NetAgentA

UPS SNMP Agent


User’s Manual
User Guide for NetAgentA Mini
Version 1.0

Copyright Information
Copyright © 2018, Mega System Technologies, Inc.
All rights reserved.
Reproduction without permission is prohibited.

Technical Support and Contact Information


Mega System Technologies, Inc.
Tel: +886-2-87922060
Fax: +886-2-87922066
Web: www.megatec.com.tw
E-mail: [email protected]
Contents
CHAPTER 1. INTRODUCTION ................................................................................. 4

1.1 Features ...................................................................................................................4


1.2 Applications .............................................................................................................5

CHAPTER 2. NetAgentA Series .............................................................................. 6

2.1 NetAgentA Mini Models ..........................................................................................6


2.2 NetAgentA Mini LED Indication .............................................................................6

CHAPTER 3 SOFTWARE INSTALLATION .............................................................. 8

3.1 Software Installation ...............................................................................................8

CHAPTER 4. NetAgentA Setting .......................................................................... 9

4.1 Introduction .............................................................................................................9


4.2 NetAgentA Login Procedure ..................................................................................9
4.3 Netility Installation and Setting ........................................................................... 12
4.4 NetAgentA Web Interface & Setting ................................................................... 21
 Information > UPS Status .............................................................................................................. 21

 Information > System Status ......................................................................................................... 21


 Information > Remote Control ...................................................................................................... 23

 Information > SMS Modem Status ............................................................................................... 24

 Information > NetFeeler ............................................................................................................... 24

 Configuration > UPS Configuration ............................................................................................... 24


 Configuration > UPS On/Off Schedule .......................................................................................... 26

 Configuration > Network .............................................................................................................. 29

 Configuration > Wireless LAN ....................................................................................................... 35


 Configuration > SNMP ................................................................................................................... 39

 Configuration > Email .................................................................................................................... 43


 Configuration > SMS...................................................................................................................... 45

 Configuration > Web/Telnet/FTP .................................................................................................. 47


 Configuration > BACnet ................................................................................................................. 52

 Configuration > SMS Modem ........................................................................................................ 53


 Configuration > NetFeeler ............................................................................................................. 55
 Configuration > System ................................................................................................................. 55

 Log Information > Event Log ......................................................................................................... 57


 Log Information > SMS Log ........................................................................................................... 58
 Log Information > Data Log ........................................................................................................... 59

 Log Information > Battery Test Log ............................................................................................... 60


 Management > Netility Web......................................................................................................... 60
 Management > File Manager ........................................................................................................ 61

 Management > Serial Port Debug................................................................................................. 61


 Management > Help...................................................................................................................... 62
 Management > About ................................................................................................................... 62
Chapter 1. Introduction
1.1 Features
NetAgentA is the SNMP (Simple Network Management Protocol) card for monitoring UPS.
Not only could remote control the UPS and get the current status of it, it is also support to
connect to compatible modem to send SMS notification, or our NetFeeler II and its
additional sensors for ambient temperature, humidity and water status. The product is for
“Contact Closure” and “RS232” interface UPS and the communication protocol includes
the Contact Closure, RS232[MegaTec], Phoenixtec], SEC 2400, SEC 9600, Megatec
Three Phase, ..etc. NetAgentA provides a simple and easy installation procedure. CD
provides along with NetAgentA offers several software to allow the user to configure IP
address; central monitoring and multi shutdown on different operating systems. Other
advance configurations could be accomplished in the Web browser.

Features:
(1) Provide SNMP MIB to monitor & control UPS
(2) Auto-sense 10M /100M/1000M Fast Ethernet Manage and configure via Telnet,
Web Browser or NMS
(3) Support TCP/IP, UDP, SNMP, Telnet,SNTP, PPP, HTTP, HTTPS, SMTP, FTP,
Modbus, BACnet Protocols
(4) Support SSL/TLS, SSH Encryptions
(5) Providing easy setup and upgrade tools via our Netility software
(6) Send SNMP TRAP ; E-mail and SMS for events notification.
(7) Auto email daily UPS history report
(8) Perform graceful shutdown with our ClientMate software
(9) Add-on optional NetFeeler II for temperature, humidity, water, smoke and door
sensor
(10) Add-on optional WiFi dongle for wireless network access
(11) Add-on optional GPRS modem for SMS notification
1.2 Applications
 NetAgentA allows UPS to be monitor on network
When the UPS connects with NetAgentA, the system manager could check each and
every UPS condition by a computer with Browser installed. The manager could monitor
and control the UPS by simply input the IP address of the NetAgentA which connects to
the UPS. When there is a power abnormal condition happens, the NetAgentA could also
send the trap information to the system manager to take proper action.
 NetAgentA Provides Shutdown Utilities
When a computer install our shutdown software in the network that connects to the
NetAgentA, when UPS is in AC failure condition or Battery Low condition, the software
would close all the files of the operating system and shutdown gracefully. This could avoid
system corrupt when a power disconnection happened.
 NetAgentA for Surrounding Monitoring
NetAgentA with USB ports could connect to optional sensor- USB NetFeeler to get the
surrounding temperature/humidity/smoke/fire signals. These information could also be
revealed on the NetAgentA Web page. When there is an abnormal condition happened, it
could also be sent as a trap to the system manager.
Chapter 2. NetAgentA Series

