning, protection measures may be required. Whether
they are needed, and to what extent, should be determined by risk assessment.
The risk - R - is the value of a probable average annual loss. For each type of loss
which may appear in a structure or in a service, the relevant risk shall be evaluated:
R4: risk of loss of economic values, should be assessed whenever the economic
justification of lightning protection is considered (IEC 62305-1; 2010)
To evaluate risks, R, the relevant risk components (partial risks depending on the
source and type of damage) shall be defined and calculated. Risk components
description is found in the standard IEC 62305-2; 2010.
Each risk, R, is the sum of its risk components. When calculating the risk, its
components may be grouped according to the source of damage and the type of
damage.
In Table 2, the risk components are considered for each type of loss for the structure
and line.
Source of damage Flash to a structure Flash near a Flash to a line Flash near a line
structure connected to the connected to the
structure structure
S1 S2 S3 S4
Risk component RA RB RC RM RU RV RW RZ
By calculating some of the risk components, the isokeraunic maps are used.
Isokeraunic maps show areas where a similar number of thunderstorms occur each
year.
Surge Protection Handbook 33
The lightning current is the primary source of damage. The following sources are
distinguished by the strike attachment point:
For practical application of this risk assessment, it is useful to distinguish between three
basic types of damage, which can appear as a consequence of lightning flashes. They are
as follows:
The decision to protect a structure or a service against lightning, as well as the selection of
protective measures, shall be performed according to IEC 62305-1; 2010. The following
procedure shall be applied:
identification of all types of loss in the structure and the relevant corresponding risk R
(R1 to R4);
evaluation of the need for protection comparing the risks R1,R2 and R3 with the
tolerable risk RT (IEC 62305-2;2010);
Minimum lightning current values are also defined in IEC 62305-1; 2010.
Here is the example how to choose the Iimp of the SPD according to the protection
levels. The lightning current is divided in accordance with the principle 50% to ground
and 50% to installation, provided that:
calculation shows that lightning protection level I (which is the most exacting level)
with the maximum lightning current is needed
The maximum lightning current of 200 kA (from the above table) is then divided into
the current of 100 kA, which flows to the ground, and into the current of 100 kA,
which flows to installation (across main bus bar and SPD) and from there to the other
distant buildings and a transformer. According to the type of the power supply
network, there are the minimum values of the Iimp the SPD should withstand:
three phase TT, TNS, IT (with neutral) systems: 100 kA/4 wires = 25 kA/wire
three phase TNC, IT (without neutral) systems: 100 kA/3 wires = 35 kA/wire
single phase TT, TNC system: 100 kA/2 wire = 50 kA/wire
According to Table 3, the minimum lightning strike current is 100 kA. Hence the
minimum value of the lightning current the SPD conduct is 12,5 kA. This can be seen
in the following Figure 27.
Current sharing:
50% - LPS
50% - Power supply lines
II II
III III
IV IV
Table 4: Relation between lightning protection levels (LPL) and class of LPS
(IEC 62305-3; 2010)
The class of required LPS shall be selected on the basis of the risk assessment (IEC
62305-2; 2010).
The rolling sphere method is suitable in all cases. Table 5 shows maximum values of
rolling sphere radius, mesh size and protection angle corresponding to the class of
LPS.
Protection method
Class of LPS Rolling sphere radius Mesh size Protection angle
r W
(m) (m)
I 20 5x5 See figure 29
II 30 10 x 10
III 45 15 x 15
IV 60 20 x 20
Table 5: Maximum values of rolling sphere radius, mesh size and protection angle
corresponding to the class of LPS (IEC 62305 - 3, 2010)
Figure 28 shows the mesh method, where conductors are placed on the concrete
insulation bricks and connected with flexible wires to enable extension of the system
due to temperatures, wind, etc.
The protection angle method is suitable for simple-shaped buildings, but it is subject
to limits of air-termination height (max. height is the radius of rolling sphere)
indicated in Figure 29.
38 Lightning protection
Note 1 Not apllicable beyond the values marked with .. Only rolling sphere and mesh methods apply in
these cases.
Note 2 h is the height of air-termination above the reference plane of the area to be protected.
Note 3 The angle will not change for values of h below 2m.
The mesh method is a suitable form of protection where plain surfaces are to be
protected.
The following Figures (31 to 34) show the principle of rolling sphere method in
combination with the protection angle and mesh method. Rolling sphere method is
based on the rolling the sphere around and over the building(s). Where the sphere
touches the building, it is necessary to place the lightning interception system and
down conductors.
