100% found this document useful (1 vote)
496 views52 pages

EirGrid Simulation Requirements

This document outlines simulation model requirements and studies for various types of power system equipment connecting to the Irish transmission system to demonstrate compliance with grid code requirements. It addresses synchronous generators, power park modules, demand facilities, and HVDC converter stations. Modelling details are provided for static, RMS, EMT and harmonic models. Required studies examine faults, frequency response, reactive capability, islanded operation and controls performance.

Uploaded by

tongai chigariro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
496 views52 pages

EirGrid Simulation Requirements

This document outlines simulation model requirements and studies for various types of power system equipment connecting to the Irish transmission system to demonstrate compliance with grid code requirements. It addresses synchronous generators, power park modules, demand facilities, and HVDC converter stations. Modelling details are provided for static, RMS, EMT and harmonic models. Required studies examine faults, frequency response, reactive capability, islanded operation and controls performance.

Uploaded by

tongai chigariro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 52

Simulation Studies and Modelling Requirements for

Compliance Demonstration

Version 1.0

Page | 1
Simulation Studies and Modelling Requirements for Compliance Demonstration

Disclaimer

EirGrid, the Transmission System Operator (TSO) for Ireland, makes no warranties or representations of
any kind with respect of this document, including, without limitation, its quality, accuracy and
completeness. The TSO does not accept liability for any loss or damage arising from the use of this
document or any reliance on the information it contains. Use of this document and the information it
contains is at the user’s sole risk. In addition, the TSO strongly recommends that any party wishing to
make a decision based on the content of this document should consult the TSO in advance.

Version History

Version Release Date Comments Document Owner


Version 1.0 23rd March, First approved release of document. Eirgrid Future Networks,
2021 Note part 4 (HVDC) is still draft. Innovation and Planning

Governance
Any changes to this document made by Eirgrid are to be discussed at the Ireland Grid Code
Review Panel prior to the new release. Similarly, proposed changes from industry should be
raised through the relevant Grid Code channels. Note that changes to this document are not
subject to regulatory approval.

The document includes references to the relevant EU Network


Connection Codes in various sections in the form of “(Art 15-
2)”, to help with cross-referencing.

Page | 2
Simulation Studies and Modelling Requirements for Compliance Demonstration

Contents
Contents ..................................................................................................................................................... 3
PART 1. SYNCHRONOUS POWER GENERATING MODULES ................................................................... 8
1.1. General Provisions ...................................................................................................................... 8
1.2. Simulation Model Requirements ................................................................................................ 8
1.2.1. Static Model ........................................................................................................................ 8
1.2.2. RMS Model .......................................................................................................................... 9
1.2.3. Model Submission ............................................................................................................. 10
1.3. Simulation Studies..................................................................................................................... 12
1.3.1. FRT, Active Power Recovery .............................................................................................. 12
1.3.2. LFSM-U and LFSM-O .......................................................................................................... 13
1.3.3. Frequency Sensitive Mode ................................................................................................ 14
1.3.4. Islanded Operation (Load Rejection) ................................................................................. 15
1.3.5. Reactive Power Capability ................................................................................................. 15
1.3.6. Power System Stabiliser / AVR Control ............................................................................. 16
PART 2. POWER PARK MODULES ....................................................................................................... 18
2.1. General Provisions .................................................................................................................... 18
2.2. Simulation model requirements ............................................................................................... 18
2.2.1. Static Model ...................................................................................................................... 18
2.2.2. RMS Model ........................................................................................................................ 19
2.2.3. EMT Model Requirements ................................................................................................ 20
2.2.4. Harmonic Model Requirements ........................................................................................ 20
2.2.5. Model Submission ............................................................................................................. 21
2.3. PPM Simulation Studies ............................................................................................................ 23
2.3.2. LFSM-U and LFSM-O .......................................................................................................... 25
2.3.3. Frequency Sensitive Mode ................................................................................................ 26
2.3.4. Reactive Power Capability ................................................................................................. 27
2.3.5. Islanded Operation (Load Rejection) (Only if requested by EirGrid) ................................. 28
2.3.6. Power System Stabiliser / AVR Control (Not Applicable Presently) ................................... 28
PART 3. DEMAND FACILITIES, DISTRIBUTION FACILITIES and DISTRIBUTION SYSTEMS ...................... 30
3.1. General Provisions .................................................................................................................... 30
3.2. Simulation model requirements ............................................................................................... 30

Page | 3
Simulation Studies and Modelling Requirements for Compliance Demonstration

3.2.1. Static Model ...................................................................................................................... 30


3.2.2. RMS Model ........................................................................................................................ 31
3.2.3. Harmonic Model Requirements ........................................................................................ 32
3.2.4. Model Submission ............................................................................................................. 32
3.3. DCC Simulation Studies ............................................................................................................. 34
3.3.1. Reactive Power Capability ................................................................................................. 34
3.3.2. Very Fast Active Power Control ......................................................................................... 34
PART 4. HVDC Converter Stations, DC Connected PPMs .................................................................... 36
4.1. General Provisions .................................................................................................................... 36
4.2. Simulation model requirements ............................................................................................... 36
4.2.1. Static Model ...................................................................................................................... 36
4.2.2. RMS Model ........................................................................................................................ 37
4.2.3. EMT Model ........................................................................................................................ 38
4.2.4. Harmonic Simulation Model.............................................................................................. 38
4.2.5. Model Submission ............................................................................................................. 39
4.3. Simulation Studies..................................................................................................................... 41
4.3.1. Fault Ride Through ............................................................................................................ 41
4.3.1. Fast fault current injection ................................................................................................ 42
4.3.2. Active power recovery ...................................................................................................... 43
4.3.3. Reactive power capability ................................................................................................. 43
4.3.4. Power oscillations damping control .................................................................................. 44
4.3.5. Active power modification ................................................................................................ 45
4.3.6. Fast active power reversal................................................................................................. 46
4.3.7. Interaction studies (Art 29 not within simulation study part) ........................................... 46
4.3.8. Subsynchronous torsional interaction studies (Art 31 not within simulation study part) . 47
APPENDIX A: PRINCIPLES FOR SIMULATION COMPLIANCE EVALUATION AND INTERPRETATION OF GRID
CODE FAULT RIDE THROUGH CLAUSES ..................................................................................................... 48

Page | 4
Simulation Studies and Modelling Requirements for Compliance Demonstration

Introduction
With the advent of the European Network Codes, and their integration into the Ireland Grid Code, it was
felt necessary to collate the requirements around simulations and modelling into one document,
particularly in areas where a more detailed description than that set out in the Grid Code is warranted.

Simulation studies are an integral part of power system design, analysis and operation as they provide
an easy to follow analytical process in establishing various system parameters during for example the
connection of a new facility to the grid. As such, provision of up-to-date and accurate models is an
imperative part of this process.

In general, simulation studies can be utilised to model and analyse power networks’ dynamic behaviour
in terms of voltage and frequency stability as well as other transient phenomena.

The detail and specifics of the model required is normally dictated by the type of study intended to be
used. For generation facilities, this usually implies analysis of behaviour in steady-state and quasi-
steady-state and as such static and RMS models to be used for various studies are required. The
following table provides a summary of the different model requirements for simulation purposes.

For non-synchronous generation, more detailed modelling is required in order to capture detailed
control system behaviour. This is because voltage source technologies can exhibit control instabilities
due to the use of technologies that is system voltage dependent. In addition, control interaction in close
proximity is a distinct possibility and the ability to model and predict these has become paramount.
Electromagnetic transient time domain modelling is the industry norm for such studies and hence
generator models (an in most cases the inverter/converter model) in EMT domain are required.

Generation type Model requirement

Power Quality
HF Transients
Short Circuit
Load flow

Transient
Stability

SSCI

Synchronous Power Static simulation model  


Generating Module RMS simulation model   
Power Park Module Static simulation model  
RMS simulation model 
EMT simulation model    
Harmonic simulation model    
Demand Facilities, Static simulation model  
Distribution Facilities, RMS simulation model 
Closed Distribution
Harmonic simulation model  
Systems
HVDC Systems Static simulation model  
RMS simulation model 
EMT simulation model    
Harmonic simulation model    

Page | 5
Simulation Studies and Modelling Requirements for Compliance Demonstration

Compliance Process
Simulation studies and model provision is part of a larger compliance process that involves other items
as per the check list1 for the connection of a given category.

The process with regards to the provision of simulation studies and model, their check and provisional
acceptance and later update and final acceptance is summarised in the next flow chart.

The process as indicated in the flow chart should be followed by all connections (or modifications)
irrespective of technology.

In exceptional circumstances due to system security requirements, it may be necessary to energise a


connection in the absence of a simulation study report or model with the express permission of senior
level EirGrid management. In such cases, a temporary Grid Code derogation would still be required.

It is expected that there may be some adjustment of dynamic model parameters between the initial
model submission, and following energisation and validation of the model, once final as-built technical
parameters become known. Users are required to confirm the final model parameters when they
submit model validation reports, as described in PC.A8.6.

1
https://www.eirgridgroup.com/customer-and-industry/general-customer-information/grid-code-compliance-
test/compliance-testing/

Page | 6
Simulation Studies and Modelling Requirements for Compliance Demonstration

EirGrid Simulation Studies and Model Provision Compliance Process


EON ION FON

Proceed with other Proceed with ION Proceed with any


Provide simulation Proceed with
EON stage check list stage check list other FON stage
studies report and physical FON stage
items prior to items prior to check list items
Customer

models tests
receiving EON receiving ION prior to issuing FON

Update simulation
report comparing
actual tests with
simulations to
provide validation

Receive updated Facilitate meetings Customer informed


Testing Team

Proceed with ION simulation report between Customer that updated


Facilitate meetings Customer informed and pass it for and Access Planning models/report are
Report and Models stage check list
between Customer that models / checks as required satisfactory
received and passed items
and Access Planning reports are
to checks
as required satisfactory

Customer asked to
Customer asked to
EirGrid Network explain differences
resubmit models/
Data Provided to and inconsistencies
report or answer
Customer or re-submission Yes
Access Planning

queries
Yes required
18 months in advance of
No No
proposed Energisation date
Assess Customer Assess validated
simulation studies Report and simulation studies Reports and
report and usability Models Ok? and any other Models Ok?
of models update

Page | 7
Simulation Studies and Modelling Requirements for Compliance Demonstration

PART 1. SYNCHRONOUS POWER GENERATING MODULES

1.1. General Provisions


Simulation studies are aimed at demonstrating the performance requirements of individual power-
generating modules and the following general provisions apply: (Art 43-1)

 Generating facility shall provide technical data and documentation as part of the simulation
studies compliance procedures (Art 41-3-a and b). All data requirements are detailed in the
Planning Code Appendix of the Grid Code;
 Generating facility shall provide an appropriate model as part of the simulation studies
compliance procedures (Art 41-3-c and d). The timeline of the model provision is covered by the
phases of Operational Notification Procedure;
 EirGrid shall not accept an alternative set of simulations to those given as part of this
compliance procedure (Art 43-2-a);
 EirGrid may require additional or alternative sets of simulations to those given in this procedure
when deemed insufficient to demonstrate compliance (Art 43-2-b);
 Generation facility shall provide a report that includes modelling and results of all the simulation
studies detailed in this procedure (Art 41-3-e & Art 43-3);
 Generation facility shall provide a validated simulation model as detailed in this procedure (Art
43-3);
 EirGrid may perform its own simulation studies based on the simulation model, simulation
reports and compliance test measurements (Art 43-4);
 EirGrid shall provide the generation facility owner system data in order to carry out the
simulation studies detailed in this procedure (Art 43-5); and
 EirGrid shall not accept provision of equipment certificates submitted as part of demonstrating
compliance with relevant simulation study requirement (Art 52-1, 53-1, 55-1 and 56-2).

