COMPREHENSIVE MAINTENANCE REPORT

Split, Standing, VRV/VRF Type Air Conditioner

Check List V1.4.3

Contractor, PIC Name MKU dan Mohamad Rudi 081558000525


Site ID 17DPS0040
Site Name MSC Gatsu Barat
Area Denpasar Bali
Region BALOM
Maintenance Date, time 14-15 Agustus 2023

Page 1 of 10
I. Safety Precautions
A. General Safety

• Before maintaining the equipment, read this document and observe all the safety instructions on the equipment and in this document.
• The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the
safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage
safety standards.
B. General Requirements

• Before maintaining the equipment, remove any conductive objects such as watches or metal jewelry like bracelets, bangles, and rings to avoid electric shock.
• When operating, or maintaining the equipment, wear dedicated protective gears such as insulation gloves, goggles, and safety clothing, helmet, and shoes, as
shown in the following figure.
• Use insulated tools or tools with insulated handles
• Follow the specified procedures for operation, and maintenance
• In the case of a fire, immediately leave the building or the equipment area, and turn on the fire alarm bell or make an emergency call. Do not enter the
building on fire in any case.
C. Personal Safety

• If there is a probability of personal injury or equipment damage during operations on the equipment, immediately stop the operations, report the case to the
supervisor, and take feasible protective measures.
II. Personnel Requirements

• Personnel who plan to maintain Huawei equipment must receive through training, understand all necessary safety precautions, and be able to correctly perform
all operations.
• Only qualified professionals or trained personnel are allowed to operate, and maintain the equipment.
• Only qualified professionals are allowed to remove safety facilities and inspect the equipment.
• Personnel who will operate the equipment, including operators, trained personnel, and professionals, should possess the local national required qualifications in
special operations such as high-voltage operations, working at heights, and operations of special equipment.

Page 2 of 10
Split, Standing, VRV/VRF Type Air Conditioner
PREVENTIVE MAINTENANCE CHECK LIST

Site Name / ID MSC Gatsu Barat/17DPS0040


Date of PM 14-15 Agustus 2023
PIC Name & Phone number MKU dan Mohamad Rudi
AC UNIT NO, ROOM LOCATION AC2, Rectifier Room [Gedung Lt.3]
AC Brand, Type / Capacity Panasonic, CS-PN12RKJ; 1.5Pk
AC Serial Number 13461238241

No Description Unit Status Remarks


A Room Temperature & Humidity OK NOK N/A Value
1 Actual room Temperature (Before) √ 26.8 ⁰C
2 Actual room Temperature (AFTER) √ 26.3 ⁰C
3 Actual room Humidity (Before) √ RH
4 Actual room Humidity (AFTER) √ RH
B Indoor OK NOK N/A Value
1 Evaporator cleaning √
2 Air filter cleaning √
3 Cross-flow fan cleaning √
4 Drainage to water pipe cleaning √
5 Mounting Plate √
6 Power cable connection √
7 Remote controller √

Page 3 of 10
C Outdoor OK NOK N/A Value
1 Condenser cleaning √
2 Axial flow-Fan & Motor condition √
3 Capacitor compressor √ 50Uf+ 5%
4 Compressor condition √
5 Outdoor unit position (No Obstacle/Blocking) √
6 Outdoor Cage condition, Lock √
7 Compressor winding measurement:
a. Common (C) to Start (S) Range 0-30Ω √ 3.2 Ω
b. Common (C) to Run (R) Range 0-30Ω √ 9.8 Ω
D COMPRESSOR OK NOK N/A Value
1 Compressor Measurement (Ampere) √ 0A
Compressor input voltage (Range 220 ±10%)
2 UNDER <198Vac, NORMAL: 198-242Vac, OVER:>242Vac
√ 0Vac
E REFRIGERANT OK NOK N/A Value
1 Refrigerant pipes condition (No leakage) √
2 Refrigerant Type √ R32
3 Refrigerant Measurement √ 0Psi
Threshold: R32 R410A R22
UNDER: <100psi UNDER: <100psi UNDER <55psi
Suction Pressure (psi) NORMAL: 100psi - 110psi NORMAL: 100psi – 145psi NORMAL: 55psi – 85psi
OVER: >110psi OVER: >145psi OVER: >85psi
UNDER: <325psi UNDER: <325psi UNDER: <200psi
Discharge Pressure (psi) NORMAL: 325psi - 450psi NORMAL: 325psi – 450psi NORMAL: 200psi-280psi
OVER: >450psi OVER: >450psi OVER: >280psi
F PANEL SYSTEM OK NOK N/A Value
1 Main Input Rate MCB at ACPDB/SDP/MDP √ 20 A
2 Connected to AC Control √
3 Running Configuration, Duration √
4 Main input Rate MCB for the unit √ 20 A
G Final Conclusion: AC ABNORMAL,
Condenser leakage, compressor broken

Page 4 of 10
H Part List For Replacement (propose) :
Need replaced condenser and compressor

I Acknowledges & Approvals


MAINTENANCE BY REPRESENTATIVE OF VENDOR
Name / ID Mohammad Rudi Name / ID Doni Andiwijaya
Position Engineer Position TOC Engineer
Signature Signature

Date 21-08-2023 Date

APPROVED BY REPRESENTATIVE OF PT HUAWEI TECH INVESTMENT


Name / ID Name / ID
Position Huawei Regional Manager Position Huawei Regional General Manager
Signature Signature

Date Date

APPROVED BY REPRESENTATIVE OF PT INDOSAT OOREDOO HUTCHISON


Name / ID Name / ID
Position IOH Operation Maintenance & Technical Position IOH Deputy General Manager
Branch Manager
Signature Signature

Date Date
Page 5 of 10
1 View Of Airconditioning Unit 2 Room Temperature Humidity (before) 3 Room Temperature Humidity (after)

4 Evaporator Before Cleaning 5 Evaporator After Cleaning 6 Air Filter after Cleaning

Page 6 of 10
7 Cross-Flow After Cleaning 8 Overall Indoor Cleaning Process 9 Remote Control (Photo with Set Point Temp)

10 Condenser Status Before Cleaning 11 Condenser Status Cleaning Process 12 Condenser Status After cleaning

Page 7 of 10
13 Axial Flow-Fan & Motor Condition 14 Capacitor Compressor 15 Compressor Condition (clear photo with type)

16 Outdoor View and Cage Condition, lock 17 Compressor Winding Measurement (1) 18 Compressor Winding Measurement (2)

Page 8 of 10
19 Compressor Measurement (Ampere) 20 Compressor Input Voltage 21 Refrigerant Measurement (1)

22 Refrigerant Measurement (2) 23 Main Input Rate MCB at ACPDB/SDP/MDP 24 AC Control Panel ( if any )

NA NA

Page 9 of 10