Surge Protection Handbook 39
The first example shows two small buildings where higher building has the mash and
Franklin rod as a lightning interception system. The rod protects the objects on the
roof which are inside the angle α2 (shaded area) and the complete smaller building
which is “covered under” the angle α1.
Loop dimension
Air temination system
Protective angle
Lightning strike
h2
1 2
h1
dimensions
Radius (R)
LPS type
Loop
I 20 m 5 x 5 m
II 30 m 10 x 10 m
III 45 m 15 x 15 m
Earth
Down conductor termination IV 60 m 20 x 20 m
system system
In Figure 32 we see that one of the buildings is much higher and the air terminal
does not protect the lower building any more (rolling sphere can touch it), the
lightning interception system is thus placed also on the lower structure.
Loop dimension
Protective angle
Air temination
system
h2
Lightning
strike
h1
dimensions
Radius (R)
LPS type
Loop
I 20 m 5 x 5 m
II 30 m 10 x 10 m
III 45 m 15 x 15 m
Down conductor IV 60 m 20 x 20 m
Earth termination
system system
On structures taller than 60 m, flashes to the side may occur especially to points,
corners and edges of surfaces. In general, the risk due to these flashes is low
because only a few percent of all flashes to tall structures will hit the side and,
moreover, their parameters are significantly lower than those of flashes to the top of
structures. However, electrical and electronic equipment on walls outside structures
may be destroyed even by lightning flashes with low peak current values.
An air termination system shall be installed to protect the upper part of tall structures
- typically the topmost 20% of the height of the structure - with the equipment
installed on it.
The rules for positioning air-termination system on roofs shall also apply to those
upper parts of structures.
Additionally, structures taller than 120m should have protected all parts which may
be endangered (above 120 meters).
According to the LPS and protective measures against LEMP, the protection zones are
defined.
Surge Protection Handbook 41
LPZ 0A
S1
Air temination
system
Structure
S3 (shield of LPZ 1)
LPZ 0B
Incoming MB
utilities
Down conductor
ds system
LPZ 1
Room
R (shield of LPZ 2) R
S4 ds S2
MB
SPD LPZ 2 SPD
1/2 SB 1/2
LPZ 0B LPZ 0B
MB
SPD
Earth termination system 0A/1
In Figure 34 we see the building with the lightning protection system on top, down
conductors, grounding system, installed surge protection and Faraday cages. There
are different points of lightning strikes:
S1 - flash to the structure (air termination system)
S2 - flash near the structure
S3 - flash to a line connected to the structure
S4 - flash near a line connected to the structure
Letter R in the red areas represents a radius of rolling sphere, which is rotated
around and above the building. Everything it touches (building, service, objects on the
building, ground, etc.) is considered to be in protection zone 0A. This is the zone
where a direct lightning flash is possible and a full lightning current and magnetic
field are present. In the case of S3, the incoming cable is protected at the entering
point into the building with the SPD capable surviving a direct lightning strike (SPD
0A/1). Strike S2 can influence the underground cable; that is why this cable is
protected at the entrance into the building with the same type of the SPD (SPD 0A/1).
Where direct lightning strike is not possible, but partial lightning or induced current
and full magnetic field are possible, there exists zone 0B. Strike S1 hits the air
42 Lightning protection
terminal, but it is unable to hit the area between these two rods (zone 0B); the SPDs
for indirect strike can be used there (SPD 0B/1). These 2 zones are also seen on the
left and right side of the structure below the rolling spheres. In the case of S2, we use
SPDs for direct lightning strike even though there is a 0B/1 zone. The reason for this
is that S2 strike can hit the underground cable away from the building and the
lightning current can flow through the cable into the building.
Inside the building we have zone 1 where no direct flash is possible, limited lightning
or induced currents are present and magnetic filed is damped. Further on, we have
zone 2 or even more, which have in common: no direct flash, only induced current,
further damped magnetic field. Between zones 1/2, the appropriate SPDs for indirect
strikes are placed.
Protective volumes inside LPZ 1 and LPZ 2 must respect safety distances ds (Figure
34) against too high magnetic field (e.g. the equipment is placed in the room away
from the Faraday cage at least for the distance ds) .