1.2. Simulation Model Requirements


1.2.1. Static Model
The static simulation model for synchronous power generating modules should represent the steady
state characteristics of the generating facility at the point of connection suitable to be used in network
wide load flow and short circuit calculation studies. More specifically the static model shall be capable
of:

 covering a range of frequencies (47 to 52 Hz) and voltages (0 to 1.4 pu);


 representing the characteristics of the generation facility’s operating ranges for active and
reactive power;

Page | 8
Simulation Studies and Modelling Requirements for Compliance Demonstration

 providing calculated RMS values of all phases for all types of system faults (balanced and
unbalanced); and
 providing control functionality with reference points for the following modes
o reactive power control mode
o voltage control mode including parameters for droop setting
o power factor control mode

1.2.2. RMS Model


The RMS model is aimed to be used for dynamic studies and as such the simulation model shall include
information or be capable of:

 representing the dynamic properties of the generation facility;


 representing the characteristics of the generation facility’s operating ranges for active and
reactive power;
 covering a range of frequencies (47 to 52 Hz) and voltages (0 to 1.4 pu);
 handling control functionality (with input/output signals) with indication of reference point
o power factor control,
o reactive power control,
o voltage control including parameters for droop setting,
o frequency control including droop and deadband,
o activation of protection functionality (if present);
 activating an internal protection functionality in the event of external network faults;
 utilising an internal excitation system that includes relevant voltage, frequency, stator current,
over and under excitation limiters;
 providing a numerically stable simulation for a minimum of 60 seconds following any set point
changes or system incidents/faults;
 be capable of running with a variable integration time step in the range of 1 to 10 ms;
 initialising in a stable operating point;
 not requiring any special settings to be implemented into a larger network model;
 simulating the dynamic behaviour of the generators (or generating facility) under system faults,
voltage disturbances and frequency disturbances; and
 not containing any encrypted or compiled parts.

For newly built synchronous power generating modules and for those installed but going through a
modification involving any part of the drive train, in addition to the standard RMS model, information
relating to mechanical mass model for each drive train element is also required. Specific information
required are:

 inertia constants;
 spring and damping constants;
 torque shear stress; and
 natural oscillation frequencies.

Page | 9
Simulation Studies and Modelling Requirements for Compliance Demonstration

1.2.3. Model Submission


The provision of the simulation model shall be supported and include:

 description of each individual model components and their related parameters;


o saturation, dead bands, non-linearity, time delays, any interpolation assumptions and
any look-up tables utilised within the parameters utilised
 description of initialisation of the model for simulations
 Laplace domain transfer functions, sequence diagrams and any arithmetic or logical sequence
modules within the model description
 description of input and output signals
 explanation of set-up and initialisation of the model
 limitations of the model provided
 list of protection functionality that can be triggered by external events
 diagrams of excitation system, AVR, PSS and any other equipment implemented within the
excitation system in the form of standardised block diagrams
 information on excitation system constraint functions such as current limiter, over-excitation
and under-excitation limiters

For a generation facility that comprises more than one generator unit, the submitted simulation model
must be such that the characteristics of the generation facility is represented at the point of connection.
Submitted model parameters must contain all data sets for each unit.

The RMS simulation model submitted to EirGrid must be compatible with PSSE 34 and later versions,
and should be in a format that can be readily integrated into other simulation packages, such as
DigSilent PowerFactory, or DSA Tools. Information relating to the mechanical mass model can be
submitted in written data form rather than in a model. No special settings other than standard software
settings should be required for the submitted model to be implemented.

Model validation against test measurements is a requirement and the specific simulation that needs to
be validated are indicated.

The submitted simulation model and studies shall have the following accuracy requirements:

 For a linear response over a frequency range of 0.1 to 5Hz, deviations between simulated and
measured waveforms of the control system must be less than 10% for amplitude and less than 5
degrees for the phase angle. Discrete waveform changes (amplitude spikes) on the simulated
waveform should be less than 10% in relation to measured quantity and in the case of where
this level is exceeded due to numerical integration issues, this should be documented in the
report.
 For dynamic time domain simulations where non-linear response is included to replicate set
point changes or response to disturbances on the wider network, the following requirements
apply for deviations between simulated and measured response:

Page | 10
Simulation Studies and Modelling Requirements for Compliance Demonstration

o for rapid slopes within 10% for 95% of the samples recorded within a defined event
window2, and time offset of the gradient start or end time must be less than 20
milliseconds;
o for events (e.g. switching) resulting in positive and negative spikes, the amplitude must
be less than 10% from the corresponding measured value for 95% of the samples
recorded;
o oscillation in active power, reactive power, voltage and frequency in the 0.1-5Hz range
must have damping and the deviation in the frequency of oscillation must be less than
10% for 95% of the recorded samples;
o considering possible difference in the voltage at the point of connection, deviation in
active and reactive power response must be less than 10% for 95% of the samples;
o considering possible difference in the final settled value of voltage at the point of
connection, the final value of active and reactive power must settle to within 2% of the
plants rated capacity.

2
An event window is defined as the instant a reference value changes or a disturbance is initiated and lasts until
the response returns to within 5% of the maximum induced or reference quantity change.

Page | 11
Simulation Studies and Modelling Requirements for Compliance Demonstration

1.3. Simulation Studies


This section details simulation studies required for synchronous power generating modules (SPGM). In
most of the simulation studies, a model as given in Figure 1 is sufficient for study purposes and when
this is the case each simulation study directs the user to use the given model arrangement.

Generator Generator
POC System Voltage
Transformer feeder impedance source
Zth
Generator
Auxiliary
transformer ZF Sys tem
and load Fault

Figure 1

System impedance shown in the figure needs to be taken from Minimum System Strength Report.

A summary of the simulation studies for SPGM is given in the following table along with reference to the
EU Network Code (2016/631) simulation requirement and the related EirGrid Grid Code capability
requirement.

Capability Area EU – NC (2016/631) EirGrid GC Capability Validate against test


Fault Ride Through Art(53)3 & Art 51(4) CC.7.3.1.1.(y)
LFSM-O Art51(2) OC.4.3.4.1.8 Yes
LFSM-U Art52(2) OC.4.3.4.1.9 Yes
FSM Art52(3) OC.4.3.4.1.10 Yes
Load Rejection Art52(4) CC.7.3.2.1, CC.7.3.2.2 &
CC.7.3.2.3
Reactive Capability Art52(5) CC.7.3.6 Yes
Power System Stabiliser Art53(2) CC.7.3.8

1.3.1. FRT, Active Power Recovery


Simulate fault-ride-through and active power recovery using a model as in Figure 1 with system
impedance set equal to a value representing minimum short circuit level.

Set generator operation to P=Pmax, Q=Qmin (maximum leading reactive power) for the simulations.

Simulate:

Apply four different types of faults at the POC:

 phase-to-earth fault;
 phase-to-phase fault;

Page | 12
Simulation Studies and Modelling Requirements for Compliance Demonstration

 phase-to-phase-to-earth fault;
 three-phase fault.

Under each of the above faults, set the faulted phases retained voltage at the POC to the values given
below for the given duration. In each case clear the fault and let steady-state condition be reached
before commencing the next study.

Faulted Phase Retained Voltage Fault Duration (milliseconds)


(p.u.)
0 150
0.5 300
0.9 1550

Check and report:

Voltage at generator terminals and POC (Point of Connection)

Active power at generator terminals

Reactive power at generator terminals

Rotor angle

Excitation Voltage

AVR and PSS output signal

Success Criteria:

Generator remains synchronised and stable while meeting the capability requirements in CC.7.3.1.1.(y)

1.3.2. LFSM-U and LFSM-O


This simulation needs to be validated against field tests.

Simulate limited frequency response using the model as in Figure 1 with system impedance set to
minimum short circuit level and the generator operated at Limited Frequency Sensitive Mode with a
droop setting set to 4% with active power as indicated in the table and reactive power at zero

Simulate:

Apply the following frequency step and ramps at the given loading. Each setpoint change is only initiated
when steady state conditions are met.

Page | 13
Simulation Studies and Modelling Requirements for Compliance Demonstration

Loading f step or ramp

Min load -0.5Hz (ramp of 1Hz/sec or step)

Min load +0.5Hz (ramp of 1Hz/sec)

75% -0.5Hz (ramp of 1Hz/sec or step)

75% +0.5Hz (ramp of 1Hz/sec)

90% -0.5Hz (ramp of 1Hz/sec)

-0.5Hz (ramp of 1Hz/sec or step)


92%

-0.5Hz (ramp of 1Hz/sec or step)


95%

100% +0.5Hz (ramp of 1Hz/sec)

Check and report:

Voltage at generator terminals

Active power at generator terminals

Reactive power at generator terminals

Frequency

Success Criteria:

Generator remains stable while meeting the capability requirements in OC.4.3.4.1.8 and OC.4.3.4.1.9

1.3.3. Frequency Sensitive Mode


This simulation needs to be validated against actual compliance tests.

Simulate frequency sensitive mode using the model as in Figure 1 with system impedance set to
minimum short circuit level and the generator operated in Frequency Sensitive Mode.