2.1 NetAgentA Mini Models

NetAgentA Mini Model

Model Name Package Contents Internal External RJ45 RS232 ENV USB Single Three

Phase Phase

1. NetAgentAA Mini SNMP Card


DA520 2. NetAgentA Utility CD
v v v v
3. Quick Installation Guide (Optional)
1. NetAgentAA Mini SNMP Card
2. NetAgentA Utility CD
DA806 3. Quick Installation Guide (Optional) v v v v v
4. M2509 Cable (USB)
1. NetAgentAA Mini SNMP Card
DA807 2. NetAgentA Utility CD
v v v v v
3. Quick Installation Guide (Optional)

2.2 NetAgentA Mini LED Indication

Status LED RJ45 Ethernet

Amber Red

Communication Connection Status with UPS


Flashing Flashing Off
Lost Connecting
Transferring data with UPS
connection with UPS
Green Yellow
Green Yellow
On Flashing On Flashing
Sending/ Sending/
Power Status NetAgentA Mini Status 100 10
Receiving Receiving
Mbps Mbps
On Off On Off Data Data
Normal No Power Operating Stop working
When Green and Yellow LED are both ON,
it runs at 1000M mode

NOTE : When writing firmware, red led alternating flashing, DO NOT remove any power
D5 D4
Green Blue

Power Communication
On Off Flashing
No Sending/Receiving
Normal
Power Data

Red

UPS connection
Flashing Off
Lost Connecting
connection with UPS
Yellow

NetAgentA Mini 9 Status


On Off
Stop
Operating
Working

Power Lost Writing


Status On Communication Firmware
Yellow

On On Off

NetAgentA Mini 9
Status
Red

Off Flashing Flashing


UPS
Communication
Green

On On On

Power
Chapter 3 Software Installation

3.1 Software Installation

NetAgentA Utility CD offers several management and shutdown software. Insert CD


into CD-ROM and software can be select under 【Program Installation】

Netility: Configure and Search


NetAgentA. Refer to 4.3

ClientMate:
Shutdown OS Software .
Refer to Chapter 6

SMS Server:
SMS notification Softwar.
Refer to Chapter 9

SNMPView :
Multi monitoring Software. Time Server:
Refer to Chapter 7 Time server software

iMConfig:
Muti-configuration Software.
Refer to Chapter 8

If the PC does not executes CD program automatically, please select from File
Managment
Chapter 4. NetAgentA Setting

4.1 Introduction
NetAgentA can be login via web or HyperTerminal with protocol and encryption of
HTTP/HTTPS/SSH/Telnet. Enter the IP address of NetAgentA to configure and monitor
the UPS status.

HTTP

HTTPS

SSH

TELNET

4.2 NetAgentA Login Procedure

1. Connect NetAgentA to modem/router

2. Install Netility under same network

3.NetAgentA searches all available


NetAgentA within same network

4.Configure IP address of NetAgentA


(1)DHCP IP (Default) (2)Static IP

5. Enter IP address of the 5. Double click NetAgentA 5. Login via HyperTerminal


NetAgentA on browser from Netility

6. Select the compatible protocol under


UPS Configuration webpage of NetAgentA
7.Enter other parameter on NetAgentA
webpage

NOTE 1:Each NetAgentA has its unique serial number / MAC address and Password.
This is available on the label of each unit. This helps to identify the card information on
Netility

NOTE 2: NetAgentA with LCD display may obtain the IP info from it.

