0% found this document useful (0 votes)
173 views20 pages

Using Dielectric Frequency Response To Assess Insulation in Bushings

The document discusses using dielectric frequency response measurements to assess insulation condition in bushings and transformers. DFR measurements provide insulation property data over a frequency range, which can be used along with mathematical modeling to determine moisture content and temperature dependence of insulation systems. DFR allows more accurate evaluation of insulation condition than standard 50/60 Hz tests alone.

Uploaded by

Muhammad Rasyidi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
173 views20 pages

Using Dielectric Frequency Response To Assess Insulation in Bushings

The document discusses using dielectric frequency response measurements to assess insulation condition in bushings and transformers. DFR measurements provide insulation property data over a frequency range, which can be used along with mathematical modeling to determine moisture content and temperature dependence of insulation systems. DFR allows more accurate evaluation of insulation condition than standard 50/60 Hz tests alone.

Uploaded by

Muhammad Rasyidi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 20

Using Dielectric Frequency Response to Assess

Insulation in Bushings & Instrument


Transformers
Bushings
 February 3, 2023 Transformers  14 min read




Leer artículo en español
Modern technology in signal acquisition and analysis techniques has provided new tools for
transformer diagnostics. Of particular interest are dielectric response measurements where
insulation properties of oil/paper systems can be investigated. Dielectric frequency response or
DFR, (also known as Frequency Domain Spectroscopy or FDS), was introduced over 25 years ago
and has been evaluated in research projects and field tests, usually with good results. DFR data, in
combination with mathematical modeling of the oil/paper insulation, has proven to be an excellent
tool for moisture assessment. Since the modeling theory contains influence of temperature, DFR and
modeling can also be used to calculate temperature dependence of the insulation system.
This edited past contribution to INMR by experts at Megger in Sweden, provided a background on
DFR as well as on insulation modeling. It also explained how these can improve understanding of
insulation properties and be used for assessing condition of insulation on bushings and instrument
transformers.  
The condition of insulation is essential to ensuring operational reliability of
transformers, generators, cables and other high voltage equipment. Transformers with
high moisture content cannot sustain high loads without elevated risk. Moreover,
bushings and cables with high dissipation factor at high temperature can explode due
to ‘thermal runaway’. On the other hand, it’s also important to identify ‘good’ units in
the ageing population of equipment. Adding just a few more years to the expected
end-of-life of a transformer or bushing can yield substantial savings.

50/60 Hz Dissipation Factor Measurements


A common insulation diagnostic test is measurement of capacitance and dissipation
factor (DF) at 50/60 Hz. This is the standard test performed whenever there is a need to
investigate insulation properties. DF tests are typically done at ‘any’ temperature using
a test voltage from about 30 V up to about 10 kV for field tests and up to nominal
voltage in factory measurements. There are also tests with variable voltage
(tip-up/step-up testing) as well as tests where tan delta over temperature is measured.
Analysis is based on standards, historical data and comparison against factory values.
Since insulation properties are temperature dependent, temperature correction is
commonly used for measurements not performed at 20°C. This is normally achieved
using temperature correction table values for certain classes of devices. In e.g. IEEE
C57.152, IEEE C57.12.90 and CIGRE TB 445, typical tan delta (power factor) values for
transformers and bushings are categorized.

Table 1: Typical Tan


Delta Assessment Values
Typical temperature correction values are shown in Fig 1.
Fig. 1: Typical
dissipation factor temperature corrections.
It’s obvious that given values are only approximate guidelines. IEEE C57.152, for
example, states; “While the power factors for older transformers will also be <0.5% (20°C),
power factors between 0.5% and 1.0% (20°C) may be acceptable; however, power factors >1.0%
(20°C) should be investigated.” Moreover, in IEEE C57.12.90-2006 it is stated; “Experience
has shown that the variation in power factor with temperature is substantial and erratic so that no
single correction curve will fit all cases.”
Dielectric Frequency Response Measurements
The first field instrument for DFR/FDS measurements of transformers, bushings and
cables was introduced in 1995. Since then, thorough evaluation of the technology has
been performed. In fact, several international projects/reports define dielectric
response measurements together with insulation modeling as the preferred method
for measuring moisture content of the cellulose insulation in power transformers. In
DFR tests, capacitance and dissipation/power factor is measured. The measurement
principle and set-up is similar to traditional 50/60 Hz DF testing but with the difference
that lower measurement voltage is often used (140 to 1400 V) and, instead of
measuring at line frequency 50/60 Hz, insulation properties are measured over a
frequency range – typically from 1 mHz to 1 kHz. The results are presented as
capacitance and/or tan delta/power factor versus frequency. Measurement set-up is
shown in Fig. 2.
Fig. 2: DFR
measurement set-up.
Typical DFR results from measurement on transformers with different moisture
conditions are presented in Fig 3.

