Specifications For Transmitters-R1pdf
Specifications For Transmitters-R1pdf
Sheet 1 of 6
PROJECT NAME 1 x 5.05MW Capitive power plant
CLIENT M/s LA SUERTE RICE MILL CORP. Philippines
CONSULTANT NA
ITEM:- PRESSURE TRANSMITTER
1 Tag No. Refer Table
2 Service Description Refer Table
GENERAL PB598P&I06,PB598P&I01,PB598-108-P-PID-
3 PID No. 0502,PB598-107-P-PID-0503,PB598-109-P-PID-0504
& PB598-102-M-PID-0506
4 Manufacturer -----
5 Model No. As Per Manufacturer
6 Type Electronic , Smart with HART Protocol
7 Function Transmit, Indicate
8 Service Gauge Pressure
TRANSMITTER 9 Calibrated Span Refer Table
10 Adjustable Range As Per Manufacturer
11 Over pressure As Per Manufacturer
12 Accuracy 0.075% Of Span
13 Power Supply 24V DC (2-Wire)
14 Output 4-20 mA DC
15 Process connection 1/2" NPT-14 (F)
16 Housing IP66
BODY 17 Body Material Polyurethane Covered Aluminium
18 Mounting Bracket for 2-in. Pipe Mounting
19 Conduit Entry Size Thread NPT 1/2"
20 Isolating Diaphragm SS 316L
ELEMENT
21 Fill Fluid Silicon
22 Cert/Approval Type Non-Hazardous Area
OPTIONS 23 Meter LCD Meter
24 Zero and Span Adjust By HART/Buttons
25 Scope :- Transmitter + Mounting Bracket
26 The installation is outdoor.
27 Certificate :- Calibration certificate,
NOTES 28 Operation & Maintenance manual shall be supplied with Transmitter
29 Digital communication shall be possible with Hand Held Communicator
30 For steam service condensate pot shall be supplied.
31 Output 4-20 mA DC shall be superimposed on Digital Signal.
DOCUMENT TITLE DATA SHEET FOR PRESSURE TRANSMITTER
Prepared HARI
UTTAM ENERGY SYSTEMS LTD. PUNE Checked ARM
Approved ---
Rev 0
Sheet 2 of 6
PROJECT NAME 1 x 5.05MW Capitive power plant
CLIENT M/s LA SUERTE RICE MILL CORP. Philippines
CONSULTANT NA
TAG LIST FOR PRESURE TRANSMITTER
Calibration
Sr. No. Tag. No. Service Description Unit Qty
Range
1 551-S-PT-5004 De-aerator Tank Pressure 0 to 4 Kg/cm2 1
Boiler Feed Water Pump
2 551-S-PT-5011 0 to 160 Kg/cm2 1
Discharge Line
3 551-W-PT-5020 Steam Drum Pressure 0 to 130 Kg/cm2 1
4 551-S-PT-5025 Steam Line To Soot Blowers 0 to 35 Kg/cm2 1
5 551-S-PT-5027 Main Steam Line 0 to 130 Kg/cm2 1
Auxiliary CoolingWaterPump
6 555-W-PT-4003 0 to 8 Kg/cm2 1
common Dicharge line
DM Water Transfer Pump
7 554-W-PT-3003 0 to 16 Kg/cm2 1
Common Discharge
Instrument Air Receiver Tank
8 559-A-PT-8002 0 to 12 Kg/cm2 1
Outlet Pressure
9 552-S-PT-1015 After De-superating to Ejector 0 to 60 Kg/cm2 1
Total 10
Note : There can be minor change in calibration range same shall be confirmed before