Example of LCD display format as below

IP address 192.168.0.70

192 168 0 70
Subnet Mask: 255.255.255.0

255 255 255 0


Gateway:192.168.0.1

192 168 0 1
When NetAgentA IP is known, enter such IP address on the browser to login. If non-LCD
NetAgentA model, install Netility software to find and configure its IP address.
4.3 Netility Installation and Setting
 Netility Installation
Netility is tool software that helps the user to search all the available NetAgentA within
network as well as to configure IP address and firmware upgrade. Mount the NetAgentA
Utility CD on CD-ROM and click on Program Installation>Netility>Windows

Netility installation directory

Netility Software

Under All Programs/ Megatec File Directory


 Netility Operation and Setting

Netlity main pages divided into 2 sections:

1. Online NetAgentA List 2. Function Selection

2. Function

1. Online NetAgentA
List
2.5 Refresh List
2.4 About

2.3 Firmware Upgrade

2.2 Network Settings

2.1 Launch Web User Interface

1.2 Individual NetAgentA Info

1.1 Online NetAgentA List


1.1 Online NetAgentA List

When open up Netility , it automatically searches all the available online NetAegntA
within the network with its serial number, IP address, MAC address. Double click on the
specific NetAgentA with valid IP address, it will direct to the NetAgentA’s webpage. (List
refreshes automatically every 2 minutes)

Double click to login to the webpage


1.2 Individual NetAgentA Info

Click on specific NetAgentA , the bottom column shows its hardware , firmware version
and MAC address. It also shows the total NetAgentA number that found by Netility and
selected

Click on NetAgentA

Hardware Version

Firmware Version

Total Number of NetAgentA


found and selected
2.1 Launch Web User Interface
Select specific NetAgentA from the list and click on Launch Web User Interface to
login to the NetAgentA’s webpage

2. Click on
Launch Web
User Interface

1.Click on NetAgentA

Login to the webpage of such NetAgentA


2.2 Network Settings
 When connecting the NetAgentA for the first time, ensure IP address and other
network setting are correctly entered in order to login to the NetAgentA’s webpage via
browser or HyperTerminal

 When select to obtain IP address by DHCP or BOOTP, IP address and other network
parameter will be assign by the network

 NetAgentA offers 4 network protocols - HTTP / HTTPS / TELNET / SSH for


management with security consideration. If any change on port number, the it require
to enter the full IP address with port number in order to login
For example:HTTP port number change to 81
The full address to be enter on browser should be ”http://X.X.X.X:81” (X.X.X.X is
the IP address of the NetAgentA)
For Example:Telnet port number change to 24
The full address to be enter on HyperTermnal should be
”http://X.X.X.X 24” (X.X.X.X is the IP address of the NetAgentA)

 When password of the NetAgentA is enabled, it is necessary to enter the correct


password before making any configuration change and firmware upgrade

1. Click on specific NetAgentA


2. Click on
Network
Settings

Select to assign IP by DHCP

Columns requires to be entered for


Static IP address
Default port for each protocol

Once password is enabled and


Enter password configured, it is required to enter the
correct password when change any
setting or firmware upgrade
2.3 Firmware Upgrade
 This is to upgrade or re-load the firmware to the NetAgentA unit. Firmware version is
available on the official website. Ensure to check the NetAgentA model, hardware
version for the correct firmware version (.bin)
 Ways to select NetAgentA for firmware upgrading
(1) Click on specific NetAgentA from the Netility list
(2) Press and hold on CTRL key then select multi NetAgentA unit from the list=>This
is to upgrade multi units at once
(3) Click on the first NetAgentA from the list, then press and hold on SHIFT key as
well as click on the last unit of the NetAgentA =>This is if all NetAgentA from the list
are same model
 WARING:Please makes sure the multi NetAgentA selected are same model
 If any failure during firmware upgrading, please upgrade again until it is successfully
done
 While upgrading, red and yellow LED would alternating flashing, or red led flashing.
DO NOT remove any power or cable to the NetAgentA. Once firmware is successfully
upgraded, NetAgentA would reboot automatically.

Upgrade Single Selection of Multi-NetAgentA Upgrade consecutive


NetAgentA NetAgentA

1.Select .bin file

3. Upgrade message
4. Cancel to exit

2.Click on Download
2.4 About
Here shows the current Netility verison

2.5 Refresh List


The list on Netility would refresh every 2 minutes automatically, however, manual
refresh is also possible by clicking Refresh List

Click on Refresh List


Searching

List out all the Online NetAgentA


4.4 NetAgentA Web Interface & Setting
 Information > UPS Status
 UPS Status
This page is to show the current UPS connection status in graphic mode with Voltage,
Frequency and other information.

