Instruction Manual 6.

Mounting and Installation


Do not mount a damaged or polluted device.
1. Marking The device is designed for mounting on a 35 mm DIN mounting rail
according to EN 60715.
SMART Current Driver Mount the device in a way that the device is protected against mechanical
KFD2-SCD2-Ex1.LK, KFD2-SCD2-Ex2.LK hazard. Mount the device in a surrounding enclosure for example.
ATEX certificate: BAS 00 ATEX 7240 X The device fulfills a degree of protection IP20 according to IEC/EN 60529.
The device must be installed and operated only in a controlled
ATEX marking: environment that ensures a pollution degree 2 (or better) according to
1 II (1)G [Ex ia Ga] IIC IEC/EN 60664-1.
1 II (1)D [Ex ia Da] IIIC If used in areas with higher pollution degree, the device needs to be
1 I (M1) [Ex ia Ma] I protected accordingly.
ATEX certificate: FIDI 22 ATEX 0002X Do not mount the device in the dust hazardous area.
ATEX marking: 1 II 3G Ex ec IIC T4 Gc The device must be installed and operated only in an environment of
overvoltage category II (or better) according to IEC/EN 60664-1.
IECEx certificate: IECEx BAS 04.0014X Supply the device with a power supply that meets the requirements for
IECEx marking: safety extra-low voltage (SELV) or protective extra-low voltage (PELV).
[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Only connect or disconnect the connections within the specified ambient
Ex ec IIC T4 Gc temperature range.
North America Certifcates: E106378 (UL) Temperature range -5 °C to maximum permissible ambient
Class I, Division 2, Groups A-D, T4 temperature
Associated apparatus with intrinsically safe circuits for: Observe the installation instructions according to IEC/EN 60079-14.
Class I, Division 1, Groups A-D; Class II, Division 1, Groups E-G; If you install the device in safety-related applications, observe the
Class III requirements for functional safety.
Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc
Class I, Zone 2, Ex ec [ia Ga] IIC T4 Gc X Requirements for Cables and Connection Lines
Use only one conductor per terminal.
Pepperl+Fuchs Group Observe the permissible core cross section of the conductor.
Lilienthalstraße 200, 68307 Mannheim, Germany When using stranded conductors, crimp wire end ferrules
Internet: www.pepperl-fuchs.com on the conductor ends.
When installing the conductors the insulation must reach
up to the terminal.
2. Target Group, Personnel Use conductors with a rated temperature suitable for the application.
Responsibility for planning, assembly, commissioning, operation, If you use the device in an ambient temperature above 60 °C, use
maintenance, and dismounting lies with the plant operator. conductors rated for a temperature of at least 80 °C.
The personnel must be appropriately trained and qualified in order to carry Observe the tightening torque of the terminal screws.
out mounting, installation, commissioning, operation, maintenance, and Requirements for Usage as Associated Apparatus
dismounting of the device. The trained and qualified personnel must have
read and understood the instruction manual. If circuits with type of protection Ex i are operated with non-intrinsically
Prior to using the product make yourself familiar with it. Read the safe circuits, they must no longer be used as circuits with type of
instruction manual carefully. protection Ex i.
Observe the respective peak values of the field device and the associated
3. Reference to Further Documentation apparatus with regard to explosion protection when connecting intrinsically
safe field devices with intrinsically safe circuits of associated apparatus
Observe laws, standards, and directives applicable to the intended use (verification of intrinsic safety). Also observe IEC/EN 60079-14 and
and the operating location. IEC/EN 60079-25.
For mining applications, observe laws, standards, and directives Keep the separation distances between all non-intrinsically safe circuits
applicable to the operating location. and intrinsically safe circuits according to IEC/EN 60079-14.
The corresponding datasheets, manuals, declarations of conformity, EU- Observe the compliance of the separation distances between two
type examination certificates, certificates, and control drawings if adjacent intrinsically safe circuits according to IEC/EN 60079-14.
applicable supplement this document. You can find this information under Requirements for Equipment Protection Level Gc
www.pepperl-fuchs.com.
For specific device information such as the year of construction, The device must be installed and operated only in surrounding enclosures
scan the QR code on the device. As an alternative, enter the serial number that
in the serial number search at www.pepperl-fuchs.com. l comply with the requirements for surrounding enclosures according to
If you use the device in safety-related applications, observe the IEC/EN 60079-0,
requirements for functional safety. You can find these requirements in the
functional safety documentation under www.pepperl-fuchs.com. l are rated with the degree of protection IP54 according to
IEC/EN 60529.
4. Intended Use Connection or disconnection of energized non-intrinsically safe circuits is
only permitted in the absence of a potentially explosive atmosphere.
The device is only approved for appropriate and intended use. Requirements for Division 2
Ignoring these instructions will void any warranty and absolve
the manufacturer from any liability. The device must be installed and operated only in surrounding enclosures
The device is used in control and instrumentation technology that
(C&I technology) for the galvanic isolation of signals such as 20 mA and l comply with the requirements for surrounding enclosures according to
10 V standard signals or alternatively for adapting or standardizing signals. UL/CSA 60079-0,
The device has intrinsically safe circuits that are used for operating
intrinsically safe field devices in hazardous areas. l are rated with the degree of protection IP54 according to
IEC/EN 60529.
The device repeats the input signal from a control system to drive
HART I/P converters, electrical valves, and positioners located in a Ensure that the surrounding enclosure can only be opened with a tool.
hazardous area. Connection or disconnection of energized non-intrinsically safe circuits is
Use the device only within the specified ambient and operating conditions. only permitted in the absence of a potentially explosive atmosphere.
Only use the device stationary.
The device is an associated apparatus according to IEC/EN 60079-11. 7. Operation, Maintenance, Repair
The device is an electrical apparatus for hazardous areas of Zone 2. If you operate the device in safety-related applications, observe the
The device may be installed in the non-hazardous area. requirements for functional safety. In case of operating in low demand
If you use the device in safety-related applications, observe the mode, plan appropriate intervals for the proof test.
information for safety function and safe state. Do not use a damaged or polluted device.

5. Improper Use
Protection of the personnel and the plant is not ensured if the device
is not used according to its intended use.
If circuits with type of protection Ex i are operated with non-intrinsically
safe circuits, they must no longer be used as circuits with type of
protection Ex i.

DOCT-6593B / 2023-03 1/2


Do not repair, modify, or manipulate the device.
If there is a defect, always replace the device with an original device.
Requirements for Equipment Protection Level Gc

Connection or disconnection of energized non-intrinsically safe circuits is


only permitted in the absence of a potentially explosive atmosphere.
Only use operating elements in the absence of a potentially explosive
atmosphere.
Requirements for Division 2

Connection or disconnection of energized non-intrinsically safe circuits is


only permitted in the absence of a potentially explosive atmosphere.
Only use operating elements in the absence of a potentially explosive
atmosphere.

8. Delivery, Transport, Disposal


Check the packaging and contents for damage.
Check if you have received every item and if the items received are the
ones you ordered.
Always store and transport the device in the original packaging.
Store the device in a clean and dry environment. The permitted ambient
conditions must be considered, see datasheet.
The device, built-in components, packaging, and any batteries
contained within must be disposed in compliance with the applicable laws
and guidelines of the respective country.

DOCT-6593B / 2023-03 2/2