0% found this document useful (0 votes)
333 views20 pages

Solenoid Valve Selection Guide

This document discusses solenoid valves, including: 1) Solenoid valves are electro-mechanical devices that use electromagnetic force to control fluid flow by opening and closing valve seats. 2) Solenoid valves are classified as direct acting or pilot operated. Direct acting valves operate the valve directly, while pilot operated valves use a differential area principle and media or external pressure to operate the main valve. 3) Direct acting valves can be 2-port or 3-port valves, and are either normally open or normally closed. Pilot operated valves can be internal or external pilot types.

Uploaded by

Amarjeet Baxla
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
333 views20 pages

Solenoid Valve Selection Guide

This document discusses solenoid valves, including: 1) Solenoid valves are electro-mechanical devices that use electromagnetic force to control fluid flow by opening and closing valve seats. 2) Solenoid valves are classified as direct acting or pilot operated. Direct acting valves operate the valve directly, while pilot operated valves use a differential area principle and media or external pressure to operate the main valve. 3) Direct acting valves can be 2-port or 3-port valves, and are either normally open or normally closed. Pilot operated valves can be internal or external pilot types.

Uploaded by

Amarjeet Baxla
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

FCS : SOV : 2021

Fluid Control System

E-7.4
INTRODUCTION : SOLENOID VALVE
Solenoid valve is an electro-mechanical device used for Fluid Control application.
Using the Electro magnetic force (generated due to the passage of Electric current in the coil), it converts the Electrical
energy into a mechanical movement of the Plunger and closing, opening of the valve seat (part of the plunger). The resulting
action starts or stops the flow.
The solenoid valve in most cases is either ON or OFF, there by creating two states or positions as more commonly referred
to. As is evident from the construction, pressure plays an important part in the valve operation.
All ROTEX solenoid valves are of pack less construction and have zero leak characteristics due to the soft elastomer sealing.
Based on their operating principle, the valves are classified as direct acting and internal/ external pilot operated Valve.

DIRECT ACTING
These are the most basic variation in the ROTEX Solenoid Valve program.
Since the solenoid is directly responsible for the operation of these Valves, they are called Direct acting. Refer the diagram.
In the de-energized condition Plunger seat is resting on the Orifice. There by blocking the flow.
On energization, the current flowing generates a magnetic field that couples with the Core and the plunger. This creates
sufficient force to overcome all resistance and lifts the plunger. This action opens the blocked orifice and thus allows the flow
to start. On switching OFF the current to the Solenoid, the current level drops below the holding level. Spring pulls down the
plunger and plunger seat blocks the orifice, blocking the flow. Direct acting solenoid Valves are available in two basic
varieties, 2 port valve and 3 port Valve. Based on the Flow connection in the de-energized and energized condition of the
Solenoid, these are further classified as Normally Closed, Normally Open or Universal.

2 PORT VALVE
Solenoid valves with 2 ports
Ports: Inlet and outlet.
Normally Closed: 1
Port 2 (Inlet) and port 1 (outlet) are disconnected in the
de-energized condition. On energization, the ports are
connected. 2 1 2 1 2

DE ENERGIZED ENERGIZED

Normally Open:
Port 3 (Inlet) and Port 2 (Outlet) are connected in the 3 3
de-energized condition. On energization, the ports are
disconnected. 2

3
2 2

DE ENERGIZED ENERGIZED

All ROTEX 2 Port Valves are positively sealed with the operating pressure. This ensures that the Valves are tight shut even
against pressure surges.
In general the 2 port Valves are uni-directional, thus holding pressure in the flow direction only.
However ROTEX also has a range of bi-directional shut off Valve for special application.

12

Specifications are subject to change without notice 391


INTRODUCTION : SOLENOID VALVE
3 PORT VALVE
Solenoid valve with 3 ports, are configured depending on the operation.

Normally Closed: 3
This configuration is most commonly used for the 3
operation of single acting/ spring return device. In de-
2
energized condition, port 1 (inlet) is disconnected from
port 2 (outlet connected to apparatus) port-2 is
connected to port 3 (exhaust/ vent). On energizing the 1
1 2 3
solenoid the plunger lifts and closes the port 3. Port 1 1 2
is connected to port 2.
DE ENERGIZED ENERGIZED

Normally Open:
3 3
In the de-energized condition the port 3 (inlet) is
connected to port 2 (outlet, connected to apparatus). 2
Port 1 (vent) is blocked by the plunger. On
energization, plunger blocks the Port 3. The port 2 is
connected to port 1. 1
3
1 2 1 2

DE ENERGIZED ENERGIZED

Both these versions use different plunger and consequently can not be reconfigured by merely changing the port
connections.

Universal :
This version is basically derived from the above two as a combination, allowing user to connect the valve in various
configurations like:
Normally closed, Normally open, as described above can also be used for mixing, diverting of the fluid.

Mixing: Inlet at Port 1 and Port 3 are alternately


3 3
connected to port 2 when The solenoid is energized/
de-energized. 2

3 1
1 2 1 2

DE ENERGIZED ENERGIZED

Diverting: Inlet at Port 2 is alternately connected to 3 3


Port 1 or Port 3 depending on the energization/ de-
energization of the solenoid.
2

1 2 31
1 2

DE ENERGIZED ENERGIZED

This Valve can also be used as 2 Port bidirectional Normally Closed by plugging port 3 and as 2 Port bidirectional Normally
Open by plugging port 1.
The universal Valve uses a special plunger and can not be directly converted at user end from a pre ordered Normally
Closed / Open Valve to Universal without affecting the operating pressure rating and change of plunger assembly

12 Variations to the above Valve construction are family of ROTEX Valves using pressure balanced plunger technology. This
greatly negates the effect of pressure in the Valve operation. This allows for better pressure holding and flow characteristics
in the Direct acting range of solenoid Valve.

