0% found this document useful (0 votes)
35 views6 pages

I-7043D Quickstart

The I-7043D is a 16 channel digital output module that supports non-isolated sink-type output. It has LED indicators to monitor channel status and supports Modbus RTU and DCON protocols for configuration via software. The module can be installed by connecting the analog outputs, RS-485 network, and power supply, then using the DCON utility software to configure settings like address and baud rate and send commands to control the digital outputs.

Uploaded by

Silvio Neto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views6 pages

I-7043D Quickstart

The I-7043D is a 16 channel digital output module that supports non-isolated sink-type output. It has LED indicators to monitor channel status and supports Modbus RTU and DCON protocols for configuration via software. The module can be installed by connecting the analog outputs, RS-485 network, and power supply, then using the DCON utility software to configure settings like address and baud rate and send commands to control the digital outputs.

Uploaded by

Silvio Neto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

I-7043D

16 Channel Digital Output Data Acquisition


Module
Quick Start Guide
Product Website:
https://www.icpdas-usa.com/i_7043_d.html
http://www.icpdas-usa.com/dcon_utility_pro.html

1. Introduction
The I-7043D offers 16 digital output channels, each of which are non-
isolated and support sink-type output using an open collector. There are
also options to enable both power-on and safe values. The I-7043DD has
16 LED indicators that can be used to monitor the status of DO channels.
The hardware specifications for the M-7043D are the same as the I-7043D,
and both support the Modbus RTU and DCON protocols, which can be
configured via software.

2. Terminal Assignment

I-7043D 16 Ch DO DAQ Module- QuickStart (Jul/2018)


ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
1
3. Block/ Wiring Diagram

4. Default Settings
Default settings for the I-7043D DIO modules are as follows:
。 Module Address: 01
。 DIO Type: Type 40
。 Baud Rate: 9600 bps
。 Checksum disabled
。 J3 set to INIT mode enabled for I-7043D/43D a

I-7043D 16 Ch DO DAQ Module- QuickStart (Jul/2018)


ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
2
5. Configuration
To install the module, follow the steps below:
1. Connect the analog output.
2. Connect the module to the RS-485 network using the DATA+ and DATA- terminals. If
the host is only equipped with an RS-232 interface, then an RS-232 to RS-485
converter will be required.
3. Connect the module to the power supply using the +Vs and GND terminals. Note that
the voltage supplied should be in the range of +10 to +30V DC.

I-7043D 16 Ch DO DAQ Module- QuickStart (Jul/2018)


ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
3
4. Open DCON utility pro
click on COM port(first icon).
It can select multi-options such as Baud Rate, Protocol, Checksum, and Format to
search module. The default settings for the module can be found in Section 3. Click OK
after selecting the COM port setting.

I-7043D 16 Ch DO DAQ Module- QuickStart (Jul/2018)


ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
4
5. DCON utility pro will search for the selected COM port according the setting
previously set. DCON Utility Pro supports DCON and Modbus protocol for all ICPDAS
and the others modules.

6. Configuration I/O module setting on PC

I-7043D 16 Ch DO DAQ Module- QuickStart (Jul/2018)


ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
5
7. For I-7000 modules, DCON utility pro terminal can send command to the module.
See user manual Sections 2 for details command.

Configure the module: sending the %AANNTTCCFF command. See user manual
Section 2 for details.

Read data from the input channels: send either the #AA or #AAN command to the
module.

8. If user doesn’t know command, user can select Address and ID, it will show some
refer commands as below. User can select necessary command to test or debug
modules.

I-7043D 16 Ch DO DAQ Module- QuickStart (Jul/2018)


ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717