Transmission & Distribution of Air: Fan Systems
Transmission & Distribution of Air: Fan Systems
Transmission & Distribution of Air: Fan Systems
A fan can be used to deliver air to one or more places, to remove air from
one or more areas, or both. Delivery or removal can be achieved by connect-
ing the necessary number of branch ducts to a main duct. In this chapter the
principles of fluid flow are applied to the problem of proportioning the system
so that the required flow will be transmitted through the various duct
branches, and to the equally important problem of achieving the necessary
distribution in the rooms or spaces being served. Additional details of various
systems are given in the chapters dealing with specific applications. Refer to
the chapter on fan systems for information on the relationship of system
characteristics to fan characteristics.
çæ V äã = ç 880x ρ C F ä 13
å 1000â æå fρ t C ãâ
opt m m m
. (3.1)
a 0 p
i
F=
1 6
1− 1+ i − n
(3.2)
The expression, as given assumes negligible exit loss and perfect fan
efficiency so that it yields only approximate results even for simple straight-
run systems. For more complex systems, it is customary to use different
design velocities in the different branches as required to equalize friction.
The inclusion of fittings and other duct elements such as heaters, etc., which
reduce the fraction of the total system pressure loss due to straight-duct
friction, reduces the accuracy of the results of Equation 3.1.
Usually, the mains and branches will transmit a constant volume of air at
all times. Whenever a system is expected to handle a variable volume, the
duct sizes should reflect the anticipated operation. The fan in such cases must
be capable of delivering the maximum amount even if the ducts are sized for
some lesser amount.
Another special situation where the optimum duct sizes can be based on
reduced volume is that of a double-duct system. Even though each space
served may receive a constant volume of conditioned air (hot plus cold), the
amounts handled by the hot and cold mains individually may fluctuate. As
the number of spaces increases, there is a decrease in the probability that
either main will be required to deliver the maximum amount of conditioned
air at any particular time. The probability may be even further reduced by
using controls to reset the temperature of the air in one or both mains. Ac-
cording to Wilson1 some designers take this into account by arbitrarily sizing
the hot mains for 75% of the total possible capacity. The cold mains are
generally sized to handle 100% of the demand in the extreme downstream
section. Successive upstream sections, each with several branches, can be
sized for a progressively smaller percentage of the demand. Typical values
may be 90%, 80%, and 70% for the third, second, and first quarter sections.
The total pressure requirement must be calculated on the basis of maximum
demand through all sections. The fan and the volume controls must be so
designed that operation under both full and partial load is satisfactory. Refer
to the air-conditioning chapter for a discussion of design and operating
problems.
The optimum velocity based on the owning and operating costs of the
ducts alone is not always the controlling factor in determining duct sizes. In
the so-called conventional systems, which do not use elaborate sound treat-
ment, duct velocities can be limited to rather low values by noise considera-
tions. On the other hand, very high velocities may be justified in cases where
the savings in building costs, etc., due to reduction in duct size more than
offset the increase in power required to move the air through the system.
1
C. M. Wilson, "Handbook on High Velocity Air Distribution Design," Anemostat Corp. of
America, New York, Reprinted from Heating, Piping and Air Conditioning, Chicago,
November 1954, pp. 94-108.
Conventional High-Velocity
Public Industrial Commercial
Duct Residences Buildings Buildings Buildings
Element Norm. Max. Norm. Max. Norm. Max. Norm. Max.
Main Ducts 700 1200 1000 1600 1500 2200 2500 6000
Branch Ducts 600 1000 800 1300 1000 1800 2000 4500
Outside Air Intakes 500 800 500 900 500 1200 600 1000
Filters 250 300 300 350 350 350 350 350
Heating Coils 450 500 500 600 600 700 600 700
Air Washers 500 500 500 500 500 500 500 500
Cooling Coils 450 450 500 500 500 600 500 500
Adapted from the data of ASHRAE: ASHRAE Guide and Data Book - Equipment, New York,
1969, p. 38.
