EE4533 Part II2021
EE4533 Part II2021
PROTECTION
BY
Wang Peng
School of EEE, Block S2, NTU
Office: S2-B2c-104
Phone: 6790-6856(o)
Email: [email protected]
1
INTRODUCTION
• A power system is a three-phase system because of three
voltage sources produced by three-phase generators and three
phase transmission lines to deliver power to three phase loads.
(Can you draw a typical three phase circuit of a power system???)
• A power system usually operates in a normal balance
operating condition (what is balance condition?), a single-phase
diagram (why??) is used in power system analysis and
calculations.
• A power system “sometime” operates in an abnormal (three
phases are unbalanced) condition when a unbalanced short
circuit occurs (designated as a unbalanced fault). In this case,
the fault must be isolated (how?) and (a single-phase diagram
can still be used to analyze current and voltage??).
• The main objectives of Part II:
To study methods for analyzing power systems under
various abnormal (unbalanced) conditions.
To study techniques for protecting power system
equipment and network when a abnormal condition occurs.
2
COURSE OUTLINE
1. Basic Concepts of Power System Analysis (Review)
2. Fault Analysis (voltages and currents calculation)
3. Power System Protection Techniques
References:
1. Power System Analysis, John J. Grainger and William
D. Stevenson, JR., McGraw-Hill, 1994.
2. Power system analysis, Arthur R. Bergen, Vijay Vittal,
Prentice Hall, Inc. , 2000.
3. J. Lewis Blackburn, “Protective Relaying Principle and
Application,” Marcel Dekker, Inc. New York, 1997.
4. GEC Measurements, “Protective Relays Application
Guide,” The General Electric Company, p.l.c., of England,
London & Wisbech, 1987.
5. P. M. Anderson, “Power System Protection,” McGraw-
Hill, IEEE Press, New York, 1999.
3
1. Basic Concepts of Power System Operation and Analysis
1.1 Three Phase Generators(three balanced voltage sources)
Three voltage sources in a power system are always balanced
(Circuit?). There is 120 phase difference between two sources.
o
4
1.2 Three-phase balanced power system (normal operation)
When a three-phase generator supplies three identical loads through
three identical lines, the system as follow is called the balanced system.
Ia N
ZL Z load
S Ib N
Ia + Ia
Va
Va Z
Ic
-
IN ZN S
VNS Single phase diagram
Three phase diagram (Y connection)
VNS VNS Va V Vb V Vc
KCL at N : I N I a I b I c 0 NS NS 0
Z N Z L Z load Z L Z load Z L Z load
1 1 1 1 1
VNS Va Vb Vc
Z N Z L Z load Z L Z load Z L Z load Z L Z load
VNS 0 There is no current through ZN N and S can be
connected together. Each phase becomes a separate single loop
(a single phase diagram).
5
Example 1.1: A Y-connected load of (2+j3) per phase and a delta-
connected load of (6+j6) per phase are connected in parallel to a
three-phase, 400V, 50Hz supply. Calculate the current in each supply
line, the total power supplied and the overall power factor.
Solutions: *All delta connected components must be converted to Y
connection to draw a single phase diagram.
6 j6
ZY 2 Z 2 / 3 2.82842745o
3 Ia ZY 1
ZY 1 2 j 3 3.6055556.31 o
Z2 Z2
Vab
ZY 1 ZY 1
Z ta ZY 1 / / ZY 2 1.59266649.97 o Ib
Z2
400V Ic
Vab 400V , Van 0 230.940 Y
3
V I
I a an 145.002 49.97 o ZY 1 ZY 2
Z ta Van a
p. f . cos49.97 0.6432 Ib
ZY 1 ZY 1 ZY 2 ZY 2
6
1.3 Unbalance three-phase systems (abnormal operation)
When phase-a load is shorted (called fault) in the following three
phase system, the system becomes unbalanced (abnormal). The
system and can be solved by KCL and KVL equations as follows.
KCL at node N: Ia
I N I a Ib Ic
V VNS S Ib Ia
N
Ia a
ZL
Vb VNS Ic
Ib
Z L Z load
Vc VNS
Ic IN
Z L Z load VNS
VNS Va VNS Vb VNS V VNS
I N I a Ib Ic c
ZN ZL Z L Z load Z L Z load
1
V Vb Vc 1 1 1 1
VNS a 0
L
Z Z L Z load Z L Z load Z N Z L Z L Z load Z L Z load
7
Example 1.2 The phases-b and c of a three-phase power system are
short circuited to the Ground as below. Calculate the voltage from
the generator terminal to ground and the current If, where
VAN Vrms 00 , VBN Vrms 1200 , VCN Vrms 1200
Vrms
X
120o 240o 90o Note :
1
90o
jX
rms 210o 330o
V
X
8
1.4 Thevenin Equivalent Viewed from Bus k (Review)
V3 3 n
Vn
Z th
V2 2
transmission
Vk
Vth Vk
+
V1 1 network k
k
-
0
Reference
0
9
Example 1. 3: Find the Thevenin Equivalent seen from Bus 3 of the
following power system.
j 0.10
∆-Y transformation:
Za j 0.20 j 0.20
Z ab Z ca j 0.9 j 0.9
Zb Zc
Z bc 100 pu 100 pu
Z 3,th
Z ab Z ca Y
Za Z ab Z bc
Zb
Z ab Z bc Z ca Z ab Z bc Z ca j 0.04 j 0.04
ZC ? Z1 Z2
j 0.9 Z 3 j 0.08
j 0.20 j 0.10 j 0.9
Z a Zb j 0.04
j 0.20 j 0.20 j 0.10
100 pu Z 3,th 10 pu 0
Z c j 0.08?
Thevenin impedance from bus 3:
Z 3,th j 0.08 ( j 0.04 j 0.9) || ( j 0.04 j 0.9) j 0.04 j 0.04
j 0.5500 j 0.9 j 0.08 j 0.9
Thevenin voltage: V3,th 10
0
10
1.5 Important concepts (to add more??)
11
2. Fault Analysis
2.1 Faults types
A fault is an event which causes system unbalance operation. There
are open or short circuit faults. The short circuit faults at bus k can
be classified into symmetric (Type 4) and unsymmetrical faults
(Types 1, 2 and 3) as follows. Zf is the short circuit impedance.
a a
Ifa Ifa
Zf
b b
Ifb Ifb Type 2
Type 1 Zf
c c
Ifc Ifc
12
2.2 How to analyze a unbalanced power system?
When a double phase fault occurs between phase a and b in the
following system, the system becomes unbalanced.
Ia
S Ib N
Ic
IN 0
VNS 0
13
2.3 Sequence components of 3 unbalanced phasors
It has been proven mathematically that an unbalanced set of three-
phase voltages or currents could be broken down into the three
balanced sequence sets each with three-phase sequence components.
