Structural Notes:: Schedule of Columns

1. A schedule of columns and beams listing their sizes, reinforcement details, and spacing. The column sizes are 300x300mm with 2-16mm diameter longitudinal bars and 10mm diameter stirrups spaced at various intervals. 2. Beams are listed as 12450mm with 6-16mm diameter main bars and 10mm diameter stirrups. 3. Notes indicate a 10mm gravel bed under the columns.

Uploaded by

Zhey Garcia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views1 page

Structural Notes:: Schedule of Columns

1. A schedule of columns and beams listing their sizes, reinforcement details, and spacing. The column sizes are 300x300mm with 2-16mm diameter longitudinal bars and 10mm diameter stirrups spaced at various intervals. 2. Beams are listed as 12450mm with 6-16mm diameter main bars and 10mm diameter stirrups. 3. Notes indicate a 10mm gravel bed under the columns.

Uploaded by

Zhey Garcia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

1 2 3 1 2 3

7788 7788 3
1688 6100 1688 6100
S 1 SCHEDULE OF COLUMNS
3050 3050 3050 3050
COLUMN
(SEE DETAILS)
REMARKS COLUMN SIZE
SECTION REBARS LAT. TIES SPACING
1.20 GRADE LINE

(MM)
E E E T1 T1 E
WF1 C1-F1 WF1 C1-F1 WF1 C1-F1
2 - 16mm ø 10mm ø STIRRUPS SPACED;
C-1 300X300 3 @ 50mm, 4 @ 100mm,

WF1

WF1
WF2
3050

3050

3050

3050
RB RB 2 - 16mm ø 5 @ 150mm, REST @ 200mm O.C.

1.20
WF1 WF2 WF2 RB RB COLUMN
D D D T1 T1 D 4
C1-F1 C1-F1 C1-F1
S 1 SCHEDULE OF BEAMS

WF2

WF1
WF1
3050

3050

3050

3050
RB RB RB
REMARKS BEAM STIRRUPS
@ SUPPORT @ MIDSPAN
SIZE (MM) SPACING 10mm GRAVEL BED
RB 6-16mm ø MAIN BARS 6-16mm ø MAIN BARS
C C C C
12450

12450

12450

12450
BOTHWAYS
C1-F1 C1-F1 C1-F1
T1 T1 2 - 12mm ø 2 - 12mm ø 10mm ø STIRRUPS SPACED;
BOTHWAYS

RB 200X300 3 @ 50mm, 4 @ 100mm, PLAN F1 SECTION


2 - 12mm ø
WF2

2 - 12mm ø 5 @ 150mm, REST @ 200mm O.C.


3050

3050

3050

3050
WF1

WF1
9400

9400
RB RB RB
15 SETS
RB RB
B C1-F1 C1-F1 C1-F1
B B T1 T1 B COLUMN
(SEE DETAILS)
GRADE LINE
100 mm THK SLAB ON FILL 1.20
WF1

WF1
3300

3300

3300

3300
w/10mm Ø REBAR SPACED
@ 400mm O.C. BOTHWAYS RB RB

3 - 10mm Ø Cont. Bars W/ 10mm 3 - 10mm Ø Cont. Bars W/ 10mm 3 - 10mm Ø Cont. Bars W/ 10mm
WF1 WF1 RB RB Ø Cleats spaced @ 400mm O.C. Ø Cleats spaced @ 300mm O.C. Ø Cleats spaced @ 400mm O.C.
A C1-F1 C1-F1 C1-F1
A A T1 T1 A

1.20
3050 3050 3050 3050 COLUMN
1687 6100 1687 6100
7787 7787

1 2 3 1 2 3 125/100 mm Thk. CHB w/ 10mm


Ø Vert. Bar spaced @ 800mm
O.C. & 10mm Ø Horz. Bar on
125/100 mm Thk. CHB w/ 10mm
Ø Vert. Bar spaced @ 800mm
O.C. & 10mm Ø Horz. Bar on
125/100 mm Thk. CHB w/ 10mm
Ø Vert. Bar spaced @ 800mm
O.C. & 10mm Ø Horz. Bar on
every 3rd Layer of CHB every 3rd Layer of CHB every 3rd Layer of CHB 10mm GRAVEL BED
6-16mm ø MAIN BARS
1 FOUNDATION PLAN 2 ROOF FRAMING PLAN PLAN PLAN PLAN BOTHWAYS
6-16mm ø HORIZ. BAR
BOTHWAYS
S 1 SCALE 1 : 100 MTS. S 1 SCALE 1 : 100 MTS. WALL REINFORCEMENT
125/100 mm Thk. CHB w/ 10mm
Ø Vert. Bar spaced @ 800mm CHB WALL
125/100 mm Thk. CHB w/ 10mm PLAN F2 SECTION
O.C. & 10mm Ø Horz. Bar on DOWEL BARS TO MATCH Ø Vert. Bar spaced @ 800mm
every 3rd Layer of CHB CHB WALL VER. BARS
NGL NGL O.C. & 10mm Ø Horz. Bar on
every 3rd Layer of CHB