392 Specifications are subject to change without notice


INTRODUCTION : SOLENOID VALVE
PILOT OPERATED
For application where sufficient media pressure is not available or requires a combination of high flow capacity and pressure
rating, the media pressure / external pilot pressure is used to operate the Valve. This group of valves uses a differential area
principle (for both Poppet and Diaphragm construction), utilizing the media pressure or external pressure to operate the main
valve.
All of ROTEX Pilot operated Solenoid Valves are pressure assisted positively sealed, there by sealing the Valve against
pressure surges. Integral Direct acting solenoid Valve acts as a Pilot valve controlling the application of the media pressure/
release of the media pressure from the operating area of the main valve and hence the name Pilot operated solenoid Valve.
Internal Pilot operated solenoid Valve uses the media pressure itself to operate the Valve.
External Pilot operated solenoid Valve uses an external pressure source for Valve operation. The applications where
media pressure is insufficient or media is unsuitable for the pilot solenoid Valve operation.

Based on the number of ports, the Valves are classified as:

2 PORT NORMALLY CLOSED DIAPHRAGM VALVE


In de-energized state, the media pressure connected to
Port 2 (inlet) acts under the diaphragm and through the
Bleed orifice, acts on top of the diaphragm. Since the
diaphragm area is larger above, It maintains the valve 1
closed disconnecting port 1 (outlet) from supply inlet
media pressure. Same pressure also acts in the pilot 2
2 1 2 1
solenoid over the main Pilot orifice.
On energizing the solenoid, the pressure above of
diaphragm is released through the Pilot orifice (which is DE ENERGIZED ENERGIZED
larger than the bleed orifice), thus lifting the diaphragm
with the help of the media pressure under the diaphragm.
The Pilot chamber pressure is released into the downstream of the valve near the outlet port. With the solenoid de-energized,
the Pilot orifice is blocked by the plunger. The media pressure now builds up on top of the diaphragm. With the help of inherent
material stiffness, the diaphragm returns to the de-energized state, ensuring tight shut off.

2 PORT NORMALLY OPEN DIAPHRAGM VALVE


In the de-energized state, the media pressure connected to Port 2(inlet) lifts the diaphragm as the pilot orifice is open to the
downstream, there by not allowing required pressure build up above the diaphragm, thus maintaining flow to Port 1(outlet).
On energizing the solenoid, plunger blocks the pilot orifice there by allowing build up of pressure above the diaphragm, which
is then closed by the inherent material stiffness of the diaphragm, stopping the flow.
On de-energizing the solenoid, the pilot orifice opens and vents the pressure from the pilot chamber to the downstream, there
by lifting the diaphragm with the media pressure below.

2
2 1 2 1

DE ENERGIZED ENERGIZED

12

Specifications are subject to change without notice 393


INTRODUCTION : SOLENOID VALVE
2 PORT NORMALLY CLOSED POPPET VALVE
In de-energized state, the media pressure connected to Port 2 (inlet) acts under the Poppet and through the Bleed orifice in
the piston, acts on top of the Poppet. Since the above Poppet area (piston seal area) is larger then the seat area, it
maintains the valve closed disconnecting port 1 (outlet) from supply. Same pressure also acts in the pilot solenoid over the
main Pilot orifice.
On energizing the solenoid, the pressure from the top of Poppet is released through the Pilot orifice (which is larger than the
bleed orifice), thus lifting the Poppet with the help of the media pressure below. The Pilot chamber pressure is released into
the downstream of the valve near the outlet port. Port 2 is connected to Port 1.
With the solenoid de-energized, the Pilot orifice is
blocked by the plunger. The media pressure now
builds up on top of the Poppet. With the help of the
main Valve spring, the Poppet returns to the de-
energized state, ensuring tight shut off.
It is important to note that, if the differential pressure
1
across the Valve falls below the minimum required
level, the Valve will start to close / completely close 2 2
even if the solenoid is energized continuously. For 2
1 1
certain applications, ROTEX offers a special
execution to overcome such conditions. Please DE ENERGIZED ENERGIZED
contact ROTEX local office for more details.

2 PORT NORMALLY OPEN POPPET VALVE


In the de-energized state, the media pressure connected to Port 2(inlet) lifts the Poppet as the pilot orifice is open to the
downstream, there by not allowing required pressure build up above the poppet. This maintains the flow to Port 1(outlet).
On energizing the solenoid, plunger blocks the pilot orifice there by allowing build up of pressure above the Poppet, which is
then closed by the main Valve spring above the Poppet. This stops the flow.
On de-energizing the solenoid,the pilot orifice opens
and vents the pressure from the pilot chamber to the
downstream, thereby lifting the Poppet with the
media pressure below. Similar to Normally Closed
1
version, when differential pressure dropsbelow the
minimum required, the valve will get closed in the de-
2 2
energized state even though the solenoid is OFF. For 2
certainapplications,ROTEX offers a special execution 1 1
to overcome such conditions.
DE ENERGIZED ENERGIZED
Please contact ROTEX local office for more details.

