0% found this document useful (0 votes)
24 views1 page

Design Computation:: Fire Pump Schedule

This document provides design computations and specifications for fire pumps and a jockey pump for a proposed 3-story commercial building. It includes pump capacity and head requirements, ideal and required horsepower calculations, water tank sizing of 8000 gallons, and a pump schedule listing pump types, capacities, motors, voltages and other details. Dimensions of a below ground cistern tank of 3.11m x 3.11m x 3.11m are also provided.

Uploaded by

lormel jame
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views1 page

Design Computation:: Fire Pump Schedule

This document provides design computations and specifications for fire pumps and a jockey pump for a proposed 3-story commercial building. It includes pump capacity and head requirements, ideal and required horsepower calculations, water tank sizing of 8000 gallons, and a pump schedule listing pump types, capacities, motors, voltages and other details. Dimensions of a below ground cistern tank of 3.11m x 3.11m x 3.11m are also provided.

Uploaded by

lormel jame
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

DESIGN COMPUTATION:

FOR FIRE PUMP :


LEGEND & SYMBOLS 167.16 GPM x 296.65 ft
HP =
3960 X Ep xEm

Pump Efficiency 70%


Motor Efficiency 80%

HP = 22.36 HP

IDEAL HP = 25 HP

FOR JOCKEY PUMP :


10 GPM x 296.65 ft.
HP =
3960 X Ep xEm

Pump Efficiency 70%


Motor Efficiency 80%

HP = 1.34 HP

IDEAL HP = 2 HP

WATER TANK CAPACITY :

FWT = Fire Pump cap. x Water supply duration x 150%

Light Hazard = 30 mins

GPM = 167.16

FWT = 167.16 GPM x 30 mins x150%


= 7522.2 GAL
= 8000 GAL

FWT total = 8000 GAL or 30 cu. m


CISTERN TANK BELOW GROUND LEVEL
= 3.11 m x 3.11 m x 3.11m

FIRE PUMP SCHEDULE


PUMP CAPACITY MOTOR POWER
SERVICE PUMP TYPE HEADS RPM REMARKS
NO. (GPM) (HP) VOLTS PHASE HERTZ

UL/FM
1.0 FIRE PUMP VERTICAL TURBINE PUMP 167.16 GPM 25 HP 3500 230 3 60
FIRE PUMP
296.65 PSI
UL/FM
2.0 JOCKEY PUMP VERTICAL TURBINE PUMP 20 GPM 2 HP 3500 230 3 60
JOCKEY PUMP

PROFESSIONAL SEAL PROJECT TITLE : SHEET CONTENTS : SHEET NO.

PROPOSED 3-STOREY COMMERCIAL GENERAL NOTES NO. DATE DRAWN BY: CHECKED BY:
MATERIAL AND SPECIFICATION
BENJAMIN V.D. ESTRALLADO JR., ME, PME, RMP, MEPME
HVAC DESIGNER / CONSULTANT
BUILDING WITH ROOF DECK
LOCATION :
LEGEND AND SYMBOL
DESIGN COMPUTATION
M-08
PRC No. : 0003062 VALIDITY : 11-18-2022 FIRE PUMP SCHEDULE
PTR No. : 6220695 DATE ISSUED : 01-11-2022
A.PICHON ST., MAGALLANES, MR & MRS. ALLAN BASARTE
PLACE : DAVAO CITY TIN : 124-950-263 DAVAO CITY OWNER

You might also like