STRUCTURAL NOTES:

400
10mmØ TRANSVERSE
BOTTOM BARS SPACED
@ 300mm O.C. 100 3 - 10mm Ø Cont. Bars W/ 10mm
5 COLUMN FOOTING DETAILS

100
Ø Cleats spaced @ 400mm O.C.

200

200
3 - 10mm Ø Cont. Bars W/ 10mm
NTS

100
S 1
A. GENERAL : Ø Cleats spaced @ 400mm O.C.

450 400 3-10mmØ LONG'L


450
1. ALL STRUCTURAL PLANS ,SPECIFICATIONS, AND SHOP DRAWINGS, SHALL MEET ALL BOTTOM BARS
50mm thk COMPACTED
GRAVEL BEDDING

REQUIREMENTS SET BY THE NATIONAL BUILDING CODE, NATIONAL STRUCTURAL CODE OF THE SECTION SECTION SECTION
PHILS., AND THE LOCAL CODE OF THE CITY / MUNICIPALITY / DISTRICT OF THE SITE. WF-1 WF-2 WF-3
4 - 12mm Ø ROOF BEAM w/ STIRRUPS
2. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE WALL FOOTING DETAILS SPACED: 3 @ 50mm, 4 @ 100mm, 5 @
6
SHOWN OR NOTED, MODIFY TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL CONDITIONS. S 1 NTS
150mm, REST @ 200MM 0.C.
3. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEELS, MISC. 2 - 2" X 2" X 41" KING POST,
IRON, PRE-CAST CONCRETE, ETC., SHALL BE SUBMITTED FOR THE ENGINEER / DESIGNER'S TOP AND BOTTOM CHORD
APPROVAL BEFORE FABRICATION. 2 - 1 21" X 1 21" X 41" WEB MEMBER
4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TI PROVIDE ADEQUATE SHORING &
CORRUGATED TYPE
BRACINGS OF THE STRUCTURE FOR ALL LOADS THAT MAYBE IMPOSED DURING CONSTRUCTION. ROOFING
B. CONCRETE :
1 21 " X 1 21 " X 41"
1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM WITH THE LATEST BUILDING CODE OF ANGULAR CLEATS
AMERICAN CONCRETE INSTITUTE (ACI-318). CHB
GA. 24" CUT BOX
2. ALL CONCRETE SHALL DEVELOP A MIN. COMPRESSIVE STRENGTH AT THE END OF TWENTY
GUTTER
EIGHT (28) DAYS (MAX. PERIOD):
LOCATION 28 DAYS MIXING
STRENGTH PROPORTION
FOOTINGS 3,000 PSI CLASS B / 1 : 2
:4
8 ROOF BEAM DETAILS
3. IN GENERAL THE LATEST EDITION OF ACI-315, MANUAL OF STANDARD PRACTICE DETAILING 7 TRUSS DETAILS S 1 NTS
REINFORCED CONCRETE STRUCTURES SHALL BE ADHERED TO UNLESS OTHEREWISE SHOWN S 1 NTS

REPUBLIC ACT 9266


This drawing as an instrument of service is the property CERTIFIED BY: PROJECT TITLE: CLIENT: SHEET CONTENT: SHEET NO:
of Zarc PH and as such must not be in part or in whole permit anyone to copy or FOUNDATION PLAN
duplicate said document without
PRC REG. NO:
ROOF FRAMING PLAN 3
permission. All drawings must be returned when no longer in use. TIN: STRUCTURAL NOTES S-1 4
PRESIDENTIAL DECREE NO. 49 PTR NO:
PROPOSED BUNGALOW SCHEDULE OF COLUMNS & BEAMS
WALL FOOTING DETAILS
"Protection of Intellectual Property" Works of Art, Architecture, Models & DATE ISSUED: MR. REYJER TABACON RAMONES TRUSS DETAILS DESIGN BY: Zarc PH
Designs are Creative works and considered as Intellectual Properties of its COLUMN DETAILS
Creator, Architect, Engineer or Author. STRUCTURAL ENGINEER PLACE ISSUED: LOCATION: PUROK 7, BARANGAY PANTOC, GABALDON, NUEVA ECIJA OWNERS APPROVAL ROOF BEAM DETAILS DATE: AUGUST 23, 2023