2 PORT EXTERNAL PILOT OPERATED POPPET VALVE


In case of application where media pressure is below the minimum required or when the media is aggressive, external pilot
Valve is used. External pressure media is connected to Port 7, which directly acts on the Poppet keeping it closed. On
energizing the solenoid, the Pilot orifice is blocked, blocking the external pressure to the Pilot chamber. The media pressure
under the Poppet helps to open the valve. For application where media pressure is below the required operating pressure,
an extra assistance is provided in the form of a spring to push the Poppet up.
The external pressure has to be minimum 3 bar or greater than the media pressure, which ever is higher.

2 Port External Pilot operated Normally 2 Port External Pilot operated


Closed Valve, Pilot air failure to open Normally Open Valve

7 7

1 1
7 7

2 2 2
2 7 2 7 2

12 1 1 1

DE ENERGIZED
1

ENERGIZED
DE ENERGIZED ENERGIZED

394 Specifications are subject to change without notice


INTRODUCTION : SOLENOID VALVE
3 PORT POPPET TYPE INTERNAL PILOT OPERATED NC SOLENOID VALVE
Inlet Pressure is connected to Port 1 (inlet) and blocked by the bottom valve seat assisted with spring. Port 2 (outlet) and Port
3 (vent) are connected. A pilot line is drawn from the inlet chamber to the Pilot solenoid valve and is blocked at the Pilot orifice
by the Plunger.
On energizing the solenoid, the Pilot pressure is directed to the Pilot chamber, there by applying the pressure to the top of the
Poppet.
The Piston seal area being larger than the Seat area
at the bottom, the resultant force moves the Poppet 6 6
assembly down. Port 3 is blocked as a result and
Port 1 and 2 are connected.
On de-energizing the solenoid, Plunger blocks the 2
Pilot orifice and opens the Pilot chamber to the Pilot
vent. Release of pressure, forces the Poppet 3 3
3 1
assembly up with the pressure acting at Port 3 and 2 2
the spring together, eventually blocking Port 1 and 1 1
connecting Port 2 to Port 3. DE ENERGIZED ENERGIZED

3 PORT POPPET TYPE INTERNAL PILOT OPERATED NO SOLENOID VALVE


Inlet Pressure is connected to Port 3 (inlet). Port 2 (outlet) and Port 3 are connected. A pilot line is drawn from the inlet
chamber to the Pilot solenoid Valve and is blocked at the Pilot orifice by the Plunger. Port 1 is blocked at the bottom Valve
seat by media pressure and assisted with Valve spring.
On energizing the solenoid, the Pilot pressure is directed to the Pilot chamber, there by applying the pressure to the top of
the Poppet.
The Piston seal area being larger than the Seat area at
the bottom, the resultant force moves the Poppet 6 6
assembly down. Port 3 is blocked as a result and Port
1 and 2 are connected.
On de-energizing the solenoid, Plunger blocks the Pilot 2
orifice and opens the Pilot chamber to the Pilot vent.
Release of pressure, forces the Poppet assembly up 3 3
with the pressure acting at Port 3 and the spring 3 1
2 2
together, eventually blocking 1 1
Port 1 and connecting Port 2 to Port 3. DE ENERGIZED ENERGIZED

3 PORT POPPET TYPE EXTERNAL PILOT OPERATED SOLENOID VALVE


Inlet Pressure is connected to Port 1 (inlet) and blocked by the bottom valve seat assisted with spring. Port 2 (outlet) and Port
3 (vent) are connected. A pilot pressure line (min. 3 bar greater or equal to main line pressure) is connected to Port 7 (Pilot
port) of Pilot solenoid Valve and is blocked at the Pilot orifice by the Plunger.
On energizing the solenoid, the Pilot pressure is directed to the Pilot chamber, there by applying the pressure to the top of the
Poppet. The Piston seal area being larger than the Seat area at the bottom, the resultant force moves the Poppet assembly
down. Port 3 is blocked as a result and Port 1 and 2 are connected.
On de-energizing the solenoid, Plunger blocks the Pilot
orifice and opens the Pilot chamber to the Pilot vent. 6 6
Release of pressure, forces the Poppet assembly up
with the pressures acting at Port 3 and the spring 2
together, eventually blocking Port 1 and connecting 7 7
Port 2 to Port 3.
With this version, the Valve can be configured to work 3 3
7 3 1
in either Normally Closed or Normally Open, Mixing or 2 2
1 1
Diverting mode thus making it a Universal valve.
DE ENERGIZED ENERGIZED

12

Specifications are subject to change without notice 395


INTRODUCTION : SOLENOID VALVE
5 PORT POPPET TYPE SINGLE SOLENOID VALVE
Inlet Pressure is connected to Port 1 (inlet). Through an internal passage the inlet is connected to the Port 4 (which acts as a
Normally open port). Inlet is blocked at the bottom valve seat assisted with spring. Port 2 (Normally closed outlet) and Port 3
(vent) are connected. A pilot line is drawn from the inlet chamber to the Pilot solenoid valve and is blocked at the Pilot orifice
by the Plunger. On energizing the solenoid, the Pilot pressure is directed to the Pilot chamber, there by applying the pressure
to the top of both the Poppets. The Piston seal area being larger than the Seat area at the bottom, the resultant force moves
the Poppet assemblies down.
Port 3 is blocked as a result and Port 1 and
2 are connected the same time Port 4 and
6
Port 5 are connected.
On de-energizing the solenoid, Plunger
blocks the Pilot orifice and opens the Pilot 2 4
chamber to the Pilot vent. Release of
3
pressure, forces the Poppet assemblies up 3
3 5
with the pressure and the spring together, 2 4
2 4
1
eventually blocking Port 1 and connecting 1 1 5
Port 2 to Port 3 and connecting Port 1 with 5
DE ENERGIZED ENERGIZED
Port 4 and blocking Port 5.