 Information > System Status


 System Information
Here shows all the basic information of the NetAgentA such as hardware / firmware
version; Serial Number; Uptime…etc.
 Information > System Status
 UPS Information
This page shows UPS information/Battery Information/Rating Information. The data is
obtained from the reply of UPS or the settings from [UPS Configuration] webpage

 Information > System Status


 Network Status
This page shows the network information of NetAgentA.
 Information > System Status
 Wirelss Status
This page is to show Wireless connection status and information when NetAgentA
communicates via the compatible WiFi dongle

 Information > Remote Control


User can perform several tests to the UPS remotely. Once the option is selected, please
click on Apply in order to execute it.
 Information > SMS Modem Status
This page shows the Modem status when GPRS modem is connecting with NetAgentA

 Information > NetFeeler


This page shows the environmental status when USB NetFeeler/ NetFeeler II and its
accessories are connected with NetAentA.

 Configuration > UPS Configuration


 UPS Properties (Please refer to your UPS specification)
UPS Communication Type:
In order to establish theconnection between NetAgentA and UPS, select
the compatible protocol which your UPS supported from the list. Wrong
protocol selected would cause no communication at all. (Megatec is
default protocol)
Number of Batteries:
Enter the number of battery that the UPS has.
Battery Full Charge Voltage (V):
Enter the number of the full charged voltage per battery cell. (2.267 is default, this is
recommended not to be change)
Battery Exhausted Charge Voltage(V):
Enter the number of exhausted voltage per battery cell. (1.667 is default, this is
recommended not to be change)
Date of Last Battery replacement(mm/dd/yyyy):
Enter the date of last battery replacement for record
 Test log
Test UPS Every:
Week /2 Weeks/ Month / Quarter UPS can be selected
Start Time of UPS Test (hh:mm):
To enter the time to begin the test
UPS Test Type:
Test option can be select from the drop down list
UPS Data Log:
To enter the time interval to refreshing data
 Warning Threshold Values

Time out after loss of connection:


Send warning alarm when NetAgentA and UPS lost connection at this configured time
Critical Load(%):
When loading reaches at this % configured, NetAgentA will send warning alarm
UPS Temperature (℃):
When UPS temperature reaches at this degree configured, NetAgentA will send warning
alarm
Critical Capacity (%):
When UPS battery capacity reaches at this % configured, NetAgentA will send warning
alarm

 Configuration > UPS On/Off Schedule


 UPS Action
When selected event happens at configured time range, UPS will be shut down
 Remote Shutdown
This is to shut down the network server when selected event happens without install
shutdown software. Event needs to be adding under UPS Action first and then enter the IP
address of server that wish to be shut down by SSH or Telnet with compatible shutdown
command of the server system.

For example: To shutdown Host 1 (Windows server) and Host 2 (Linux server) after 1
minute when AC power failed.
First, go to UPS Action tab, select event of “AC Power Failed” then select “shutdown Host
1 “ , press on Add. The action will be add in the list. Then the same for Host 2, select event
of “AC Power Failed” and select “shutdown Host 2” from the list and press on Add to be in
the list.

Once action is added, go to Remote Shutdown tab, enter the domain IP for Host 1 and
Host 2, select Telnet or SSH for access and then enter the user name/password of the
server with its shutdown command of the server. For Windows, “shutdown /a “ is the
shutdown command. For Linux, “halt” is the command to shut down. For MAC, it is “sudo
shutdown” as the command.

Below to check command menu for different system

- Windows : shutdown/?
- Linux : shutdown –help
- MAC : sudo shutdown
 Weekly Schedule

This section is to set the time to turn on/off the UPS each day in the week.

 Date Schedule
This section is to set the time to turn on/off the UPS on particular days.
The settings here override the settings in Weekly Schedule.

Warning will be initiated X_ before Schedule shutdown event


NetAgentA will send a warning message before a scheduled shutdown. This section sets
the delay time period after the message is sent and before the scheduled shutdown is
started.
 Wake On Lan
This section is to wake the PC within the network when AC recovery, or, when battery
capacity reaches at configured %. (Make sure the PC has such function supported and
configure as “Enabled” under BIOS.) Enter the IP address of that PC and system would
search its IP accordingly.