Fig. 3: DFR
measurements on 4 transformers at different temperatures with moisture content ranging from
0.3 to 3.4%.
Moisture Assessment
The capability of DFR to measure dissipation factor as a function of frequency gives the
user a powerful tool for diagnostic testing. Moisture assessment is a good example.
High moisture levels in transformers are a serious issue since these limit maximum
loading capacity and the ageing process is accelerated. Accurate knowledge about the
actual moisture content in the transformer is necessary to decide on corrective actions,
replacement/scrapping or re-location to a different site in the network with reduced
loading. The method of using DFR to determine moisture content in the oil-paper
insulation inside an oil-immersed power transformer has been described in detail in
several papers and articles, and is therefore only briefly summarized here.

The dissipation factor for an oil/paper insulation plotted against frequency shows a
typical inverted S-shaped curve. With increasing temperature, the curve shifts towards
higher frequencies. Moisture influences mainly the low and high frequency areas. The
middle section of the curve, with the steep gradient, reflects oil conductivity. Fig. 4
describes influence of these parameters on the reference curve.

Fig: 4: Parameters
affecting dissipation factor at various frequencies.
Using DFR for moisture determination is based on comparison of the transformer’s
dielectric response to a modeled dielectric response (reference curve). A matching
algorithm re-arranges the modeled dielectric response and delivers a new response
curve that reflects the measured transformer. The moisture content, along with the oil
conductivity for the reference curve, is presented as a result of the test. Only the
insulation temperature (top oil temperature and/or winding temperature) needs to be
entered as a fixed parameter.
Fig. 5: DFR
moisture analysis.
Three different transformers are shown in Fig. 6. The units have the same 0.5%, 50 Hz
DF value, typically characterized as ‘warning/alert’ limit status calling for ‘investigation’.
Such investigation is done as a DFR analysis.
Fig. 6. DFR analysis
of 3 transformers with different oil quality & moisture content.
The three transformers are very different and maintenance measures for them would
also be different. Transformer 1 has good oil but needs drying. Transformer 3 has low
moisture but needs oil change or regeneration. Transformer 2 is in a normal service-
aged condition.
Advertisement

Individual Temperature Correction (ITC)


DFR measurements and analysis, together with modeling of the insulation system, also
include temperature dependence. A new patented methodology is to perform DFR
measurements and convert results to dissipation factor at 50 Hz as a function of
temperature. This technique has major advantages in measurement simplicity for
bushings. Instead of time consuming heating/cooling of the bushing and doing several
measurements at various temperatures, one DFR measurement is performed and the
results are converted to 50 Hz tan delta values as a function of temperature. The
method is based on the fact that a certain dissipation factor measurement at a certain
frequency and temperature corresponds to a measurement made at a different
temperature and at a different frequency. The conversion calculations are based on
Arrhenius’ law/equation, describing how the insulation properties relate to
temperature.

κ = κ ·exp(-W /kT)
0 a

with activation energy W and Boltzmann constant k. This relationship is depicted for

single-material insulation and three different activation energies in Fig 7.

Fig. 7: Relationship
between power factor values at different frequencies taken at different temperatures.
Temperature correction tables (such as in IEEE C57.12.90) give average values
assuming ‘average’ conditions and are not correct for an individual transformer or
bushing. This is confirmed in field experiments and some utilities try to avoid applying
temperature correction by recommending measurements be performed within a
narrow temperature range. Examples are shown in Figs. 8 and 9. Dissipation factor was
measured at 10 kV on 4 transformers and 3 bushings of different age, condition and at
various temperatures. Temperature dependence is very different for the transformers
and bushings and using standard temperature correction tables will not give correct
values for the 20°C reference value.
Fig. 8: Tan delta
values as function of temperature (ºC) for 4 different transformers.