Figure 3.1
Round Pipe Sizes for the Equal-Friction-per-Foot-of-Length Method -
Figure 3.2
Round Pipe Sizes for the Equal-Friction-per-Foot-of-Length Method
Adapted from the data of R. Jorgensen: "New Chart Sizes Ducts Directly Static Regain
Method," Heating, Piping and Air Conditioning, Chicago, October 1958. pp. 107-108.
f
L2
D2
1
pv 2 = η pv1 − pv 2 . 6 (3.3)
Figure 3.3 is based on this equation using a value of 0.02 for the coefficient of
friction f and a value of 0.5 for the effectiveness η of the recovery process.
The value of 0.5 for the recovery effectiveness is reasonable for most applica-
tions, but the actual value may be as high as 0.7 or 0.8 under best conditions.
The friction coefficient is also subject to considerable variation, but results
obtained by using this chart are usually sufficiently accurate. When elbows
are encountered in any length of main, the appropriate equivalent length of
straight duct can be added to the actual length of straight duct.
Round Ducts
In all methods of design, the equation of continuity can be used to deter-
mine the duct size from the capacity and the velocity. Accordingly, the ratio
of duct sizes Da Db is related to the capacity ratio Qû a Qû b and the velocity
ratio Va Vb by
Da Qû çæ äã çæ V äã
12 12
= a
å â åV â
b
(3.4)
Db Qû b a
çæ p äã = çæ L äã çæ V äã çæ D äã çæ ρ äã çæ c äã .
1.0 2 .0 − n 1.4 − n 1.0 − n
å p â å L â åV â å D â å ρ â å c â
La a a b a a
(3.5)
Lb b b a b b
The various symbols have their usual meanings, and the values of n and c
for numerous roughness conditions can be determined from Table 2.5 in the
chapter on fluid flow. This expression yields approximately the same results
as the Colebrook equation and is considerably easier to use. Equation 3.5 is
.
equivalent to Equation 2.78 and further states that the coefficient of friction
f is inversely proportional to a constant times the Reynolds number raised to
the n power and the roughness ratio raised to the 0.4 − 2n power. The
velocity pressure is, of course, proportional to the velocity squared as
indicated by
pVa V çæ äã . 2
pVb
= a
Vb å â (3.6)
The graphical solution of this equation for average roughness conditions (that
is, n =.16 ) is given in Figures 3.1 and 3.2. Similar charts can be drawn for
other values of n . However, suitable engineering accuracy can usually be
obtained by using these charts. Reasonably accurate results can also be
obtained by reading duct sizes directly from Figure 2.15 along the appropriate
vertical line.
Another convenient relation can be derived from Equation 3.5 for uniform
gas composition and equal friction for unequal lengths L of duct:
çæ L äã = çæ D äã çæ V äã1.4 − n 2 .0 − n
çD ä
=æ ã
5.4 − 3n
å L â å D â åV â åD â
a a b a
. (3.8)
b b a b
çæ D äã = çæ L äã 1 1 5.4 − 3n 6
çL ä
≈æ ã
15
åD â åL â åL â
a a a
. (3.9)
b b b
This, too, is appropriate only for turbulent flow, and the final approximation
usually gives reasonably accurate results.
The ratio of the pressure losses for any two capacities can also be found
from the appropriate velocity ratios and diameter ratios as indicated by
çæ p äã = çæ V äã çæ D äã 2 .0 − n 1.4 − n
å p â åV â å D â
La a b
. (3.11)
Lb b La
çæ p pva äã çæ äã çæ D äã
V
−n 1.4 − n
çD ä
≈æ ã
1.4 − n
åp â å â åD â
= a
åD â
La b b
. (3.12)
Lb pVb Vb a a
The final approximation should be used only when the velocities are nearly
constant.
Total pressure losses can also be expressed as a per cent or fraction of a
velocity head pV p L . This is the reciprocal of the number of velocity heads.
For laminar flow
çæ p äã = çæ L äã çæ V äã çæ D äã çæ µ äã . 2
å p â å L âåV âå D â å µ â
La a a b a
(3.13)
Lb b b a b
çæ D äã = çæ V äã = çæ Qû äã
12 14
å D â å V â å Qû â
a a a
. (3.14)
b b b
For unequal lengths and equal friction, the length and diameter ratios are
related as indicated in
çæ L äã = çæ D äã çæ V äã = çæ D äã , and
2 4
å L â å D â åV â å D â
a a a a
(3.15)
b b b b
çæ D äã = çæ L äã . 14
åD â åL â
a a
(3.16)
b b
For constant capacity and uniform gas composition, diameters and total
pressure losses are related as indicated by
çæ D äã = çæ p äã 14
åD â åp â
a Lb
. (3.17)
b La
For equal lengths and uniform gas composition, the total pressure loss
ratio can be found from velocity and diameter or from capacity ratios as
indicated by
çæ p äã = çæ V äã çæ D äã = çæ V äã çæ Qû äã .
