BACnet Application Map TME27091 Release Date: 07/2023
InRow® RC Chilled Water Air Conditioners, 300 mm
This document details the BACnet objects and properties supported by the
application firmware v6.0.0 and higher (v6.0.0+), which is available on the APC or
Schneider Electric Web site.
What’s in This Document
Additional Information ................................................................................1
Analog Value Objects .................................................................................2
Binary Value Objects (alarms; 0=Inactive, 1=Active) ............................4
Binary Value Objects (data) .......................................................................6
Character String Value Objects ................................................................7
Notification Class Objects..........................................................................8
Index .............................................................................................................8
Additional Information
• Information on the BACnet protocol specification can found at www.bacnet.
org.
• Schneider Electric recommends EcoStruxure Building Operation software
(formerly known as StruxureWare Building Operation/SBO) for integrated
monitoring, control and management of BACnet-enabled devices.
• See the Network Management Card 2 User Guide available on the APC
website for more information on configuring the NMC 2 for BACnet.
• The application firmware v2.4.2.1+ for InRow CW ACRC301S and
ACRC301H cooling units supports BACnet/IP only.
Schneider Electric As standards, specifications, and design
35 rue Joseph Monier change from time to time, please ask for
92500 Rueil Malmaison - confirmation of the information given in this
France publication.
+ 33 (0) 1 41 29 70 00 © 2023 – 2023 Schneider Electric. All rights
+ 91 9886115853 reserved.
www.schneider-electric.com
InRow® RC Chilled Water Air Conditioners, 300 mm Analog Value Objects
Analog Value Objects
Index ID Name Description Options Access
0 79691776 On or Standby On / Standby 1=Standby, 2=On RW
1 79691777 Idle on Leak Detect Idle on Leak Detect 1=No, 2=Yes RW
2 79691778 Operating Mode Operating Mode 1=Standby, 2=On, 3=Idle, 4= RO
Maintenance
3 79691779 Idle On Cool Fail Idle On Cool Fail 1=No, 2=Yes RW
4 79691780 Power Source Power Source 1=Single, 2=Dual RW
5 79691781 Chilled Water Valve Chilled Water Valve 1=Automatic, 2=Open RO
Control Control
6 79691782 Bypass Valve Position Bypass Valve Position 1=Open, 2=Closed RW
7 79691783 Air Filter Type Air Filter Type 1=Standard, 2=Pleated RW
8 79691784 Alarm On Standby Alarm On Standby 1=No, 2=Yes RW
9 79691785 Auto Recover Cool Fail Auto Recover Cool Fail 1=No, 2=Yes RO
32 79691808 Circulation Pump Circulation Pump Model 1=None, 2=Stratos, 3=Stratos RO
Model Maxo
10 79691786 Air Filter Service Alarm Air Filter Service Alarm 1=Disable, 2=Enable RW
Enable Enable
11 79691787 Unit Service Alarm Unit Service Alarm Enable 1=Disable, 2=Enable RO
Enable
12 79691788 Reset Air Filter Service Reset Air Filter Service 1=No, 2=Yes RW
Alarm Alarm
13 79691789 Standby Input Normal Standby Input Normal 1=Open, 2=Closed RW
