Using Dielectric Frequency Response To Assess Insulation in Bushings
Using Dielectric Frequency Response To Assess Insulation in Bushings
Leer artículo en español
Modern technology in signal acquisition and analysis techniques has provided new tools for
transformer diagnostics. Of particular interest are dielectric response measurements where
insulation properties of oil/paper systems can be investigated. Dielectric frequency response or
DFR, (also known as Frequency Domain Spectroscopy or FDS), was introduced over 25 years ago
and has been evaluated in research projects and field tests, usually with good results. DFR data, in
combination with mathematical modeling of the oil/paper insulation, has proven to be an excellent
tool for moisture assessment. Since the modeling theory contains influence of temperature, DFR and
modeling can also be used to calculate temperature dependence of the insulation system.
This edited past contribution to INMR by experts at Megger in Sweden, provided a background on
DFR as well as on insulation modeling. It also explained how these can improve understanding of
insulation properties and be used for assessing condition of insulation on bushings and instrument
transformers.
The condition of insulation is essential to ensuring operational reliability of
transformers, generators, cables and other high voltage equipment. Transformers with
high moisture content cannot sustain high loads without elevated risk. Moreover,
bushings and cables with high dissipation factor at high temperature can explode due
to ‘thermal runaway’. On the other hand, it’s also important to identify ‘good’ units in
the ageing population of equipment. Adding just a few more years to the expected
end-of-life of a transformer or bushing can yield substantial savings.
Fig. 3: DFR
measurements on 4 transformers at different temperatures with moisture content ranging from
0.3 to 3.4%.
Moisture Assessment
The capability of DFR to measure dissipation factor as a function of frequency gives the
user a powerful tool for diagnostic testing. Moisture assessment is a good example.
High moisture levels in transformers are a serious issue since these limit maximum
loading capacity and the ageing process is accelerated. Accurate knowledge about the
actual moisture content in the transformer is necessary to decide on corrective actions,
replacement/scrapping or re-location to a different site in the network with reduced
loading. The method of using DFR to determine moisture content in the oil-paper
insulation inside an oil-immersed power transformer has been described in detail in
several papers and articles, and is therefore only briefly summarized here.
The dissipation factor for an oil/paper insulation plotted against frequency shows a
typical inverted S-shaped curve. With increasing temperature, the curve shifts towards
higher frequencies. Moisture influences mainly the low and high frequency areas. The
middle section of the curve, with the steep gradient, reflects oil conductivity. Fig. 4
describes influence of these parameters on the reference curve.
Fig: 4: Parameters
affecting dissipation factor at various frequencies.
Using DFR for moisture determination is based on comparison of the transformer’s
dielectric response to a modeled dielectric response (reference curve). A matching
algorithm re-arranges the modeled dielectric response and delivers a new response
curve that reflects the measured transformer. The moisture content, along with the oil
conductivity for the reference curve, is presented as a result of the test. Only the
insulation temperature (top oil temperature and/or winding temperature) needs to be
entered as a fixed parameter.
Fig. 5: DFR
moisture analysis.
Three different transformers are shown in Fig. 6. The units have the same 0.5%, 50 Hz
DF value, typically characterized as ‘warning/alert’ limit status calling for ‘investigation’.
Such investigation is done as a DFR analysis.
Fig. 6. DFR analysis
of 3 transformers with different oil quality & moisture content.
The three transformers are very different and maintenance measures for them would
also be different. Transformer 1 has good oil but needs drying. Transformer 3 has low
moisture but needs oil change or regeneration. Transformer 2 is in a normal service-
aged condition.
Advertisement
κ = κ ·exp(-W /kT)
0 a
with activation energy W and Boltzmann constant k. This relationship is depicted for
a
Fig. 7: Relationship
between power factor values at different frequencies taken at different temperatures.
Temperature correction tables (such as in IEEE C57.12.90) give average values
assuming ‘average’ conditions and are not correct for an individual transformer or
bushing. This is confirmed in field experiments and some utilities try to avoid applying
temperature correction by recommending measurements be performed within a
narrow temperature range. Examples are shown in Figs. 8 and 9. Dissipation factor was
measured at 10 kV on 4 transformers and 3 bushings of different age, condition and at
various temperatures. Temperature dependence is very different for the transformers
and bushings and using standard temperature correction tables will not give correct
values for the 20°C reference value.