Generator operating at P= min load, 75%, 90%, 95%, Q=0

Generator droop settings set to 4%.

Simulate:

Apply the following frequency step and ramps.

1- Start with nominal system frequency for t<0 s

Page | 14
Simulation Studies and Modelling Requirements for Compliance Demonstration

2- apply a ramped reduction of 0.5 Hz over x seconds


3- run with the reduced frequency for y seconds
4- apply a ramped increase of 0.3 Hz over z seconds
5- run with this frequency for t seconds

[x,y,z,t to be chosen as appropriate to the simulation in question].

Check and report:

Voltage at generator terminals

Active power at generator terminals

Reactive power at generator terminals

Frequency

Success Criteria:

Generator remains stable while meeting the capability requirements in OC.4.3.4.1.10

1.3.4. Islanded Operation (Load Rejection)


Simulate load rejection using the model as in Figure 1 with system impedance set to minimum short
circuit level and the generator operating at P= Pmax and Q=0

Simulate:

While the generator is at maximum active power output, island the generator from the system by
opening the generator breaker such that it supplies only the house load.

Check and report:

Voltage at generator terminals

Active power at generator terminals

Reactive power at generator terminals

Frequency

Success Criteria:

Generator remains connected and in operation while meeting the capability requirements in
CC.7.3.1.1.w and CC.7.3.1.1.x

1.3.5. Reactive Power Capability


This simulation needs to be validated against field tests; if this is not possible then simulate as per
below.

Page | 15
Simulation Studies and Modelling Requirements for Compliance Demonstration

Simulate reactive power capability of the generator using the model in Figure 1 with system impedance
set to minimum short circuit level. Generator operating at various points as indicated.

Simulate:

Run load flow studies with the generator at various points on the VQ/Pmax diagram.

Check and report:

Check it can supply maximum leading and lagging reactive power at Pmax at specified voltage levels in
CC.7.3.6.5.

Check it can supply maximum leading and lagging reactive power at Pmin at specified voltage levels in
CC.7.3.6.5.

Voltage at generator terminals

Active power at generator terminals

Reactive power at generator terminals

Success Criteria:

Simulation shows output within the boundaries of the VQ/Pmax diagrams given in CC.7.3.6.5.

1.3.6. Power System Stabiliser / AVR Control


Three separate simulations cases are expected for Power System Stabiliser:

Simulation 1:

This simulation is aimed at obtaining the response time of the AVR controls and is named idle response
or open circuit test.

Set generator active and reactive power to zero and apply 10% generator terminal voltage step change
to check excitation system response time.

Check and report:

Generator terminal voltage

AVR output signal

Success Criteria:

Compliance with respect to rise time requirements

Simulation 2:

Voltage variation test under different disturbances

Page | 16
Simulation Studies and Modelling Requirements for Compliance Demonstration

Use minimum system fault level impedance as in Figure 1 and set the generator active power to
maximum and reactive power to maximum leading reactive power (i.e. Qmin).

Apply 5% step to reference voltage to check PSS response to voltage disturbances. Repeat test with PSS
on and off.

Apply three-phase short-circuit at generator transformer HV side. Repeat it with PSS on and off.

Check and report:

Generator terminal voltage

Active power

Reactive power

Excitation voltage

PSS output signal

AVR output signal

Success Criteria:

Improved attenuation of system power fluctuation when PSS is on compared to when PSS is off.

Simulation 3:

This simulation is aimed at obtaining frequency response of the SPGM Excitation System in the form of
Bode diagrams (both gain and phase) in order to have an insight into possible stability margins. Two
separate frequency responses are expected:

Open loop frequency response

Closed loop frequency response

Check and report:

Gain and phase Bode plot for open loop frequency response with PSS on and off.

Gain Bode plot for closed loop on load frequency response with PSS on and off. Generator is operating
at Pmax and unity pf.

Success Criteria:

Improved contribution with PSS operation with respect to the gain and phase margin of Excitation
System during open loop frequency response.

Improved active power damping with PSS during closed loop frequency response.

Page | 17
Simulation Studies and Modelling Requirements for Compliance Demonstration

PART 2. POWER PARK MODULES

2.1. General Provisions


Simulation studies are aimed at demonstrating the performance requirements of individual power-
generating modules and the following general provision apply: (Art 43-1)

 Generating facility shall provide technical data and documentation as part of the simulation
studies compliance procedures (Art 41-3-a and b). All data requirements are detailed in the
Planning Code Appendix of the Grid Code;
 Generating facility shall provide an appropriate model as part of the simulation studies
compliance procedures (Art 41-3-c and d). The timeline of the model provision is covered by the
phases of Operational Notification Procedure;
 EirGrid shall not accept an alternative set of simulations to those given as part of this
compliance procedure (Art 43-2-a);
 EirGrid may require additional or alternative sets of simulations to those given in this procedure
when deemed insufficient to demonstrate compliance (Art 43-2-b);
 Generation facility shall provide a report that includes modelling and results of all the simulation
studies detailed in this procedure (Art 41-3-e & Art 43-3);
 Generation facility shall provide a validated simulation model as detailed in this procedure (Art
43-3);
 EirGrid may perform its own simulation studies based on the simulation model, simulation
reports and compliance test measurements (Art 43-4);
 EirGrid shall provide the generation facility owner system data in order to carry out the
simulation studies detailed in this procedure (Art 43-5); and
 EirGrid shall not accept provision of equipment certificates submitted as part of demonstrating
compliance with relevant simulation study requirement (Art 52-1, 53-1, 55-1 and 56-2).

2.2. Simulation model requirements


2.2.1. Static Model
The static simulation model for power park modules should represent the steady state characteristics of
the generating facility at the point of connection suitable to be used in network-wide load flow and
short-circuit calculation studies. More specifically the static model shall be capable of:

 covering a range of frequencies (47 to 52 Hz) and voltages (0 to 1.4 pu),


 representing the characteristics of the generation facility’s operating ranges for active and
reactive power,

Page | 18
Simulation Studies and Modelling Requirements for Compliance Demonstration

 providing calculated RMS values of all phases for all types of system faults (balanced and
unbalanced),
 providing control functionality with reference points
o reactive power control mode
o voltage control mode including parameters for droop setting
o power factor control mode

2.2.2. RMS Model


The RMS model used for dynamic simulation studies shall include information on or be capable of:

 representing the static and dynamic properties of the generation facility


 covering a range of frequencies (47 to 52 Hz) and voltages (0 to 1.4 pu)
 representing the characteristics of the generation facility’s operating ranges for active and
reactive power,
 handling control functionality (with input/output signals) with indication of reference point
o power factor control,
o reactive power control, and
o voltage control including parameters for droop setting
o frequency control including droop and deadband
o activation of protection functionality
o control signal(s) to external plants such as FACTS devices
 providing calculated RMS values for all types of system faults (balanced and unbalanced),
 activating an internal protection functionality in the event of external network faults,
 utilising an internal excitation system that includes relevant voltage, frequency, stator current,
over and under excitation limiters,
 providing a numerically stable simulation for a minimum of 60 seconds following any set point
changes or system incidents/faults
 running with a variable integration time step in the range of 1 to 10 ms
 initialising in a stable operating point
 not requiring any special settings to be implemented into a larger network model
 simulating the dynamic behaviour of the generators (or generating facility) under system faults,
voltage disturbances and frequency disturbances

If an aggregated model instead of individual units is used, then the aggregated model must be able to
represent the characteristics of the whole facility at the point of connection. Descriptive information on
the aggregation approach and assumptions should be provided.

The provision of the simulation model should be supported and include:

 description of each individual model components and their related parameters,


 description of input and output signal
 explanation of set-up and initialisation of the model
 limitations of the model provided
 list of protection functionality that can be triggered by external events

Page | 19
Simulation Studies and Modelling Requirements for Compliance Demonstration

The model should not contain any compiled parts in order to be embedded within a larger network
model without any restrictions.

2.2.3. EMT Model Requirements


In addition to static and RMS simulation models, PPMs are required to provide an EMT model.

The EMT model should be capable of recreating all the requirements of the static and RMS models and
in addition shall:

 Represent all components, control and protection systems relevant for time domain analysis
 Initialise at a fraction of the simulation time. Conditions under which the model can be assumed
initialised shall be documented.
 Give the user the ability to set various activation schemes within the model (for example
activation of protection functions or apparent power dispatch)
 Allow the user to set all parameters relevant to the analysis
 Be repeatable, i.e. can be used multiple times within the same model without numerical issues
 Be able to capture high frequency transients
 Be capable of representing possible signal delays between various elements (for example park
controller to individual wind turbine generators)
• Include any relevant non-linearities, deadbands, saturation, limits or mathematical functions.
• Primarily be based on the use of standard components that are within the given software
environment
• In the case of compiled or encrypted part, not create any complications or incompatibility with
respect to its integration to a wider network model.
• Be capable of being used in later versions of the given software.

2.2.4. Harmonic Model Requirements


Harmonic model to represent the power park generating facilities harmonic emissions as well as the
effect of its passive network on the transmission system harmonics is required.

The model shall be capable of or include:

• Representing integer harmonic emissions at a single unit level from 2nd to 50th harmonic.
• Being defined either as Thevenin or Norton equivalent
• Passive response of the units (lumped impedance) within 50-2500 Hz range at a resolution of
1 Hz for all sequence networks.
• Specify a summation process from multiple units either using correct phase angles for injections
or utilising a summation law
• Dependency on the power park generating facilities level of generation or operating point –
model valid for at least three different operating regimes (minimum, average and maximum)
shall be submitted
• Details of power park generating facility infrastructure equipment such as cables, transformers,
shunt compensation etc as frequency dependent components.

Page | 20
Simulation Studies and Modelling Requirements for Compliance Demonstration

If the power park generating facility has more than one unit, an aggregated harmonic simulation model
can be submitted instead. The aggregated model shall be such that it represents the total emissions and
include the total passive harmonic impedance at the point of connection within the 5-2500 Hz frequency
range may be used.