State State
14 79691790 Standby Input State Standby Input State 1=Open, 2=Closed RO
15 79691791 Output State_1 Output State 1 1=Abnormal, 2=Normal RO
16 79691792 Output State_2 Output State 2 1=Abnormal, 2=Normal RO
17 79691793 Output State_3 Output State 3 1=Abnormal, 2=Normal RO
18 79691794 Output State_4 Output State 4 1=Abnormal, 2=Normal RO
19 79691795 Leak Detector_1 Leak Detector 1 1=No Leak, 2=Leak Detected RO
20 79691796 Leak Detector_2 Leak Detector 2 1=No Leak, 2=Leak Detected RO
21 79691797 Leak Detector_3 Leak Detector 3 1=No Leak, 2=Leak Detected RO
22 79691798 Leak Detector_4 Leak Detector 4 1=No Leak, 2=Leak Detected RO
23 79691799 Active Power Source Active Power Source 1=Primary, 2=Secondary, 3=No RO
Mains
24 79691800 Active Flow Control Active Flow Control Status 1=Under, 2=Okay, 3=Over, 4=N/A RO
Status
25 79691801 Clear Active Alarms Clear Active Alarms 1=No, 2=Yes RW
26 79691802 Reset Unit Energy Reset Unit Energy 1=No, 2=Yes RW
27 79691803 Configuration Type Configuration Type 1=RACS, 2=HACS, 3=In-Row, 4= RO
CACS
28 79691804 Airflow Control Airflow Control 1=Automatic, 2=60%, 3=70%, 4= RW
80%, 5=90%, 6=100%
29 79691805 Delta-T Setpoint Delta-T Setpoint 1=10F/5.6C, 2=15F/8.3C, 3=20F/ RW
11.1C, 4=25F/13.9C, 5=30F/
16.7C, 6=35F/19.4C, 7=40F/
22.2C
30 79691806 Active Flow Control Active Flow Control Bias 1=Positive, 2=Slightly Positive, 3= RO
Bias Zero, 4=Slightly Negative, 5=
Negative
31 79691807 Active Flow Control Active Flow Control Lamp 1=Off, 2=On RW
Lamp Test Test
2 TME27091
Analog Value Objects InRow® RC Chilled Water Air Conditioners, 300 mm
TME27091 3
InRow® RC Chilled Water Air Conditioners, 300 mm Binary Value Objects (alarms; 0=Inactive, 1=Active)
Binary Value Objects (alarms; 0=Inactive, 1=Active)
Index ID Name Description Access
0 20971520 BN3902 Internal Communication Error RO
1 20971521 BN3904 Unexpected Number of Units in Group RO
2 20971522 BN3906 Cool Fail RO
3 20971523 BN3908 Rack Temperature High Violation RO
4 20971524 BN390A Air Filter Clogged RO
5 20971525 BN390C Upper Return Air Sensor Fault RO
6 20971526 BN390E Lower Return Air Sensor Fault RO
7 20971527 BN3910 Upper Supply Air Sensor Fault RO
8 20971528 BN3912 Lower Supply Air Sensor Fault RO
9 20971529 BN3914 Rack Temperature Sensor 1 Fault RO
10 20971530 BN3916 Rack Temperature Sensor 2 Fault RO
11 20971531 BN3918 Rack Temperature Sensor 3 Fault RO
12 20971532 BN391A Rack Temperature Sensor 4 Fault RO
13 20971533 BN391C Fan 1 Fault RO
14 20971534 BN391E Fan 2 Fault RO
15 20971535 BN3920 Fan 3 Fault RO
16 20971536 BN3922 Fan 4 Fault RO
17 20971537 BN3924 Fan 5 Fault RO
18 20971538 BN3926 Fan 6 Fault RO
19 20971539 BN3928 Fan 7 Fault RO
20 20971540 BN392A Fan 8 Fault RO
21 20971541 BN392C Chilled Water Valve Actuator Fault RO
22 20971542 BN392E Water Detected Fault RO
23 20971543 BN3930 Water Detected Shutdown RO
24 20971544 BN3932 Check Condensate Management System RO
25 20971545 BN3934 Chilled Water Flow Meter Fault RO
26 20971546 BN3936 Entering Chilled Water Temperature High Violation RO
27 20971547 BN3938 Entering Chilled Water Temperature Sensor Fault RO