 Configuration > Network


This page is to set NetAgentA’s Network settings.
 IPv4
NetAgentA and DNS IP address can be obtain by drop down list with option of Manually,
Using DHCP, or Bootp. If the IP address and DNS has been configured on Netility, then
info will automatically show here
 IPv6
All NetAgentA series supports IPv6. IP address can be obtain from the drop down list with
option of ( Automatic/Stateless DHCPV6/DHCPV6/Manual )
Once click on Apply, NetAgentA will reboot

 Ethernet
Connection Type
This section is to set communication speed between NetAgentA and Network.
Once click on Apply, NetAgentA will reboot
Stop UPS communication when Ethernet disconnected
This section is to set if to stop UPS communication when NetAgentA disconnects with
Ethernet
Modbus on TCP Device ID:
Enter device ID to read/write data when using Modbus on TCP communication with
Megatec protocol and Modbus Register Table
 Dynamic DNS
This is a free service that allows the user to alias a dynamic IP address to a static
hostname. Ensure account/password has been registered from the DNS service provider
Service Provider
Dynamic DNS providers can be select from the list
Domain Name
This is the Domain Name you have created from the above selected DDNS provider
Login Name
This is the Login / Account name that you have created with the selected DDNS provider.
Login Password:
Enter the Password you have assigned to your DDNS Account.
Use external STUN server to get Public IP to register
Choose Yes to ensure that NetAgentA uses the WAN / Public IP to update
the selected DDNS server
If to use iCV99.net as Service Provide which host by Megatec, instruction as below:
1. Ensure NetAgentA is able to connect to Internet. Select icv99.net from the drop down
list of the Service Provider. The Domain Name and Login Name will automatically be
fill-in with serial number of the device. Enter the password of the NetAgentA which is
printed on the NetAgentA label, then click Apply.

1.Select icv99.net

2. Enter password
3. Click Apply

2. If using router, please login to router and direct IP and port number under virtual
server for port forwarding. Kindly refer to router’s manual

Router Configuration
3. After 20 minutes, NetAgentA should be login with its DDNS Domain name

4. To change domain name or password, please go to www.icv99.net

New Domain name

Enter new password

Enter email

Click on Done
 PPPoE
Use this option to allow NetAgentA to connect to the Internet directly using your xDSL
modem by PPPoE. Enter the Login name and password to enable the connection. Once
set-up, NetAgentA will connect directly to the Internet , any abnormal connection failure
would also cause to re-dial

Select Connect Always

Enter Login Name

Enter Password
 Configuration > Wireless LAN
This is to configure NetAgentA Wireless network with compatible USB wireless dongle.
Login to the Wireless Router
(1)SSID : Name it (any)
(2)Authorization:Select WPA2-Personal
(3)WPAEncryption:AES
(4)WPA-PSKKey:Enter any password (8~63 digits ASCII code)

(1)

(2)

(3)
(4)

Ensure Wireless>WPS>Enable WPS is


“ON”
(1)Connect U1 Tamio dongle to NetAgentA card ( If it is model-DA806, use the M2509
cable to convert)。
(2)Press WPS button on Tamio dongle for 2~3 seconds until the yellow LED begins
to flashing.

LAN cable is not


required

WPS Button
WPS Setting for the wireless router:

When yellow LED of the NetAgentA is flashing , open up WPS setting page of the
wireless router. With WPS connection mode,
(1)Select ”WPS button”
(2)Click on”Start”
Start WPS Connection
Process

When WPS connection successfully, the yellow


LED on NetAgentAA stop flashing
Open up Netility to login to NetAgentA:

(1)Once NetAgentA is connected with wireless router via WPS, Netility should be
able to find this wireless NetAgentA
(2)Login to NetAgentA’s webpage , under Configuration > Wireless Lan
webpage, it shows
the wireless signal
(With distance of 6-10 meters. Router RT-AC53 still shows with full signal)

When NetAgentA connects with wireless router, it shows


this sign to indicate the router that NetAgentA is connecting.
 Configuration > SNMP
This page is to configure NetAgentA SNMP settings to be used by NMS ( Network
Management System). (e.g: SNMPView, it is available on the NetAgentA Utility CD.)
 General
MIB System
System Name
This section is to give a name to the NetAgentA.
System Contact
This section is to give a name to the administrator.
System Location
This section is to set NetAgentA location.
SNMP UDP Port
NetAgentA SNMP Port:
The port that NetAgnetA receive and send SNMP command. (Default is 161)
Trap Receive Port:
The port to receive trap. (Default is 162)
SNMPv3 Engine ID
SNMPv3 Engine ID Format Type:
When using SNMPv3, NetAgentA requires to have its Engine ID for identification to
generates authentication and encryption key . Format type can be select from the drop
down list with option of MAC Address / IPv4 / IPv6 / Manual
Once click on Apply, NetAgentA will reboot
SNMPv3 Engine ID Text:
SNMPv3 Engine ID content
 Access Control
Manager IP Address:
This is to set the IP address that the administrator can manage NetAgentA from. It is valid
for up to 8 IP addresses. To manage NetAgentA from any IP address, enter *.*.*.* into
Manager IP address.
Version:
This is to select between SNMPv1& SNMPv2 or When select All and V3, user name,
password, authentication and privacy are required
Community:
This section is to set a Community name for NMS. The community name has to be as the
same as the setting in NMS. (Default is public)
Permission:
This is to set authorities of administrators. Options are Read, Read/Write, and No Access.
Description:
This is to make note for administrator’s reference