The function of the internal LPS is to prevent dangerous sparking within the structure
and it is thus important to use either equipotential bonding or a separation distance
S (and hence electrical isolation) between the LPS components and other electrically
conducting elements internal to the structure.
thermal:
mechanical:
electromagnetic:
electrical:
Example:
Melting of imax = 100kA; RG = 5Ω
material Heating of
coductor Uo = imax . RG = 100.5 = 500kV
s
3 50μ
10/ Interception system
Dangerous F
sparking Dynamic
forces Us step voltage
F VFG foundation grounding
u
1.2/50μs VGR grounding ring
Induced Down conductor
voltage Testing clamp
Step
Contact voltage
voltage Power supply cable
Earth Grounding
RG ring Conductor
termination
system Grounding
conductor 1m
V [V]
VFG
Us 0 Ut1 Ut2
VGR
Uo
VFG VFG +VGR
Us
0
l [m]
Figure 35: Lightning effects
The key solution to avoid step and touch voltage is to build a proper grounding system
and to connect all metal parts together, first to local bus bars, then to the main bus
bar. In some cases, the connection is not done directly but with assistance of special
elements - for example, cathode protected oil pipe connected to the bus bar with gas
discharge tubes or spark gaps to prevent stray current flow.
44 Lightning protection
Utility
Cathode
protected
pipe
Foundation grounding
4.6 Grounding
Grounding is needed to dissipate the energy of the lightning strike, to limit the noise,
to reduce electrostatic charge, as well as to ensure personal safety, fuse operation in
earth short circuits and device protection, etc.
The main goal of a grounding system for the needs of a lightning protection is energy
dissipation of the lightning strike, as fast as possible. Consequently, the occurrence
of dangerous voltages has to be prevented. When dealing with the dispersion of the
lightning current (high frequency behaviour) into the ground, whilst minimizing any
potentially dangerous overvoltages, the shapes and dimensions of the earth
termination system are the important criteria.
All different grounding systems should be directly connected together or through the
spark gap and gas discharge tube into a common grounding system.
Naturally, the lower grounding resistance, the more favourable conditions. In general,
a low earthing resistance, if possible lower than 10 Ω when measured at low
frequency (IEC 62305-3; 2010), is recommended to avoid high voltage drop values
on the grounding system. Figure 38 shows the conditions at the SPD in the moment
of a lightning strike.
Surge
arrester 1.2 kV 6.2 kV
2m 2.5 kV
Earthing
Equipotential bonding
10 Ω
The requirements for the SPD grounding resistance are regulated referring to
different countries. In Slovenia, the value is 5 Ω.
F Foundation grounding
J Iron frame joint
R Grounding bus bar conductor
Y Grounding fix point
T Transformer
C Cable tray
P Metal pipes
M Motor
L Data lines
B Control box
S Switchboard
X Supporting small column for double floor
system
D Control desk
G Grounding bus bar
A Down conductor
R Grounding rings for potential equalization
N Connection to the neighbouring grounding
systems
Figure 39: Proper grounding solution and potential equalization ( Blitzshutz, Montage-
handbuch, VBD)
Transformer, cable trays, metal pipes, motor, data line screen, control box,
switchboard, double floor system supporting column, control desk are all connected
to the grounding bus bar conductor, which is fastened on the grounding fix point to
the foundation grounding. Iron frame joints are attached to the foundation grounding
as well. Grounding bus bars are fixed to the foundation grounding and to the
grounding rings for potential equalization. Down conductors are connected to the
grounding bus bars. This complete system is connected to the grounding system of
neighbouring buildings.
Surge Protection Handbook 47
The main task of surge protective device (SPD) in low-voltage power supply lines is
suppression of the overvoltage transients travelling along lines to the sensitive
electronic devices connected to the line terminals. Overvoltage impulse appears
between phase conductors and the earth or between various phase conductors. In
both cases, there is a risk of dielectric breakdown which can lead to the destruction
of the equipment. In order to avoid damage of the equipment, surge protective
devices must be utilized. Equipment vulnerability depends on the sensitivity of the
used electronic components determining the level of overvoltage protection needed
for installation. Surge protective devices consist of basic electrical elements, such as
resistors, inductivities, capacitors and overvoltage protection elements as crucial
elements of device. Characteristics of basic electrical components are well known
and their descriptions can be found in any textbook about basic electrical circuits.
The overvoltage protection elements are closely related to overvoltage protective
devices since their characteristics directly determine the characteristic of an
overvoltage protective device. A surge protective device contains at least one
nonlinear element; usually, surge protective devices available on the market are
mainly composed of two or more nonlinear components. Additionally, they may
include other components, such as fuses, disconnections, indicators, inductors,
capacitors and other components. In order to assure easier design and installation of
surge protective systems, SPDs are classified into groups, in accordance with general
and electrical parameters in common. After introductory explanation of surge
protection principles and nonlinear elements used in LV power supply systems, the
classification of SPDs and their electrical characteristics is presented.