2 2
å p â å V â å D â å V â å Qû â
La a b a b
(3.18)
Lb b a b a
çæ p äã çæ äã
pV Qû
åp â å â
= b .
La
(3.19)
Lb pV Qû a
Equations 3.13 through 3.19 are all for laminar flow and, consequently,
limited in application.
Although Equations 3.5 through 3.19 are based on the flow of air through
straight ducts, some can also be used to proportion systems involving elbows.
For easy bends, where it is safe to assume that the loss is equal to a certain
number of diameters regardless of size, the ratio of losses for any two such
bends can be determined from Equation 3.11. It is usually even more con-
venient to add the equivalent length of straight duct for each elbow to the
actual length of straight duct in each case and to proportion the system as if it
consisted entirely of straight duct. When abrupt turns are involved, for which
the equivalent lengths of straight pipe vary appreciably with size, greater
accuracy is obtained by calculating the losses for these turns separately from
the straight sections to which they join. If the loss for one such turn is deter-
mined in velocity heads or per cent velocity pressure, Equation 3.12 or its
reciprocal, respectively, can be used to find the loss for any similar turn
regardless of size.
Rectangular Ducts
All the preceding equations and charts are for round ducts. When rectan-
gular ducts are to be used, it is necessary to determine the diameter of an
equivalent round duct using either Figures 2.14 or 2.16. Figure 2.14 is based
on equal velocities and equal mean hydraulic radii for the rectangular duct and
its equivalent round duct. It is a graphical solution of the equation
2 xy
DV = , (3.20)
x+ y
Figure 3.4
Rectangular Pipe Sizes for Equal-Friction-per-Foot-of- Length
which can be derived by equating the mean hydraulic radii for equivalent
round and rectangular sections.
Figure 2.16 is based on equal capacities and equal friction per foot of
length for the rectangular duct and its equivalent round duct. It is a graphical
solution of the equation
which can be derived from Equations 3.7 and 3.20. Figure 2.16 is drawn for
average roughness (that is, n = .16). Similar charts can be drawn for other
roughnesses. Equation 3.21 is for turbulent flow. For laminar flow
ç 4ä ç 2 äã
= æ ã 1 xy 6 æ
14 12
åπâ å x + yâ
34
DQ . (3.22)
çæ Qû äã 2 .0 − n
ç x y äã çæ x + y äã
=æ
3.4 − 2 n 1.4 − n
å Qû â åx y â åx +y â
a a a b b
, (3.23)
b b b a a
Given the system sketched below and the problem of determining duct
sizes and fan requirements, we can calculate the theoretical optimum velocity
from Equation 3.1 at least approximately by using the appropriate rates and
other factors indicated. For this problem let us assume that we use 22 ga
(0.030 in.) steel (0.283 lbm/in.3) duct work costing $4.15 per lbm installed,
that the system operates 2200 hours a year handling standard air (0.075
lbm/ft3), and that the power rate is 4 cents per kilowatt hour. If we assume a
.
life of 10 years and an interest rate of 15%, the annual owning cost as a
fraction of the first cost is
015
.
F= = 0.20.
1 6
1 − 115
.
−10
Here it is not necessary to check the validity of the 0.02 friction factor
since we will assume that the material being handled with the air requires
approximately 4000 fpm transport velocity. The duct sizes can be determined
directly from the capacity and the velocity, but as indicated in the table below,
this procedure yields odd duct sizes. Practical duct sizes giving velocities
within 10% of the required transport velocity will generally be satisfactory.
The duct friction per 100 ft of length p L 100 ft can be found from Figure
2.15.
The overall pressure drop in in. wg for each of the alternate air paths can
be determined by adding the appropriate individual drops as indicated in the
following table:
The calculations for this example have been greatly simplified since the
losses through hoods, elbows, etc. were predetermined. The losses through
the various ducts are based on average friction, but for most exhaust systems,
smooth or medium-smooth duct friction corrections should be made, depend-
ing upon the material and the number of joints used. As is usually so, the
longest run has the highest pressure drop. With enough experience a designer
can determine by inspection which run will have the highest pressure drop.