Or: three unbalanced voltages are the sum of the respective balanced
sequence components as shown in the following phasor diagram or in
equation (1). V (1)
A VC
VA V V V
(0) (1) (2) Introducing phasor constant a=11200 ,
A A A
The properties of a are as follows:
VB VB(0) VB(1) VB(2) (1)
a2 =a a=11200 11200 12400
VC VC(0) VC(1) VC(2)
a3 =1; a4 a; 1+a+a2 =0
14
Positive-sequence components: A set of three balance positive-
sequence components have the same magnitude, displaced from
each other by 1200 with the sequence ABC. ( a=11200 a2 =12400 )
VA(1) V 0o
VB(1) =VA(1) 1 1200 VA(1) 12400 a 2 VA(1) V 120o
VC(1) =VA(1) 1 2400 VA(1) 11200 aVA(1) V 240o
Note: VA(1) VB(1) VC(1) 0
Negative-sequence components: A set of three balance negative-
sequence components have the same magnitude, displaced from
each other by 1200 with the sequence ACB.
VA(2) V 0o
VB(2) VA(2) 11200 =VA(2) 1 2400 aVA(2) V 120o
VC(2) =VA(2) 1 1200 VA(2) 12400 a 2 VA(2) V 240o
Note: VA(2) VB(2) VC(2) 0
Zero-sequence components: A set of three balance zero-sequence
components consisting of three phasors equal in magnitude and
phase.
VA VB VC
(0) (0) (0)
Note: VA(0) VB(0) VC(0) 3VA(0)
15
(Replace sequence components of phase B and C by sequence elements
of phase A in (1):
Multiply both side of (2) by A1 : (find sequence voltages from phase
voltages)
VA0 VA 1 1 1 VA 1 1 1
1
1 1 1
a 2 VB (3) where A-1 = 1 a a2
VA A VB 3 1 a 3
VA 2 VC 1 a 2 a VC 1 a a
2
1 1 1
Or VA(0) (VA + VB + VC ) VA(1) (VA + aVB + a2VC ) VA(2) (VA + a2VB + aVC )
3 3 3
16
Example 2.1: A three-phase line feeding a balanced Y connected
load has phase b opened. The load neutral is grounded, and the
unbalanced line currents are shown in the figure.
Calculate
(a) the sequence currents in phase a; I A 2000
A
(b) sequence currents in phase b and IB IC 201200
(c) the neutral current IN.
C
ZY ZY
17
b) The sequence components in phase b:
B I A 6.66660
I(0) (0) 0
(A)
B a I A 13.333240
I(1) 2 (1) 0
(A)
B aI A 6.666( 60 120 ) 6.66660
I(2) (2) 0 0 0
(A)
I B I(0)
B I B I B 6.66660 13.333240 6.66660 0
(1) (2) 0 0 0
18
Summary
A unsymmetrical set can be decomposed into three symmetrical sets:
VC(1) -ve-sequence
VA V V V
(0) (1) (2)
VA(1)
A A A
VA(2)
VB VB(0) VB(1) VB(2) + +
VB(2)
VA(0) VB(0) VC(0)
VC VC(0) VC(1) VC(2) +ve-sequence
VC(2) zero-sequence
VB(1)
Transform phase components to sequence components:
VA(0) 1 1 1 VA VA VB(0) = VA(0) VC(0) = VA(0)
(1) 1
VA 3 1 a a 2 VB = A -1 VB VB(1) = a 2 VA(1) VC(1) = aVA(1)
VA(2) 1 a 2 a VC VC VB(2) = aVA(2) VC(2) = a 2 VA(2)
VA 1 1 1 VA(0) VA(0)
V
1 a 2
a VA(1) A VA(1)
B
VC 1 a a VA(2)
2
VA(2)
19
2.4 Sequence circuits of power system components
20
2.4.1 Sequence circuits of a 3-phase Y-connected load with neutral
impedance ZN
a) The relationships of unbalanced phase voltages and currents:
KVL: VAg ZY I A Z N I N ZY I A Z N (I A I B IC ) IA
A
( ZY Z N )I A Z N I B Z N IC (1) +
C IC
VBg Z N I A ( Z N +ZY )I B Z N IC (2) ZY ZY
VCg Z N I A Z N I B ( ZY Z N )IC (3) VAg
N IN
Matrix form of KVL equations (1)-(3):
ZY ZN
VAg ZY Z N ZN ZN IA IA B IB
VBg Z N ZY Z N Z N I B Z I B (4) g
V Z ZY Z N IC IC
Cg N ZN Three phase circuit
VAg VAg
(0)
IA I(0)
A
VAg(0)
I(0)
A
(1) I A I(1) (6) (1) (1)
V = A VAg (5) A V
Ag A -1
Z A IA (7)
Bg B
VCg VAg
(2)
IC I(2)
A
VAg
(2)
I(2)
A
21
b) Multiplying A-1ZA in (7), the relationship of sequence voltages,
currents and impedances are as:
VAg
(0)
ZY 3Z N 0 0 I(0)A Z0 0 0 I(0) A
(0)
VAg ( ZY 3Z N )I(0)A Z 0IA
(0)
(1)
VAg 0 ZY 0 I(1) 0 Z1 0 I(1) or V (1)
Z I (1)
Z I (1)
(8)
A A Ag Y A 1 A
VAg
(2)
0 0 ZY I(2)
A
0 0 Z 2 I(2)
A
VAg(2)
ZY I (2)
A Z I
2 A
(2)
22
Example 2.2: A three phase Y connected load
with neutral impedance ZN =j1Ω. ZY =j1Ω. If A I A 200o
three phase unbalanced currents are supplied IC 20120o
C
to the three phase loads, ZY ZY
a) Determine three sequence currents.
b) Determine three sequence impedances. N IN
c) Calculate sequence voltages for phase-a. IB 0 ZY ZN
d) Calculate voltage from neutral to ground. B
g
Solutions:
a) I(0) 1 (I + I + I ) 1 (2000 0 201200 ) 6.666600 (A)
A A B C
3 3
1 1
I(1)
A (I A + a I B + a 2
I C )
20 0 0
0 20(120 0
240 0
)
13.3330 0
(A)
3 3
1 1
I(2)
A (I A + a 2
I B + a I C ) 2000 0 20(1200 1200 ) 6.666 600 (A)
3 3
b) Sequence impedances: Z1 Z 2 ZY j1 ; Z 0 ZY 3Z N j 4
c) Sequence voltages: VAg Z1I A j1 13.333 j13.333 (V)
(1) (1)
(2)
VAg Z1I (2)
A j1 6.666 60 6.66630
o o
(V)
(0)
VAg Z 0 I (0)
A j 4 6.666 60 o
26.664 150 o
(V)
A Z N I N 3I A j 3 6.66660 19.998150
d) VN =I N Z N 3I (0) (0) o o
(V)
23
2.4.2 a Y-connected load without neutral impedance
IA A IA
A
C IC
C IC
ZY ZY
ZN ZY ZY
N IN
N
ZY ZN
ZY B IB
B IB
g
(0) ZY (1) ZY (2)
A IA N A IA N A IA
ZY N
(0) (1) (2)
VAg 3Z N VAg VAg
AI A 0 Y
(0) Z (1) ZY (2)
A IA
ZY
N N A IA N
(0)
VAg ZN (1)
VAg (2)
VAg
24
2.4.3 a 3-phase Δ-connected balanced load
IA A IA
A
1 C IC
I AB ZY Z
Z ZY ZY
Z 3
ICA Z
IC N
C
I BC
IB ZY
B B IB
Sequence circuits: ZN
(2) Z / 3
A IA Z / 3
(1)
A IA 0 A IA
(0)
25
2.4.4 Sequence circuits of a synchronous generator
Using the similar method as (2) I(0)
I (1)
I a a
2.4.1, the sequence circuits a a a a
are as: (See appendix)
Z
a Z 2
Ia V 1
(1)
Z Vaag(2) n (0)
0
V aag Vag
Va
Z E an 3Z n
Reference
Reference
E Reference
Z n I an
n n
E bn Positive, negative and zero sequence circuits
g
E cn
Ib Vag Ean ZI a Ean Z1 I a
1 1 1
Z Z Sequence
c b Vag ZI a Z 2 I a
2 2 2
circuit
Ic equations:
Vag Z 3 Z n I a Z 0 I a
0 0 0
26
2.4.6 Sequence circuits of transformers
A transformer is connected between two buses. Three windings on each
side can be connected into Y or ∆. Therefore, there are six type
transformers based on connections.