dispatch of Transmitters
Sheet 3 of 6
PROJECT NAME 1 x 5.05MW Capitive power plant
CLIENT M/s LA SUERTE RICE MILL CORP. Philippines
CONSULTANT NA
ITEM:- DIFF. PRESSUR TRANSMITTER
1 Tag No. Refer Table
2 Service Description Refer Table
GENERAL PB598P&I06,PB598P&I01,PB598-108-P-PID-
3 PID No. 0502,PB598-107-P-PID-0503,PB598-109-P-PID-
0504 & PB598-102-M-PID-0506
4 Manufacturer -----
5 Model No. As Per Manufacturer
6 Type Electronic , Smart with HART Protocol
7 Function Transmit, Indicate
8 Service Level Measurement
TRANSMITTER 9 Calibrated Span Refer Table
10 Adjustable Range As Per Manufacturer
11 Over Pressure As Per Manufacturer
12 Accuracy 0.075% Span
13 Power Supply 24V DC (2-Wire)
14 Output 4-20 mA DC
15 Process connection 1/2" NPT(F) By Using 3-Valve Manifold
16 Housing IP66
BODY 17 Body Material Polyurethane Covered Aluminium
18 Mounting Bracket for 2-in. Pipe Mounting
19 Conduit Entry Size 1/2" NPT
20 Isolating Diaphragm SS 316L
ELEMENT
21 Fill Fluid Silicon Oil
22 Cert/Approval Type Non-Hazardous Area
OPTIONS 23 Meter LCD Meter
24 Zero and Span Adjust By HART/Buttons
25 Scope :- Transmitter + Mounting Bracket + 3-Valve Manifold
26 The installation is outdoor.
27 Certificate :- Calibration certificate,
NOTES 28 Operation & Maintenance manual shall be supplied with Transmitter
29 Output 4-20 mA DC shall be superimposed on Digital Signal.
30 Digital communication shall be possible with Hand Held Communicator
Calibiration
Sr.no Tag No Service Description Unit Note
Range
De-aerator Tank
1 551-W-LT-5001 -2000 to 0 mmH2O
Water Level
Boiler Feed water
2 551-W-FT-5015 0 to 3000 mmH2O Sq. Root Output
flow
551-W-LT-5019 Steam Drum Water mmH2O
3 -500 to 0
Level
Steam Drum Water
4 551-W-LT-5021 -500 to 0 mmH2O
Level
5 551-S-FT-5030 Main Steam Flow 0 to 5000 mmH2O Sq. Root Output
6 551-G-DT-5040 Furnace -25 to 25 mmH2O
Boiler Bank Outlet
7 551-G-DT-5055 -50 to 50 mmH2O
Flue Gas
Economizer Outlet
8 551-G-DT-5056 -150 to10 mmH2O
Flue Gas
9 551-G-DT-5057 APH Outlet Flue Gas -300 to 10 mmH2O
ID Fan Common
10 551-G-DT-5058 -450 to 10 mmH2O
Inlet
Cooling Tower
11 554-W-LT-4005 0 to 4000 mmH2O
Water Level
DMW Storage Tank
12 553-W-LT-3000 0 to 12000 mmH2O
Water Level
FD Fan discharge
13 551-A-FT-5035 0 to 50 mmH2O Sq. Root Output
flow
TOTAL 13 No's
There can be minor change in calibration range same shall be confirmed before dispatch
Note :
of Transmitters
Sheet 5 of 6
PROJECT NAME 1 x 5.05MW Capitive power plant
CLIENT M/s LA SUERTE RICE MILL CORP. Philippines
CONSULTANT NA
Temperature Transmitter
1 Tag No. Refer table below
GENERAL 2 Description of Service Refer table below
3 PID No. PB598-102-M-PID-0506
4 Process Fluid Steam
SERVICE
5 Design Operating Units
CONDTIONS
6 Temperature Refer table Refer table Deg.C
7 Measurement Temperature
8 Type TC (Type-K)
9 Wire Configuration 2-Wire
10 Element Configuration Simplex
SENSOR
11 Response Time 30 Sec
12 Process Connection NA
13 Transmitter Type SMART (HART)
14 Calibration Range 0 - 550 Deg.C
15 Transmitter range VTI
16 Output Signal 4 - 20 mA DC With HART
17 Power Supply 24V DC
TRANSMITTER 18 Enclosure Class Minimum IP65
19 Accuracy (+/-) 0.5% or better
20 Cable Entry 1/2" NPT(F)
21 Area Classification Safe Zone
22 Mounting Bracket Required - 2" Pipe Mount (CS)
OPTIONS
23 LCD Indicator on Transmitter LCD 4 - Digit
24 Manufacturer ------
PURCHASE
26 Model VTI
S.No Tag No. Description of Service Operating Temp Design Temp. Qty
After Desuper heating of Ejector
1 552-S-TT-1014 370⁰C 380⁰C 1
PRDS
After Desuper heating of
2 552-S-TT-1008 300⁰C 310⁰C 1
Pegging PRDS
Total 2 No's
Notes:
1) VTI - Vendor to Inform.
2) Vendor Have to submit their data sheet for Customer's approval.
3) Vendor Have to submit test and calibiration certificate.
DOCUMENT TITLE DATA SHEET FOR TEMPERATURE TRANSMITTER
Prepared HARI
UTTAM ENERGY SYSTEMS LTD. PUNE Checked ARM
Approved ---
Rev 0
Sheet 6 of 6