5 PORT POPET TYPE EXTERNAL PILOT OPERATED SINGLE SOLENOID VALVE


Inlet Pressure is connected to Port 1 (inlet). Through an internal passage the inlet is connected to the Port 4 (which acts as a
Normally open port). Inlet is blocked at the bottom valve seat assisted with spring. Port 2 (Normally closed outlet) and Port 3
(vent) are connected. A pilot pressure line (min. 3 bar or equal or greater than main line pressure) is connected to Port 7 (Pilot
port) of Pilot solenoid Valve and is blocked at the Pilot orifice by the Plunger. On energizing the solenoid, the Pilot pressure is
directed to the Pilot chamber, there by applying the pressure to the top of both the Poppets.
The Piston seal area being larger than the
Seat area at the bottom, the resultant force
moves the Poppet assemblies down. Port 4 6
is blocked as a result and Port 1 and 2 are
connected and at the same time Port 4 and
7 7 2 4
Port 5 are connected. On de-energizing the
solenoid, Plunger blocks the Pilot orifice and 3
3
opens the Pilot chamber to the Pilot vent. 7 3 5
2 4
Release of pressure, forces the Poppet 2 4 1
1 5
assemblies up with the pressure and the 1
5
spring together, eventually blocking Port 1 DE ENERGIZED ENERGIZED
and connecting Port 2 to Port 3 and connect
Port 1 with Port 4 and blocking Port 5.

5 PORT POPPET TYPE DOUBLE SOLENOID VALVE


Inlet Pressure is connected to Port 1 (inlet). Through an internal passage the inlet is connected to the Port 4 (which acts as
a Normally open port). Inlet is blocked at the bottom Valve seat assisted with spring. Port 2 (Normally closed outlet) and Port
3 (vent) are connected. A pilot line is drawn from the inlet chamber to the Pilot solenoid valve and is blocked at the Pilot
orifice by the Plunger.
On energizing the Latch solenoid(M1), the Pilot pressure is directed to the Pilot chamber, there by applying the pressure to
the top of both the Poppets. The Piston seal area being larger than the Seat area at the bottom, the resultant force moves
the Poppet assemblies down. Port 3 is blocked as a result and Port 1 and 2 are connected and at the same time Port 4 and
Port 5 are connected. After energization of the Valve, the bleed orifice connected to the Port 2 latches the Poppets. This
allows the Latching solenoid to be switched off (impulse operation).
On energizing the De-latching solenoid(M2),
Plunger opens the Vent orifice and releases
the Pilot pressure from the Pilot chamber to M1 M2
M1 M2
Pilot vent port 6. Release of pressure, forces
the Poppet assemblies up with the pressure 2 4

12
and the spring together, eventually blocking 3 3
Port 1 and connecting Port 2 to Port 3 and M1
3 5 M2
2 4 2 4
connecting Port 1 with Port 4 and blocking 1
Port 5 and Since this valve is pneumatically 1 1 5
5
latched, the Loss of Air pressure will cause DE ENERGIZED ENERGIZED
the Valve to reset.

396 Specifications are subject to change without notice


INTRODUCTION : SOLENOID VALVE
5 PORT INLINE POPPET INTERNAL PILOT OPERATED SOLENOID VALVE
Inlet pressure is connected to the Port 1(inlet). Port 1 is connected to Port 4 (Normally open outlet) with the Port 5 (vent)
blocked by the Poppet seat. Port 2 (Normally closed outlet) is connected to Port 3 (vent). Inlet air is connected to the bottom
of the Poppet and acts on the bottom piston which works as a return spring keeping the Poppet assembly up.
On energization, inlet air is drawn from the Pilot line and connected to the Top piston chamber. Since the Top piston is larger
than the bottom piston, resultant force moves the entire Poppet assembly down.
With the inlet seal crossing over the
port, port 1 which is disconnected from
port 4 and is connected to port 2. The 2 4 2 4
Poppet seat closes Port 3 and opens 2 4
Port 4. On de-energization the force 6 6
from the bottom piston pushes the
Poppet assembly up to its original 3 5
condition. Breather port is provided to
3 1 5 3 1 5
vent the air under the top piston. This 1
DE ENERGIZED ENERGIZED
hole should not be plugged.

5 PORT INLINE POPPET DOUBLE SOLENOID VALVE


Inlet pressure is connected to the Port 1(inlet). Port 1 is connected to Port 4 (Normally open outlet) with the Port 5 (vent)
blocked by the Poppet seat. Port 2 (Normally closed outlet) is connected to Port 3 (vent).
On energization of the latching solenoid(M1), inlet air is drawn from the Pilot line and connected to the Top piston chamber.
The resultant force moves the entire Poppet assembly. With the inlet seal crossing over the port, port 1 is disconnected from
port 4 and is connected to port 2. The Poppet seat closes Port 3 and opens Port 5.
De-energizing the latch solenoid does not change the valve position. To reset the Valve to original state, de latching solenoid
(M2), is energized. Inlet air is connected to the bottom piston. The force from the bottom piston pushes the Poppet assembly
up to its original condition. Breather port is provided to vent the air under the top piston. This hole should not be plugged.