28 20971548 BN393A Leaving Chilled Water Temperature Sensor Fault RO
29 20971549 BN393C Condensate Pan Full RO
30 20971550 BN393E Primary Power Source Fail RO
31 20971551 BN3940 Secondary Power Source Fail RO
32 20971552 BN3942 Fan Power Supply 1 Fault RO
33 20971553 BN3944 Fan Power Supply 2 Fault RO
34 20971554 BN3946 Air Filter Run Hours Violation RO
35 20971555 BN3948 Supply Air High Temperature Violation RO
36 20971556 BN394A Return Air High Temperature Violation RO
37 20971557 BN394C Filter DP Sensor Failure RO
38 20971558 BN394E Standby Due to Input Contact RO
39 20971559 BN3950 Chilled Water Valve Control Not Set to Auto RO
40 20971560 BN3952 EcoAisle Door Open RO
41 20971561 BN3954 Unexpected Number of Active Flow Controllers RO
4 TME27091
Binary Value Objects (alarms; 0=Inactive, 1=Active) InRow® RC Chilled Water Air Conditioners, 300 mm
Index ID Name Description Access
42 20971562 BN3956 Insufficient Airflow RO
43 20971563 BN3958 Active Flow Controller Sensor Fault RO
44 20971564 BN395A Unit Service Required RO
45 20971565 BN395C Humidity Sensor Fault RO
46 20971566 BN395E Coil Condensation Possible RO
47 20971567 BN3960 Controller Power Supply 1 Fault RO
48 20971568 BN3962 Controller Power Supply 2 Fault RO
49 20971569 BN3964 Coil Chilled Water Temperature Sensor Fault RO
50 20971570 BN3966 Fan Power Supply 1 Current Sense Fault RO
51 20971571 BN3968 Fan Power Supply 2 Current Sense Fault RO
52 20971572 BN396A Factory Configuration Not Completed RO
53 20971573 BN396C Unit is in Maintenance Mode RO
54 20971574 BN396E Unexpected Number of Rack Inlet Temperature RO
Sensors
55 20971575 BN3970 Unexpected Number of Leak Detectors RO
56 20971576 BN3972 Output Relay 1 Active RO
57 20971577 BN3974 Output Relay 2 Active RO
58 20971578 BN3976 Output Relay 3 Active RO
59 20971579 BN3978 Output Relay 4 Active RO
60 20971580 BN397A Circulation Pump Fault RO
61 20971581 BN397C Standby Due to User Action RO
62 20971582 BN397E Circulation Pump Communication Loss RO
63 20971583 BN3980 Circulation Pump Warning Present RO
64 20971584 BN3982 Circulation Pump Needs Service RO
TME27091 5
InRow® RC Chilled Water Air Conditioners, 300 mm Binary Value Objects (data)
Binary Value Objects (data)
None
6 TME27091
Character String Value Objects InRow® RC Chilled Water Air Conditioners, 300 mm
Character String Value Objects
Index ID Name Description Max. Chars Access
0 167772160 Model Number Model Number 19 RO
1 167772161 Serial Number Serial Number 19 RO
2 167772162 Firmware Revision_1 Firmware Revision (Executing) 19 RO
3 167772163 Firmware Revision_2 Firmware Revision (Newest) 19 RO
4 167772164 Firmware Revision_3 Firmware Revision (Oldest) 19 RO
5 167772165 Firmware Revision_4 Firmware Revision 19 RO
(Bootloader)
6 167772166 Hardware Revision Hardware Revision 7 RO
TME27091 7
InRow® RC Chilled Water Air Conditioners, 300 mm Notification Class Objects
Notification Class Objects
Index Bacnet ID BACnet Name Description Access
0 62914560 DefaultNotifier Default Notification Class RW
Index
BACnet Name Object Type Table Position BACnet Index
Active Flow Control Multi-State Value 32 30
Bias