However, when there is doubt, all pressure drops should be calculated as in
this example.
The fan requirements can be stated as 3500 cfm and 9.71 in. wg static
pressure if blast gates can be used to balance the friction loss in the runs that
do not have a loss as great as 9.71 in. wg. If blast gates are not used and if the
fan is selected for 3500 cfm at 9.71 in. wg static pressure, the actual capacities
through the various branches will be different from the design values. The
run with the greatest pressure drop will suffer a loss in capacity, and the
shortest run will handle more air than required. The exact values for all runs
could be calculated by a trial-and-error procedure, but the differences will
generally be negligible. The conservative designer might add 5% - 10% to the
fan capacity to ensure that the longest run would not suffer too big a drop in
the amount of air handled.
It is also possible to balance the total pressure losses by reducing the duct
size in those branches with less than maximum pressure drop. In this prob-
lem, for the branch nearest the fan, the overall pressure drop is 9.71 - 8.82, or
0.89 in. wg less than the maximum. The branch loss could theoretically be
0.89 + 0.88, or 1.77 in. wg. With Equation 3.10, the diameter required to
produce this higher pressure drop can be calculated to be 4.34 in. as indicated
below
çæ 0.88äã 15
D = 5.0
å 177
. â
= 4.34 in.
If the ducts could be sized exactly to the required fractions of an inch, the fan
could be selected for 3500 cfm @ 9.71 in. wg static pressure and, theoreti-
cally, no blast gates would be needed. Blast gates are frequently used except
where they may create great hazards so that the inevitable discrepancies
between actual and theoretical requirements can be balanced out.
Example 3.2 Round and Rectangular Duct Design for Supply Systems
The optimum velocity for round duct costing $4.00 per lbm installed when
the power rate is 4.5 cents per kilowatt hour assuming 24 ga (0.024 in.) steel
(0.283 lbm/in. ) and 3500 hours annual operation can be found by means of
Equations 3.1 and 3.2:
015
.
F= = 016
1 6
1 − 115
.
−20
.
A velocity of 2790 fpm is obtained for a 0.02 friction factor and an annual
owning cost equal to 16% of the initial installed cost. The latter is based on
an annual interest rate of 15% and a 20-year life. The validity of the assumed
0.02 friction factor can be determined by calculating the Reynolds number
and referring to Figure 2.8 for the appropriate roughness condition.
The first section of main riser can be sized for any reasonable velocity.
The static-regain method produces a considerable reduction in main-riser
velocity so that, for an average riser velocity approaching the optimum, the
velocity in the first section must exceed the optimum. A value of 3500 fpm
requires an area of 11.72 ft2, which roughly corresponds to a 46-in. diameter
and a 0.27-in. wg pressure loss (or friction) per 100 ft.
The remaining main-riser sizes can be obtained directly from Figure 3.3.
The most convenient way of using this chart is to tabulate the information
indicated below using the subscript 2 to indicate the portion of main riser
under consideration and the subscript 1 to indicate the preceding, or upstream,
portion of main riser. For the second portion of main riser, which must handle
30000 cfm, we have already established that the velocity in the upstream
portion will be 3500 fpm. From 30000 divided by 3500 a figure of 8.57 is
obtained and at the intersection of this value of Qû 2 V1 with the appropriate
length L2 of 15 ft, a diameter of 42 in. can be read directly from the chart.
The velocity in a 42-in. pipe carrying 30000 cfm is 3120 fpm. Similar calcu-
lations are required for the remaining sections of main riser.
Qû 2 V1 Qû 2 V1 L2 D2 V2
30000 3500 8.57 15 42 3120
23000 3120 7.37 10 38 2920
16000 2920 5.48 10 33 2690
9000 2690 3.48 10 26 2260
The procedure for sizing rectangular ducts is basically the same. The
installed cost of rectangular duct is slightly higher than that of round duct so
that, assuming all other conditions to be the same, the optimum velocity for
rectangular duct costing 10% more would be 2900 fpm as indicated by
çæ 110
. ä
ã
13
Vopt = 2810
å 100
. â
= 2900 fpm.
