System Diagram

This document provides an electrical design analysis for a residential/commercial building. It specifies using a 100A/100AF main circuit breaker with 2- 30mm2 THHN wires to provide power from the 220V service entrance through a 32mm PVC pipe conduit. The total calculated load is 85.85 amps based on general lighting, appliances, air conditioners, and other loads for the building.

Uploaded by

Laedyn Faye Isip
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views7 pages

System Diagram

This document provides an electrical design analysis for a residential/commercial building. It specifies using a 100A/100AF main circuit breaker with 2- 30mm2 THHN wires to provide power from the 220V service entrance through a 32mm PVC pipe conduit. The total calculated load is 85.85 amps based on general lighting, appliances, air conditioners, and other loads for the building.

Uploaded by

Laedyn Faye Isip
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

ELECTRICAL DESIGN ANALYSIS

2- 30 MM2 THHN WIRE


Name

Occupancy RESIDENTIAL COMMERCIAL BUILDING

Address URDANETA CITY, PANGASINAN


MAIN 100 AT/100AF 220 Volts
Service

15 AMP. 15 AMP. Floor Area 20.00 m x 10.00 m 200 m²


1- L.O 2- L.O Required general
24 VA/m²
lighting load
20 AMP. 20 AMP.
3- L.O. 4- C.O. Computations :
20 AMP. 20 AMP.
General lighting LOAD 4,800 Volt Amperes

5- C.O. 6-ACU
Sub-total 4,800 Volt Amperes
30 AMP. 20 AMP.

7- WA 8- REF Application of
Demand Factor
30 AMP. 20 AMP.
First 4,000 V.A. @100%D.F. 4,000 Volt Amperes
9- RANGE 10- ACU
20 AMP. 20 AMP. NEXT 800 V.A. @35% D.F. 280 Volt Amperes

11- REF 12- REF


Sub-total 4,280 Volt Amperes

20 AMP. 20 AMP.

13 - ACU 14- REF Other Loads:

20 AMP. 2500 Volt Amperes


1 unit Washing Machine, @ 2500 W
15 - SPARE
Volt Amperes
4 unit Refrigerator, @ 780 W 3120

2238 Volt Amperes


3 units 1.0HP ACU, @ 746 W

Volt Amperes
1 unit Range, @ 3000 W 3000
EARTH GROUND 1 -8.0mm² TW WIRE
GROUNDING CONDUCTOR 10,858 Volt Amperes
Total other loads:

1 RISER DIAGRAM GROUNDFLOOR


E-9 Total Current: (4,280 + 10,858 + 1.25 X 3000)V.A./220 v 85.85 Amperes
SCALE NTS
For the Main
Circuit Breaker :
Use: 100AT/100AF Main Circuit Breaker and 2-30 mm2 THHN wire service
entrance @ 32mm Ø PVC pipe Conduit

INSTRUCTOR: SUBMITTED BY: PROJECT TITLE: RATING: SHEET NO.:

JAN DENVER C. LOPEZ TEN STOREY RESIDENTIAL/COMMERCIAL


ENGR. SOCRATES NACIS E-9
BUILDING
2- 30 MM2 THHN WIRE

ELECTRICAL DESIGN ANALYSIS

Name
MAIN 100 AT/100AF
Occupancy RESIDENTIAL COMMERCIAL BUILDING
15 AMP. 15 AMP.
1- L.O Address URDANETA CITY, PANGASINAN
2- L.O

15 AMP. 20 AMP. 220 Volts


Service
3- L.O. 4- C.O.
Floor Area 20.00 m x 10.00 m 200 m²
20 AMP. 20 AMP.
Required general
5- C.O 24 VA/m²
6-ACU lighting load
20 AMP. 20 AMP.
Computations :
7- ACU 8- REF
General lighting LOAD 4,800 Volt Amperes
20 AMP. 20 AMP.
9- REF 10- ACU Sub-total 4,800 Volt Amperes