Active Flow Control Multi-State Value 33 31
Lamp Test
Active Flow Control Multi-State Value 26 24
Status
Active Power Source Multi-State Value 25 23
Air Filter run hours Analog Value 46 43
Air Filter Service Multi-State Value 12 10
Alarm Enable
Air Filter Service Analog Value 9 8
Interval
Air Filter Type Multi-State Value 8 7
Airflow Analog Value 29 27
Airflow Control Multi-State Value 30 28
Alarm On Standby Multi-State Value 9 8
Altitude Analog Value 53 50
Auto Recover Cool Multi-State Value 10 9
Fail
BN3902 Binary Value 1 0
BN3904 Binary Value 2 1
BN3906 Binary Value 3 2
BN3908 Binary Value 4 3
BN390A Binary Value 5 4
BN390C Binary Value 6 5
BN390E Binary Value 7 6
BN3910 Binary Value 8 7
BN3912 Binary Value 9 8
BN3914 Binary Value 10 9
BN3916 Binary Value 11 10
BN3918 Binary Value 12 11
BN391A Binary Value 13 12
BN391C Binary Value 14 13
BN391E Binary Value 15 14
BN3920 Binary Value 16 15
BN3922 Binary Value 17 16
BN3924 Binary Value 18 17
BN3926 Binary Value 19 18
8 TME27091
Index InRow® RC Chilled Water Air Conditioners, 300 mm
BACnet Name Object Type Table Position BACnet Index
BN3928 Binary Value 20 19
BN392A Binary Value 21 20
BN392C Binary Value 22 21
BN392E Binary Value 23 22
BN3930 Binary Value 24 23
BN3932 Binary Value 25 24
BN3934 Binary Value 26 25
BN3936 Binary Value 27 26
BN3938 Binary Value 28 27
BN393A Binary Value 29 28
BN393C Binary Value 30 29
BN393E Binary Value 31 30
BN3940 Binary Value 32 31
BN3942 Binary Value 33 32
BN3944 Binary Value 34 33
BN3946 Binary Value 35 34
BN3948 Binary Value 36 35
BN394A Binary Value 37 36
BN394C Binary Value 38 37
BN394E Binary Value 39 38
BN3950 Binary Value 40 39
BN3952 Binary Value 41 40
BN3954 Binary Value 42 41
BN3956 Binary Value 43 42
BN3958 Binary Value 44 43
BN395A Binary Value 45 44
BN395C Binary Value 46 45
BN395E Binary Value 47 46
BN3960 Binary Value 48 47
BN3962 Binary Value 49 48
BN3964 Binary Value 50 49
BN3966 Binary Value 51 50
BN3968 Binary Value 52 51
BN396A Binary Value 53 52
BN396C Binary Value 54 53
BN396E Binary Value 55 54
BN3970 Binary Value 56 55
BN3972 Binary Value 57 56
BN3974 Binary Value 58 57
BN3976 Binary Value 59 58
BN3978 Binary Value 60 59
BN397A Binary Value 61 60
BN397C Binary Value 62 61
TME27091 9
InRow® RC Chilled Water Air Conditioners, 300 mm Index
BACnet Name Object Type Table Position BACnet Index
BN397E Binary Value 63 62
BN3980 Binary Value 64 63
BN3982 Binary Value 65 64
Bypass Valve Position Multi-State Value 7 6
Chilled Water Flow Analog Value 23 22
Chilled Water Valve Multi-State Value 6 5
Control
Chilled Water Valve Analog Value 16 15
Position
Circulation Pump Flow Analog Value 26 56
Circulation Pump Multi-State Value 11 32
Model
Circulation Pump Analog Value 34 57
Power
Circulation Pump run Analog Value 51 48
hours
Circulation Pump Analog Value 33 31
Speed
Clear Active Alarms Multi-State Value 27 25
Coil Chilled Water Analog Value 25 24
Temperature
Condensate Pump run Analog Value 49 46
hours
Configuration Type Multi-State Value 29 27
Cool Demand Analog Value 27 25
Cool Output Analog Value 28 26
Cool Setpoint Analog Value 55 52
DefaultNotifier Notification Class 1 0
Delta-T Setpoint Multi-State Value 31 29