48 Surge protective devices
Figure 41: Installation of overvoltage protection element in parallel with line protected
equipment
These two solutions require the usage of elements with different electrical
characteristics under normal operation and during overvoltage impulse. In the first
case, the protective component is installed in series with the power supply line and
must have the as small impedance in normal operation and as large impedance
during an overvoltage impulse (thermal or automatic fuses) as possible. These
elements can be used for over-current protection but their response time represents
main limiting factor for the overvoltage protection. This method of overvoltage
protection is equivalent to equipment unplug from the all incoming lines during an
expected storm or announced switch manipulations in the power grid.
In the second case, the protective component is installed in parallel with the protected
equipment and must have large impedance in normal operation and small impedance
during overvoltage impulse, providing that overvoltage impulse can be conducted to
the earth. The second solution is primarily used in surge protection because of
existence of appropriate elements assuring adequate protection.
Surge Protection Handbook 49
Voltage switching elements operate by switching from high to low resistance state at
a certain threshold voltage (breakdown voltage) and behave like a short circuit.
Breakdown voltage must be above the maximum continuous operating voltage of the
system. Spark gap, gas discharge tube (GDT) and PNPN structures (thyristors,
breakover diodes, triacs) operate in accordance with this principle. Voltage-current
characteristics of some ideal element and GDT are presented in Figure 42.
The ideal characteristics of the surge protection elements described above cannot be
achieved with commercially available components. The real characteristics of a
particular component play very important role in the design of overvoltage protectors.
Such elements are mainly described by their nonlinear terminal voltage-current
characteristics. Basic overvoltage protective components are presented using
classification introduced in the previous section. Surge protective devices used in LV
power supply systems are mainly based on elements with high energy withstand
capability. Used material of the element determines its energy withstand capability.
The elements with high energy capability are spark gap, GDT, and MOV. A description
of overvoltage protection elements used in LV power supply systems is limited, in this
section, to the previously mentioned elements. Such elements have relatively slow
response. However, slow response can be compensated by semiconductive
protection elements. The low-power components based on semiconductive materials,
such as diodes, transistors and thyristors, which have low energy withstand capability
but very fast response. They must be capable of carrying the surge energy until the
moment at which the element in first stage responds, which represents the main
reason for the utilization of such components. The low-power components are
principally installed in the last stage of overvoltage protective system (Figure 44).
Metal Oxide
Varistor
Silicon
Avalange Diodes
VFC
(Final
clamping
voltage)
230VAC
typical 50V
typical
UO = 24V
Class I Class II Class III
Figure 45: The sequence of the individual components results in an increasing response
sensitivity towards the output
52 Surge protective devices
Interference voltage with a rise of 1 kV/µsV and a peak value of 10 kV at input of first
stage is limited by a MOV to approx. 400 V. Second stage, decupled from the first by
means of inductance, suppresses this value to approx. 100 V. This voltage pulse is
then reduced to approx. 35 V (in a 24 V network voltage Uo) by the suppression diode
(Figure 45). Therefore, the downstream electronics need only be able to cope with a
voltage pulse of approx. 1.5 x Uo.
Spark gap
A spark gap was historically the first element used in the overvoltage protective
circuits. This component consists of two electrodes with air gap between them. The
distance between the electrodes defines the breakdown voltage. When the voltage
between the electrodes exceeds the breakdown voltage of the air, the “conduction
path” (ionized air) between electrodes is established and the current flows through
the space between the electrodes. The current initiates intensive thermal ionization,
the spark gap resistance drops and a current increases very rapidly. The major
problem recognized in the spark gap application is electrical arc extinguishing in the
power supply circuits after the surge current disappears.
GDT usually consist of two or three electrodes in a glass or ceramic, inert gas (neon
or argon) filled package (Figure 46). The electrodes are opposed each other across a
short distance. When the three electrodes are used, the middle electrode lies
between the other two electrodes located at the ends of the tube. The middle
electrode has a small hole allowing conduction between the other two end
electrodes. Commercially available GDTs are enclosed in ceramic tubes whose
terminals are metal electrodes.
U [kV] U [kV]
1.0 1.0
0.5 0.5
1 t [μs] 1 t [μs]
Figure 46: Voltage rise shape of 1 kV/µsV without voltage switching component and pulse
response voltage switching component (a peak value of 1 kV is limited to approx.