2.2.5. Model Submission


The provision of simulation model shall be supported and include:

 instruction of integrating the provided model into a wider network model so as to be used as
part of wider system studies.
 guidance on the interpretation of error messages and troubleshooting.
 a comprehensive list of parameters, default and range of values applicable, block diagrams and
transfer functions.
 model single line diagram showing main electrical components and connectivity to the network
interface point.
 description of each individual model components and their related parameters,
 description of initialisation of the model for simulations,
 Laplace domain transfer functions, sequence diagrams and any arithmetic or logical sequence
modules within the model description
 saturation, dead bands, non-linearity, time delays, any interpolation assumptions and any look-
up tables utilised within the parameters utilised
 description of the electrical input and output signals, explanation on the measurement point
used, signal units and base values.
 explanation on any restrictions on its use, limits applicable such as the maximum integration
step size, and accuracy of the model.
 list of protection functionality that can be triggered by external events
 diagrams of control system and any other equipment implemented within the control system in
the form of standardised block diagrams
 information on applicable software version, compiler version if any and simulation model
unique version control.

For a power park that comprises more than one generator unit, the submitted simulation model must
be such that the characteristics of the power park is represented at the point of connection. Submitted
model parameters must contain all data sets for each unit.

The static and RMS simulation models submitted to EirGrid must be implemented in (or compatible
with) PSSE34 and later versions. No special settings other than standard software setting should be
required for the submitted model to be implemented.

The EMT model must be developed and delivered in PSCAD version 4.6.3 or later.

The harmonic simulation model shall be delivered in PowerFactory version 2020.

Page | 21
Simulation Studies and Modelling Requirements for Compliance Demonstration

RMS and EMT models require verification and validation which shall be included in the submitted
simulation report. The EMT model must be validated for simulations at different simulation time steps
and should also include comparison of the static and RMS dynamic model response. Model validation
against test measurements is a requirement and the specific simulation that needs to be validated
against actual tests are indicated above.

In general accuracy requirement for PPM models and simulation follow a similar line to SPGM as in the
previous section and repeated below. For EMT model and simulation accuracy, identical approach to
RMS is used. However, the comparison is evaluated using RMS quantities with an appropriate filtering
for power frequency component of measured and simulated parameters. The method of filtering must
be agreed between EirGrid and the facility owner prior to any measurements and simulations.

The submitted simulation model and studies shall have the following accuracy requirements:

 For a linear response over a frequency range of 0.1 to 5Hz, deviations between simulated and
measured waveforms of the control system must be less than 10% for amplitude and less than 5
degrees for the phase angle. Discrete waveform changes (amplitude spikes) on the simulated
waveform should be less than 10% in relation to measured quantity and in the case of where
this level is exceeded due to numerical integration issues, this should be documented in the
report.
 For dynamic time domain simulations where non-linear response is included to replicate set
point changes or response to disturbances on the wider network, the following requirements
apply for deviations between simulated and measured response:
o for rapid slopes within 10% for 95% of the samples recorded within a defined event
window3, and time offset of the gradient start or end time must be less than 20
milliseconds;
o for events (e.g. switching) resulting in positive and negative spikes, the amplitude must
be less than 10% from the corresponding measured value for 95% of the samples
recorded;
o oscillation in active power, reactive power, voltage and frequency in the 0.1-5Hz range
must have damping and the deviation in the frequency of oscillation must be less than
10% for 95% of the recorded samples;
o considering possible difference in the voltage at the point of connection, deviation in
active and reactive power response must be less than 10% for 95% of the samples;
o considering possible difference in the final settled value of voltage at the point of
connection, the final value of active and reactive power must settle to within 2% of the
plants rated capacity.

3
An event window is defined as the instant a reference value changes or a disturbance is initiated and lasts until
the response returns to within 5% of the maximum induced or reference quantity change.

Page | 22
Simulation Studies and Modelling Requirements for Compliance Demonstration

2.3. PPM Simulation Studies


This section details simulation studies required for power park modules generating modules (PPM). In
most of the simulation studies, a model as given in Figure 2 is sufficient for study purposes and when
this is the case each simulation study directs the user to use the given model arrangement.

Generator Generator
POC System Voltage
Transformer feeder impedance source
Zth
Generator
Auxiliary
transformer ZF Sys tem
and load Fault

Figure 2

System impedance shown in the figure needs to be taken from Minimum System Strength Report.

A summary of the simulation studies for PPM is given in the following table along with reference to the
EU Network Code (2016/631) simulation requirement and the related EirGrid Grid Code capability
requirement.

Capability Area EU – NC (2016/631) EirGrid GC Capability Validate against test


Fast Fault Current Art54(3), Art54(5) & GC PPM1.4.2.a,
Active Power Recovery Art56(3) PPM1.4.2.b, PPM1.4.2.c
Fault Ride Through & PPM1.4.2.f
LFSM-O Art54(2) PPM1.5.3.11 Yes
LFSM-U Art55(2) PPM1.5.3.12 Yes
FSM Art55(3) PPM1.5.3.13 Yes
Load Rejection Art55(4) CC.7.3.2.1, CC.7.3.2.2 &
CC.7.3.2.3
Reactive Capability Art55(6) PPM1.6.3.1 & Yes
PPM1.6.3.4
Power Oscillation Art55(7) N/A
Damping

2.3.1. FRT, Active Power Recovery and Fast Fault Current


Simulate fault-ride-through and active power recovery using a model as in Figure 2 with system
impedance set equal to a value representing minimum short circuit level.

Note: Please refer to the notes in Appendix A with respect to the interpretation of PPM1.4.2(c).

Page | 23
Simulation Studies and Modelling Requirements for Compliance Demonstration

Set generator operation to P=Pmax, Q=0 for the simulations.

Simulation 1: Fault Ride-Through

Apply four different types of faults at the POC:

 phase-to-earth fault;
 phase-to-phase fault;
 phase-to-phase-to-earth fault;
 three-phase fault.

Under each of the above faults, set the faulted phases retained voltage at the POC to the values given
below for the given duration. In each case clear the fault and let steady-state condition to be reached
before commencing the next study.

Faulted Phase Retained Voltage Fault Duration (milliseconds)


(p.u.)
0 150
0.4 1250
0.85 2900

Check and report:

Voltage at generator terminals and POC

Active power and Active Current at generator terminals and POC

Reactive power and Reactive Current at generator terminals and POC

Success Criteria:

(i) Generator remains connected and stable while meeting the capability requirements in
PPM1.4.2.f
(ii) Show compliance against GC PPM1.4.2.a, PPM1.4.2.b and PPM1.4.2.c Note that Rise Time
and Settling will be checked in Simulation 2 below.

Simulation 2: Rise Time / Settling Time

Apply a three-phase fault leading to a voltage step-change to 0.5 pu retained voltage at the POC.

Check and report:

Voltage at the generator terminals and POC

Active power and active current at generator terminals and POC

Reactive power and reactive current at generator terminals and POC.

Success Criteria:

Page | 24
Simulation Studies and Modelling Requirements for Compliance Demonstration

Show compliance against PPM1.4.2.c Rise Time and Settling Time criteria.

2.3.2. LFSM-U and LFSM-O


This simulation needs to be validated against actual compliance tests.

Simulate Limited Frequency Sensitive Mode response using the model in Figure 2 with system
impedance set to minimum short circuit level. The generator should be operated at LFSM with an active
power P as indicated in the curve shown below and reactive power set to zero.

Generator droop settings set to 4%.

Simulate:

Apply Curve 1 Resource Following Mode as shown in the next figure and table. Each setpoint change is
only initiated when steady state conditions are met.
Controllable WFPS Active Power Output

100
as a % of Available Active Power

100% AAP (Curve 1)

% Reserve (Curve 2)
`

Default (95% of AAP)

Frequency Droop Slope

Curve 1 & Curve 2


response

DMOL

0 FA FB FC FD FE
50
Frequency (Hz)

Transmission System Required Active Power Output


Frequency f (Hz)
f < 48 100% of AAP
FA 48 PA 100% of AAP
Under Frequency 48 < f < 49.8 100% of AAP
Response
FB f = 49.8 PB 100% of AAP
+/-0.2Hz 49.8 < f < 50.2 100% of AAP
Deadband
FC f = 50.2 PC 100% of AAP
Over Frequency 50.2 < f < 51.9 AAP + ∆MW2
Response
FD f = 51.9 PD Minimum of: AAP and DMOL
FE f = 52 PE 0%3
f > 52 0%3

Page | 25
Simulation Studies and Modelling Requirements for Compliance Demonstration

Check and report:

Voltage at generator terminals and POC

Active power at generator terminals and POC

Reactive power at generator terminals and POC

Frequency

Success Criteria:

Generator remains stable while meeting the capability requirements in PPM1.5.3.11 and PPM1.5.3.12

2.3.3. Frequency Sensitive Mode


This simulation needs to be validated against actual compliance tests.

Simulate Frequency Sensitive Mode response using the model in Figure 2 with system impedance set to
minimum short circuit level. The generator should be operated at FSM with an active power P as
indicated in the curve shown below and reactive power set to zero

Generator droop settings set to 4%.

Simulate:

Apply the Curve 1 Active Power Control Mode as shown in the next figure and table. Each setpoint
change is only initiated when steady state conditions are met.

Transmission Required Active


Controllable WFPS Active Power Output

100 System Power Output


as a % of Available Active Power

Frequency f
(Hz)
100% AAP (Curve 1)

% Reserve (Curve 2)
`

Default (95% of AAP)

Frequency Droop Slope

Curve 1 & Curve 2


response

DMOL

0 FA FB FC FD FE
50
Frequency (Hz)

f < 48 100% of AAP


FA f = 48 PA 100% of AAP
Under Frequency Response 48 < f < 49.985 Minimum of: APC
Setpoint + ∆MW
and AAP
FB f = 49.985 PB Minimum of: APC

Page | 26
Simulation Studies and Modelling Requirements for Compliance Demonstration

Setpoint and AAP


+/-0.015Hz Deadband 49.985 < f < Minimum of: APC
50.015 Setpoint and AAP
FC f = 50.015 PC Minimum of: APC
Setpoint and AAP
Over Frequency Response 50.015 < f < 51.9 Minimum of: APC
Setpoint + ∆MW
and AAP + ∆MW1, 2
FD f = 51.9 PD Minimum of: APC
Setpoint and AAP
and DMOL
FE f = 52 PE 0%3
f > 52 0%3

Check and report:

Voltage at generator terminals and POC

Active power at generator terminals and POC

Reactive power at generator terminals and POC

Frequency

Success Criteria:

Generator remains stable while meeting the capability requirements in PPM1.5.3.13.

2.3.4. Reactive Power Capability


This simulation needs to be validated against actual compliance tests.

Demonstrate reactive power capability using the model in Figure 2 with system impedance set to
minimum short circuit level and the generator operating at various points.