Fig. 8: Tan delta
values as function of temperature (ºC) for 4 different transformers.
• Between nameplate tan delta and up to twice nameplate tan delta – Bushing deemed
acceptable
• Between twice nameplate tan delta and up to 3 times nameplate tan delta – Monitor
bushing closely
Looking at Table 1 and the above guidelines, typical benchmarking values for oil-
impregnated paper (OIP) bushings can be identified, as shown in Table 2.
Table 2: Tan
Delta Values for Typical OIP Bushings
Measuring bushings over temperature – and in particular at high temperature – gives
additional information about condition of the insulation and an indication of
ageing/high moisture content (see Fig. 12). Increased dissipation factor at higher
temperatures is a good indicator of bushing problems. A high dissipation factor at
higher temperatures results in increased heating of the bushing, which in turn
increases losses causing additional heating, which increases losses even further until
the bushing finally explodes.
Fig. 12. Dissipation
factor (%) vs. temperature for OIP bushings with various moisture contents.
GE type U – Accelerated Ageing Tests
GE Type U bushings have exhibited a poor record of performance and provided utilities
with major asset replacement issues. In one research project initiated by the former
Ontario Hydro (now HydroOne) in Canada and Pacific Gas & Electric in the U.S., an
accelerated ageing program was performed on 6 x 155 kV Type U bushings involving
various diagnostic tests performed on the bushings. The bushings were subjected to
simultaneous thermal and electrical ageing.
During the ageing program, 66 kV (nominal line-to-ground voltage) was applied to the
bushings. Thermal ageing was accomplished by means of circulating power frequency
current through the bushings, starting at 1200 A and slowly increasing to 2000 A. Two
bushings (#3 & #4) failed at elevated current (1900 A) during the ageing program. The
bushings were selected for test on the basis of tan delta (power factor) measurement
results. Two units had low values, two units had high values and two had ‘intermediate’
values (see Fig. 13). Nameplate DF is assumed to be 0.25%. During ageing, periodic and
continuous diagnostic tests were performed, i.e. Tan delta, capacitance, DFR, PD, DGA
etc. Results from traditional test methods have been reported elsewhere and this
paper focuses only on DFR measurement results.
Fig. 13: Dissipation
factor (%) for the 6 GE Type U bushings at 20°C.
DFR Measurements
DFR measurements were performed at the beginning of the program. The bushings
were tested at various voltages (tip-up tests) and temperatures (see Table 3). Insulation
temperatures are estimates based on using DFR data at ambient temperature to
determine temperature dependence (ITC).
Table 3: DFR
Measurements On GE Type U Bushings
Fig. 14: Tan delta vs
frequency measured at 0.13 kV and ambient temperature.
Low voltage DFR results are presented in Fig. 14. Differences in dissipation factors
between bushings are much larger at low frequencies compared to 60 Hz values.
Temperature Dependence
Using the technique described, DFR data can be used to estimate temperature
dependence. The results are shown in Fig. 15 as tan delta temperature dependence for
the 6 bushings. Temperature dependence for bushings #5 and #6 corresponds to
factory data indicating that these bushings are in good condition. The other bushings
have higher temperature dependence. Bushing #2, classified as M/ ‘intermediate’ has
the same temperature dependence as the ‘bad’ bushings (#3 and #4) that failed during
the accelerated ageing test.
Table 5: Ct 7, Temperature
Discussion
The temperature dependence of the dissipation factor of an insulating material needs
to be considered when comparing measurement results between phases, with
previous tests or factory values. Historically, this has been done using average
temperature correction tables. Results are disappointing and asset owners therefore
try rather to perform diagnostic measurements at a specific (narrow) temperature
range. The new method of using frequency data and estimating temperature
dependence of the actual component offers an alternative to waiting for the ‘correct’
temperature – and then doing the test. It gives the possibility to have correct 20°C
reference values and also to make a correct comparison to previously measured non-
corrected data at other insulation temperatures. Temperature dependence can also be
used as an analysis method for bushings and instrument transformers. Comparing
measured temperature dependence with manufacturer data for temperature
correction will tell if the condition of the unit is good or not. In insulation diagnostics,
high tan delta values at low frequencies and large tan delta temperature dependence
(increased dissipation factor at high temperatures) are good indicators of insulation
deterioration.