Fig. 9: Tan delta


values as function of temperature (ºC) for 3 different bushings.
With DFR and the technique for converting data to temperature dependence, it is
possible to do accurate, individual temperature correction (patent pending). For a
‘good’ component, temperature dependence is weak. When the component gets older
and/or deteriorated, the temperature correction factor becomes much larger, i.e. the
temperature dependence is a function of ageing status. This observation is in line with
several projects and studies.
Fig. 10: Dissipation
factor as function of frequency for dry kraft paper.
An example of using the technique is shown in Figs. 10 and 11. Samples of kraft paper
with various moisture contents were measured at different temperatures. The
dielectric response for dry paper (moisture content <0.5%) is shown in Fig. 10.

Using DFR technique to estimate temperature dependence based on measurements


only at one temperature yields the results shown in Fig 11. As seen, calculated
temperature dependence closely matches actually measured dissipation factors at
different temperatures.

Fig 11: Tan delta at


50Hz for dry kraft paper as function of temperature.
Bushing Diagnostics
50/60 Hz DF measurements are the most common insulation diagnostic test performed
on bushings. C1 (UST) is a common test and typical guidelines for evaluating the C1
dissipation factor are:

• Between nameplate tan delta and up to twice nameplate tan delta – Bushing deemed
acceptable

• Between twice nameplate tan delta and up to 3 times nameplate tan delta – Monitor
bushing closely

• Above 3 times nameplate tan delta – Replace bushing

Looking at Table 1 and the above guidelines, typical benchmarking values for oil-
impregnated paper (OIP) bushings can be identified, as shown in Table 2.

Table 2: Tan
Delta Values for Typical OIP Bushings
Measuring bushings over temperature – and in particular at high temperature – gives
additional information about condition of the insulation and an indication of
ageing/high moisture content (see Fig. 12). Increased dissipation factor at higher
temperatures is a good indicator of bushing problems. A high dissipation factor at
higher temperatures results in increased heating of the bushing, which in turn
increases losses causing additional heating, which increases losses even further until
the bushing finally explodes.
Fig. 12. Dissipation
factor (%) vs. temperature for OIP bushings with various moisture contents.
GE type U – Accelerated Ageing Tests
GE Type U bushings have exhibited a poor record of performance and provided utilities
with major asset replacement issues. In one research project initiated by the former
Ontario Hydro (now HydroOne) in Canada and Pacific Gas & Electric in the U.S., an
accelerated ageing program was performed on 6 x 155 kV Type U bushings involving
various diagnostic tests performed on the bushings. The bushings were subjected to
simultaneous thermal and electrical ageing.

During the ageing program, 66 kV (nominal line-to-ground voltage) was applied to the
bushings. Thermal ageing was accomplished by means of circulating power frequency
current through the bushings, starting at 1200 A and slowly increasing to 2000 A. Two
bushings (#3 & #4) failed at elevated current (1900 A) during the ageing program. The
bushings were selected for test on the basis of tan delta (power factor) measurement
results. Two units had low values, two units had high values and two had ‘intermediate’
values (see Fig. 13). Nameplate DF is assumed to be 0.25%. During ageing, periodic and
continuous diagnostic tests were performed, i.e. Tan delta, capacitance, DFR, PD, DGA
etc. Results from traditional test methods have been reported elsewhere and this
paper focuses only on DFR measurement results.
Fig. 13: Dissipation
factor (%) for the 6 GE Type U bushings at 20°C.
DFR Measurements
DFR measurements were performed at the beginning of the program. The bushings
were tested at various voltages (tip-up tests) and temperatures (see Table 3). Insulation
temperatures are estimates based on using DFR data at ambient temperature to
determine temperature dependence (ITC).

Table 3: DFR
Measurements On GE Type U Bushings
Fig. 14: Tan delta vs
frequency measured at 0.13 kV and ambient temperature.
Low voltage DFR results are presented in Fig. 14. Differences in dissipation factors
between bushings are much larger at low frequencies compared to 60 Hz values.