Simulate:

Run load flow studies with the generator at various points on the VQ/Pmax diagram.

Check and report:

Check it can supply maximum leading and lagging reactive power at Pmax at specified voltage levels in
PPM1.6.3.4.

Check it can supply maximum leading and lagging reactive power at Pmin at specified voltage levels in
PPM1.6.3.4.

Page | 27
Simulation Studies and Modelling Requirements for Compliance Demonstration

Voltage at generator terminals

Active power at generator terminals

Reactive power at generator terminals

Success Criteria:

Simulation shows output within the boundaries of the VQ/Pmax diagrams given in PPM1.6.3.4.

2.3.5. Islanded Operation (Load Rejection) (Only if requested by EirGrid)


Demonstrate islanded operation capability using the model in Figure 2 with system impedance set to
minimum short circuit level and the generator operating at P= Pmax and Q=0.

Simulate:

While the generator is at maximum active power output, island the generator from the system by
opening the breaker connecting the power park to the system such that it supplies only the auxiliary and
any local load.

Check and report:

Voltage at generator terminals

Active power at generator terminals

Reactive power at generator terminals

Frequency

Success Criteria:

Generator remains connected and in operation while meeting the capability requirements in
CC.7.3.1.1.w and CC.7.3.1.1.x

2.3.6. Power System Stabiliser / AVR Control (Not Applicable Presently)


If a Power System Stabiliser is specified for voltage control or if there is one already included in the
voltage control system, then a simulation demonstrating power oscillation damping capability is
required. The purpose is to confirm correct operation of AVR system in kV, Q and power factor control
modes, and changing between modes and to validate simulations against filed tests; if this is not
possible then simulate as per below. For the AVR A step change in system voltage is created to allow
analysis of the AVR rate of response. The step change is ideally created by NCC carrying out switching on
the system. If this is not possible, the PPM shall carry out a manual tap change to induce a small step
change in system voltage.

Simulate:

Page | 28
Simulation Studies and Modelling Requirements for Compliance Demonstration

Voltage variation test under different disturbances

Use minimum system fault level impedance.

P=Pmax and Q=Qmin (maximum leading reactive power)

Apply 5% step to reference voltage to check PSS response to voltage disturbances. Repeat test with PSS
on and off.

Apply an appropriate three-phase short-circuit at grid connection point, with PSS on and off, in order to
show improvement with PSS on.

Check and report:

Generator terminal and POC voltage

Active power

Reactive power

Excitation voltage

PSS output signal

AVR output signal

Success Criteria:

Improved attenuation of system power fluctuation when PSS is on compared to when PSS is off.

Page | 29
Simulation Studies and Modelling Requirements for Compliance Demonstration

PART 3. DEMAND FACILITIES, DISTRIBUTION FACILITIES


and DISTRIBUTION SYSTEMS

3.1. General Provisions


 Simulation studies are required for new and modified (further development or modernisation of
equipment) demand facilities, when the demand facility or closed distribution system is
contracted to provide very fast active power control or alleged incompliance with the
requirements of the Grid Code(Art 42-2)
 EirGrid shall not accept an alternative set of simulations to those given as part of this
compliance procedure (Art 42-3a)
 EirGrid may require additional or alternative sets of simulations to those given in this procedure
when deemed insufficient to demonstrate compliance (Art 42-3b)
 Demand facility shall provide a report that includes modelling and results of all the simulation
studies detailed in this procedure (Art 42-4)
 EirGrid may perform its own simulation studies based on the simulation model, simulation
reports and compliance test measurements (Art 42-5)
 EirGrid shall provide the demand facility owner system data in order to carry out the simulation
studies detailed in this procedure (Art 42-6)
 Demand facility shall provide the following documents and technical data as part of the
simulation studies compliance procedures (Art 35-3-a and b)
 Demand facility shall provide appropriate model as part of the simulation studies compliance
procedures (Art 35-3-c and d) [timeline is covered by the phases of operational notification].

3.2. Simulation model requirements


The level of simulation model under DCC generally includes the steady-state properties of the
transmission-connected demand facility or transmission-connected distribution system. Dynamic
simulation models (and in some cases harmonic simulation models) are also required as part of data
submission.

3.2.1. Static Model


The static simulation model for transmission connected demand facility or transmission connected
distribution system should be suitable for load flow and short circuit calculation studies. More
specifically the static model shall include information on:

 Total active and reactive power consumption.


 Dependency of active and reactive power on voltage and frequency (if any)

Page | 30
Simulation Studies and Modelling Requirements for Compliance Demonstration

 Composition of load in terms of type (induction motor load, power electronic converter-based
load etc)
 Installed embedded generation capacity
 Reactive power data both from discrete components such as shunt reactors/capacitors and also
from those generated by equipment such as cables.
 covering a range of frequencies (47 to 52 Hz) and voltages (0 to 1.4 pu),

3.2.2. RMS Model


The RMS model used for dynamic simulation studies shall include information or be capable of:

 representing the static and dynamic properties of the transmission-connected demand facility
or transmission connected distribution system
 covering a range of frequencies (47 to 52 Hz) and voltages (0 to 1.4 pu)
 representing the characteristics of the demand facility’s operating ranges for active and reactive
power,
 providing calculated RMS values for all types of system faults (balanced and unbalanced),
 representing the voltage dependency (overvoltage and undervoltage) of the facility
 representing the frequency dependency of the facility
 activating any internal protection functionality in the event of external network faults,
 including any control functionality (such as tap changers or blocking functionality)
 utilising any internal reclosing or swapping functionality (for example local demand to UPS)
 providing a numerically stable simulation for a minimum of 60 seconds following any system
incidents/faults
 initialising in a stable operating point
 running under with a variable time step in the range of 1 to 10 ms
 not requiring any special settings to be implemented into a larger network model
 simulating the dynamic behaviour of the demand facility under system faults, voltage
disturbances and frequency disturbances

If an aggregated model instead of individual units is used, then the aggregated model must be able to
represent the characteristics of the whole facility at the point of connection. Descriptive information on
the aggregation approach and assumptions should be provided.

The provision of simulation model should be supported and include:

 description of each individual model components and their related parameters,


 description of input and output signal
 explanation of set-up and initialisation of the model
 limitations of the model provided
 list of protection functionality that can be triggered by external events

The model should not contain any compiled parts in order to be embedded within a larger network
model without any restrictions. We suggest using a standard library model if possible.

Page | 31
Simulation Studies and Modelling Requirements for Compliance Demonstration

3.2.3. Harmonic Model Requirements


A harmonic model is required to represent the transmission connected demand facility or transmission
connected distribution system harmonic emissions as well as the passive network’s effect on the
transmission system harmonics.

The model shall be capable of or include:

• Representing integer harmonic emissions if any either as aggregate or at individual unit level
• Emissions being defined either as Thevenin or Norton equivalent
• Passive response of the facility (lumped impedance) within 50-2500 Hz range at a resolution of
1 Hz for all sequence networks.
• Specify a summation process from multiple units either using correct phase angles for injections
or utilising a summation law

An aggregated model representative of the demand facility’s total emissions, instead of multiple units
can be submitted. The aggregated model must be able to represent the characteristics of the whole
facility at the point of connection such that it represents the total emissions and include the total
passive harmonic impedance at the point of connection within the 5-2500 Hz frequency range.
Descriptive information on the aggregation approach and assumptions should be provided.

3.2.4. Model Submission


The provision of simulation model shall be supported and include:

 instruction on integrating the provided model into a wider network model so as to be used as
part of wider system studies.
 guidance on the interpretation of error messages and troubleshooting.
 a comprehensive list of parameters, default and range of values applicable, block diagrams and
transfer functions.
 model single line diagram showing main electrical components and connectivity to the network
interface point.
 description of each individual model components and their related parameters,
 description of initialisation of the model for simulations,
 Laplace domain transfer functions, sequence diagrams and any arithmetic or logical sequence
modules within the model description
 saturation, dead bands, non-linearity, time delays, any interpolation assumptions and any look-
up tables utilised within the parameters utilised
 description of the electrical input and output signals, explanation on the measurement point
used, signal units and base values.
 explanation on any restrictions on its use, limits applicable such as the maximum integration
step size, and accuracy of the model.
 list of protection functionality that can be triggered by external events
 diagrams of control system and any other equipment implemented within the control system in
the form of standardised block diagrams
 information on applicable software version and simulation model unique version control.

Page | 32
Simulation Studies and Modelling Requirements for Compliance Demonstration

The static and RMS simulation models submitted to EirGrid must be implemented in or compatible with
PSSE 34 and subsequent versions. No special settings other than standard software setting should be
required for the submitted model to be implemented.

The harmonic simulation model shall be delivered in PowerFactory version 2020.

RMS models require verification and validation which shall be included in the submitted simulation
report.

Accuracy requirement for PPM models and simulation follow a similar line to SPGM as in the previous
section and repeated below.

The submitted simulation model and studies shall have the following accuracy requirements:

 For a linear response over a frequency range of 0.1 to 5Hz, deviations between simulated and
measured waveforms of the control system must be less than 10% for amplitude and less than 5
degrees for the phase angle. Discrete waveform changes (amplitude spikes) on the simulated
waveform should be less than 10% in relation to measured quantity and in the case of where
this level is exceeded due to numerical integration issues, this should be documented in the
report.
 For dynamic time domain simulations where non-linear response is included to replicate set
point changes or response to disturbances on the wider network, the following requirements
apply for deviations between simulated and measured response:
o for rapid slopes within 10% for 95% of the samples recorded within a defined event
window4, and time offset of the gradient start or end time must be less than 20
milliseconds;
o for events (e.g. switching) resulting in positive and negative spikes, the amplitude must
be less than 10% from the corresponding measured value for 95% of the samples
recorded;
o oscillation in active power, reactive power, voltage and frequency in the 0.1-5Hz range
must have damping and the deviation in the frequency of oscillation must be less than
10% for 95% of the recorded samples;
o considering possible difference in the voltage at the point of connection, deviation in
active and reactive power response must be less than 10% for 95% of the samples;
o considering possible difference in the final settled value of voltage at the point of
connection, the final value of active and reactive power must settle to within 2% of the
plants rated capacity.

4
An event window is defined as the instant a reference value changes or a disturbance is initiated and lasts until
the response returns to within 5% of the maximum induced or reference quantity change.