2 4 2 4
2 4
6 6 6 6

M2 3 5 M1
1
M2 3 1 5 M1 3 1 5
M2 M1

12

Specifications are subject to change without notice 397


DEFINITION
Solenoid Enclosure
Metal housing around the coil for electrical and mechanical protection. It also gives protection against environmental
hazards.

Maximum Operating Pressure Differential


This refers to the difference in pressure between inlet and the outlet. If the pressure at the outlet is not known, conservative
approach suggests to treat inlet pressure as maximum operating pressure differential.

Minimum Operating Pressure Differential


This is the pressure that is required to open the Valve and keep it open. For 3 ports and 5 ports pilot Valves, the minimum
operating pressure is measured between the inlet pressure and exhaust ports and must be maintained through out the
operation cycle for smooth operation of the Valve. At minimum operating pressure differential, Rotex Valve have 80 % of
the flow factor.

Proof Pressure
It is the pressure which Valve can withstand before bursting/ causing permanent physical deformation.

Maximum Ambient Temperature


Maximum ambient temperature determines safe working limit for coil insulation in energized condition , with maximum fluid
temperature in the existing Valves.

Response Time
It measures the time lapse after energizing or de energizing a solenoid Valve until the outlet pressure reaches a specific
percentage of its maximum steady value, the outlet being connected to a circuit having specified flow parameters .
Response time depends on mainly five factors like electrical supply, type of the Valve ie. direct or pilot operated, fluid
handled, size of the moving parts of the main Valve mechanism, circuit in which the time is measured.

Response ON
Time taken for the pressure at the outlet port to reach 80% of the inlet pressure, from the moment electrical supply to the
solenoid is applied.

Response OFF
Time taken for the Valve to exhaust (pressure shall be 20% of the inlet pressure at its outlet port) from the moment supply to
the solenoid is cut off.

The response time of Rotex valve , under average condition is ;


Response ON Response OFF
• Small direct acting Valve 6-8 ms 8 - 10 ms
• Large direct acting Valve 6 - 10 ms 10 - 15 ms
• Diaphragm Valve ≤25 mm 300 ms 800 ms
• Diaphragm Valve ≥ 25 mm 600 ms 1800 ms
• 3/2, 5/2 Pilot operated Valve 15-50 ms 25-90 ms

12

398 Specifications are subject to change without notice


DEFINITION
Solenoid
It is an electrical part of a Valve which includes a bobbin wound with insulated copper wire, magnetic core, enclosure.
This creates a magnetic flux when energized.

Inrush current
When solenoid is energized with AC supply, the plunger moves and creates a momentary surge of current , known as inrush
current. Inrush current is observed in AC circuit and not in DC circuit.

Holding current
For AC supply Solenoid, Once plunger completes the travel and rest in a position, current drawn by Solenoid is known as
holding current.

Insulation class
The selection of insulation is a function of ambient temperature and the internal temperature rise of the solenoid. The
temperature limit for class F insulation is 155 ° C and for class H insulation, is 180 °
C. Rotex solenoid Valve is fitted with class F
insulation and class H is available as an option.

Temperature class
This is the highest temperature any part or the entire surface of an electrical device can reach under the most
unfavorable operating conditions, capable of igniting a surrounding explosive atmosphere.

Pick up voltage
Is a minimum voltage at which the Valve operates at minimum/ maximum operating pressure.

Drop down voltage


Is minimum voltage at which Valve does not remain actuated once energized

Temperature rise
It is a maximum temperature that the solenoid attains when the same is kept energized continuously.

Leakage port
When the unneeded fluid passing out from the out let port/ s or exhaust ports of the valve at energized/ de energized
condition of the Valve

Leakage joint
Is the fluid coming out from various joints of the valve assembly

TB
It is a weather proof Terminal Box solenoid having IP67 protection and integrated junction box for terminating cable.

FPJB
It is a Flame Proof solenoid suitable for hazardous locations having integrated Junction Box for termination of cable.

CONTINUOUS DUTY RATED SOLENOID

12
The solenoid when capable of operating continuously at higher rated voltage without affecting any of its parameter
is know as continuously rated solenoid.

Specifications are subject to change without notice 399


IDENTIFICATION
Valve label
Label on the ROTEX Solenoid Valve shows the following details.

(1) (1) Logo + Manufacture's Name and address


(2) Valve Type / Code
51400 = Valve Model
ROTEX AUTOMATION LIMITED Suffix = Nil
VADODARA-390 010, INDIA 6 = Orifice
FLUID CONTROL SYSTEM 2G = 1/4" / BSP
TYPE Port Connection
51400-6-2G-B5-S2 B5 = Body Material (SS 316)
WO No. ATM MFG S2 = Manual Override (Push and Turn)
18100377 2-10 01/2018 = Seal Material (Viton)
110 V = Solenoid Voltage
50 Hz = Current (AC)
(3) (2) (4) (5) 22 = Solenoid Construction
(Enclosure Plug in)
(1) H = Solenoid Class H Insulation
(3) ROTEX Work Order reference/
ROTEX AUTOMATION LIMITED Sr. No of the valve
VADODARA-390 010, INDIA (4) Operating Pressure
FLUID CONTROL SYSTEM (5) Month and Year of Manufacture
(6) Valve Symbol
CODE 51400-6-2G-B5-S2 (7) Media
2 3 ATM 2-10 (8) ATEX Ex. GOST mark for Valve (Non Electrical Part)
MEDIA AIR
(9) mark for ATEX and/ or PED compliance
DATE 1/2018
4 5 WO. No. 18100377
1