Temperature Dependence
Using the technique described, DFR data can be used to estimate temperature
dependence. The results are shown in Fig. 15 as tan delta temperature dependence for
the 6 bushings. Temperature dependence for bushings #5 and #6 corresponds to
factory data indicating that these bushings are in good condition. The other bushings
have higher temperature dependence. Bushing #2, classified as M/ ‘intermediate’ has
the same temperature dependence as the ‘bad’ bushings (#3 and #4) that failed during
the accelerated ageing test.

Fig. 15: Tan delta


temperature dependence (relative tan delta) for 6 bushings (temperature on x-axis).
DFR measurements at 3 temperatures are presented for two bushings in Figs. 16 and
17.

Fig. 16: DFR


measurement on bushing #1 at different temperatures.

Fig. 17. DFR


measurement on bushing #5 at different temperatures.
Tip-Up Measurements
Two tip-up results are shown in Figs. 18 and 19.
Fig. 18: DFR tip-up
measurement on bushing #3 (‘bad’).

Fig. 19: DFR tip-up


measurement on bushing #5 (‘good’).
60 Hz tan delta values are almost independent of test voltage and not sensitive to
ageing effects. At lower frequencies there is a ‘tip-down’ effect that, for the ‘good’
bushing, is very small.

Current Transformer Diagnostics


Similar experience from a past project has been gained for instrument transformers. In
one experiment, for example, 6 current transformers of the same type but in various
conditions were measured at temperatures ranging from 25°C to 50°C. Table 4
summarizes the CT units:
Table 4: Current Transformer
Measurements
The first analysis was to confirm that the insulation material behaves as expected and
determine the activation energy for the material. Results showed that the activation
energy was 0.9 and quite similar for the 6 units (example shown in Fig. 20).

Fig. 20: DFR results


for CT #1 at different temperatures. Values scaled to 25°C with activation energy 0.9 eV.
Based on these positive results it is possible to investigate the temperature
dependence for the units. Examples are shown in Tables 5 and 6. CT 7 is a ‘good’ unit
and in this case, the table correction makes it even ‘better’. CT 3 is a ‘bad’ unit and the
table correction makes it even ‘worse’. ITC estimates the correct 20°C value for all the
actual temperatures.

Table 5: Ct 7, Temperature

Corrected Data Table 6: Ct 3,


Temperature Corrected Data
As noted in several publications, large temperature dependence is often aligned with a
high dissipation factor at low frequencies. This can also be seen for the CTs in this
investigation. In Fig. 21, 1 Hz and 50 Hz values are plotted for 4 series of current
transformer measurements – in total 26 units.
Fig. 21: 1 Hz and 50
Hz tan delta values for 26 current transformers.
As expected, CTs with high values for 50 Hz tan delta (>1%) also have high values at 1
Hz. However, units with a tan delta within the ‘accepted’ range of 0.2-0.4% may differ
significantly when looking at the 1 Hz values. This confirms that the low frequency data
and/or the tan delta temperature dependence are better diagnostic parameter than
the traditional 50 Hz value – especially when looking for early indications of insulation
deterioration.

Discussion
The temperature dependence of the dissipation factor of an insulating material needs
to be considered when comparing measurement results between phases, with
previous tests or factory values. Historically, this has been done using average
temperature correction tables. Results are disappointing and asset owners therefore
try rather to perform diagnostic measurements at a specific (narrow) temperature
range. The new method of using frequency data and estimating temperature
dependence of the actual component offers an alternative to waiting for the ‘correct’
temperature – and then doing the test. It gives the possibility to have correct 20°C
reference values and also to make a correct comparison to previously measured non-
corrected data at other insulation temperatures. Temperature dependence can also be
used as an analysis method for bushings and instrument transformers. Comparing
measured temperature dependence with manufacturer data for temperature
correction will tell if the condition of the unit is good or not. In insulation diagnostics,
high tan delta values at low frequencies and large tan delta temperature dependence
(increased dissipation factor at high temperatures) are good indicators of insulation
deterioration.

You might also like