Once again sizing the 4000 cfm branch for the optimum velocity, the
required area is 1.38 ft2, which can be satisfied with rectangular dimensions of
16 in. × 12.4 in. The equivalent diameter based on constant friction per foot
of length as determined from Figure 2.16 is 15 in., and the corresponding
friction per 100 ft is 0.92 in. wg. The remaining branches are easily sized by
noting the appropriate equivalent diameter opposite the necessary cfm for the
same friction per 100 ft on Figure 2.15. The corresponding rectangular
dimensions can be found in Figure 2.16 and the actual velocity calculated as
indicated.
Sizing the first section of main for 3800 fpm means that 10.79 ft2 are
needed. This requirement is matched by a 24-in. × 65-in. rectangular cross
section. The equivalent diameter based on constant capacity is approximately
42 in., and the corresponding friction is 0.32 in. wg per 100 ft of length.
Using 3800 fpm in the first section of main and 30000 cfm in the second, the
Qû 2 V1 equals 7.90, and for a 15-ft L2 , the equivalent diameter D2 is 39.8 in.
.
From Figure 2.16, this corresponds to a rectangular section 24 in. × 59 in., and
the actual velocity here is 3050 fpm. Similar calculations must be made for
the remaining sections of main as indicated below.
Qû 2 V1 Qû 2 V1 L2 D2 x× y V2
30000 3800 7.90 15 39.8 24 × 59 3050
23000 3050 7.54 10 38.3 24 × 54 2650
16000 2650 6.03 10 34.5 24 × 44 2180
9000 2180 4.13 10 28.7 14 × 7 1860
The fan should be selected for a capacity of 41000 cfm and a static
pressure of at least 3.97 in. wg as indicated by the following tabulation.
Construction Details
The Sheet Metal and Air Conditioning Contractors National Association
has established standards for duct construction based on experience and tests.
Table 3.2 lists sheet metal thicknesses and some of the joint and reinforcing
details found in those standards. The joint details for low-velocity ducts are
keyed to the sketches given in Figure 3.5. The joints indicated provide
sufficient rigidity except that additional transverse stiffening is necessary
when the length of a duct section exceeds the centers listed. No special
provisions for air tightness are required if the joints are made in a workman-
like manner.
Adapted from the data of SMACNA: Low Velocity Duct Construction Standards, Washing-
ton, D.C., Fourth Edition, April 1969, pp. 11-39, and High-Velocity Duct Construction
Standards, Washington, D.C., Second Edition, January 1969, pp. 6, 14-17.Copper data added.
Adapted from the data of SMACNA: Low- Velocity Duct Construction Standards, Washing-
ton, D.C., Fourth Edition, April 1969, pp. 13 and 15.
S=
1 2
2
1
π rD = πr x + y .6 (3.24)
For the same center line radius, it is immaterial whether the aspect ratio is
x y or y x . Table 3.6 can be used together with Tables 3.3 through 3.5 to
determine the weight of a galvanized or black-steel elbow of either rectangu-
lar or round cross section. The thickness of the material in an elbow or other
fitting should be equal to or greater than that of the connecting straight pipe or
duct. Under highly abrasive conditions, rectangular-section elbows are
generally used since their wearing surfaces can be replaced more easily.
1
Round lndustrial Construction Standards, SMACNA, Vienna, Virginia,1977.