(6) (2) (4) (3) (5) (7)

(1)

ROTEX AUTOMATION LIMITED


VADODARA-390 010, INDIA

I M2 T6
TYPE II 2GD T6

WO No. ATM MFG

(3) (2) (9) (8) (4) (5)

Solenoid label
(1) (1) Logo + Manufacture's Name and address
(2) Solenoid Type
III = Solenoid Size III
ROTEX 110 V = Solenoid Voltage
VADODARA-390010, 50 Hz = Solenoid Current
INDIA 22 = Solenoid Construction (Plug in DIN)
III-110V-50Hz-22-H H = Solenoid Class H Insulation
04/2018-09/18 (3) ROTEX Plan No. and Month/Year of Manufacture
(4) Also refer to bottom of the solenoid for voltage, current
(2) (3) and other marking

12
Cable Entry
A solenoid with NPT (F) threading is marked “N” near the Cable entry and with Metric thread is marked
“M”. There is no marking for Solenoid having Cable entry with 3/4” ET.

NOTE : The product without label is out of warranty.

400 Specifications are subject to change without notice


SELECTION GUIDE : ORIFICE
ROTEX Solenoid Valves are modular in construction facilitating the user to select valves for various
Application from wide range and different construction of solenoids independently

SELECTION OF BASIC VALVE TYPE:

Depending on the application of valve in system select e.g a 2/2 Valve for ON/ OFF application, 3/2 valve for a single acting
actuator, mixing, diverting, Universal applications, 5/2 Valve for double acting actuator, cylinder etc.

VALVE SIZE and PORT CONNECTION :

The basic size of the valve is based on the kv (flow factor) of the valve

The kv Value is calculated through basic application information

(A) FLOW REQUIRED


I) Flow data
ii) Calculate flow from time in which a specific volume is to be delivered

(B) INLET PRESSURE - Po


C) Outlet Pressure-P1 In most of the cases the outlet pressure is not known, the same can be arrived at
from back pressure from equipment or based on the load on the equipment under operation
D) D P-Pressure drop across the valve (Po-P1)
E) Operating temperature of media
F) Specific gravity of media

The flow factor (kv) can be calculated using following methods for AIR, LIQUIDS, GASES.

(1) FOR AIR


Refer into the kv chart No.1 (Page 412) for AIR. Select the inlet pressure and differential pressure. The result from chart
yields flow in Nm3 /hr. For a value of flow factor kv=1, calculate the flow factor for the specific application.

Q (Application specific)
kv = --------------------------------
Q ( for kv=1)

Select the valve orifice size having calculated kv or nearest higher kv

TO FIND AN ORIFICE OF A VALVE


EXAMPLE 1
REQUIREMENT: To fill a volume of 100 liters, the inlet air pressure Po is 7 bar. The Volume to be filled in 20 seconds from
0-5 bar. P1 is 5 bar

First calculate m3/ hr at 5 bar

100 60x60
–----- X –---------- = 18m3/ hr.
20 1000

12

416 Specifications are subject to change without notice


SELECTION GUIDE : ORIFICE
So Nm3/ hr= 18 x 5=90m3 /hr
Pressure drop P across the valve is Po- P1=7-5 = 2 bar ( D P)
Now refer Chart No1 (Page 412)
For Pressure drop D P=2 bar at Po=7 bar the flow rate
Q(Nm3/hr/kv) for air at ambient temperature is 5.5 Nm3/hr/kv
90
Kv = ------- = 16.36
5.5
Nearest higher kv= 18 for an orifice of 7 mm
NOTE:
The exact formula for filling in and exhaust time for compressible fluid is different. The above example is most
conservative

EXAMPLE 2
REQUIREMENT: To operate a cylinder of Ø100 mm ; stoke 300 mm, to complete travel in 3 seconds, the
operating air pressure Po=5 bar

Flow require in Nm3/ hr


p
Volume of air = ----- x d2 x L
4
p 100x100 300
= ---- x -------------- x -------- = 0.0023571m3
4 1000x1000 1000

Volume of air per hour at 5 bar in m3/hr

60
= 0.0023571 x ------ x 60 = 2.82852m3/ hr
3
So Volume required at ambient temperature and pressure (Using Formula P1 V1 = P2 V2)

= 2.82852 x 5 = 14.1424 Nm3/ hr

Now refer Chart No.1 (Page 412) for D


P=0.1 bar at Po=5 bar the flow rate Q (Nm3/ hr/ kv for air at ambient
temperature is 1.2 Nm / hr
3

14.1424
kv = ------------ = 11.7855
1.2

Nearest kv= 12 for an orifice of 6 mm

12

Specifications are subject to change without notice 417


SELECTION GUIDE : ORIFICE
For any other gases and liquids, the kv is calculated as under :

(2) FOR GASES


Q = Flow rate in Nm3/hr
T = t+273 °C
t = Temperature in °C
Po = Inlet Pressure in atmospheric absolute in bar
D P = Differential pressure, bar
g = Density in kg/m3
kv = Flow factor of valve.

D P x Po x Y
(1) Q = 28.5 x kv x -----------------
g (t + 273)
Y = Correction factor

1- D P
(2) Y = ----------------
2 x Po
Y is a correction factor which depends upon the relation between the inlet pressure
and the pressure drop through the valve.
Y is always smaller than 1.
Select the valve orifice size having calculated kv or nearest higher kv.
Corresponding to a selected kv value for a given valve type, select an orifice for the valve.