Type 1: Three-phase Y-Y transformer with the two grounded neutrals. Z
is the total impedance of transformer refer to primary side.
Based on dot convention: I A and I a are in phase. VAn and Van are in phase.
Phasor diagram:
IA Ia VAn Van
Z A IA Ia
Voltage equation: A' a
Z B NA Na
VAN N A B' b
Van N a IB N N VAN Van n Nb Ib
B
Current equation: IN Z N Zn In
I A Na NC g
Z C IC Nc Ic
Ia N A C' c
27
a) The relationship of phase currents, voltages and impedance of the Y-Y
transformer under per unit system:
Z A IA N1 : N 2 Ia
Under per A' a
+ +
unit system: Z B VA’g Vag
B' b
VAN Van IB N VAN Van n Ib
I A Ia IN Z N Zn In
IC - g - Ic
Z C
KVL equations: C' c
Primary side: VA' VA' g VAN ZI A Z N I N VAN Z Z N I A Z N I B Z N I C
Secondary sides: Va Vag Van Z n I n Van Z n I a Z n Ib Z n I c
28
VA' Va VA 0' Va 0 IA I A 0
Replacing phase voltages 1 1
1
and currents in (4) by the VB ' Vb A VA' Va (5) I B A I A (6)
sequence voltages (5) VC ' Vc 2 2 IC 2
A'
V Va I A
and currents (6),
equation (4) becomes:
VA 0' Va 0 Z Zm Zm I A
0
1 s
1
A VA' Va Zm
1
Zs
Zm A I A (7)
2 2 Z Z s I A 2
A'
V Va m
Zm
29
c) From (9), sequence circuits and equations for two neutrals-grounded Y-Y
transformer are as follows:
Positive-sequence
Z1 Z
(1)
VA' Va(1)
VA1' Va1 Z1 I A1
Reference
A' I(2)
A
Z I(2)
a
A' I(0)
A Z 3Z N 3Z n I(0)
a
30
Type 2: Y-Y transformer with one neutral-grounded
I a0
1
I a I b I c 0
I A 0 I a 0
3 0 0
A'
*Due to the magnetic
N 2 0 Va(0)
coupling I A
0 (0)
Ia 0 . VA'
N1
Reference
Zero-sequence circuit
31
Type 3: ∆-∆ connected transformer
The positive and negative sequence circuits for all the transformer are the
same because they are only related to winding impedance Z.
However, the zero sequence circuit depends on the routes of zero
sequence currents and magnetic couplings.
32
Type 4: Y-∆ transformer with grounded Y
A' (0) (1) (2)
A I A =I A +I A +I A Ia =I(0) (1) (2)
a +I a +I a
Magnetic coupling: N1 : N 2
a
A N 2 I ab
N1I(0) (0) Iab
VANVab
(0) (1) (2)
B I B =I B +I B +I B Ic =I(0) (1) (2)
NI (0)
1 B N I (0)
2 bc
B' I N =3I(0)
A I bc Ica c +I c +I c
N
ZN c
NI (0)
1 C N I (0)
2 ca (0) (1) (2)
I b =I(0) (1) (2)
C' C IC =IC +IC +IC b +I b +I b
33
Type 5: Y-∆ with ungrounded Y transformer
There are no zero-sequence currents in Y
side because of KCL.
IA Ia
I A I B IC 0
IB
I A I B I C 0
0 1
IA N
3 Ib
IC
Similarly, there are no zero-sequence
currents in ∆ side terminal because of Ic
KCL.
I a Ib Ic 0
1
I a 0
3
I a Ib Ic 0 I(0)
A Z I(0) 0
a
I A 0 I a 0 I ab
0
0
Zero sequence circuit:
34
Summary of sequence circuits of three-phase transformers:
Type Symbol Connection diagram Zero-sequence , +-tive circuits
Z 3Z N 3Z n Z
P Q
1 ZN Zn
N
Z N Zn
n
Reference Reference
Z
2 ZN
N
ZN
n
Reference Reference
3
N n
Reference Reference
4 Reference
Reference
Z 3Z N
Z
5 N
ZN Reference
Reference
Z
6 N
Reference
Reference
35
2.4.7 Sequence circuits of transmission lines
The positive and negative sequence impedances are the same. However,
zero sequence impedance is larger than the positive sequence
impedance because of different sequence magnetic fields.
36
The sequence circuits of major components for fault analysis
Symbol Zero-sequence , +-tive circuits
Z
Z 3Z N 3Z n
ZN Zn
Reference Reference
Z
Z 3Z N
Reference Reference
Z
Other
connections of
transformers Reference Reference
Transmission Z0 Z1 Z 2
line Reference Reference
P P
Z0 Z1
jX N + Z2
P 3Z N Reference
E an Reference Reference
-
Z0 P P
Other Z1
connections + Z2
of machines Reference E an Reference Reference
-
37
2.5 Sequence circuits of a power system
Example 2.3: Sketch the positive-, negative- and zero-sequence equivalent circuits for
the following power system. (Connect the sequence impedances of the components to
the corresponding buses to form the system sequence circuits)
Bus 2
Zero
Negative
(2) (2) ZT(0)3 ZT(0)6
Z Z
jX G(2)1
T3 T6
jX G(2)2 jX G(0)1 jX G(0)2
Z L(2)2 Z L(2)3 Z L(0)2 Z L(0)3
3Z N
Z (2)
T4
Z (2)
T5
ZT(0)4 ZT(0)5
38
2.6 Thevinin equivalent circuit of a sequence circuit seen from bus k
The Thevinin equivalent circuits seen from a bus of the sequence circuits are
very important for fault analysis. As we discussed in section 1.4, any complex
circuit seen from bus k to ground can be represented by the Thevenin
equivlant circuit, which consists of a Thevenin impedance connected in series
with Thevenin voltage source. Therefore the Thevinin equivalent circuits seen
from bus k of the sequence circuits are as follows:
Z kk(1) I (1)
fa
Z kk(2) I(2)
fa
Z kk(0) I(0)
fa
Vka(1) , Vka(2) , and Vka(0) : Sequence components of voltage Vka at the fault bus
I (0)
fa , I (1)
fa , and I (2)
fa : Sequence components of current Ifa at the fault point
39
Example 2.4: The single-phase diagram of a power system is shown in the
following figure, where the reactances are also given. The neutral of the
synchronous motor (Machine 2) is grounded through a reactance Xn=0.05 per
unit on the motor base. Draw the per-phase per-unit sequence networks and
associated Thevinin equivalent circuits seen from bus 2 on 100-MVA, 13.8-kV
(machine side) base. Assume that source voltage Vs=1.05pu
T1 T2 Machine2
Machine1
1 3 Line 4 2
X 1 X 2 20 Xn
100MVA X 0 60 100MVA
13.8kV 13.8kV
X " X1 100MVA 100MVA X " X 1 0.20 p.u.