At least 8 characters

*.*.*.* means any IP

 Trap Notification
Trap Notification
Destination IP Address:
To set receivers IP address for receiving traps sent by NetAgentA. It is valid for up to 8 IP
Addresses.
Accept:
Select the trap type of its SNMP version or Inform from drop down list. When SNMPv3 trap
or SNMPv3 Inform is selected, username/password and authentication information are
required.
Community:
Trap receiver and NetAgentA must be same community. (Default is public)
Trap Type:
Select from PPC MIB or RFC1628 MIB (Default is PPC)
MIB file is available in the CD provided with NetAgentA
Severity:
This section is to set Trap level for each receiver. There are three levels as below
 Information: To receive all traps.
 Warning: To receive only “warning” and “severe” traps.
 Severe: To receive only “severe” traps.
( Please refer to NMS manual for Trap levels.)
Description:
This is to make note for administrator’s reference
Events:
This is to select events for NetAgentA to send traps. Click on Select to show the full Events
List. Click on Test to send test trap to ensure all setting is correct

Send Power Restore and Adaptor Restore Traps for X time(s) in X second(s) Interval.
This is to set number of trap to send in preset second when power restore on NetAgentA.
This is to check if the communication between trap receiver and NetAgentA remains well
or not after power recovers
SNMP Inform Request
This is to set the number of times that the NetAgentA can request a response from the
sending Inform host with a preset value. (Default is 3 times and an interval of 5 seconds)
 Device Connected
This section is to set the usage power and connection status of other devices which
connects to the same UPS as NetAgentA uses.

 Configuration > Email

To send email notification when event occurs or data log. Encryption supports are
SSL/TLS/STARTTLS
 Email Setting
Email Server:
Enter the address of email server
Email Port:
Email Port that use for sending email
Enable SSL on Email Transmission:
Select SSL type for email transmission

Sender’s Email Address:


To enter the email address that for sending email
Email Server Requires Authentication:
If such email server requires authentication or not
Account name:
If authentication is required, enter its account name
Password:
If authentication is required, enter its password
Sending Test Mail:
Enter email address to check all configuration is correct or not to receiving mail
Test Email Received

 Email for Event Log (To received email notification


To set email addresses to receive warning email sent by NetAgentA when selected event
occurs. It is valid for up to 8 Email addresses.
 Email for Daily Report (To receive daily report)
This section is to set email addresses to receive NetAgentA’s Daily Report at pre-set time.
It is valid for up to 4 email addresses. Daily report will be the content of event and data log.

 Configuration > SMS


When UPS events occurs, it allows Short Message Signals (“SMS”) to be sent and
received using a GSM/GPRS/CDMA Modem. Operation information are as below for
single and three ports of NetAgentA.

 SMS Setting
Send SMS When Event Occurs:
 Disable :No SMS Service
 Use Local Modem:When GSM modem is connected to NetAgentA directly
(Refer to SMS Modem section for its installation)
 Use Remote Service:When GSM modem connects to PC with SMS Server
software installed
(Refer to SMS Server section for SMS Server Software installation)
SMS Server:
If select to use Remote Service to send SMS, then enter the IP address of the SMS
Server.
(The PC that installed SMS Server Software)
SMS Port:
If select to use Remote Service to send SMS, enter the port number that SMS Server uses
for sending SMS. (Port 80 is default)
Account Name:
If select to use Remote Service to send SMS, enter SMS Server’s account name if
required
Password:
If select to use Remote Service to send SMS, enter SMS Server’s password if required
Sending test SMS:
When modem and configuration are ready, enter a mobile number to receive testing SMS
 Mobile for Event Log
To set the recipient’s mobile number for SMS notification when event or NetFeeler event
occurs. A total of 8 mobile numbers can be assign.