26 U.S.S. Gauge
Duct Size 6 7 8 9 10 11 12
6 2.00 2.17 2.34 2.50 2.67 2.84 3.00
7 2.17 2.34 2.50 2.67 2.84 3.00 3.17
8 2.34 2.50 2.67 2.84 3.00 3.17 3.34
9 2.50 2.67 2.84 3.00 3.17 3.34 3.50
10 2.67 2.84 3.00 3.17 3.34 3.50 3.67
11 2.84 3.00 3.17 3.34 3.50 3.67 3.84
12 3.00 3.17 3.34 3.50 3.67 3.84 4.00
14 3.34 3.50 3.67 3.84 4.00 4.17 4.34
16 3.67 3.84 4.00 4.17 4.34 4.50 4.67
18 4.00 4.17 4.34 4.50 4.67 4.84 5.00
24 U.S.S. Gauge
Duct Size 18 20 22 24 26 28 30
8 5.65 6.07 6.50 6.94 7.37 7.80 8.24
9 5.87 6.29 6.72 7.15 7.59 8.02 8.45
10 6.08 6.50 6.94 7.37 7.80 8.24 8.67
11 6.30 6.72 7.15 7.59 8.02 8.45 8.89
12 6.52 6.94 7.37 7.80 8.24 8.67 9.10
14 6.95 7.37 7.80 8.24 8.67 9.10 9.54
16 7.38 7.80 8.24 8.67 9.10 9.54 9.97
18 7.82 8.24 8.67 9.10 9.54 9.97 10.42
20 8.25 8.67 9.10 9.54 9.97 10.42 10.85
22 8.68 9.10 9.54 9.97 10.42 10.85 11.29
24 9.12 9.54 9.97 10.42 10.85 11.29 11.72
26 9.55 9.97 10.42 10.85 11.29 11.72 12.13
28 10.00 10.42 10.85 11.29 11.72 12.13 12.56
30 10.43 10.85 11.29 11.72 12.13 12.56 13.00
22 U.S.S. Gauge
Duct Size 32 34 36 38 40 42
8 10.00 10.50 11.00 11.50 12.00 12.50
9 10.25 10.75 11.25 11.75 12.25 12.75
10 10.50 11.00 11.50 12.00 12.50 13.00
11 10.75 11.25 11.75 12.25 12.75 13.25
12 11.00 11.50 12.00 12.50 13.00 13.50
13 11.25 11.75 12.25 12.75 13.25 13.75
14 11.50 12.00 12.50 13.00 13.50 14.00
16 12.00 12.50 13.00 13.50 14.00 14.50
18 12.50 13.00 13.50 14.00 14.50 15.00
20 13.00 13.50 14.00 14.50 15.00 15.50
22 13.50 14.00 14.50 15.00 15.50 16.00
24 14.00 14.50 15.00 15.50 16.00 16.50
26 14.50 15.00 15.50 16.00 16.50 17.00
28 15.00 15.50 16.00 16.50 17.00 17.50
30 15.50 16.00 16.50 17.00 17.50 18.00
32 16.00 16.50 17.00 17.50 18.00 18.50
34 16.50 17.00 17.50 18.00 18.50 19.00
36 17.00 17.50 18.00 18.50 19.00 19.50
22 U.S.S. Gauge
Duct Size 44 46 48 50 52 54
8 13.00 13.50 14.00 14.50 15.00 15.50
9 13.25 13.75 14.25 14.75 15.25 15.75
10 13.50 14.00 14.50 15.00 15.50 16.00
11 13.75 14.25 14.75 15.25 15.75 16.25
12 14.00 14.50 15.00 15.50 16.00 16.50
14 14.50 15.00 15.50 16.00 16.50 17.00
16 15.00 15.50 16.00 16.50 17.00 17.50
18 15.50 16.00 16.50 17.00 17.50 18.00
20 16.00 16.50 17.00 17.50 18.00 18.50
22 16.50 17.00 17.50 18.00 18.50 19.00
24 17.00 17.50 18.00 18.50 19.00 19.50
26 17.50 18.00 18.50 19.00 19.50 20.00
28 18.00 18.50 19.00 19.50 20.00 20.50
30 18.50 19.00 19.50 20.00 20.50 21.00
32 19.00 19.50 20.00 20.50 21.00 21.50
34 19.50 20.00 20.50 21.00 21.50 22.00
36 20.00 20.50 21.00 21.50 22.00 22.50
38 20.50 21.00 21.50 22.00 22.50 23.00
40 21.00 21.50 22.00 22.50 23.00 23.50
42 21.50 22.00 22.50 23.00 23.50 24.00
44 22.00 22.50 23.00 23.50 24.00 24.50
46 22.50 23.00 23.50 24.00 24.50 25.00
48 23.00 23.50 24.00 24.50 25.00 25.50
20 U.S.S. Gauge
Duct Size 64 68 72 76 80 84 88
10 21.60 22.80 23.90 25.10 26.30 27.40 28.60
12 22.10 23.40 24.50 25.70 26.70 28.00 29.20
14 22.80 23.90 25.10 26.30 27.40 28.60 29.80
16 23.40 24.50 25.70 26.70 28.00 29.20 30.40
18 23.90 25.10 26.30 27.40 28.60 29.80 30.90
20 24.50 25.70 26.70 28.00 29.20 30.40 31.50
22 25.10 26.30 27.40 28.60 29.80 30.90 32.10