600-700 V)
Surge Protection Handbook 53
A typical V-I curve for GDT is shown in Figure 42. The problem connected with GDTs is
the presence of the electrical arc and follow-up current in the power supply network
(power-frequency current continuous to flow after surge current disappears). The
advantages are found in the application of MOV in the series with GDT.
Metal-oxide varistor
At very low voltages, MOV has the ability to indicate that conduction is blocked. When
higher voltage is applied at MOV's terminals, MOV resistance is reduces to a very
small value (Figure 50). MOV is thus classified as a strongly nonlinear resistor. The
electrical properties described in this section are defined by physical dimensions
(thickness, area and volume) of the varistor. Static symmetrical voltage-current curve
(Figure 48) can be modelled in three regions. In the first region, known as leakage
region, at low current values, V-I curve is approximately linear. A varistor behaves as
an open circuit having high resistance in the order of 109 Ω. The current in this region
depends on the temperature - this is especially expressed at low voltages. A leakage
current becomes noticeable when temperature increases. The capacitance in this
region has approximately constant value over a wide range of voltage and frequency.
The capacitance decreases when the voltage approaches the nominal voltage of a
varistor. The capacity of varistors available on the market is usually a few nanofarads
and depends on the diameter and thickness of the discs. As the voltage increases,
varistor becomes conductive. Temperature has influence on the nominal voltage of
the varistor. At very high current values, the current through varistor tends towards a
linear or ohmic law (upturn region). In this region, the temperature has no significant
influence on the V-I curve. The main advantage of varistors is their energy/cost ratio.
For that reason, the varistor has become the essential component in designing surge
protective devices.
54 Surge protective devices
LEAKAGE UPTURN
REGION NORMAL OPERATION REGION
Ures [V]
U2
U1
UN
1 mA In Imax I [A]
10-5 10-3 10-2 10-1 0 100 101 102 103 104 105 106
Figure 48: Typical V-I characteristics of metal-oxide varistor, and three regions of varistor
operation
i [kA] u [V]
t [μs] t [μs]
Figure 50: The response of Metal Oxide Varistor (MOV) on current shape 8/20 µs
Surge Protection Handbook 55
i [kA] u [V]
t [μs] t [μs]
In the process of SPD selection it is important that the chosen device belongs to the
required energy withstand capability class and fulfils certain electrical parameters.
SPD classification is completed through the definition of general characteristics of a
device and required conditions for its installation. On the other side, electrical
parameters describe attributes of the SPD necessary for its installation in a given
system and its response to different surges appearing in the system.
Design topology: According to this criterion SPDs are classified as: voltage-switching
component, voltage-limiting component and serial or parallel
combination of both.
Number of ports: One-port SPD, two-port SPD.
Class: Surge protection according to IEC standards is classified into three
classes (Figure 52):
56 Surge protective devices
Classification
of SPD Class I Class II Class III
Class I: The task of this stage is protection against direct and indirect lightning
currents and potential compensation of the input point into a structure. The
test pulse 10/350 μs (Figure 53) is used for tests of the protectors in this
class.
Class II: SPDs in this class are intended for protection against indirect effects of
lightning and reduction of remaining voltages from class I. The test pulse
8/20 μs (Figure 54) is used for tests of the protectors in class II.
Class III: Class III is positioned between the sub-distribution panel and the end
consumer or within the power socket. Some of the more sensitive
consumers have their own surge protection installed inside the device
casing. The task of class III is protection against switching overvoltages and
reduction of remaining voltages from class I and II. The test pulses 1.2/50
μs (Figure 55) and 8/20 μs are used in test procedures.
Surge Protection Handbook 57
i [p.u.]
1.0
0.5
0
200 400 600 800 1000 t [μs]
350 μs
i [p.u.]
1.0
90 %
0.5
10 %
0
5 10 15 20 25 30 35 40 t [μs]
10 μs
i [p.u.]
1.0
0.9
0.5
0.1
0
Tr = 8 μs t [μs]
Tf = 20 μs
u [p.u.]
1.0
0.5
Duratio = 50 μs
0
20 40 60 80 100 t [μs]
t [μs]
Figure 56: Correlation between current surge waveforms 8/20 and 10/350
Q [As]
32
Q for 8/20
28
Q for 10/350
24
20
16
12
08
04
00
0 5 10 15 20 25 30 35 40 45 50 55 60 65
-04
Imax, Iimp [kA]
Figure 57: Correlation of charge Q between Imax (8/20) and Iimp (10/350)
Surge Protection Handbook 59
Maximum value the current attains through the SPD when a current waveshape of
8/20 μs is applied through the SPD. This parameter is used for the classification of
the SPD for the class II test and also for preconditioning of the SPD for the class I and
II tests (Figure 54).
