A2.1 Fire Alarm System
A2.1 Fire Alarm System
1
Fire Alarm Panel
Single Line Diagram motorized
valve Smoke
Detector
FIRE FIRE
SILENT KNIGHT
Siren
Addressabl
e Fire Panel
2
Automatic Fire Alarm System & Components
3
Public addressing system
System includes:
• Amplifier
• Mic
• Speakers
• Zone selection console
4
FAS System Response
• Besides providing early notification, the fire alarm system also performs the following critical
functions, whenever applicable:
• Shuts down AHUs to limit the spread of fire and minimize smoke exposure of occupants
• Releases the Access doors for ease of evacuation.
• Starts pressurization fans to clear stairways of smoke for occupants to escape
• Generates alert sounds/Hooters for mass awareness.
• Initiates ventilation fans of basements.
• Monitors Water flow in Sprinkler Lines.
• Monitors CO2 and other flooding system.
5
Input Devices - FAS
Automatic Initiating Devices
• Smoke Detectors
• Heat Detectors
• Manual Call Points (MCP)
• Break Glass
6
FAS- Inspection
Schedule Checks
Daily • Visual inspection of panel trouble ‘led’ signal or location address
• Cleaning & lose contact
• Battery power
Monthly • Operational test by energizing detector & Manual Call Points (MCP)
• Cleaning & contact connection
• Battery backup & Load voltage
Quarterly • Visual inspection of all fire sprinkler devices connected to the alarm. This includes water flow switches, Test of fire
pump monitored points (loss of phase, phase reversal, pump running)
Semi-annual • Test of sprinkler water flow switches (flow water or manually trip flapper)
• Test batteries - load voltage
Annual • Test & visual inspection of panel functionality, LED's, fuses,
• Test panel battery charger Fire alarm should maintain operational and with
• Battery discharge test independent source of power supply (UPS)and
• Test & visual inspection of siren & hooters report any fault immediately. Battery must give
• Test & visual inspection of smoke detectors emergency back up supply for minimum 30
• Test & visual inspection of heat detectors minutes.
• Test & visual inspection of duct smoke detectors
• Test & visual inspection of Electromechanical Releasing Devices (Solenoid)
• Test & visual inspection of PA system
7
Fire Control Room
The fire control room is separated from the remainder of the building by fire-resistive construction,
with all openings protected by assemblies with fire resistive ratings.
It usually contains the following items as a minimum:-
• Voice communication and PA system
• Public telephone
• Stairwell intercom system
• Fire Detection and alarm system control panel
• Building and elevator keys
• First Aid Kit
• List of Emergency Contacts
• SCBA Set
• Fire fighting suits
• emergency lights etc.
8
Q&A
Q1. Access door may be held open by device linked into? Q4. Do brand new and properly functioning
A. The fire alarm. B. The lighting alarm. smoke detectors/smoke alarms get false
trips?
C. The security alarm.
A. True B. False