This document provides release notes for a software update for Johnson Controls' 4100ES and 4010ES fire alarm control panels. It includes updated programmer, executive, and slave files, as well as notes on functional changes and fixed defects. The update requires a software license to run the programmer and adds a new 4100-ESTSD touch screen display card. Several defects are listed as fixed relating to programming, networking, and specific cards. Users are instructed to find installation files and documentation in the listed directories after downloading the update.

Uploaded by

RuthMarlo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views3 pages

New 601

This document provides release notes for a software update for Johnson Controls' 4100ES and 4010ES fire alarm control panels. It includes updated programmer, executive, and slave files, as well as notes on functional changes and fixed defects. The update requires a software license to run the programmer and adds a new 4100-ESTSD touch screen display card. Several defects are listed as fixed relating to programming, networking, and specific cards. Users are instructed to find installation files and documentation in the listed directories after downloading the update.

Uploaded by

RuthMarlo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Johnson Controls Technical Support

May 21, 2020

Software Release

Product: 4100ES, 4010ES


Programmer: ESProgrammer_6.01.exe
Executive: ES_6.01.bin
Slaves included: 4010IDNETPLUS_3.12.13
(new files in bold) Amp_20203 (cards 566-205, -206, -208 use with > 28 speakers/circuit)
Amp_2.03.03 (cards 566-205, -206, -208 use with up to 28 speakers/circuit)
Amp2_3.02.05 (cards 566-521, -523, -524)
AudAna_20101
AudDig_10502 (card 566-033)
AudDig2_20102 (card 566-409)
BMUX_10102
BNIC_1.01.03
bootloader_1.01_cpu801-estsd
CPUBoot_2.04
EBOOT_1.01.03
EOS_1.01.03
EPS_1.08.03
ESNET_1.03
ESNET_EBOOT_1.01
ESNET_EOS_1.03
ESPS_1.01.01
ESS_1.08.03
estsdui_1.01_cpu801-estsd
ESXPS_1.01.01
filesystem_1.01_cpu801-estsd
FUI_1.05
FUIBoot_104
IDNAC_1.01.04
IDNET_3.12.13
IDNET1PLUS_3.12.13
idnet2_2.02.02
IDNETPLUS_3.12.13
kernel_1.01_cpu801-estsd
lmc_3.01.02
MSS_3.12.11
MSSI_3.12.13
MSS2_1.01
mxdloop_2.02.01
NAC_1.01.02
Phone_1.04.01
rps_3.12.11
SecurityZoneRelay_1.02.03
SPS_204 (for Rev E and earlier boards)
sps_3.12.13
TFXLoop_10103
tic_3.01.02
TIC2_1.01.05
TPS_1.05.05
XALIC_10105

1
XBC_10604
XPS_3.12.11
XSIG_101
Compatibility See SB11002 (in C:\4100ESINFO)

After downloading:
Find the Programmer installation file in C:\4100ESProg
Find the BIN files in C:\4100ubin\Rev6-01
Find the documentation in C:\4100ESinfo
To Install the Programmer go to C:\4100ESProg and double click on ESProgrammer_6.01.exe

ES Programmer 6.01

DBF Revision = 186


CFIG Format - 109

Functional Changes:
• A software license is required to run the programmer. The Dongle support has been discontinued.
• Add new card 4100-ESTSD – Touch Screen Display

Fixed Defects:
738837 “UNACTIVATED NEW CONFIGURATION AVAILABLE” trouble stays on until the download of
the file is completed. (Updated HELP).
772775 LEGACY: Error Cannot find ‘/massStorage’. Check the spelling and try again is displayed upon
a transfer.
989050 IDNac Point Editing reports DCAI error when no DCAI points are programmed on the card.
996321 Cannot add SIGIAMs to WalkTest Group
996532 Digital/Analog Audio Controller card can be added to Unit0 Box1 Bay1 by drag and drop but
not through the Add Card dialog. (it should not be allowed)
998793 In Programmer on an MXLoop Card, under an 850PH device there is a discrepancy between
the column view vs the properties view
998830 4100-3208 (4pt, 10A Relay Board) should NOT be allowed top of an ES-PS/ES-XPS
1013424 Add the ability to use the F9 Key for Taglist when editing Custom Control
1013588 ESNET Type Network build error on 4120 Network. #Error P10020
1019143 Add 4100-ME0504 Power Supply to 4100ES jobs

Other Changes:
• None

ES_6.01.bin

Functional Changes:
• None
Fixed Defects:
1013132 4100ES master piezo has spurious glitches when using scope to capture output
996468 Panel with many PIC32 Led/Switch Controllers may crash at startup
(ERROR 24 TRANSMIT CRASH)

2
idnet2_2.02.02.bin

Functional Changes:
• None
Fixed Defects:
1008978 IDNet device could miss the 1st data poll right after group poll response
1009110 IDNet2 randomly sends out incorrect broadcast sync packet on 4009As
1013082 It sometimes took 5+ seconds for the notification to turn on from when the HPHOTO
detector LED turned on

TIC2_1.01.05.bin

Functional Changes:
• None
Fixed Defects:
• None

SecurityZoneRelay_1.02.03.bin

Functional Changes:
• None
Fixed Defects:
1008985 Slave exec download fails