It is used for classification of the SPD for the class I test and represents current peak
value (Ipeak) and charge (Q) tested according to the test sequence of the operating
duty test. This current is associated with longer waveshapes (10/350 μs) presented
in Figure 53. Correlation between current surge waveforms 10/350 and 8/20 is
shown in Figures 56 and 57.
This current value is used in operating duty test for the class II test. It is related to the
maximum value of discharge current that can very rarely occur at the location of the
SPD. Imax is associated with the class II tests.
60 Surge protective devices
A wave characterized by defined voltage amplitude (Uoc) and waveshape under open-
circuit condition and a defined current amplitude (Icw) and waveshape under short-
circuit conditions (Figure 55).
This parameter characterizes the performance of the SPD in limiting voltage across
its terminals after surge occure. The voltage protection level is given by the
manufacturer and may not be exceeded by:
- the neasured limiting voltage, determined for front-of-wave sparkover (if applicable
and the measured limiting voltage, determined from the residual voltage
measurements at amplitudes corresponding to In and/or Iimp respectively for test
classes II and/or I;
- the measured limiting voltage at Uoc determined for the combination wave for test
class III.
The value of this voltage is equal to or greater than the highest value of the
measured limiting voltage. It is an extremely important parameter in the procedure of
selecting SPDs; lower value of Up level provides better protection.
Degradation
Failure modes
These modes are used to define the compatibility of the SPD with other equipment,
with its application and the devices used in conjunction with the SPD. Failure mode
depends on the magnitude, number and waveshape of the surge current and voltage,
short-circuit capacity of the power system and value of the voltage applied to the SPD
at the time of failure. There are two failure modes of an SPD: short circuit and open
circuit. The power supply of the protected device will not be interrupted after SPD
operation, if disconnector is applied in the shunt branch with SPD (Figure 58).
Surge Protection Handbook 61
DISCONNECTOR DISCONNECTOR
FUSE
SPD SPD
Short-circuit withstand:
1. Maximum continuous load current (for two-port SPDs or one-port SPDs with
separate input and output terminals).
2. Voltage drop (for two-port SPDs or one-port SPDs with separate input and output
terminals).
Surge Arrester
Wave shape Wave shape Back-up Fuse ISKRA ZAŠČITE
8/20 μs 10/350 μs gL Products
(kA) (kA) (A)
13.0 3.0 50
21.7 5.0 63
43.3 10.0 125 PROTEC C
56.3 13.0 160 PROTEC B2S
65.0 15.0 200
86.6 20.0 225
108.3 25.0 250 PROTEC BS, PROBLOC BS
129.9 30.0 315
151.6 35.0 315 PROTEC BS
173.2 40.0 400
200 50.0 500 PROTEC BS
5.4.1 The expected types and levels of overvoltage impulses and currents
The main risk to equipment failure connected to the power supply lines arises from
direct and indirect lightning flashes. The first step in selecting SPD is thus predicting
required types and levels of such overvoltage impulses and currents. The selected
SPDs have to withstand the predicted values of voltages and the resulting current
through them with a sufficiently high reliability.
SPDs are tested using standardized current waveforms (10/350 μs and 8/20 μs),
and voltage 1.2/50 μs waveform. Magnitudes of these overvoltage impulses depend
on the SPD class and typical model used for protection.
The power lines at the main distribution board are subject to partial direct lightning
discharges. At this point, the class I SPD must be installed. Class I SPDs are suitable
for current arrester pulses of 10/350 μs. Value of the current impulse at this point
depends on the object location, installation of external lightning protection system,
earthing resistance and existence of other objects in the vicinity.
There are three typical models used for determination of expected values of
overcurrent impulses at the input of the protected structure:
Model of two structures (earthing resistances are equal) closely together (Figure
61). The first object is equipped with external lightning protective system while the
second is not.
Model of two or more structures (earthing resistances are different). In such case,
current sharing depends on the earthing resistance of a particular object.