24 25.70 26.70 28.00 29.20 30.40 31.50 32.70
26 26.30 27.40 28.60 29.80 30.90 32.10 33.30
28 26.70 28.00 29.20 30.40 31.50 32.70 33.90
30 27.40 28.60 29.80 30.90 32.10 33.30 34.40
32 28.00 29.20 30.40 31.50 32.70 33.90 35.00
34 28.60 29.80 30.90 32.10 33.30 34.40 35.60
36 29.20 30.40 31.50 32.70 33.90 35.00 36.20
38 29.80 30.90 32.10 33.30 34.40 35.60 36.80
40 30.40 31.50 32.70 33.90 35.00 36.20 37.30
42 30.90 32.10 33.30 34.40 35.60 36.80 37.90
44 31.50 32.70 33.90 35.00 36.20 37.30 38.50
46 32.10 33.30 34.40 35.60 36.80 37.90 39.00
48 32.70 33.90 35.00 36.20 37.30 38.50 39.60
50 33.30 34.40 35.60 36.80 37.90 39.00 40.20
52 33.90 35.00 36.20 37.30 38.50 39.60 40.80
54 34.40 35.60 36.80 37.90 39.00 40.20 41.40
Principles of Distribution
Distribution requirements vary considerably from one application to
another. Some systems may require a concentrated supply of air at high
velocity, but in others, the objective may be uniform distribution without
objectionable drafts over a broad area.
Air can be circulated and distributed within a space by utilizing the kinetic
energy of one or more streams of air issuing into the space. This energy must
be supplied, directly or indirectly, by a fan.
As mentioned under "Principles of Duct Design," supply and exhaust can
be accomplished with a single fan in either position. A supply fan must
develop the necessary total pressure to produce the kinetic energy required at
the duct opening into a room, plus that necessary to overcome the losses due
to friction, etc. in the duct system, plus that necessary to produce a static
pressure in the space sufficient to force air through the available exhaust
openings. An exhaust fan, however, must develop the necessary total pressure
to overcome the losses due to friction, etc. in the duct system, plus that
necessary to create a negative static pressure in the space sufficient to produce
the required kinetic energy at the duct opening into the room.
Both supply and exhaust openings are necessary for through-circulation.
Air discharging from an opening, like any moving object, tends to continue at
its exit velocity along a straight-line path. Various effects tend to slow down
and deflect the stream. The effects of entrainment and temperature difference
are discussed below. The mutual effect of the supply and exhaust openings
may also be important.
Air entering an exhaust opening tends to approach equally from all
directions. For an opening located in the plane of the wall, the velocity at
one-diameter distance from the opening will be approximately 10% of that at
the opening itself. The velocity decreases rapidly with distance so that the
.
De = 113
. Ae (3.25)
Figure 3.6
Effective Diameters of Round and Rectangular Openings
Adapted from the data of R. D. Madison and W. R. Elliot: "Throw of Air from Slots and
Jets," ASHVE Journal Section of Heating, Piping and Air Conditioning, Chicago, November
1946, pp.108 to109.
R Aϕ i CD
De = De.S .E . . (3.26)
0.6
The values of R A and ϕ i C D for several typical outlets are given in Table
3.7.