Page | 33
Simulation Studies and Modelling Requirements for Compliance Demonstration

3.3. DCC Simulation Studies


3.3.1. Reactive Power Capability
(Art 43 -1, 44-1)

Simulate:

Run load flow studies with the demand facility or distribution system at various load and generation
conditions including minimum and maximum and simulate the lowest and highest reactive power
exchange.

Run load flow study to check the level of reactive power export while the facility or distribution system
is importing less than 25% of the maximum import capability.

Check and report:

Check that reactive power exchange is within the capability requirements specified in CC.7.4.2.4.

Voltage at the point of connection

Active power at the point of connection

Reactive power at the point of connection

Success Criteria:

Simulation shows output within the exchange boundaries given in CC.7.4.2.4

3.3.2. Very Fast Active Power Control


(Art 45-1)

Simulate:

In an RMS dynamic simulation to mimic a low frequency event apply a frequency step and/or ramps
relative to the contractual agreement in place. There should be a contractually defined change of active
power related to a measure of rate-of-change-of-frequency and a response time for the very fact active
power control that should be less than 2 seconds.

Check and report:

Voltage at the point of connection

Active power at the point of connection

Reactive power at the point of connection

Frequency

Page | 34
Simulation Studies and Modelling Requirements for Compliance Demonstration

Response time of control system

Success Criteria:

Facility remains within the technical capability specified in the contractual agreement.

Page | 35
Simulation Studies and Modelling Requirements for Compliance Demonstration

PART 4. HVDC Converter Stations, DC Connected PPMs


[Draft]

PLEASE NOTE: PART 4 IS DRAFT AND NOT YET APPROVED, BUT IS INCLUDED FOR
COMPLETENESS.

4.1. General Provisions


Simulation studies are aimed at demonstrating the performance requirements of HVDC systems and DC-
connected power park modules. (Art 68-1)

 EirGrid shall not accept an alternative set of simulations to those given as part of this
compliance procedure (Art 68-2-a)
 EirGrid may require additional or alternative sets of simulations to those given in this procedure
when deemed insufficient to demonstrate compliance (Art 68-2-b)
 HVDC system owner or DC-connected power park module owner shall provide a validated
simulation model as detailed in this procedure (Art 68-3)
 HVDC system owner or DC-connected power park module owner shall provide a report that
includes modelling and results of all the simulation studies detailed in this procedure (Art 68-3)
 EirGrid may perform its own simulation studies based on the provided simulation models,
simulation reports and compliance test measurements (Art 68-4)
 EirGrid shall provide the HVDC system owner or DC-connected power park module owner
system data in order to carry out the simulation studies detailed in this procedure (Art 68-5)
 EirGrid shall not (or shall) accept provision of equipment certificates submitted as part of
demonstrating compliance with relevant simulation study requirement (Art 73-1)

4.2. Simulation model requirements


4.2.1. Static Model
The static simulation model for HVDC system should represent the steady state characteristics of the
converter station at the point of connection suitable to be used in network wide load flow and short
circuit calculation studies. More specifically the static model shall:

 Include operational characteristics in terms of active and reactive power ranges


 Function for a range of frequencies (47 to 52 Hz) and voltages (0 to 1.4 pu)

Page | 36
Simulation Studies and Modelling Requirements for Compliance Demonstration

 Various control functionality with reference points


o Reactive power control mode
o Voltage control mode including parameters for droop setting
o Power factor control mode
 Have the capability to facilitate selection of any control mode
 Provide calculated RMS values of all phases for all types of system faults (balanced and
unbalanced),

4.2.2. RMS Model


The RMS simulation model for the HVDC system is aimed to represent the dynamic behaviour of the
installation at the point of connection to the wider network under all conditions that the HVDC system is
designed to operate. The RMS dynamic model shall:

 Include the characteristics of the HVDC system’s operating ranges for active and reactive power
 Function for a range of frequencies (47 to 52 Hz) and voltages (0 to 1.4 pu)
 Include input/output signals which include as a minimum the following:
o Active power
o Reactive power
o Frequency control
o Runback
o Control functionality
 active power
 reactive power
 power factor control
 voltage control (with droop setting capability)
 frequency control (with deadband)
 protection activation
o Emergency power control (both active and reactive)
o Power Oscillation Damping (POD)
o Blackstart
o External component control (e.g. STATCOM or battery)
 Be capable of activating an internal protection functionality in the event of external network
faults.
 Be capable of simulating the dynamic behaviour of the HVDC system under system faults,
voltage disturbances and frequency disturbances
 Provide calculated RMS values of all phases for all types of system faults (balanced and
unbalanced).
 Be able to represent the HVDC plant's FRT characteristics.
 Be able to operate with a variable time step for numerical integration running in the range of 1
to 10ms.
 Initialise to a stable operating point and be numerically stable at instantaneous phase angle
jumps of up to 20 degrees.

Page | 37
Simulation Studies and Modelling Requirements for Compliance Demonstration

 Be able to run in a stable manner for up to 100 seconds following any setpoint changes or
events on the system
 Not require any special settings to be implemented into a larger network model
 Not contain any encrypted or compiled parts
 Include any special functionality provided by the actual HVDC system, such as control scheme
for weak grids.

4.2.3. EMT Model


The static and RMS simulation models are aimed to represent the steady-state and dynamic properties
of the HVDC system at the network connection point. Therefore, the need is to have simulation models
that correspond sufficiently accurately to the steady-state response of the actual facility for a valid
steady-state operational point, and for the dynamic response associated with a setpoint change or an
external event in the wider power supply network.

In addition to the static and RMS model, an EMT model for the HVDC system shall be submitted to
EirGrid to be used in electromagnetic time domain studies.

The EMT model should be capable of recreating all the requirements of the static and RMS models and
in addition shall:

• Include implementation of network components and other assets including control systems and
protective devices that are part of the infrastructure to a level of detail valid for the EMT-
studies.
• Include component models especially with respect to power electronics at individual switching
device level.
• Include user adjustable simulation time for activation of protection functions
• Include user adjustable simulation time for apparent power dispatch
• Primarily be based on the use of standard components that are within the given software
environment
• In the case of compiled or encrypted part, not create any complications or incompatibility with
respect to its integration to a wider network model.
• Be capable of using it in later versions of the given software.
• Be suitable for use under black start and islanded operation
• Initialise at a fraction of the simulation time. Conditions under which the model can be assumed
initialised shall be documented.

4.2.4. Harmonic Simulation Model


Harmonic model to represent the HVDC system harmonic emissions as well as the effect of its passive
network on the transmission system harmonics is required.

Page | 38
Simulation Studies and Modelling Requirements for Compliance Demonstration

The model shall be capable of or include:

• Representing integer harmonic emissions


• Being defined either as Thevenin or Norton equivalent
• Passive response of the units (lumped impedance) within 50-2500 Hz range at a resolution of
1 Hz for all sequence networks.
• Dependency on the HVDC system operating point – model valid for at least three different
operating regimes (minimum, average and maximum power transfer) shall be submitted
• Details of the HVDC system infrastructure equipment such as cables, transformers, shunt
compensation etc as frequency dependent components.

4.2.5. Model Submission


The models provided must be accompanied with a user guide that should include descriptions of the
implemented automatic control, protection and regulation functions and enough information to allow
EirGrid to implement the model in other platforms as required. More specifically the model guide
document submission must include:

• Description of the setup and initialization process for the model


• Instruction of integrating the provided model into a wider network model so as to be used as
part of wider system studies.
• Guidance on the interpretation of error messages and troubleshooting.
• Model single line diagram showing main electrical components and connectivity to the network
interface point.
• Description of the electrical input and output signals, explanation on the measurement point
used, signal units and base values.
• A comprehensive list of parameters, default and range of values applicable, block diagrams and
transfer functions.
• Explanation on any restrictions on its use, limits applicable such as the maximum integration
step size, and accuracy of the model.
• Description of HVDC system functions not included in the model and the effect this will have on
the relevant model use (for example in the case if EMT model on transient studies).
• Information on applicable software version, compiler version if any and simulation model
unique version control.

The static and RMS simulation models submitted to EirGrid must be implemented in or compatible with
PSSE 34. No special settings other than standard software setting should be required for the submitted
model to be implemented.

The EMT model must be developed and delivered in PSCAD version 4.6.3.

The harmonic simulation model shall be delivered in PowerFactory version 2020.

RMS and EMT models require verification and validation which shall be included in the submitted
simulation report. The EMT model must be validated for simulations at different simulation time steps
and should also include comparison of the static and RMS dynamic model response. Model validation

Page | 39
Simulation Studies and Modelling Requirements for Compliance Demonstration

against test measurements is a requirement and the specific simulation that needs to be validated
against actual tests are indicated.

Accuracy requirement for HVDC models and simulation follow a similar line to other technologies as in
the previous sections and repeated below. For EMT model and simulation accuracy, identical approach
to RMS is used. However, the comparison is evaluated using RMS quantities with an appropriate filtering
for power frequency component of measured and simulated parameters. The method of filtering must
be agreed between EirGrid and the facility owner prior to any measurements and simulations.

The submitted simulation model and studies shall have the following accuracy requirements:

 For a linear response over a frequency range of 0.1 to 5Hz, deviations between simulated and
measured waveforms of the control system must be less than 10% for amplitude and less than 5
degrees for the phase angle. Discrete waveform changes (amplitude spikes) on the simulated
waveform should be less than 10% in relation to measured quantity and in the case of where
this level is exceeded due to numerical integration issues, this should be documented in the
report.
 For dynamic time domain simulations where non-linear response is included to replicate set
point changes or response to disturbances on the wider network, the following requirements
apply for deviations between simulated and measured response:
o for rapid slopes within 10% for 95% of the samples recorded within a defined event
window5, and time offset of the gradient start or end time must be less than 20
milliseconds;
o for events (e.g. switching) resulting in positive and negative spikes, the amplitude must
be less than 10% from the corresponding measured value for 95% of the samples
recorded;
o oscillation in active power, reactive power, voltage and frequency in the 0.1-5Hz range
must have damping and the deviation in the frequency of oscillation must be less than
10% for 95% of the recorded samples;
o considering possible difference in the voltage at the point of connection, deviation in
active and reactive power response must be less than 10% for 95% of the samples;
o considering possible difference in the final settled value of voltage at the point of
connection, the final value of active and reactive power must settle to within 2% of the
plants rated capacity.

5
An event window is defined as the instant a reference value changes or a disturbance is initiated and lasts until
the response returns to within 5% of the maximum induced or reference quantity change.