Dew Point Analog Value 24 23
Temperature
Entering Chilled Water Analog Value 14 13
Temperature
Entering Chilled Water Analog Value 8 7
Temperature High
Threshold
Fan Power Supply run Analog Value 47 44
hours_1
Fan Power Supply run Analog Value 48 45
hours_2
Fan run hours_1 Analog Value 38 35
Fan run hours_2 Analog Value 39 36
Fan run hours_3 Analog Value 40 37
Fan run hours_4 Analog Value 41 38
Fan run hours_5 Analog Value 42 39
Fan run hours_6 Analog Value 43 40
Fan run hours_7 Analog Value 44 41
Fan run hours_8 Analog Value 45 42
Fan Speed Analog Value 30 28
Filter Differential Analog Value 13 12
Pressure
10 TME27091
Index InRow® RC Chilled Water Air Conditioners, 300 mm
BACnet Name Object Type Table Position BACnet Index
Firmware Revision_1 Character String 3 2
Firmware Revision_2 Character String 4 3
Firmware Revision_3 Character String 5 4
Firmware Revision_4 Character String 6 5
Group Airflow Analog Value 37 34
Group Cool Demand Analog Value 35 32
Group Cool Output Analog Value 36 33
Hardware Revision Character String 7 6
Idle On Cool Fail Multi-State Value 4 3
Idle on Leak Detect Multi-State Value 2 1
Leak Detector_1 Multi-State Value 21 19
Leak Detector_2 Multi-State Value 22 20
Leak Detector_3 Multi-State Value 23 21
Leak Detector_4 Multi-State Value 24 22
Leaving Chilled Water Analog Value 15 14
Temperature
Maximum Chilled Analog Value 2 1
Water Flow
Maximum Fan Speed Analog Value 57 54
Maximum Rack Inlet Analog Value 21 20
Temperature
Minimum Rack Inlet Analog Value 22 21
Temperature
Model Number Character String 1 0
Number of Active Flow Analog Value 58 55
Controllers
Number of Leak Analog Value 4 3
Detectors in Unit
Number of Rack Inlet Analog Value 3 2
Temperature Sensors
in Unit
Number of Units in Analog Value 54 51
Group
On or Standby Multi-State Value 1 0
Operating Mode Multi-State Value 3 2
Output State_1 Multi-State Value 17 15
Output State_2 Multi-State Value 18 16
Output State_3 Multi-State Value 19 17
Output State_4 Multi-State Value 20 18
Percent Glycol Analog Value 52 49
Power Source Multi-State Value 5 4
Rack Inlet Analog Value 5 4
Temperature High
Threshold
Reset Air Filter Multi-State Value 14 12
Service Alarm
Reset Unit Energy Multi-State Value 28 26
Return Air Analog Value 12 11
Temperature
TME27091 11
InRow® RC Chilled Water Air Conditioners, 300 mm Index
BACnet Name Object Type Table Position BACnet Index
Return Air Analog Value 7 6
Temperature High
Threshold
Serial Number Character String 2 1
Standby Input Normal Multi-State Value 15 13
State
Standby Input State Multi-State Value 16 14
Startup Delay Analog Value 1 0
Supply Air Setpoint Analog Value 56 53
Supply Air Analog Value 11 10
Temperature
Supply Air Analog Value 6 5
Temperature High
Threshold
Unit Energy Analog Value 32 30
Unit Power Analog Value 31 29
Unit Rack Inlet Analog Value 17 16
Temperatures_1
Unit Rack Inlet Analog Value 18 17
Temperatures_2
Unit Rack Inlet Analog Value 19 18
Temperatures_3
Unit Rack Inlet Analog Value 20 19
Temperatures_4
Unit run hours Analog Value 50 47
Unit Service Alarm Multi-State Value 13 11
Enable
Unit Service Alarm Analog Value 10 9
Interval