20 AMP. 20 AMP. Application of


11- ACU 12- REF Demand Factor

20 AMP. 20 AMP. First 4,000 V.A. @100%D.F. 4,000 Volt Amperes

13 - REF 14- ACU


NEXT 800 V.A. @35% D.F. 280 Volt Amperes

20 AMP. 20 AMP.
Sub-total 4,280 Volt Amperes
15 - ACU 16- REF

20 AMP. 20 AMP. Other Loads:


17 - REF 18- SPARE

Volt Amperes
6 unit Refrigerator, @ 780 W 4680

4476 Volt Amperes


6 units 1.0HP ACU, @ 746 W
EARTH GROUND 1 -8.0mm² TW WIRE
GROUNDING CONDUCTOR

Total other loads: 9,156 Volt Amperes

1 RISER DIAGRAM 2-5TH FLOOR


E-10 SCALE NTS

Total Current: (4,280 + 9,156 + 1.25 X 3000)V.A./220 v 78.12 Amperes

For the Main


Circuit Breaker :
Use: 100AT/100AF Main Circuit Breaker and 2-30 mm2 THHN wire service
entrance @ 32mm Ø PVC pipe Conduit

INSTRUCTOR: SUBMITTED BY: PROJECT TITLE: RATING: SHEET NO.:

JAN DENVER C. LOPEZ TEN STOREY RESIDENTIAL/COMMERCIAL


ENGR. SOCRATES NACIS E-10
BUILDING
ELECTRICAL DESIGN ANALYSIS

2- 30 MM2 THHN WIRE Name

Occupancy RESIDENTIAL COMMERCIAL BUILDING

Address URDANETA CITY, PANGASINAN

220 Volts
Service
MAIN 100 AT/100AF
Floor Area 20.00 m x 10.00 m 200 m²
15 AMP. 15 AMP. Required general
24 VA/m²
1- L.O 2- L.O lighting load

20 AMP. 20 AMP. Computations :


3- L.O. 4- C.O.
General lighting LOAD 4,800 Volt Amperes
20 AMP. 20 AMP.
5- C.O. Sub-total 4,800 Volt Amperes
6-ACU
20 AMP. 20 AMP. Application of
Demand Factor
7- ACU 8- REF
First 4,000 V.A. @100%D.F. 4,000 Volt Amperes
30 AMP. 20 AMP.
9- REF 10- REF NEXT 800 V.A. @35% D.F. 280 Volt Amperes

20 AMP. 20 AMP.
Sub-total 4,280 Volt Amperes
11- REF 12- ACU

20 AMP. 20 AMP. Other Loads:

13 - ACU 14- SPARE

Volt Amperes
4 unit Refrigerator, @ 780 W 3120

2984 Volt Amperes


4 units 1.0HP ACU, @ 746 W
EARTH GROUND 1 -8.0mm² TW WIRE
GROUNDING CONDUCTOR

Total other loads: 6,104 Volt Amperes

1 RISER DIAGRAM 6-9TH FLOOR


E-11 SCALE NTS
Total Current: (4,280 + 6,104 + 1.25 X 3000)V.A./220 v 64.25 Amperes

For the Main


Circuit Breaker :
Use: 100AT/100AF Main Circuit Breaker and 2-30 mm2 THHN wire service
entrance @ 32mm Ø PVC pipe Conduit

INSTRUCTOR: SUBMITTED BY: PROJECT TITLE: RATING: SHEET NO.:

JAN DENVER C. LOPEZ TEN STOREY RESIDENTIAL/COMMERCIAL


ENGR. SOCRATES NACIS E-11
BUILDING
ELECTRICAL DESIGN ANALYSIS

Name

2- 30 MM2 THHN WIRE Occupancy RESIDENTIAL COMMERCIAL BUILDING

Address URDANETA CITY, PANGASINAN

220 Volts
Service

Floor Area 20.00 m x 10.00 m 200 m²


MAIN 100 AT/100AF
Required general
24 VA/m²
lighting load
15 AMP. 15 AMP.
1- L.O 2- L.O Computations :