 Configuration > Web/Telnet/FTP

To set permission for each user account for Web,Telnet and FTP access with up to
8 users. Also to enable/disable specific port for HTTP/HTTPS, Telnet/ SSH and FTP

 HTTP/HTTPS
Enter specific port number to access or disable for HTTP, HTTP proxy, HTTPS
HTTP/HTTPS Account
User Name:
To set password for NetAgentA Web access.
Password:
To set password for NetAgentA Web access.
Permission:
To set No Access / Read/ Read&Write)
 Permission Rule: At least one user account must be Read/Write
 Permission Rule : User name with Read and Write cannot be blank
IP Filter:
Only specific IP address could login to NetAgentA
 *.*.*.* means any IP address
Auto Logoff after Idle for minute (s). ( 0 is disabled)
NetAgentA webpage will be logoff automatically if it idles for the preset value.

 Telnet/SSH
Enter specific port number to access or disable for Telnet/SSH
Telnet/SSH Account
Same as HTTP account/password settings
This is to duplicate the same settings from HTTP
User Name:
To set password for NetAgentA Telnet access.
Password:
To set password for NetAgentA Telnet access.
Permission:
To set No Access / Read/ Read&Write)
 Permission Rule: At least one user account must be Read/Write
 Permission Rule : User name with Read and Write cannot be blank
IP Filter:
Only specific IP address could login to NetAgentA
 *.*.*.* means any IP address
 FTP/FTP-SSL
To select the access between FTP and FTP-SSL with specific port number or to disabled it
FTP/FTP-SSL Account
Same as HTTP account/password settings
This is to duplicate the same settings from HTTP
User Name:
To set password for NetAgentA FTP access.
Password:
To set password for NetAgentA FTP access.
Permission:
To set No Access / Read/ Read&Write)
 Permission Rule: At least one user account must be Read/Write
 Permission Rule : User name with Read and Write cannot be blank
IP Filter:
Only specific IP address could login to NetAgentA
 *.*.*.* means any IP address
 SSL Information
NetAgentA supports HTTPS protocol and varies SSL encryptions version for network
connection. User may upload its Public Key and Certification for authentication
HTTPS Protocols
Select the encryption version
 SSL v2
 SSL v3
 SSL v1.0
 SSL v1.1
 SSL v1.2
 Once click on Apply, NetAgentA will reboot

SSL Information
This is to upload the SSL certificate. When both public key and certificate are uploaded to
NetAgentA web server, the communication will be encrypted by SSL
(To communicate via Https, make sure to enable Https port 443.)To create its own public
key and certification, please refer to OpenSSL software in the CD

https://192.168.66.133
:

When connect via HTTPS with its own generated


public key and certification, browser may show
error, please ignore and continue.
 RADIUS Server Setting
If RADIUS server authentication is required for the network, NetAgentA could be added by
entering following parameter.

Enable RADIUS in Web/Telnet Login:


To select if to enable RADIUS
RADIUS Server Address:
To enter the IP address of the RADIUS Server
Authentication Port:
RADIUS port number (Default is 812)
Shared Key:
Enter the Shared Key between RADIUS Server and client
Connection Timeout:
Set the number of seconds to suspend the login time after the RADIUS server is rejected
Connection Retry:
Sets the number of connections to the RADIUS server again
 Configuration > BACnet

NetAgentA supports BACnet/IP (Building Automation and Control/Internet Protocol)

 BACnet
BACNet Device
Configure the device ID and access port number for the NetAgentA when using BACnet
for communication

Notification
Enter the IP address of the PC that to be notify by BACnet software when event occurs
 Configuration > SMS Modem
When compatible GPRS modem connects with NetAgentA , it is able to send SMS
notification when event occurs
 Modem Setup Procedure

2. Place the SIM card on the holder and


insert into GSM Modem

3. Attach antenna to the modem

1. Press the button to eject


the SIM card holder
:

Modem Led

Modem Led Status


1. If flash every 0.8 seconds:
Modem initializing, please wait
If no respond
(1) Check if PIN is correctly entered, or if PIN is required
(2) Check if SIM card is inserted corrected
(3) Check if no or low signal

2. If flash every 3 seconds:


Modem is ready for operation
 SNMS Modem Setting
Modem Communication Port:
Select “ ttyUSB0” for USB modem connects with NetAgentA directly;
SMS Communication:
Select between GPRS or CDMA
SIM Card PIN:
If PIN is required for the SIM card, please enter
Confirm SIM PIN:
Retype SIM card PIN

When all done, click on Apply. Modem Information and Status can be check from
Information> SMS Modem Status
 Once click on Apply ,NetAgentA will reboot

 Send Message
Cellular Phone number:
Enter mobile number
SMS Content(Max.70 Characters):
Enter the SMS content text and select coding. Unicode or Character
 Configuration > NetFeeler
NetFeeler is the external optional environmental sensor. It is to detects temperature,
humidity and water. NetFeeler has RF receiver built-in to work with extension sensors
such as smoke, security sensor.
 NetFeeler
NetFeeler
Humidity/Temperature Critical value:
To set the lowest and highest critical values for temperature and humidity. NetFeeler will
send a warning message when it detects temperature or humidity values below and above
these settings.
Security Label
NetFeeler may connect up to 7 security sensors that communicate via RF. This section is
to set the location or name of each sensor.