The effective velocity of the jet issuing from the outlet Vo is that at the
vena contracta. This can be calculated from the capacity Qû and the effective
area Ae using the equation of continuity or from the gross area Ag of the
outlet using
Qû Qû
Vo = = . (3.27)
Ag R Aϕ i CD Ae
The average residual velocity at any distance from the outlet, beyond
approximately 10 effective diameters, is about 1/3 of the maximum residual
velocity. The maximum, or centerline, residual velocity Vr relative to the
effective velocity at the outlet Vo is a function of the throw X and the
effective diameter De . Conversely, the throw in diameters X De is
proportional to the velocity ratio Vr Vo . as indicated by
X V
=K o. (3.28)
De Vr
indicated by
Qû t
2
Vr Vo
RQ = û = 0.314 1.12 + 0.35 K − 1 . (3.29)
Qj Vo Vr
Approx. Approximate†
Outlet RA φ i CD * K
Rounded-entrance
nozzles 1.00 0.99 Use Table 3.8 Values Directly
Square-edged
orifices 1.00 0.60 Use Table 3.8 Values Directly
Plain straight-duct
openings 1.00 1.00 Multiply Table 3.8 Values by 1.05
Bar grilles 0.84 0.66 Multiply Table 3.8 Values by 0.86
Bar grilles 0.74 0.78 Multiply Table 3.8 Values by 0.72
Bar grilles 0.72 0.78 Multiply Table 3.8 Values by 0.69
Perforated panels 0.40 0.83 Multiply Table 3.8 Values by 0.89
Perforated panels 0.09 0.75 Multiply Table 3.8 Values by 0.64
Perforated panels 0.03 0.79 Multiply Table 3.8 Values by 0.39
Effect of high-aspect
ratios - - Multiply Table 3.8 Values by 0.86
Effect of adjacent wall
Parallel to axis
of flow - - Multiply Table 3.8 Values by 1.42
Adapted from the data of A. Koestel, P. Hermann, and G. L. Tuve: "Comparative Study of
Ventilating Jets from Various Types of Outlets," Trans. ASHVE, vol. 56, New York, 1950,
pp. 459-478.
*Velocity-.of-.approach factors corresponding to 1400 fpm ahead of bar grilles are included
in the table.
†The value of K increases for throw calculation., but decreases for entrainment calculations.
This chart can be used to find the entrainment ratio and maximum residual
velocity at any distance from a given outlet. It can also be used to determine
the necessary combination of effective diameter and original velocity for a
given throw and a specified residual velocity. Example 3.3 illustrates a
typical use of this chart.
Given a 42-in. × 6-in. bar grille discharging 2000 cfm, find the residual
velocity and the total quantity of moving air at a throw of 30 ft.
Table 3.8
Proportionality Factors K for Throw from Nozzles and Orifices
Vo -fpm
Vr -fpm 1000 2000 3000 4000 5000
500 up - 5.3 5.5 5.7 6.0
400 - 5.0 5.2 5.5 5.8
300 4.4 4.6 4.8 5.0 5.3
200 4.1 4.2 4.4 4.6 4.8
100 3.3 3.3 3.4 3.5 3.5
Adapted from the data of G. L. Tuve and G. B. Priester: "Control of Air Streams in Large
Spaces," Trans. ASHVE. vol. 50, New York, 1944, pp 153-172.
2000 2000
Vo = = = 1980 fpm, and
. × 0.74 × 0.78 101
175 .
30
Using Figure 3.7 with V = 1980 and X De = = 26.3,
114
.
Vr = 430. (first approximation)
Since Figure 3.7 is based on Table 3.8 values and since Table 3.8 values must
be modified for bar grilles, adjustments must also be made according to
Tables 3.7 and 3.8, and Equation 3.28:
Y Xçæ äã çæ T − T äã çæ gD äã .
3
= 0.065
å â å T âå V â
o a e
2
(3.30)
De De a o
Similarly, if the primary air is cooled below the ambient temperature, the
stream will fall.
The maximum possible vertical downward projection X max of a heated
stream or the maximum upward projection of a cooled stream can be calcu-
lated from
X max çæ
Ta äã çæ V äã − 2.85.
2
= 3.4
å â å gD â
o
(3.31)
De To − Ta e
Equations 3.30 and 3.31 are adapted from the data of Koestel1, which also
give the results of temperature-distribution studies.
Given a 1.0 ft2 squared-edged orifice with a plenum approach projecting 3000
cfm of 180°F air through ambient air at 70°F, find the maximum throw for
downward projection and the vertical rise of the center line of a horizontally
projected stream at that same throw.
3000
Vo = = 5000 fpm,
1.0 × 0.6
De = 113
. 1.0 × 0.60 = 0.875 ft, or
1
A. Koestel, "Paths of Horizontally Projected Heated and Chilled Air Jets," Trans. ASHVE,
vol. 61, New York, 1955, pp. 213-232, and "Computing Temperatures and Velocities in
Vertical Jets of Hot or Cold Air," Trans. ASHVE vol. 60, NewYork, 1954, pp. 385-410.