Base
Base
Base
31
Date : 242023/8/
Page : 1/7
Comment :
Base material
Concrete resistance : C25/30
Cracking of concrete : Cracked concrete
Thickness of concrete : 200 mm
Reinforcement type : Wide concrete reinforcement
Edge reinforcement : No edge reinforcement
Conditions
Installation conditions : Dry concrete
Short term temperature : 40 °C
Long term temperature : 24 °C
Anchor plate
Thickness of part to be fixed : 20 mm
Recommended plate thickness : The base plate thickness has not been checked
Clearance diameter : 25 mm
Profile : HEA180
Profile position : Ex = 0 mm ; Ey = 0 mm
Stand-off : None
Specifications :
Static
Sustained Load : False
Ref : 24 ﺹ6:53:44 - 2023/8/ / Version 2023.03.31
Date : 242023/8/
Page : 2/7
Geometry :
Calculation Hypothesis :
- The anchoring plate is assumed to be sufficient to resist deformation imposed by the load actions.
- Connection between profile and base plate has not been checked
- The calculation is done acc. to expert judgement, based on EN 1992-4
- SPIT can only be held responsible if the calculation examples exactly reflect the application and if the installation is carried out
according to the instruction given in the SPIT specifications. The calculation is correct for SPIT anchors only. The
contractor or specifier should make sure that the base material is able to support the loads especially in the case of a group of
anchors. SPIT cannot be held responsible if this software package is modified without its written approval.
Ref : 24 ﺹ6:53:44 - 2023/8/ / Version 2023.03.31
Date : 242023/8/
Page : 3/7
Loads on anchors
4 0 kN 0 kN -0.79 kN
0 0 0 0
3.17 0.79
Utilization
Steel failure / / /
CALCULATION DETAILS
INSTALLATION DATA
INSTALLATION Method