13.8kV /138kV Y 138kV Y/13.8kV
0.15 p.u. X 2 0.21 p.u. X 0 0.1 p.u.
X 2 0.17 p.u. X 0.10 p.u. X 0.10 p.u.
X 0 0.05 p.u. X n 0.05 p.u.
40
Positive-sequence network: Thevenin equivalent circuits
j 0.1389 I(1)
fa
j 0.1 j 0.105 j 0.1 Z th(1) =
j 0.15 j 0.20
= j 0.20 || ( j 0.15 + j 0.305) 1.0500 V2a(1)
1.050 0 1.050 0
= j 0.1389
Negative-sequence network:
j 0.1456 I(2)
fa
j 0.1 j 0.105 j 0.1 Zth(2) =
j 0.17 j 0.21 = j0.21|| ( j0.17 + j0.305) V2a(2)
= j0.1456
41
Exercise: The one-line diagram for a power system with two synchronous
generators is given in the following figure. The ratings and reactances of the
generators and transformers are
G1 and G2: 100MVA, 20kV, X1=X2=20%, X0=6% and XN=5%.
Transformers T1 and T2: 100MVA, 20 / 345Y kV and X=10%.
The three transmission lines have the same sequence reactance.
On the base of 100MVA 345kV, the line sequence reactances:
X 1 X 2 10%, X 0 30%
Determine the per-unit Thevenin impedances from bus 5 for the positive-,
negative-, and zero-sequence networks, respectively.
TL1
jX N
TL2 TL3
Ans.:
42
2.7 Phase shift of a Y-∆ transformer
A' A IA N1 : N 2 Ia
a
Iab
VANVab
B' IB IN I bc Ica Ic
B
N
ZN c
C' C IC Ib
b
(1)
1) Voltage Dot convention: VAN
The voltages from the dot point to the non-dot
point of the two coupling windings are in phase: (1) Vab(1) (a)
For example, VAN and Vab are in phase; VBN and Vbc V ca
are in phase; VCN and Vca are in phase for positive (1)
sequence. VCN Vbc(1) VBN
(1)
43
3) Positive sequence: (phase shift!!!!!! Different current angle)
I(1) (1)
A leads I a by 30
0
I A(1) 1300 I a(1)
(1)
VAB leads Vab(1) by 300 I(1)
A N :N I(1)
a
A 1 2
a
V (1)
AN leads V (1)
an by 30 V0 (1)
A 130 V
0 (1)
a I(1)
ca
(2)
VAN lags Van(2) by 300 I(1)
C I(1)
b
C b
30o
Van(1)
Vab(1)
Vcn(1) Vbn(1)
Van(1)
Van(1) is the phase voltage of the
equivalent Y of the windings
44
5) Current/voltage calculation of a circuit with Y/∆ transformer
The following two circuits with/without Y-∆ transformer have the same
impedance and same current seen from terminals 11’.
45
Example 2.5: A bolted single line-to-ground fault occurs on phase a at
bus 2 of the power system. The sequence components of phase-a
current flowing from Y side of T1 to bus 2 are:
I (0)
a 1.8492 90 0
pu I (2)
a 1.3586 90 0
pu I (1)
a 1.3586 90 0
pu
Calculate per-unit phase currents flowing from G1 to bus 1.
Transmission Line
jX N
20 / 345Y kV
46
(0) (1) (2)
Ia,G1 =Ia,G1 +Ia,G1 +Ia,G1 Ia =I(0)
a +I (1)
a +I (2)
a
a 1.8492 90 pu
I (0) 0
a 1.3586 90 pu
I(1) 0
a 1.3586 90 pu
I (2) 0
Ia,G1 1 1 1 Ia,G1
(0)
0 j 2.3532
(1)
I
1 a 2
a Ia,G1 A 1.3586 1200 j 2.3532 pu
b,G1
Ic,G1 1 a a Ia,G1
2 (2)
1.3586 60
0
0
47
Summary
48
2.8 Thevenin sequence networks connection and fault analysis
at fault location
Section 2.8 introduces the connections of the Thevenin sequence circuits at
the fault bus k and the corresponding sequence current and voltage
calculations at fault location for three unbalance faults.
Vka Z f I fa 3 Z f I (0)
fa V (0)
ka +V (1)
ka +V (2)
ka 3 Z I (0)
f fa (5)
49
2.8.1 Single line-to-ground fault (continue)
• Thevenin sequence circuit connection at the Z kk(0) I(0)
fa
fault bus k:
(0) (1) (2) Vka(0)
I =I =I
fa fa fa (3)
Z kk(1) I(1)
fa
Vka(0) +Vka(1) +Vka(2) 3 Z f I (0)
fa (5)
Vf Vka(1) 3Z V
f ka
• Sequence currents at the fault bus k:
Z kk(2) I(2)
fa
Vf
I (0) (1) (2)
fa =I fa =I fa = (6) Vka(2)
Z kk(0) Z kk(1) Z kk(2) 3Z f
I(0) (1) (2)
fa =I fa =I fa
• Sequence voltages at the fault bus k:
Fig. 2 connection
Vka(1) =Vf - Z kk(1) I(1) (2) (2) (2)
fa , Vka = - Z kk I fa , Vka(0) = - Z kk(0) I (0)
fa (7)
50
2.8.2 Line-to-Line fault (double phase fault ) at bus k
a
•Phase current and voltage equations for the Ifa
fault between phase b and c:
b
I fa 0 (1), I fb I fc (2), V k b V k c Z f I fb (3)
Ifb +
Z f Vkb - Vkc
•Current equations at bus k: c
Ifc -
I(0) Fig. 1 phase-b-to-phase-c fault
fa 1 1 1 Ifa 1 1 1 0
(1) 1 1
Ifa 3 1 a a 2 Ifb 1 a a 2 Ifb I(0)
fa =0
3 (4)
1
I(2)
fa
1 a 2 a Ifc 1 a 2 a -Ifb I (1)
fa = I (2)
fa = ( a a 2
)I fb
3
Ifa 1 1 1 I(0)
fa 1 1 1 0
a I(1) a I(1) I fb a 2 I (1
fa a I fa
) (2 )
I
1 a 2
1 a 2
(5)
fb fa fa
Ifc 1 a a Ifa 1 a
2 (2)
a I(2)
2
fa ( a 2 a ) I fa(1 )
•Voltage equations at bus k:
Vka 1 1 1 Vka(0)
Vkb Vka(0) a 2 Vka(1) aVka(2)
V
1 a 2
a Vka(1) (6) Vkb Vkc Z f I fb
kb Vkc V aV a V
(0) (1) 2 (2)
Vkc 1 a a Vka(2)
2 ka ka ka
(a a)V +(a a )V
2 (1)
ka
2 (2)
ka Z f (a a)I2 (1)
fa
Vka(1) Vka(2) Z f Ifa(1) (6)
51
• Sequence network connection at bus k:
I (f 0a ) = 0 : No zero sequence current for this fault.