(3) FOR WATER


Q = kv x D
P

For a known flow rate and differential pressure calculate kv using above formula and select the valve Orifice
size having calculate kv or nearest higher kv. Alternatively, you may refer Chart No.2 (Page 413)

To FIND AN ORIFICE OF A VALVE


EXAMPLE 1
To fill up an open to atmosphere tank with 10 litres of water in 5 seconds. The inline pressure Po of
water is at 10 kg/cm2 .

V
Q = ------ x 60
T

Q = Quantity of water in litre/min


V = Volume in litre to be filled in
T = Time in seconds

10
Q = ----- x 60 = 120 litre/min
5

Now Refer Chart No.2 (Page 413)

For Pressure drop D


P of 10 bar for 126 litre/min, the kv=40

Nearest higher kv=75 for an orifice of NW=16 mm

Alternatively, you may select kv= 38 for an orifice of NW=10mm,


Provided reduction in the flow (about 0.2% in this case) is acceptable
Actual kv in this case will be :

12 Q : kv P
D kv =
Q
P
D

418 Specifications are subject to change without notice


SELECTION GUIDE : ORIFICE

(4) FOR LIQUIDS

Q = kv X D P
-----
g
Q = Flow rate required in litre/min.
DP = Differential pressure in kg/cm2.
g= Specific gravity of the liquid at the media temperature.

Select the valve orifice size having calculated kv or nearest higher kv.

Corresponding to a selected kv value for a given valve type, select an orifice for the valve
Rotex can provide standard end connection for the selected orifice e.g. 6 mm orifice can be provided with 1/4” BSP/ NPT to
3/4” BSP/ NPT. The valve can also be provided with Flanged End, ANSI B16.5 (or as per your specification) end connection.
The end connection selected should not be smaller than the orifice size. The valves can be sub-base mounted for special
application

As a user, by selecting an appropriate orifice and end connection, you


- select a product rightly suited to application
- select an economically most viable solution
- can save piping cost by selecting end connection matching nearest to the existing piping system

12

Specifications are subject to change without notice 419


SELECTION GUIDE : BODY MATERIAL AND INTERNALS
ROTEX offers a wide range of body material and internals to suit the media as well as environment. Users are
recommended to use following guide while selecting the body material of the Solenoid Valve for their application. As a
standard, Aluminum body valve is supplied with internals of Aluminum, Brass and SS. A Brass body valve is supplied with
internals of Brass and SS. SS Body valve is supplied with internals of SS.

ROTEX offers FOUR basic body materials :

1) ALUMINUM HARD ANODIZED


- Treatment produces corrosion resistant, wear resistant and a tough surface
- Increase in surface strength results in stronger threads on ports and mountings
- Achieve surface hardness
- Improves surface finish due to inherent nature of the process
- Port connection BSP/ NPT

2) BRASS (Extruded)
- Grade as per IS 319. Extruded Brass is equivalent to forged Brass specification
- Most suitable for applications for Water, Oxygen Service
- ROTEX strongly recommends that the surface treated Aluminum out perform Brass for most of
the application
- Port connection usually NPT

3) STAINLESS STEEL (SS 316)


- Ideal for highly corrosive environment involving strong Acid and Alkaline environment
- Ideal for instrumentation application
- Ideal for high temperature application
- Port connection normally NPT, except for 2/2, inline diapharm or piston actuated valve

4) PTFE BODY
- All working parts are fully lined
- Ideal for corrosive media
- Not suitable for frequent changes in mountings

5) PLASTIC BODY
- Suitable for low and medium temperature, corrosive media or commercial application
- Maximum media temperature up to 80 °C
- Not suitable for frequent changes in mountings

Following options are available for selection of Body Material and Internals :
Body Internals Code Remarks
Aluminium Standard øInternal Components of Aluminium, Brass, SS 316
Aluminium SS 316 B1 Internal Components of SS 316
Brass Standard B2 Internal Components of Brass, SS 316
SS 316 Standard B5 Internal Components of SS 316
Stainless Steel, Cast SS 316 B12 Internal SS 316

12

420 Specifications are subject to change without notice


SELECTION GUIDE : SEALS
ROTEX offers variety of solution in seals for various applications. The seals are to be selected on the basis of their
compatibility to media., temperature and pressure etc. Seal material will be generally selected by Rotex depending upon
media, media pressure and temperature. For best results, it will be better to consult Rotex

(1) NBR (Buna-N, Nitrile etc.)


Fitted as a standard in ROTEX products
Suitable for all general application up to a ambient/ media temperature of -25 °C to 75 °C

(2) EPDM (Ethylene Propylene Di-Methyl) (S1)


Excellent for Nuclear applications, especially for exposure to Radiation. (GRADE R13)
Moderate corrosion resistance
Excellent shelf life
Ideal for high temperature air, water and steam up to -60 °C to 140 °C

(3) Viton (S2)


Ideal for high temperature media/ environment
Ideal for corrosive applications
Excellent shelf life
Media temperature up to -20 °C to 160 °C

(4) NEOPRENE (S3)


Ideal for use with oils
Good shelf life
Suitable for refrigerant application
Should be opted for hydro carbon media
Media temperature -30°C to 100 °C

(5) F.SILICON (S19)


Ideal for high temperature
Good for medical application
Good corrosion resistance
Media Temperature up to -60 °C to 190 °C

(6) PTFE (S4)


Ideal for most media
Do not use as a standard unless application really calls for PTFE
Nearly unlimited shelf life
Not recommended for Radiation Exposure
Media temperature up to -70 °C to 200 °C

(7) SAPPHIRE (S6)


Excellent corrosion resistance
Ideal for high temperature up to 350 °C
Selected for service temperature above -196 °C + 350 °C

ROTEX valve can be provided with seat and seal material other than listed above.