Page | 40
Simulation Studies and Modelling Requirements for Compliance Demonstration

4.3. Simulation Studies


A summary of the simulation studies for HVDC converter station is given in the following table along
with reference to the EU Network Code (2016/1447) simulation requirement and the related EirGrid
Grid Code capability requirement.

Capability Area EU – NC (2016/1447) EirGrid GC Capability Validate against test


Fault Ride Through Art 73(3) CC.7.5.12.1
Fast Fault Current Art 73(2) CC.7.5.12.4
Active Power Recovery Art 73(4) CC.7.5.12.6
Reactive Capability Art 73(5) CC.7.5.10.(d) Yes
Power Oscillation Damping Art 73(6) CC.7.5.4.(k)
Active Power Modification Art 73(7) CC.7.5.8.5
Active Power Reversal Art 73(8) CC.7.5.1.1.(k)

DC connected Power Park Modules and remote-end HVDC converter stations are also subject to
simulation studies and these are given in the following table. Studies associated with DC connected
PPMs should in principle follow a similar line to any other controllable PPM and the remote-end HVDC
converter station simulation study should follow the study line for HVDC converter station.
Capability Area EU – NC (2016/1447) EirGrid GC Capability Validate against test
Fast Fault Current (DC PPM) Art 74(2) PPM1.4.2.c
Active Power Recovery (DC Art 74(3) PPM1.4.2.b
PPM)
Reactive Capability (DC Art 74(4) PPM1.6.3.5 Yes
PPM)
Reactive Capability (remote Art 74(5) CC.7.5.10.(f) Yes
end HVDC)
Power Oscillation Damping Art 74(6) N/A
(DC PPM)
Fault Ride Through (DC Art 74(7) PPM1.4.2.f
PPM)

4.3.1. Fault Ride Through


Simulate Fault Ride Through capability of the HVDC installation using the model in Figure 1 with system
impedance set to minimum short circuit level. HVDC system operating at both import and export
configuration with P=Pmax.

Page | 41
Simulation Studies and Modelling Requirements for Compliance Demonstration

Simulate:

Apply four different types of faults at the POC:

 phase-to-earth fault;
 phase-to-phase fault;
 phase-to-phase-to-earth fault;
 three-phase fault.

Under each of the above faults, set the faulted phases retained voltage at the POC to the values given
below for the given duration. In each case clear the fault and let steady-state condition to be reached
before commencing the next study.

Faulted Phase Voltage (p.u.) Fault Duration (milliseconds)


Uret = 0 150 (tclear = 150)
Urec1 = 0.85 2350 (trec1 = 2500)
Urec2 = 0.90 7500 (trec2 = 10000)

Check and report:

Voltage at HVDC station terminals

Active power at HVDC station terminals

Reactive power at HVDC station terminals

Real and reactive currents at the HVDC terminals.

Provide same plots for the remote end converter station.

Success Criteria:

HVDC system remains connected and stable while meeting the capability requirements in xyz [GC clause
that specifies the voltage against time profile – CC.7.5.12.1 but may change!]

4.3.1. Fast fault current injection


In order to demonstrate fast fault current injection, use simulation results from the Fault Ride Through.

Check and report:

Voltage at HVDC station terminals

Active and Reactive Current at HVDC station terminals

Active power at HVDC station terminals grid side of the converter station transformer and POC

Page | 42
Simulation Studies and Modelling Requirements for Compliance Demonstration

Reactive power at HVDC station terminals grid side of the converter station transformer POC

Success Criteria:

HVDC system provides fault current within the rating of the interconnector converter station with a rise
time and settling times as specified in GC CC.7.5.12.4.

4.3.2. Active power recovery


Simulate post fault active power recovery capability of the HVDC installation using the model in Figure 1
with system impedance set to minimum short circuit level. HVDC system operating at both import and
export configuration with P=Pmax.

Simulate:

Apply a fault and clear within 500 ms (all four fault types).

Apply a fault and clear at a time longer than 500 ms (all fault types).

Check and report:

Voltage at the HVDC station terminals

Active power from the HVDC station

Reactive power from the HVDC station

Reactive current from the HVDC station

Success Criteria:

Show compliance against GC active power recovery requirements in xyz [current proposals indicate
CC.7.5.12.6 but may change!]

4.3.3. Reactive power capability


This simulation needs to be validated against actual compliance tests.

Simulate reactive power capability of the HVDC installation using the model in Figure 1 with system
impedance set to minimum short circuit level. HVDC converter station operating at various points as
indicated.

HVDC system operating at both import and export configuration.

Simulate:

Page | 43
Simulation Studies and Modelling Requirements for Compliance Demonstration

Run load flow studies with the HVDC system at various points on the VQ/Pmax diagram given in Grid
Code CC.7.5.10.(d).

Check and report:

Check that the HVDC system can supply maximum leading and lagging reactive power at Pmax at
specified voltage levels in CC.7.5.1.1.(v) [voltage levels will be those that come due to the requirements
of Art 18 from the EU code – they are given in Annex III].

Check that the HVDC system can supply maximum leading and lagging reactive power at Pmin at
specified voltage levels in CC.7.5.1.1.(v) [voltage levels will be those that come due to the requirements
of Art 18 from the EU code – they are given in Annex III].

Check that the HVDC system operating point can move and operate anywhere within the VQ/Pmax
diagram when operating at P<Pmax.

Voltage at HVDC converter station and point of connection.

Active power at HVDC converter station and point of connection.

Reactive power at HVDC converter station and point of connection.

Success Criteria:

Simulation shows output within the boundaries of the VQ/Pmax diagrams given in GC CC.7.5.10.(d).

4.3.4. Power oscillations damping control


Power Oscillation Damping (POD) study is conducted to demonstrate performance of the damping
control of the HVDC system. POD is normally tuned to specific frequency range of oscillations and the
network conditions that lead to these oscillations. It is therefore imperative that the developer initiates
an early technical communication channel with EirGrid so that network conditions identified by EirGrid
from a dynamic stability assessment that indicate stability limits and potential stability problems can be
obtained as the starting point. Although not recommended, an alternative approach would be to
perform a survey to identify oscillation conditions on the wider system where the performance of POD
control functionality can be demonstrated.

Simulate:

Apply system fault leading to oscillations of electromechanical nature. The time domain simulations
should be of sufficient duration in order to identify stabilization (this is particularly the case for
oscillations involving frequency variations) – around 60 to 100 seconds.

Time domain studies shall be supported with additional eigenvalue studies in order to demonstrate the
oscillation modes and damping performance with and without the POD controller in operation.

Page | 44
Simulation Studies and Modelling Requirements for Compliance Demonstration

An additional time domain simulation is to introduce a change of active power transfer of the HVDC
system (level is project specific and should be agreed with EirGrid).

Check and report:

Voltage, frequency, speed, active power flow as applicable at the point (busbar, generator terminals etc)
required to demonstrate oscillation mode (local, inter-area etc) and the poorly damped oscillation itself.

Voltage, active and reactive power of HVDC station as appropriate.

Eigenvalues, eigenvectors and the frequency of oscillation with damping values and a classification on
whether these are well damped, damped, poorly damped or unstable (especially with regards to POD
being in operation or not). Unstable oscillation with the POD in operation will require appropriate tuning
of the control system and this shall be agreed between EirGrid and the HVDC system owner.

Check active and reactive power and terminal voltage of the HVDC system during the change of active
power simulation.

Success Criteria:

POD function of the HVDC system damps oscillations of the HVDC system (local mode) and/or damps or
does not make worse identified network oscillations (inter-area or global).

Change of active power transfer does not lead to undamped oscillations in active or reactive power of
the HVDC system.

4.3.5. Active power modification


Simulate active power modification capability of the HVDC installation using the model in Figure 1 with
system impedance set to minimum short circuit level. HVDC converter station operating at various
points as indicated.

Simulate:

Introduce 10% step change in active power during steady state operation for the following cases:

P=Pmax exporting with export station (connected to EirGrid system if it is providing a connection to a
different system) providing DC and AC voltage control and the remote end providing active and reactive
power control

P=Pmax importing with import station (connected to EirGrid system if it is providing a connection to a
different system) providing active power and AC voltage control and the remote end providing DC
voltage control and reactive power control

Repeat the same simulations under different pulse width modulation if that is within the HVDC system
functionality.

Check and report:

Page | 45
Simulation Studies and Modelling Requirements for Compliance Demonstration

Voltage at HVDC converter station

Current at HVDC converter station

Active power at HVDC converter station

Reactive power at HVDC converter station

Control signals relating to control settings of the station.

Success Criteria:

Change in active power within given timeframe as defined by EirGrid on site-specific basis as per Gc
CC.7.5.8.5.

4.3.6. Fast active power reversal


This study should be based on the conditions leading to the specification of fast active power reversal,
for example due to transient stability.

Use a model to represent the system such that it covers the topology leading to the conditions
necessitating the provision of fast active power reversal.

HVDC system operating at appropriate import or export configuration leading to the requirement of fast
active power reversal.

Simulate:

Apply system fault leading to transient instability (for example this could be a critical fault clearance
time issue) with appropriate signals to the HVDC system.

Check and report:

Voltage at HVDC station terminals

Active power at HVDC station terminals

Active power associated with the condition leading to transient stability.

Other signals as appropriate (for example if it is associated with the critical clearance time of a
generator, rotor angle plot of the generator can be presented).

Success Criteria:

HVDC system remains connected and stable while meeting the capability requirements in CC.7.5.1.1.(k).
[GC clause that specifies the fast active power reversal Art 13-1-c within the specified time limit]

4.3.7. Interaction studies (Art 29 not within simulation study part)

Page | 46
Simulation Studies and Modelling Requirements for Compliance Demonstration

When several HVDC converter stations or other plants and equipment are within close electrical
proximity, adverse control interactions may occur. EirGrid may request that a study is performed to
demonstrate that no adverse interaction will occur. If adverse interactions are identified, the studies
shall identify possible mitigating actions to be implemented to ensure compliance with the
requirements of the Grid Code.

The responsibility of these studies rests with the connecting HVDC system owner. All parties relevant to
the connection point as identified by EirGrid shall provide relevant data and models as reasonably
required to meet the scope of the studies.

The result of the studies shall be assessed by EirGrid and if deemed necessary, additional studies in line
with the scope may be requested.

All relevant data and models as part of the interaction study shall be provided to EirGrid such that the
studies can be replicated if required.

Any mitigation actions identified by the studies shall be carried out by the HVDC system owner as part of
the connection compliance process.