Vka 1 1 1 0
• Phase voltages at bus k:
a Vka(1)
(9)
V
kb 1 a 2
Vkc 1 a a Vka
2 (2)
52
2.8.3 Double line-to-ground fault analysis (double phase-to-ground fault)
53
• Sequence network connection:
54
2.9 Procedure of fault analysis at fault bus (Summary)
The procedure to calculate phase voltages and currents at the fault bus
includes seven steps.
Step 1: Draw system single phase sequence networks based on the
sequence circuits of components and network connection (before the
fault). (Section 2.5)
Step 2: Determine Thevenin equivalent circuits of the phase sequence
networks seen from the fault bus k. (Section 2.6)
Step 3: Draw connection of the Thevenin equivalent circuits of
sequence networks at the fault bus based on fault type. (Section 2.8)
Step 4: Calculate the sequence currents at the fault bus based on the
connection of Thevenin equivalent networks. (Section 2.8)
Step 5: Calculate the sequence voltages at the fault bus based on the
sequence current using the equations at Step 2.
Step 6: Calculate the phase currents and voltages at fault bus based on
the sequence currents and voltages using A matrix.
The procedure will be illustrated in the following examples.
55
Example 2.6: The system in the example 2.4 is shown as follow. If a
bolted single line-to-ground fault occurs on phase a at bus 2.
a) Determine the sequence currents of phase a at the fault
point.
b) Calculate the fault currents flowing from bus 2 to ground.
c) Sequence voltages and phase voltages at bus2 ???
T1 T2 Machine2
Machine1
1 3 Line 4 2
X 1 X 2 0.105 p.u. X n 0.05 p.u.
100MVA X 0 0.315 p.u. 100MVA
13.8kV 13.8kV
X 1 0.15 p.u. 100MVA 100MVA X 1 0.20 p.u.
X 2 0.17 p.u. 13.8kV /138kV Y 138kV Y/13.8kV X 2 0.21 p.u.
X 0 0.05 p.u. X 0.10 p.u. X 0.10 p.u. X 0 0.1 p.u.
56
Solutions:
From example 2.4, The Thevinin equivalent circuits of the sequence
networks seen from bus 2 (Step 2):
j 0.1389 I(1)
fa
j 0.1456 I(2)
fa
j 0.25 I(0)
fa
57
2.10 Current and voltage calculation for other system parts
When a fault occurs at a bus, it will affect not only the currents and
voltages at the fault bus but also other part of a power system.
Therefore it is also important to calculate the currents and voltages in
the other parts of a power system. The procedure includes the
following steps.
Step 7: Add the sequence currents at the fault bus from Step 4 to the
fault bus as sequence current sources in the original sequence
networks.
Step 8: Calculate the sequence currents and voltages from the
corresponding circuits using the methods for circuit analysis such as
KCL and KVL.
Step 9: Add the phase shift for the sequence voltages and currents
cross ∆/Y transformers using the current and voltage at the fault bus
as the references.
Step 10 (Same as Step 6): Calculate the phase voltages and currents
based on the sequence voltages and currents.
The procedure will be illustrated using the following example.
58
Example 2.7: For the system shown in Example 2.4, a bolted single line-to-
ground fault occurs on phase a at bus 2.
a)Calculate phase currents flowing from machine 2 to bus 2.
b)Calculate phase currents through transmission line.
Solutions:
Step1: From the solutions of example 2.4, the sequence networks are as:
1 3 4 2
j 0.1 j 0.105 j 0.1 j 0.1 j 0.105 j 0.1
j 0.15 j 0.20 j 0.17 j 0.21
1.0500 1.0500
g
59
a) Connect the sequence currents (
calculated in example 2.6) to the I(1)
corresponding system sequence
j 0.1 j 0.105 j 0.1 A
j0.455
I A1 I fa1 0.695I fa1 I A 1 1 1 I(0)
j0.2 j0.455 A
j0.475 I
B 1 a 2
a I(1) ?? (1)
I A2 I fa 2 0.693I fa 2 A
j0.21 j0.475 IC 1 a a 2 I(2)
A (Step 10)
60
b) The sequence currents through transmission line:
Because transmission line is connected to Y side and the fault is at ∆
side of the transformer, the phase shifts for positive and negative
sequence currents have to be considered.
Line
X 1 X 2 20 Xn
100MVA X 0 60 100MVA
13.8kV 13.8kV
100MVA 100MVA
(1)
without considering phase shift (step 8): Iline
(1)
Iline Ifa(1) I(1)
A line Ifa IA
I(2) (2) (2) (0)
Iline 0 j 0.1 j 0.105 j 0.1 I(1)
A
j 0.15 j 0.20
Add phase shift (Step 9): I(1)
fa
I(1)
line I (1)
fa I (1)
A 30 Iline I(2)
o (2)
fa IA 30
(2) o
1.0500
(Step 7): 1.0500
The phase currents : (2)
Iline
Ifaline 1 1 1 I (0)
I(2)
A
line j 0.1 j 0.105 j 0.1
I
I
fbline 1 a 2
a (1)
? j 0.17 I(2) j 0.21
line
fa
Ifcline 1 a a I
2 (2)
line
61
Example 2.8: When a bolted line-to-line fault between phases b and c occurs
at bus 2 of the system in Example 2.4,
a)Calculate the phase fault currents at bus 2.
b)Calculate the phase voltages at bus 2 after the fault.