64 Surge protective devices
Figure 60: Current sharing in the case of exposed structure and installed external lightning
protection system
Figure 61: Current sharing in the case of objects in the vicinity (earthing resistances are equal)
Surge Protection Handbook 65
It is required to choose appropriate model for own application and define current per
pole Iimp/pole (for some systems also current between N and PE). For a three-phase
TT system current IN-PE = 4 Iimp/pole, and for a single-phase TT system IN-PE = 2
Iimp/pole are required. Required values are summarized in Table 8.
Parameters of the LV power distribution system required for the definition of this
stage are summarized in Table 9. Designer of the surge protective system should fill
the parameters of the LV power supply system in the table. The values represent
starting parameters in the process of the SPD selection.
Protected devices in the structure have different dielectric withstand categories. The
values of dielectric withstand are given by the manufacturer of a particular device.
Table 10 shows standardized values of dielectric withstand levels for different
categories and their installation locations in the object.
The minimum required protection level represents the starting value in the process of
designing overvoltage protection. The following calculation is based on this value. It
shows the sensitivity of protected appliances to overvoltage impulses. The dielectric
strength of the most sensitive device should be defined by Table 11.
In general, it is preferred to install the SPD at the entrance of the object in order to
avoid current sharing through conductors located inside the structure. This approach
will provide the protection of in-home power supply installations. If the SPD protection
level of the first stage is not acceptable or equipment is not within the protective
distance of the SPD installed at the entrance (main distribution board), the second
class of the SPD should be installed at sub-distribution board and power socket. The
voltage sensed by the device Uprot has to be less than dielectric strength:
Uprot ≤ Ui
The voltage UPROT is the sum of protection level of the SPD Up and inductive voltage
drop appearing on the conductors connecting SPD and protected device:
From the last expression, protection level of the SPD (kV) is determined as:
The SPD class I installed at the main distribution board is intended to protect
equipment classified for the installation in categories III and IV (Table 12).
Installation of additional SPD depends on the actual protection level of the selected
device, protection level of the SPD class I and induced voltage Uind in the installation
conductor loop connection between SPD and protected appliances (Figure 62). The
value of protection level of the SPD at class I may be obtained from the catalogue,
while the distance between the SPD and protected appliance may be obtained from
the project documentation of the protected structure. If the condition
UPROT=Up+Uind ≤ Ui/2
At the sub-distribution board SPD of class II should be installed. Such devices are
intended to protect against the effect of induced voltages. Installations of the class III
SPDs are based on the same procedure and the condition:
230/380V
Figure 62: Voltage induction in the electrical installation due to lightning current in the down
conductor
The previously described four steps define the necessary parameters for the SPD
selection. In this phase, obtained parameters are used for proper selection of SPDs.
The process of the SPD selection should be completed using the parameters in the
same order as applied through the four steps. Therefore, the first parameter for SPD
selection is impulse current per pole and optionally current between N and PE for the
TT system.
5.4.6 Installation of SPDs and analysis of its effect on the protection provided by
SPDs
F F
a + b ≤ 0.5m b ≤ 0.5m
b b
EBB EBB
Figures 63a, b: Example of correct connection and maximum length of connected conductors.
6. Applications
6.1 Households
SINGLE HOUSE
Based on the isokeraunic levels chart and lightning protection calculations, it was
found that an isolated object (without the surrounding buildings) sized 11 x 11 m is
located in the environment with a large annual flash density per km2 required degree
is Lightning Protection Level I. This suggests that it must be designed in accordance
with all the parameters applied to this level.
The entire lightning system is tested by rolling sphere method. Imaginary sphere rolls
up and over (and is supported by) lightning masts, shield wires, substation fences
and other grounded metallic objects that can provide lightning shielding. An
object/equipment is said to be protected from a direct stroke if it remains below the
curved surface of the sphere. For Lightning Protection Level I, sphere radius is 20
meters (Figure 31).
Safety network (5 x 5 meters) is established on the roof (Figure 31), with additional
air terminal mast for satellite antenna protection. Air terminal mast is protecting
satellite antenna under certain fixed angle method (isolated solution).
The antenna is thus located in Zone 0B and the rest of the roof in zone 0A. From the
side of the building, deployment of the zones 0A and 0B is also visible. Given the
dimensions of the building, four discharge paths exist.
All metal parts of the building are connected to the grounding bus bar, which is
associated with the basic grounding and earthing ring, preventing the danger of step
and touch voltages resulting from ground potential rise in the event of lightning. The
earth resistance of the building is less than 10 ohms, which corresponds to the
Surge Protection Handbook 71
The main distribution box is located in front of the building, i.e. in the 0A zone and
thus requiring arresters of the class I (2), the same as in the segment (3). As well low
aerial lines voltage are protected with a special silicone surge arresters resistant to
weathering (1), nearby the transition to an underground cable system. Mounting
frequency depends on the electrical distribution company´s policy, calculations, law,
finance, etc.