4.3.8. Sub-synchronous torsional interaction studies (Art 31 not within simulation study
part)
It is required that HVDC system shall not cause subsynchronous torsional interaction and that shall be
capable of contributing to electrical damping of torsional frequencies.

Simulation studies confirming the damping characteristics of the HVDC system with regards to SSTI shall
be submitted by the HVDC system owner. All parties relevant to the connection point as identified by
EirGrid shall provide relevant data and models as reasonably required to meet the scope of the studies.

The result of the studies shall be assessed by EirGrid and if deemed necessary, additional studies in line
with the scope may be requested.

All relevant data and models as part of the interaction study shall be provided to EirGrid such that the
studies can be replicated if required.

Any mitigation actions identified by the studies shall be carried out by the HVDC system owner as part of
the connection compliance process.

Page | 47
Simulation Studies and Modelling Requirements for Compliance Demonstration

APPENDIX A: PRINCIPLES FOR SIMULATION COMPLIANCE


EVALUATION AND INTERPRETATION OF GRID CODE FAULT
RIDE THROUGH CLAUSES
Background:
This note summarizes the Eirgrid position in relation to simulation and compliance of Power Park
Modules (PPMs), and how certain clauses within the Grid Code should be interpreted. This note is the
result of several years of discussions between Eirgrid and the Irish wind industry, trying to resolve some
ambiguities encountered in the simulation and testing of the performance of windfarms, that grew out
of changes made to the Grid Code by the DS3 project. There are two parts to the note: the first part sets
out some guiding principles Eirgrid will use in assessing Fault Ride-Through reports submitted by users;
and the second part attempts to clarify the intention and meaning of PPM1.4.2 (c) in the Ireland Grid
Code.

High-Level Principles:
1. PPMs such as windfarms and solar farms generally operate in two distinct modes – normal
operation, and fault-ride through mode. In normal operation, the TSO is chiefly concerned with the
PPMs behaviour and characteristics at the HV connection point, such as P-Q capability, voltage
control modes, ramping behaviour, and frequency response. During faults, the behaviour of the
PPM is typically delegated to the individual PPM units, such as individual wind turbines or solar
modules. However the TSO does not have visibility down to the individual module level at present,
and so performance monitoring of PPMs is done at the connection point. From a simulation and
model compliance viewpoint, performance assessment should take into account behaviour at this
lower voltage level as well as at the connection point in order to capture the effects of depressed
voltages on cables and transformers and obtain a more holistic view of the PPM FRT response.
2. While PPMs are expected to ride through a variety of different fault types and durations, very short
faults (less than or equal to 150ms) can be difficult to assess, as a steady-state may not be reached
within such a short time frame. Accordingly, very short faults will be assessed to confirm overall
stability and direction of response, but not in a strictly quantitative way.
3. The Grid Code PPM1.4.2(c) states that the reactive current shall be supplied within the rating of the
PPM. By extension, this means that the maximum expected current at the connection point should
not exceed the current at full power output and 0.95 power factor. Similarly, at the PPM module
level, the current from an individual module is not expected to exceed the value when operating at
maximum power output and 0.95 power factor at the connection point. We note that the DS3
System Service products incentivise performance in excess of the Grid Code requirements to help
achieve high levels of non-synchronous generation, and so depending on the DS3 product

Page | 48
Simulation Studies and Modelling Requirements for Compliance Demonstration

definitions, reactive currents in excess of the Grid Code requirement could be warranted for those
services, but that assessment is separate from the normal Grid Code assessment.
4. The reactive current during a fault should be greater than zero as measured at the PPM element
terminals irrespective of pre-fault reactive current value. We understand that other jurisdictions
have different requirements but we have not seen stability issues in Ireland related to this
requirement. If stability issues are experienced in reality, the Grid Code empowers the TSO to
reduce the magnitude of the response from the PPM, in discussions with the PPM owner.
5. The Rise Time and Settling Time requirements are to be assessed by applying a step-change to 50%
retained voltage at the PPM connection point in the simulation, and plotting the reactive current,
reactive power, and voltage at the PPM element terminals, and also the reactive current, reactive
power, and voltage at the connection point. It is assumed by the TSO that the gains and time
constants in the PPM control systems do not change depending on the fault. If this is not the case,
the OEM or PPM must inform the TSO so that a wider suite of simulations are carried out.
6. In assessing the simulated reactive current response, a tolerance of +/-10% of the maximum reactive
current as measured at the connection point, will be allowed. Thus if the maximum current for a
PPM is 1kA (reactive), the tolerance will be +/-100A. If 500A was the expected response, a value
between 400-600A will be deemed acceptable. Ultimately, the response of the model should
accurately represent the behaviour of the physical unit under fault conditions. Deviations outside
the tolerance band will need to be explained and discussed with the TSO.
7. Once the voltage has recovered above 0.9pu, the PPM has 500ms to switch back into normal
operation (pre-fault control mode, and pre-fault reactive setpoint). It then has a further 1 second to
achieve those values based on PPM 1.6.2.4. The voltage droop should take into account the fact
that the transmission voltage may be different to what it was before the fault. We do not necessarily
expect the PPM to go back to the pre-fault MVAr value if system conditions have changed.
8. Accurate dynamic models are of utmost importance to the TSO for both system operations and
planning. Every device or PPM that connects to the grid should have an appropriate dynamic model.
As TSO we expect (and require through the Grid Code) that developers will supply us with models
that are good enough for carrying out transient simulations, and these should be in the form of
standard PSSE/WECC 2nd Generation models and DigSilent PowerFactory models, or customised
models with supporting documentation and Laplace diagrams. In summary, if the developer is able
to produce simulations to allow us to assess compliance, then they should also be in a position to
provide the TSO with the models used to carry out those simulations, so that the TSO can carry out
its own functions. We also now seek EMT models for PPMs to help us manage the power system as
the proportion of power electronic converter based devices increases significantly. These may be
supplied as “Black Box” models within PSCAD.

Page | 49
Simulation Studies and Modelling Requirements for Compliance Demonstration

Clarification and Interpretation of Grid Code FRT Requirement PPM1.4.2(c):


“During and after faults, priority shall always be given to the Active Power response as defined in
PPM1.4.2(a) and PPM1.4.2(b).”
The PPM should give active power in proportion to retained voltage, and this is always the priority to
mitigate against a potential large deficit of MW that could occur if a cluster of PPMs were all affected by
the same transmission fault and were prioritising reactive power. From the power relationship, P = V x I ,
it is understood that active current should remain constant during the fault. If angular instability is
detected in reality due to weak network conditions, the PPM should do what it can to remain
connected, including reducing active power. This should not occur in the FRT simulation as a rule, as the
expected minimum strength will have been provided by the TSO, and the PPM should be capable of
handling the faults described in the Grid Code at the minimum specified system strength.

“The reactive current response of the Controllable PPM shall attempt to control the Voltage back
towards the nominal Voltage, and should be at least proportional to the Voltage Dip.”
This means that the reactive current should be in a direction such as to tend to increase the voltage –
the PPM should not be absorbing reactive power during a fault as a rule, although there may be
particular cases where the reactive power at the connection point is effectively zero despite the best
efforts of the individual PPM modules.
All other things being equal, a voltage dip by 0.5pu should elicit a reactive current response
approximately twice that of a dip of 0.25pu. In other words, the reactive current response should be
proportionate – it should depend on the severity of the fault. However, the available reactive current
will also depend on the pre-fault MW output of the PPM. The following diagram illustrates the general
principle, where the reactive current should ideally be on or close to the diagonal line, with more severe
faults eliciting larger reactive responses from the PPM. Some examples are given of compliant and
incompliant responses. Note the diagrams are assuming that the available reactive current is constant
across the different voltage dips – this may not necessarily be true in reality.

Page | 50
Simulation Studies and Modelling Requirements for Compliance Demonstration

Voltage at
Connection Point

Normal Operating Mode

0.9pu

+10%
IQmax

-10%
IQmax

0.15pu Reactive
Current at
Connection Point

I Qavail
PPM reactive current IQavail  I max
2
 I P2
Figure A.1: Guideline on how much reactive current response a PPM should give, assuming I Qavail
is the same for each fault, and assuming the fault is long enough for a steady-state to be reached

Voltage at
Connection Point

Normal Operating Mode

0.9pu

0.15pu Reactive
Current at
Connection Point

I Qavail
PPM reactive current
Figure A.2: Incompliant response example – reactive current is not proportional to voltage dip;
Upper point shows too large a response for a slight voltage dip, and the middle voltage dip point
has less of a reactive response than the upper point.

Page | 51
Simulation Studies and Modelling Requirements for Compliance Demonstration

Voltage at
Connection Point

Normal Operating Mode

0.9pu

0.15pu Reactive
Current at
Connection Point

I Qavail
PPM reactive current
Figure A.3: Compliant response example - reactive current increases as voltage dip worsens

IQavail is the available reactive current (the active current being prioritized), with I max being the total
maximum current based on the rating of the PPM or on the prevailing wind/solar conditions at the time
of the fault. A voltage dip to 0.15pu elicits the maximum reactive response, and allowance is given for
over and under provision (see principles above). The TSO expects that the control systems of the PPM
would consider the difference between the nominal voltage and the fault voltage and provide a type of
fast-acting proportional response, although it is up to the PPM on how they actually implement this.
Under PPM1.4.2(e), the TSO can seek to change the slope of the line to elicit a smaller reactive response
if it is found that the reactive response is too great.
Note that for unbalanced faults, the response should be determined with respect to the positive
sequence voltage, but within the technical limits of the plant.

“The reactive current response shall be supplied within the rating of the Controllable PPM, with a Rise
Time no greater than 100ms and a Settling Time no greater than 300ms.”
As stated above, the normal maximum current within the rating of the PPM is the current at the
connection point when the PPM is operating at maximum MW output and 0.95 power factor, and this
current will consist of a real and a reactive component. The magnitude of the reactive component will
depend on the severity of the fault and the available reactive current. The rise time and settling time
are defined terms, but these can only be accurately assessed for long duration faults or application of a
step-change to the PPM controller.

“For the avoidance of doubt, the Controllable PPM may provide this reactive response directly from
individual Generation Units, or other additional dynamic reactive devices on the site, or a combination
of both.”
Some PPMs have installed statcoms, and these may be used to provide some of the necessary reactive
current during a fault in addition to the reactive current from the individual generation units (Wind
Turbines / Solar Modules etc.)

Page | 52

You might also like