j 0.1389 I(1)
fa
I(2)
fa
j0.1456
Solutions:
For a bolted fault, Z f =0 (1)
1.0500 V2a V2a(2)
Vf 1.0500
a): fa 0
I(0) I = I = (1)
(1)
fa
(2)
fa j 3.6907 pu
Z th Z th(2) 0 j 0.1389 j 0.1456
Ifa 1 1 1 I(0)
fa 1 1 1 0 0
I
fb 1 a 2
a Ifa(1) 1 a 2 a j 3.6907 6.3925 pu
Ifc 1 a a Ifa 1 a
2 (2)
a j 3.6907 6.3925
2
b): V2a(2) =V2a(1) = -Z th(2) Ifa(2) = - j 0.1456´ j 3.6907 = 0.5374pu and V2a(0) = 0
0
V2 a 1 1 1 V2 a 1 1 1 0 1.0748
V 1 a 2 1
2b a V2 a 1 a 2 a 0.5374 -0.5374 pu
V2 c 1 a a 2 V2a2 1 a a 2 0.5374 -0.5374
62
2.9 Three phase-to-ground fault
The fault conditions at fault bus k: a
Ifa
Vka =Vkb =Vkc =0 b
Ifb
Sequence voltages at bus k: c
Ifc
1
Vka(0) = (Vka + Vkb + Vkc ) = 0 Fig. 1
3
1 1
Vka(1) = (Vka + aVkb + a 2 Vkc ) = 0 Vka(2) = (Vka + a 2 Vkb + aVkc ) = 0
3 3
Apply the above sequence voltages to the equivalent circuits:
Z kk(1) I(1)
fa Z kk(2) I(2)
fa Z kk(0) I(0)
fa
Vf
I fa
(1) 1
Vf V ka 1 I(2)
fa = 0
(2)
V I(0)
fa = 0 Vka(0)
Z kk ka
Therefore, three phase fault is the balanced fault and there are only
positive fault voltages and currents to be calculated from positive
network.
63
Summary for Chapter 2:
• Draw the per-phase per-unit positive-, negative-, and zero-
sequence networks of a power system.
• Develop the Thevenin equivalent circuits as viewed from the fault
bus k for the positive-, negative- and zero-sequence networks.
Z kk(1) I(1)
fa
Z kk(2) I(2)
fa
Z kk(0) I(0)
fa
+
• Calculate the sequence voltage and currents at the fault point based
on the connection of the sequence networks for the different faults:
(0)
Single Line (or phase) to Z kk I (0)
fa
64
Double line (or phase) fault:
fa = I fa
I(1)
a (2)
I fa Z kk(1) I(1)
fa
Zf I(2)
fa Z kk(2)
b Vf
I fb (1)
Zf Vf V ka Vka(2) Z kk(1) Z kk(2) Z f
c
I fc
Double line (or phase)-to-ground Vf
I(1)
fa =
a fault Zkk(1) + Zkk(2) || (Zkk(0) +3Z f )
I fa
Z kk(1) I(1)
fa
Z kk(2) I(2)
fa
Z kk(0) I(0)
fa Z kk(0) + 3Z f
(2)
b I =-
fa (2) (0)
Ifa(1)
I fb Vf Vka(1) Vka(2) Vka(0) + Z + 3Z f
Z kk kk
(2)
c Z
I fc 3Z f I(0)
fa =- (2)
I(1)
kk
fa
(0)
I fb + I fc Z f Zkk + Z +3Z f kk
65
3. Power System Protection
66
3.1 Basic Protection System
1) Relay Circuit:
• Detect abnormal conditions through measuring changes of currents,
voltages and impedances.
• Initiate actions to trip the circuit breakers.
2) Sensing devices:
• Current transformer
(CT): Provide current
signal for relay circuit.
• Voltage or potential
transformer (VT or PT):
Provide voltage signal
for relay circuit.
Fig. 3.1
3) Signal network:
• Transfer the accurate signals from CTs and VTs to relay circuit.
4) Circuit breaker (CB):
• Isolate the fault through opening circuits (just like a switch).
5) Auxiliary power source: (Battery)
• Provide back-up power for relay and circuit breaker.
67
3.2 CT and VT Selection and Operation Issue
3.2.1 VT and CT selection
Voltage transformer selection is based on the voltage level of a protected
circuit and the rated voltage (110V) of a voltage relay connected to VT
secondary side. Standard VT ratios are shown in the following table.
Table 3-1 Standard VT ratios
1:1 2:1 2.5:1 4:1 5:1 20:1
40:1 60:1 100:1 200:1 300:1 400:1
600:1 800:1 1000:1 2000:1 3000:1 4500:1
68
3.2.2 CT Equivalent Circuit
CT is an important comeponent of a protection system beucause it
provide the signal to current relay. CT equivalent circuit is as follow:
I 1:n Zp’ Zs I’
Ie +
+
Ve Zb V’
Ze
- -
Equivalent circuit Burden
Fig. 3.2
Zp’ : Primary winding impedance refer to the secondary side
Zs : Secondary winding impedance
Ze : Magnetizing impedance
Zb : CT burden which is the total impedance of the circuit connected to
CT (Relay and it connections).
Ve : Secondary exciting voltage
Ie : Secondary exciting current
n : Turns of secondary winding
I : Primary current
I’ : Secondary current
69
3.2.2 CT Saturation problem during operation
Zp’ Zs
I 1:n I’
Ie +
+
Knee Point Ze
Ve Zb V’
- -
Equivalent circuit Burden
Ve
70
3.2.2 CT Saturation evaluation and adjustment
Knee Point Step 1: Voltage Ve (Vef) is
approximately calculated
from the equivalent circuit
shown in Fig. 3.2 based on
primary current I as:
Ve=I/n×(Zs+Zb)
Step 2: Check CT saturation
from the excitation curve (Ve
, Ie ) of the selected CT ratio.
Ve • CT is saturated if the
operating point is behind
the knee point and not
saturated if it is before
the knee point.
Step 3: If the CT is
saturated, increase the CT
ratio and go to Step 1
otherwise the adjusted CT
ratio is satisfied.
I 1:n Zp’ Zs I’
Ie +
+
Ve Zb V’
Ze
- -
Equivalent circuit Burden
71
3.2.2 CT Saturation evaluation and adjustment
Knee Point
Example: Evaluate
performance of the multi-
ratio Class-C CT with 100:5
CT ratio setting when
(a) I=100 A, Zb=0.5 Ω
(b) I=280 A, Zb=2.6 Ω.
Ve
(a) I’=100/20=5 A.
Ve=5×(0.082+0.5)=2.91V.
From the curve, Ie=0.2 A, CT
is not saturated.
(b) I’=280/20=14 A,
Ve=14×(0.082+1.6)=23.5 V,
Ie=30 A
From Fig. 3-4, Ie=30 A,
CT is saturated
72
3.3 Overcurrent Protection
3.3.1 An overcurrent protection system (overcurrent relay)
An overcurrent protection system is usually designed to protect
distribution networks when short circuit faults occur.
73
3.3.2 An induction disc overcurrent relay
The key component of overcurrent protection is overcurrent relay. An
electromagnetic induction disc relay and its components are shown in the figure:
74
3.3.3 Relay settings
There are two relay parameters to be selected in overcurrent protection design.
1. Plug Setting (PS): The PS or the pick-up current of a overcurrent relay can be
set to different values through changing the number of turns N for the same Tm.