15 AMP. 20 AMP. General lighting LOAD 4,800 Volt Amperes

3- L.O. 4- C.O.
Sub-total 4,800 Volt Amperes
30 AMP. 20 AMP.
Application of
5- ACU 6-ACU Demand Factor
20 AMP.
First 4,000 V.A. @100%D.F. 4,000 Volt Amperes

7- SPARE
NEXT 800 V.A. @35% D.F. 280 Volt Amperes

Sub-total 4,280 Volt Amperes

EARTH GROUND 1 -8.0mm² TW WIRE Other Loads:


GROUNDING CONDUCTOR

3,730 Volt Amperes

1 RISER DIAGRAM 10TH FLOOR 2 units 2.5HP ACU, @ 1865 W


E-12 SCALE NTS

Total other loads: 3,730 Volt Amperes

Total Current: (4,280 + 3,730 + 1.25 X 3000)V.A./220 v 53.45 Amperes

For the Main


Circuit Breaker :
Use: 100AT/100AF Main Circuit Breaker and 2-30 mm2 THHN wire service
entrance @ 32mm Ø PVC pipe Conduit

INSTRUCTOR: SUBMITTED BY: PROJECT TITLE: RATING: SHEET NO.:

JAN DENVER C. LOPEZ TEN STOREY RESIDENTIAL/COMMERCIAL


ENGR. SOCRATES NACIS E-12
BUILDING
7620 V Primary

L.A. 37.5 KVA X'former


Available utility
7620V 115 / 220 V
infinite assumption
(Common Transformer)
1SET 3- #250 MM2 THHN WIRE
MAIN PANEL BOARD
@400 AT

2- 14 MM2 THHN WIRE

3- #250 MM2 THHN WIRE

2- 14 MM2 THHN WIRE MAIN 400 AT

100 AMP. 100 AMP.


1- GF 2- 2ndFLR.

100 AMP. 100 AMP.


MAIN 100 AT/100AF 3- 3rdFLR. 4- 4thFLR.

100 AMP. 100 AMP.


65 AMP. 15 AMP.
5- 5thFLR. 6-6thFLR.
1- ELEV 2- SPARE
100 AMP. 100 AMP.
7- 7thFLR. 8-8thFLR.

100 AMP. 100 AMP.


9- 9thFLR. 10-10thFLR.
EARTH GROUND 1 -8.0mm² TW WIRE
65 AMP. 60 AMP.
GROUNDING CONDUCTOR
11- ELEV 12-SPARE

1 RISER DIAGRAM ELEVATOR EARTH GROUND 1 #150mm² TW WIRE


E-13 SCALE NTS GROUNDING CONDUCTOR

2 RISER DIAGRAM MAIN


E-13 SCALE NTS

INSTRUCTOR: SUBMITTED BY: PROJECT TITLE: RATING: SHEET NO.:

JAN DENVER C. LOPEZ TEN STOREY RESIDENTIAL/COMMERCIAL


ENGR. SOCRATES NACIS E-13
BUILDING
GENERAL NOTES
1. ALL ELECTRICAL WORKS HEREIN TO BE DONE IN THIS BUILDING SHALL CONFORM IN
ACCORDANCE WITH THE PROVISIONS AND CODE STANDARD AS FOLLOWS:

1.1 LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE AND NEW ELECTRICAL
ENGINEERING LAW
LEGEND:
1.2 EXISTING LOCAL UTILITY COMPANY AND REQUIREMENTS ITSELF,
SYMBOL DESCRIPTION
1.2 REQUIREMENTS OF THE BUREAU OF LABOR STANDARS.
CIRCLE LIGHTING CEILING
2. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION MOUNTED 40 WATTS
OF QUALIFIED AND A DULY LICENSED ELECTRICAL ENGINEER OR MASTER ELECTRICIAN. SQUARE LIGHTING CEILING