(8)
(8)Viton
VitonGLT
GLT(S2G)
(S2G)
Ideal for high temperature media/ environment
Ideal for corrosive applications
Excellent shelf life
Media temperature up to -40 °C to 160 °C 12
(8)
(9)Viton
HytrelGLT
(S11)
(S2G)
Used for replacing NBR diaphragm.
Excellent Resistance to most Chemicals and provides long life.
Media temperature up to 0 °C to 80 °C 421
Specifications are subject to change without notice 3
SELECTION GUIDE : MANUAL OVERRIDE

PUSH AND TURN (M6) UP TO 20 bar


With this manual override, valve can be operated by pushing Manual
Override. The valve will reset when Manual Override is released. The valve
can be latched by pushing Manual Override and turning Clockwise(CW). To
release, to turn Manual Override anticlock wise(ACW). Suitable up to 20 bar
pressure

PUSH (M8) UP TO - 20 bar


With this type of Manual Override the valve can be actuated by pushing
Manual Override. This type of Manual Override is supplied for double
solenoid valve. The valve will reset when Manual Override is released.
Suitable up to 20 bar pressure

PUSH AND TURN (M2) WITH KNOB UP TO 20 bar


This Manual Override is same as M6 however it has a knob for operating
Manual Override
This type of manual override can be opted for valve type which can be
supplied with manual override type M6 or M8

PUSH WITH KNOB (M8K) UP TO 20 bar


Same as M8 but with knob

12

422 Specifications are subject to change without notice


SELECTION GUIDE : MANUAL OVERRIDE

LEVER TYPE (M5) UP TO 40 bar


This is momentary type Manual Override suitable up to 40 bar pressure. The
valve can be actuated by pressing lever. Releasing lever shall reset valve

MALA (M12 M17) UP TO 40 bar


This is a stayput type Manual Override. Suitable up to 40 bar pressure. The
valve can be actuated by turning lever CW, and to release turn lever ACW
The manual override operated by hand (MR). This manual override can
be provided with knob. (M17)

HIGH PRESSURE LEVER TYPE (M4) UP TO 150 bar


This is similar to M5 but suitable for pressure up to 150 bar

HIGH PRESSURE MALA (M11 M16) UP TO 150 bar


This is similar to M12 but suitable for pressure up to 150 bar
Select (M16) when this type of manual override is required with knob

KNOB TYPE LATCHED MANUAL OVERRIDE (M7 M13) UP TO 20 bar


M7 (For Latch Valve): -In normal condition manual override is to be kept in horizontal.
To latch the valve, Turn Manual Override anti clock wise. Then brings to normal
position. To delatch the valve, Turn the Manual Override clock wise. Then bring to
normal position.
M13 (Manual Reset OFF Valve): -In normal condition Manual Override is to be kept in
horizontal. To delatch the valve, turn the Manual Override clock wise. Then bring to
normal position.
12

Specifications are subject to change without notice 423


CLASS OF INSULATION AND SOLENOID LIFE
Life of the Solenoid depends on ambient temperature, duty cycle, temperature rise and class of insulation used for the
solenoid. Temperature rise depends on design, current density and insulation system of the coil. Rotex ensures that for all
its design of the coil, temperature rise above ambient is less than 70 °C
As per IS 4800 standard, insulation system is designed for minimum life of for 20000 Hours When used continuously. Using
the half life decay principle, every 10 °C reduction of the coil temperature, twice the life can be extra polated. Considering
worst temperature rise of the coil at 1.2 times the rated voltage, continuously energized coil shall be less than 70 °C. For a
ambient temperature of 55 °C, the maximum temperature of the coil will be 55 + 70 = 125 °C
For a Solenoid having class F insulation minimum life expected shall be as under:
20000 Hours at 155 °C
40000 Hours at 145 °C
80000 Hours at 135 °C
160000 Hours at 125 °C
Which means, Life of a Continuously energized Solenoid having Class F Insulation, i.e. (ambient of 55 °C) is Minimum of
160000 Hrs ie 18 Yrs.
In case if more life is expected then Solenoid with better insulation or lower temperature rise is to be used (e.g. Low Power
Solenoid)

ELECTRICAL SPECIFICATION
STANDARD
CURRENT AC DC AC/ DC
PICK UP (Cold <
_ 70% <
_ 70% <
_ 70%
% of rated voltage)

DROP DOWN <


_ 50% <
_ 10% <
_ 10%
(% of rated voltage)
RESPONSE ‘ON’ <
_ 10ms <
_ 8ms <
_ 8ms
VOLTAGE VARIATION ± 20% ± 20% ± 20%

ELECTRICAL SPECIFICATION FOR SOLENOID FEATURES LC, LW, ML


CURRENT AC DC
PICK UP <
_ 80% <
_ 80%
(% of rated voltage)

DROP DOWN <


_ 10% < 10%
(% of rated voltage)
RESPONSE ‘ON’ <
_ 10ms <
_ 8ms
VOLTAGE VARIATION ±10% ±10%

POWER (Watt)
SOLENOID SIZE AC DC
8 6 5
10 6 8
13 0.3 0.3
14 6 8
18 13 13

12 HUMIDITY

95% rh 95 °C

424 Specifications are subject to change without notice

You might also like