2. Time dial Setting (TDS): The operating time of relay can be set to different
value through changing the space (TDS) between the fixed and movable contacts
for the same current I’.
3. T-I curve: For a given PS and TDS, the relay operating time changes
nonlinearly with the current through relay, which is represented by a time-current
(T-I) curve. The larger is the current, the shorter the operating time. For a given
current I1, the operating time t1 can be found from T-I curve.
t
t1
I1 I’
T-I curve
75
3.3.4 Time-current curves for different overcurrent relays
1. CO-8 relay: The plug
settings, the time dial
settings and the related I-
T curves for a CO-8 relay
is shown in the figure.
The current axis of the I-
T curves is not absolute
current (A) but the
multiple of pick up
current:
MPC=I’/Ipickup
For Ipickup=5A and I’=25A,
MPC=5.
The fastest TDS setting is
TDS=0.5.
76
For given PS and TDS, the relay operating time for a current can be
determined using the I-T curve or the equation on page 72.
Example 3-2: A relay is selected to protect a distribution feeder
(line). The fault current is 2000A and CT ratio is 200:5. PS is set to
200% of the rated current 5 A and TDS is 2. Determine the
operating time of the following two relays.
A CO-8 relay with the time current curve
An IDMT relay with the time-current equation
Solutions:
The current through the relay=2000/40=50A
The pickup current is 200%×5=10A
The MPC is 50/10=5
77
3.3.5 Overcurrent protection of distribution network
Over-current protection is commonly used to protect system
components in a radial distribution system as shown in the figure.
When a fault occurs in a distribution system, the related relays and
circuit breakers have to operate reliably to isolate the fault and to
limit the affected area to the minimum.
Reliable operation of the protection system for a short circuit fault
needs one main protection and one back-up protection. If the main
protection fails to operate for a fault, the back-up needs to operate.
78
3.3.5 Overcurrent protection of distribution networks
There are many components in a distribution network. Therefore
many relays and circuit breakers are required for faults at different
parts of network. PSs and TDSs of relays have to be properly selected
based on different fault currents and required operating times.
1) Selection of PS (based on the maximum load current):
Step 1: Determine the relay minimum operating current (MOC) seen
from the primary side of a CT (line) for the relay to pick up.
In order to avoid malfunction of relays during the peak load periods,
MOC is set to 200% of the maximum load current for a phase relay.
MOC
Step 2: Select PS using this formula: I pickup (or PS )
CT ratio
Example 3.3: A 50-Hz radial distribution system is shown in the figure.
The loads at Buses 2, 3 and 4 are 12MVA, 5 MVA and 7MVA
respectively with the same power factor. Select PSs for phase relays if
Co-8 relays are provided.
Bus1 Bus2 Bus3 Bus4
B1 B2 B3
G1
Line1 Line2 Line3
34.5kV Load3
Load1 Load2
79
Solutions: Bus2 Bus3 Bus4
Bus1 B3
PS selection: (Ignore B1 B2
line losses and voltage G1
Line1 Line2 Line3
drop when calculate
maximum load current) 34.5kV 7MVA
12MVA 5 MVA
B1 relay (all loads):
Select CT ratio=400/5
MOC=2×401.6=803.2A
CT Secondary current:
MOC 803.2
I 'L1 10.4 A
CT ratio 400 / 5
Select PS1 =12A
80
B2 relay (Load2 anad Load3): S L 2 S L 3 5 7 12 MVA
S2 S3 12 10 6
CT Primary current: I L2 200.8 A
3 V2 3 34.5 10 3
Select CT ratio=200/5,
MOC=2×200.8=401.6A
MOC 401.6
CT Secondary current: I 'L 2 10.04 A
CT ratio 200 / 5
Select PS2 =12A
B3 relay (Load3):
S3 7 10 6
CT Primary current: I L3 117.1 A
3 V3 3 34.5 10 3
Select CT ratio=200/5,
MOC=2×117.1=234.2A
MOC 234.2
CT Secondary current: I 'L 3 5.85 A
CT ratio 200 / 5
Select PS3 =6A
81
2) Selection of TDSs (the maximum three phase fault current):
Example 3.4 is used to illustrate the procedure of TDS selection
Example 3.4: For the same system as shown in example 3.3 The
maximum fault currents at Buses 2, 3 and 4 are 3500A, 2500A and
1000A respectively. The CO-8 relays are provided for breakers. The
ratios of the CTs corresponding to B1, B2 and B3 are 400:5. 200:5 and
200:5 respectively. Set PSs and TDSs for the phase relays. The CTI is
0.5s for two adjacent relays.
Step1: Select the minimum TDS for the last relays at the end of a
radial network. The bottom relay for the system as shown in Fig. 1 B3
relay. Therefore TDS3=0.5.
Step2: Find the pairs of main and back up relays. For the system as
shown in Fig.1, there are two pairs of main and back-up relays which
are (B3 and B2) for the faults of line 3, (B2 and B1) for line 2.
82
Step3: Calculate t Main of Bus1 Bus2 Bus3 Bus4
min B1 B2 TDS2=2 B3 TDS3=0.5
the main relay based on the G1
*maximum fault current* Line1 Line2 Line3
through it. 34.5kV
Load1 Load2 Load3
For B3 (main) and B2 (back-up) pair:
B3 relay as main relay (PS3=6A) for the max fault current at bus 3 (2500A):
B2 relay as back up of B3 (PS2=12A) for the same fault current 2500A, the
required fault clearing time:
t 2 t req
backup Main
tmin CTI t3 0.5 s 0.57 s
For the same current (2500A): 2500 /( 200 / 5 )
MPC 2 5. 2
12
Based on the operating point of B2 relay ( t 2 0.57 s and MPC 2 5.2 ), the
TDS2=2 curve should be selected.
83
84
Bus1 Bus2 Bus3 Bus4
B1 TDSb1=2 B2 TDSb2=2 B3 TDSb3=0.5
G1
Line1 Line2 Line3
34.5kV Load3
Load1 Load2
For B2 (main) and B1 (back-up) pair:
Step 3: B2 relay as the main protection: (PS2=12A, TDS=2)
For the faults occurring on line2, B2 relay is the main protection.
85
3) Calculation of operating time after a fault
Bus1 Bus2 Bus3 Bus4
B1 TDSb1=2 B2 TDSb2=2 B3 TDSb3=0.5
G1
Line1 Line2 Line3
34.5kV Load3
Load1 Load2
Calculate the operating time of relays R1, R2 and R3 for a fault
at Bus 4 with the current 2000A
86
Summary for Protection Zone, CT and VT selection and
overcurrent protection
87
3.4 Differential protection
3.4.1 Percentage differential relay
Differential protection is used to protect only internal faults of a
power system element. It is not for protecting the external faults. A
differential protection system with a percentage differential relay for
a single phase is shown in the figure. Two CTs provide two current
signals for the relay. Two circuit breakers are required to isolate the
protected component. The relay has two restraint windings and one
operating winding.