72 Application Surge Protection Handbook 73
R= 20m
1 T2
L1
L2 Air temination
N 8 200kA system
Mesh size 5 x 5m
L3
Down conductor
R= 20m system
SB 2
2 T1
RECEIVER
6 4 T2
CABLE DUCT
9 R= 20m
MB 8
7 SB 1 3 T1
TK
5
box
100kA 200kA
1 T2, Class II 2 3 T1, Class I 4 T2, Class II 5 C2 6 T3, Class III/ C2 7 T3, Class III/ C2 8 C2 9 T3, Class III
PROTEC AQS 40 SAFETEC B(R) 25 SAFETEC C(R) 40 LPA 08 K1 xDSL protection modules ZES 1M+5S ZE 200 xDSL CCP-F Series MPE - Mini
Uc = 275V (PROTEC B2S(R) 12.5) Uc = 275V Uc = 180V Uc = 250V Uc = 275V Uc = 180V Uc = 275V
Power
Power
In = 20kA Uc = 275V In = 20kA In = 5kA Uoc = 3.0kV In = 16A In = 10kA Uoc/Isc = 6kV/3kA
Imax = 40kA In = 25kA Imax = 40kA Imax = 10kA Up < 1.0 kV Uoc/Isc= 6kV/3kA Imax = 20kA Up < 0.8kV
Up < 1.4 kV Imax = 100kA (60kA) Up < 1.6 kV Up < 0.3V Up < 1.5kV Up < 0.7kV
IP ≥ 67 Iimp = 25kA (min. 12.5kA) TOV resistant LL/K strip + K1 earthing contact Uc = 50V
Data
Up < 1.3 kV (1.5kA) NMI-22-1 earthing mounting frame In = 5kA Uc = 175VDC
Data
TOV resistant Up < 0.7kV In = 2.5kA
Up < 0.3kV
CONTENT - FIGURES
Figure 30: Chimney lightning protection with Franklin rod (Blitzshutz, Montage-handbuch, VDB) 38
Figure 39: Proper grounding solution and potential equalization (Blitzshutz, Montage-handbuch, VDB) 46
Figure 41: Installation of overvoltage protective element in parallel with line protected equipment 48
Figure 45: The sequence of the individual components results in an increasing response sensitivity
towards the output 51
Figure 46: Voltage rise shape of 1kV/µsV without voltage switching component and pulse response
voltage switching component (a peak value of 1kV is limited to approx. 600-700 V) 52
Figure 48: Typical V-I characteristics of metal-oxide varistor, and three regions of varistor operation 54
Figure 50: The response of Metal Oxide Varistor (MOV) on current shape 8/20 µs 54
Figure 56: Correlation between current surge waveform 8/20 and 10/350 58
Figure 57: Correlation of charge Q between Imax (8/20) and Iimp (10/350) 58
Figure 60: Current sharing in the case of exposed structure and installed external lightning protection
system 64
Figure 61: Current sharing in the case of objects in the vicinity (earthing resistances are equal) 64
Figure 62: Voltage induction in the electrical installation due to lightning current in the down conductor 68
Figure 63a, b: Example of correct connection and maximum length of connected conductors. 69
CONTENT - TABLES
Table 1: Temporary overvoltage for different types of neutral earthing, fault type and fault location
[adopted from IEC 61643-11 Ed 1] 26
Table 4: Relation between lightning protection levels (LPL) and class of LPS (IEC 62305-3; 2010) 36
Table 5: Maximum values of rolling sphere radius, mesh size and protection angle corresponding
to the class of LPS (IEC 62305-3, 2010) 37
- Domestic (EU) producer of MOVs and Present 20 years with production located in Europe
own development of GDTs
100% functional control and traceability
- Own testing laboratory
- 20% of staff working in R&D ISO 9001 and in the process for ISO 14000
ISKRA ZAŠČITE d.o.o., Surge Voltage Protection Systems, Engineering and Cooperation
Stegne 35, 1521 Ljubljana, Slovenia, EU
P: 00386(1)5003 100; F: 00386(1)5003 236
E: [email protected];
www. iskrazascite.si
Published by: ISKRA ZAŠČITE, d.o.o. / July 2012 / Edition 1.0 /
Copyright: All right reserved