System Diagram
System Diagram
5- C.O. 6-ACU
Sub-total 4,800 Volt Amperes
30 AMP. 20 AMP.
7- WA 8- REF Application of
Demand Factor
30 AMP. 20 AMP.
First 4,000 V.A. @100%D.F. 4,000 Volt Amperes
9- RANGE 10- ACU
20 AMP. 20 AMP. NEXT 800 V.A. @35% D.F. 280 Volt Amperes
20 AMP. 20 AMP.
Volt Amperes
1 unit Range, @ 3000 W 3000
EARTH GROUND 1 -8.0mm² TW WIRE
GROUNDING CONDUCTOR 10,858 Volt Amperes
Total other loads:
Name
MAIN 100 AT/100AF
Occupancy RESIDENTIAL COMMERCIAL BUILDING
15 AMP. 15 AMP.
1- L.O Address URDANETA CITY, PANGASINAN
2- L.O
20 AMP. 20 AMP.
Sub-total 4,280 Volt Amperes
15 - ACU 16- REF
Volt Amperes
6 unit Refrigerator, @ 780 W 4680
220 Volts
Service
MAIN 100 AT/100AF
Floor Area 20.00 m x 10.00 m 200 m²
15 AMP. 15 AMP. Required general
24 VA/m²
1- L.O 2- L.O lighting load
20 AMP. 20 AMP.
Sub-total 4,280 Volt Amperes
11- REF 12- ACU
Volt Amperes
4 unit Refrigerator, @ 780 W 3120
Name
220 Volts
Service
3- L.O. 4- C.O.
Sub-total 4,800 Volt Amperes
30 AMP. 20 AMP.
Application of
5- ACU 6-ACU Demand Factor
20 AMP.
First 4,000 V.A. @100%D.F. 4,000 Volt Amperes
7- SPARE
NEXT 800 V.A. @35% D.F. 280 Volt Amperes
1.1 LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE AND NEW ELECTRICAL
ENGINEERING LAW
LEGEND:
1.2 EXISTING LOCAL UTILITY COMPANY AND REQUIREMENTS ITSELF,
SYMBOL DESCRIPTION
1.2 REQUIREMENTS OF THE BUREAU OF LABOR STANDARS.
CIRCLE LIGHTING CEILING
2. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION MOUNTED 40 WATTS
OF QUALIFIED AND A DULY LICENSED ELECTRICAL ENGINEER OR MASTER ELECTRICIAN. SQUARE LIGHTING CEILING
SERVICE ENTRANCE POWER THE ELECTRICAL ENGINEER SHALL BE RESPONSIBLE FOR THE INTERPRETATION OF
OF THE DESIGN INTENT, LAYOUT PLANS AND SPECIFICATIONS; AND THE REQUIRED
MOUNTED 30 WATTS
CONVENIENCE OUTLET
3. ALL WIRES SHALL BE COPPER TYPE THHN IN (PVC) POLYVINYL CHLORIDE FOR MAIN
& SUB-FEEDER: (PVC) POLYVINYL CHLORIDE CIRCUITS & AUXILIARY CIRCUITS OR RANGE OUTLET
RANGE
UNLESS OTHERWISE SPECIFIED IN THE PLAN.
REFRIGERATOR OUTLET
3-#250mm² REF
THHN AND 4. ALL JUNCTION, UTILITY, SQUARE AND PULL BOXES SHALL BE GA. NO. 18 OR AS PER
WA
WASHING MACHINE OUTLET
APPROVED EQUIVALENT AND PAINTED WITH ONE COAT PRIMER PRIOR TO INSTALLATION.
1-#150mm² TW
CONVENIENCE OUTLET
WIRES FOR 5. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED TYPE. APPROPRIATE AU
AIRCON UNIT
WITH LOCATION AND INTENDED TO BE USED.
MAIN PB PANEL BOARD
6. POWER SUPPLY SHALL BE 230 VOLTS, THREE PHASE, 60 HERTZ, TWO WIRES SYSTEM.
M
7. MINIMUM SIZE OF CONDUCTORS SHALL BE 2.0mm² THHN IN 15mm DIA. TRADE SIZE.
CIRCUIT HOMERUN
KILOWATTHOUR METER 8. ALL VERTICAL AND HORIZONTAL CONDUITS SHALL BE CONCEALED OR EMBEDDED ON S1 ONE GANG SWITCH
CONCRETE WALLS AND FLOORS.
11. VERIFY MOUNTING HEIGHTS & EXACT LOCATIONS OF WIRING DEVICES WITH THE ARCHITECT SWITCH LINE
PRIOR TO INSTALLATION.
LP-1
2P, 115/220V
1500 mm
worktop
1500 mm
(panel board)
convenice outlet
1200 mm (kitchen area)
2000 mm
minimum
height
(aircon outlet )
1500 mm
1200 mm
1200 mm
1200 mm (light
switch)
900 mm
450 mm
minimum height
450 mm
(convenience
,ref,washing
outlet )
1 ELECTRICAL DETAILS
E-15 SCALE NTS