How To Select The Right Fuse For Power Systems Protection

To select the right fuse, engineers must consider several key factors: the fuse's current rating which specifies its nominal amperage; its breaking capacity which is the maximum current it can safely interrupt; the ambient temperature surrounding the fuse; and its time-current characteristic which determines how quickly it will blow based on the load. Considering these factors helps ensure the fuse can reliably protect circuits from overloads and short circuits without prematurely blowing during normal operation.

Uploaded by

rajesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views4 pages

How To Select The Right Fuse For Power Systems Protection

To select the right fuse, engineers must consider several key factors: the fuse's current rating which specifies its nominal amperage; its breaking capacity which is the maximum current it can safely interrupt; the ambient temperature surrounding the fuse; and its time-current characteristic which determines how quickly it will blow based on the load. Considering these factors helps ensure the fuse can reliably protect circuits from overloads and short circuits without prematurely blowing during normal operation.

Uploaded by

rajesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

9/5/23, 5:55 PM How to Select the Right Fuse for Power Systems Protection

(Selection Guide) - How to Select the


Right Fuse for Power Systems
Protection

Last updated: Oct 2, 2020

"A fuse is essentially a metal wire or strip that heats up and melts when too much current
flows through it, thereby opening the circuit and interrupting the current flow."

In order to select the right fuse for a given system, it is imperative that the various fuse parameters
are thoroughly understood. Hence, this guide will first define each contributing factor and then
explain how it is used by engineers and circuit designers to choose the best device for circuit
protection.

The factors to be considered when selecting a fuse are as follows:

https://www.allumiax.com/blog/how-to-select-the-right-fuse-for-power-systems-protection 1/4
9/5/23, 5:55 PM How to Select the Right Fuse for Power Systems Protection

1. Current Rating
The current rating specifies the nominal amperage value of the fuse, given by the manufacturer as
the level of current that the fuse can carry under normal working condition.

A fuse, which is designed according to an IEC standard, can continuously operate at 100% of rated
current of the fuse. Fuses are temperature-sensitive devices and the projected life of a fuse can be
shortened drastically when loaded to 100% of its nominal value.

In order to prolong the life of the fuse, the circuit designer should ensure that the load on the fuse
does not exceed the nominal rating listed by the manufacturer. So a fuse with a current rating of
10A would not be recommended for operation at more than 7.5A in a 25°C ambient temperature.

Hello there! On a related topic, we previously wrote a blog about Selecting the Right Circuit
Breaker and Its Type. If this peaks your interest, check it out and let us know what you think

2. Breaking Capacity
Also known as interrupting rating or short circuit rating, the breaking capacity is the maximum
current which the fuse can safely break or interrupt at rated voltage.

When selecting a fuse, one should verify that the breaking capacity of the fuse is sufficient for
circuit operation. The interrupting rating must be equal to or greater than the short-circuit current.

When a fault or short circuit condition arises, the instantaneous current passing through the fuse
can be several times greater than its current rating. If this current is beyond the level that the fuse
can bear, the device may explode or rupture, causing additional damage. Hence, for safe operation,
it is imperative that the fuse selected is able to withstand the largest short-circuit current possible
and can clear the circuit safely.

It is usually recommended that a fuse with high breaking capacity is to be used in circuits with
inductive loads, and a fuse with low breaking capacity is used for circuits with resistive or capacitive
loads.

3. Ambient Temperature
The ambient temperature is a measure of the temperature of the air immediately surrounding the
fuse. Since the fuse is enclosed in a panel mounted fuse-holder, or placed near other heat
dissipating components, like resistors, the ambient temperature is usually much higher than the
surrounding room temperature.

The current carrying capacity of a fuse varies as the ambient temperature changes. Operating the
fuse at high ambient temperatures can potentially shorten its life. On the other hand, lower
ambient temperatures can lead to longer fuse life.

The fuse also becomes hotter as the operating current becomes equal to or greater than the
breaking capacity. Experiments have shown that a fuse will continue to work indefinitely, as long as
the load does not exceed 75% of the nominal current rating.

https://www.allumiax.com/blog/how-to-select-the-right-fuse-for-power-systems-protection 2/4
9/5/23, 5:55 PM How to Select the Right Fuse for Power Systems Protection

4. Fuse Types and Time-current Characteristics


Fuses can be of different types based on the speed at which they can blow. It is helpful to define
fuses using time-current curves, since fuses with the same current rating can be represented by
considerably different time-current curves.

Fast-acting fuses will melt rapidly and sever the connection immediately when subjected to high
current levels. This characteristic becomes important in applications where speed is critical, such as
in variable speed drives. Fast-acting fuses are used for distribution feeders and branch circuits.

Time-delay fuses employ a time-delay mechanism and are designed to tolerate the start-up
overload pulses which are normal in some applications. These pulses produce thermal cycling
which can lead to premature aging of fuses. An example of this is a capacitor that draws a large
amount of current when initially charged. The time lag prevents the fuse from needlessly blowing
during a temporary current overload or surge. Time-delay fuses are most useful in the startup of
high-powered motors. The delay which they provide can help to prevent nuisance tripping.

Time-delay fuses employ a time-delay mechanism and are designed to tolerate the start-up
overload pulses which are normal in some applications. These pulses produce thermal cycling
which can lead to premature aging of fuses. An example of this is a capacitor that draws a large
amount of current when initially charged. The time lag prevents the fuse from needlessly blowing
during a temporary current overload or surge. Time-delay fuses are most useful in the startup of
high-powered motors. The delay which they provide can help to prevent nuisance tripping.
https://www.allumiax.com/blog/how-to-select-the-right-fuse-for-power-systems-protection 3/4
9/5/23, 5:55 PM How to Select the Right Fuse for Power Systems Protection

Knowing which fuse to use depends on the requirements of the control circuitry. Typically, time-
delay fuses are used for inductive and capacitive loads, while fast-acting fuses are selected for
resistive loads.

5. Nominal Melting I2t Rating


The fuse's nominal melting I2t rating must also meet the startup pulse requirements. Nominal
melting I2t is a measure of the energy required to melt the fusing element and is expressed as
"Ampere Squared Seconds" (A2Sec). There two parts to a fuse's "reaction time".

1. The time it takes for the fuse element to melt (also known as the melting time, Tm).
2. The time it takes for the electrical arc to settle (also known as the arcing time, Ta).

The total time it takes to open the fault is known as the total clearing time.

Tc = Tm + Ta

The circuit designer should select a fuse whose I2t rating is greater than the energy of the inrush
current pulse. This ensures that the fuse will not cause a nuisance opening during transient
conditions. In order to achieve reliable system operation, it is a good design practice to select a
fuse such that the energy of the current pulse is not more than 20% of the nominal melting I2t
rating of the fuse.

Every fuse has a different fusing element, which means that the I2t value is unique for each type of
fuse. It is a constant value for each element material and is also independent of temperature and
voltage. Hence, the nominal melting I2t rating is an important parameter to consider when
selecting a fuse and is necessary to be determined.

6. Maximum Fault Current


The Interrupting Rating of a fuse must meet or exceed the Maximum Fault Current of the circuit.

7. Voltage Rating
A fuse can safely interrupt its rated short circuit current as long as the voltage is less than or equal
to its rated voltage.

Conclusion
In short, the following factors should be considered when selecting a fuse for a given system:

1. Normal operating current


2. Operating Voltage
3. Ambient Temperature
4. Inrush Currents
5. Maximum Fault Current
6. Length of time in which the fuse must open
7. Maximum allowable I2t

https://www.allumiax.com/blog/how-to-select-the-right-fuse-for-power-systems-protection 4/4