SERVICE ENTRANCE POWER THE ELECTRICAL ENGINEER SHALL BE RESPONSIBLE FOR THE INTERPRETATION OF
OF THE DESIGN INTENT, LAYOUT PLANS AND SPECIFICATIONS; AND THE REQUIRED
MOUNTED 30 WATTS

STANDARD ELECTRICAL CODE SQUARE PINLIGHT 18WATTS

CONVENIENCE OUTLET
3. ALL WIRES SHALL BE COPPER TYPE THHN IN (PVC) POLYVINYL CHLORIDE FOR MAIN
& SUB-FEEDER: (PVC) POLYVINYL CHLORIDE CIRCUITS & AUXILIARY CIRCUITS OR RANGE OUTLET
RANGE
UNLESS OTHERWISE SPECIFIED IN THE PLAN.
REFRIGERATOR OUTLET
3-#250mm² REF

THHN AND 4. ALL JUNCTION, UTILITY, SQUARE AND PULL BOXES SHALL BE GA. NO. 18 OR AS PER
WA
WASHING MACHINE OUTLET
APPROVED EQUIVALENT AND PAINTED WITH ONE COAT PRIMER PRIOR TO INSTALLATION.
1-#150mm² TW
CONVENIENCE OUTLET
WIRES FOR 5. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED TYPE. APPROPRIATE AU
AIRCON UNIT
WITH LOCATION AND INTENDED TO BE USED.
MAIN PB PANEL BOARD
6. POWER SUPPLY SHALL BE 230 VOLTS, THREE PHASE, 60 HERTZ, TWO WIRES SYSTEM.

M
7. MINIMUM SIZE OF CONDUCTORS SHALL BE 2.0mm² THHN IN 15mm DIA. TRADE SIZE.
CIRCUIT HOMERUN

KILOWATTHOUR METER 8. ALL VERTICAL AND HORIZONTAL CONDUITS SHALL BE CONCEALED OR EMBEDDED ON S1 ONE GANG SWITCH
CONCRETE WALLS AND FLOORS.

9. ALL C ONDUITS SHALL BE PROPERLY REAMED PRIOR TO INSTALLATION TO AVOID


S2 TWO GANG SWITCH

DAMAGES TO THE SKIN OF WIRE.


S3 THREE GANG SWITCH
10. THE WORKMANSHIP OF THE WORKS SHALL BE EXECUTED IN THE BEST MOST THOROUGH
MANNER TO THE SATISFACTION OF THE ARCHITECT AND THE ENGINEER. POWER LINE

11. VERIFY MOUNTING HEIGHTS & EXACT LOCATIONS OF WIRING DEVICES WITH THE ARCHITECT SWITCH LINE
PRIOR TO INSTALLATION.

LP-1
2P, 115/220V

1 POWER SINGLE LINE DIAGRAM


E-14 SCALE NTS

INSTRUCTOR: SUBMITTED BY: PROJECT TITLE: RATING: SHEET NO.:

JAN DENVER C. LOPEZ TEN STOREY RESIDENTIAL/COMMERCIAL


ENGR. SOCRATES NACIS E-14
BUILDING
1500 mm above

1500 mm
worktop

1500 mm
(panel board)

convenice outlet
1200 mm (kitchen area)

2000 mm
minimum
height
(aircon outlet )
1500 mm

1200 mm

1200 mm
1200 mm (light
switch)

900 mm
450 mm
minimum height

450 mm
(convenience
,ref,washing
outlet )

FINISH FLOOR LINE

1 ELECTRICAL DETAILS
E-15 SCALE NTS

INSTRUCTOR: SUBMITTED BY: PROJECT TITLE: RATING: SHEET NO.:

JAN DENVER C. LOPEZ TEN STOREY RESIDENTIAL/COMMERCIAL


ENGR. SOCRATES NACIS E-15
BUILDING