88
3.4.2 Relay operation:
External fault: Relay hardly operates because the operating force is
cancelled by the two restrain forces and the operating current Io=I1’-
I2’ is very small. Relay cannot operate.
I1 CB CB I2 I1 CB Protected CB I2
Protected
component component
I1’ Fe I1’ Fi
I1’ Restraint coils I2’ I1’ I2’ I2’
I2’
Io =I1’-I2’ Operating coil Io =I1’+I2’ Operating coil
89
3.4.3 Generator differential protection
Two important aspects of differential protection are CT and relay
connections and current calculation. Relay connection must make sure
that the currents flow in the two restraint windings are in phase for
external faults. Three CTs in both sides of a Y connected generator are
connected in Y as shown in the following figure.
Ia1 Ia2
Ib1 G Ib2
Ic1 Ic2
Ia1’ Op
R R Ia2’
Ib1’ Op Ib2’
R R
Ic1’ R
Op
R Ic2’
From dot convention, Ia1 and Ia1’ (Ia2 and Ia2’) are in phase. For
external fault Ia1 and Ia2 are in phase. Ia1’ and Ia2’ are also in phase.
90
Current calculation: Example 3.4: A Y-connected generator is
connected to a 345 kV system through a Δ-Y 18/345 kV transformer
as shown in figure. A differential relay with 1A pick up current is used
to protect the generator. The system parameters are also shown in
figure. CT ratio is 1100:1. Determine relay operation for three phase
faults at F1 and F2.
Δ
SBN=100 MVA
CT B B CT B B System:
VBN=18 kV at G: G 345kV
100000 100MVA
IB 3207.5 A 18kV F1 F2 18/345kV
3 18 X S1=5%
160MVA 160MVA
X SN 1 0.05 X G1=0.3pu X T1=15%
S 100
X GN 1 X G 1 BN 0.3 0.1875
S BO 160
100
X TN 1 0.15 0.09375
160
VF
I FS I B / CTratio 20.28 A
X TN 1 X SN 1
VF 1
I FG I B / CTratio 3207.5 / 1100 15.55 A
X GN 1 0.1875
91
IFG IFG IFS
For external fault F2:
G F2
Two restraint currents
are the same:
I FG 15.55 A
IFG Op
R R IFG
Operating current:
I o I FG I FG 0 A Op
R R
92
3.4.4 Transformer differential protection
CT and relay connections for a Δ-Y transformer are shown in the
figure. The two restraint currents IHa and ILa are in phase for the
normal load from the phasor diagram.
Ic1 Ic2
’
Ia1 -Ib1 ’ Ic2’
Ia2’-Ib2’
CT: Y CT: Δ
R R
IHa Op IHa-ILa ILa
Ib1’-Ic1’ Ib2’-Ic2’
R R
IHb Op IHb-ILb ILb
’ ’
Ic1 -Ia1 Ic2’-Ia2’
R R
IHc Op IHc-ILc ILc
Current calculations: When CT ratios are selected based on the
maximum load current and the operating current is calculated as
follow:
50 MVA
The current at 138 kV (CT primary side): I a 1 I b1 209.18 A
3 138kV
Select CT ratio 250:5 =50
The current at left-hand side of the restraint winding:
I a1 I b1
I Ha I a' 1 I b' 1 4.18 A
CTratio
50 MVA
The current at 69 kV (CT primary side): I a2 418.37 A
3 69kV
Select CT ratio 500:5 =100
Ia2 418.37
The current at the secondary side of CT: I a' 2
4.18 A
CTratio 100
The current at right-hand side of the restraint winding (∆ CTs):
I La I a' 2 I b' 2 3 I a' 2 7.25 A
The operating current:
I o I Ha I La 3.07 A
94
Example 3.5 For the transformer in Section 3.4.4, the CT ratios at high
and low voltage sides of the transformer are 200:5 and 400:5
respectively. The transformer positive impedance is 0.5 pu. Ignore the
source impedance. Calculate the currents in two restraint windings for
an external three phase to ground fault which occurs at low voltage
side of the transformer.
Solution:
SB 50 MVA
The base current at 138 kV: I Bp 209 A
3VB 3 138kV
The base current at 69 kV: IB=418 A
The fault current=1/0.5=2pu
The fault currents at 138kV and 69kV from CT primary side are 418A
and 836A respectively.
The current at left-hand side of the restraint winding:
IH=418/40=10.45
The current at right-hand side of the restraint winding:
IL=836/80 3 =18.1
95
Summary for Differential Protection
d) Requirements for relay connection: IHa and Ila in phase for normal
operation and external fault.
96
2.4.4 Sequence circuits of a synchronous generator (Appendix)
KVL: Vag Ean ZI a Z n I n Ean ZI a Z n I a Z n I b Z n I c Ean Z Z n I a Z n I b Z n I c
Vbg Ebn Z n I a Z Z n I b Z n I c a
Vcg Ecn Z n I a Z n I b Z Z n I c Ia
Vag Z
Matrix form:
Vag Ean Z Z n Zn Zn Ia E
Z n I an
V E Z Z Z n Z n I b g n n
bg bn E bn
Z Z n I c
n
Vcg Ecn Z n Zn
Z
E cn
Z Ib
Ean Z Z n
0
Vag 0
Zn Zn Ia
0
c b
AVag1 A Ean1 Z n Z Z n Z n A I a1 Ic
2 2 Z I 2
Vag an
E n
Z n
Z Z n
a
Vag0 Ean0 Z Z n
0
Zn Zn Ia
V 1 E 1 A1 Z Z Z Z A I 1
ag 2 an 2 Z Z n I a 2
n n n a
Vag Ean Zn Zn
2
ag an
0 0 Z I 2 2 E aE 0
ag
V 0 a Ean cn an
97
a I(0)
Sequence circuits: a
Zg0
Vag0 Z 3 Z n I a0 n Only zero sequence
VVaga0
(0)
3Z n current through ZN
Reference
a I(1)
a a I(2)
a
Z1
Vag1 Ean ZI a1 V 1
(1) Vag 2 ZI a 2 Z2
(2)
Vag2
V aag
a
E an
Reference
Reference
98
2.4.7 Sequence circuits of transmission lines (Appendix)
99
Same method with 2.4.1 to obtain relationship of sequence components:
VAn 0 VA 0'n' V V IA I A 0
VAn VA ' n ' Z s Z m Z m I A
1 An A'n '
V V Z I A I 1
A VAn VA ' n ' VBn VB ' n '
1
Z s Zm IB B A
Bn B'n'
m
2
2 V V VCn VC ' n ' Z m Z m Z s I C I C
2
VAn VA ' n ' Cn C ' n ' I A
VAn 0 VA 0' n' Z 2Z I A 0 Z IA
0
1 1
s m
1 0 I 1
VAn VA ' n ' Zs Zm
A
I Z1
A
2 2 2 Z 2 I A 2
An
V V A' n ' Z s Z m I A
(1) Z1 (2) Z2
(0)
A IA Z0 A' A IA A' A IA A'
100