 Configuration > System

This page is to set NetAgentA’s system time, language and configuration.

 Date/Time
NetAgentA to synchronize with external or internal Time Server for correct date and time.
System Time
System Time(yyyy/mm/dd hh:mmm:ss):
To display the current system time/date of NetAgentA. Or click on Adjust Now to adjust to
the correct time/date automatically
Time Between Automatic Updates:
To set an interval for time synchronization.
Time Server:
Time server can be select from the drop down list , or add other time server manually.
Time Zone(Relative to GMT):
To select its GMT time zone

Using Daylight Saving Time:


Select whether to use the daylight saving time system to adjust the clock for 1 hour in
advanced
Restart
Auto Restart System for Every (0 is disabled):
NetAgentA to restart automatically at preset hour or minute
Manual Restart System After 30 seconds:
Once click on Apply, NetAgentA would restart after 30 seconds

 Language
This page is to set the language interface for NetAgentA.
Interface Language
To set the language of NetAgentA web pages. When first start login to the webpage of
NetAgentA, NetAgentA will auto detects the OS language of the PC and shows the same
language on its web pages. Users may choose the language per preference
Note: Users will have to enable cookies before they use this function.
Email Preference
Select language preference when receive emails and SMS.
Languages supported by NetAgentA

 English  繁體中文
 Deutsch  簡體中文
 Português  한글
 Español  日本語
 Français  Русский
 Italiano  ไทย
 Türkçe  Polska
 Save/Restore
Save Current Configuration
Click on Save to save the configuration to your PC. The text file will have a default format
of YYYY_MMDD_####.cfg. Administrator permission required.
Restore previous configuration
Use this function to restore a *.cfg configuration that has been saved earlier. Click
Browse… to the location of the file and click Restore.
Reset to factory default
This function will reset all settings to its default value.

 Log Information > Event Log

 Event Log
Event List
It shows record of all events, giving the Date/Time of the event with detailed description of
each. Event can be check on specific date from the calendar
Event census
Here is to present the event statistically on the selected date

 Log Information > SMS Log


 SMS Log
It shows SMS record of all mobile number, giving the Date/Time of the SMS sent and a
detailed description of each. When reach to the limit, it rewrites on the previous logs.
SMS log can be save as csv file .
 Log Information > Data Log
 Data Chart
It records UPS Input Voltage/Output Voltage/ Frequency/ Loading/Capacity/
Temperature..etc in chart format. Logs can be saved in CSV format by clicking on “Save”.
The bar on top can be adjusted to check the log status at specific time of the day.

 Data Log
It records UPS Input Voltage/Output Voltage/ Frequency/ Loading/Capacity/
Temperature..etc in detailed list. When NetFeeler is connected, status will be available
too.
 Log Information > Battery Test Log

 Battery Test Log


To record the UPS Self-Test and it shows in graphic. UPS Self-Test option is available
under System Information > Remote Control.

 Management > Netility Web


This to display all the NetAgentA within network with its serial number; Mac Address;
Hardware/Firmware version and its IP address. Double click on the highlighted unit to
open the webpage of such device.
If the NetAgentA is access by WAN IP , Netility Web would also be able to list out all the
other available NetAgentA under same LAN as the NetAgentA that has WAN IP. (HTTP
port 81 must be enabled on the NetAgentA with WAN IP and domain to be as
http://xxx.xxx.xx:81 ( xxx.xx is the WAN IP or domain name)
 Management > File Manager
This is manage log file generates by NetAgentA. Specific log.dat can be download, delete.
Once dat. file is deleted, the log record will also be erased on the Log display under Log
Information

 Management > Serial Port Debug


It shows the communication status between NetAgentA and UPS by Sent and Received
columns.

 Debug Information
Command can send automatically by NetAgentA, or manually enter the command to UPS.
Sent Information
This column shows the real time sent command
Received Information
This display the response that NetAgentA receives from UPS
 Port Information
This is to configure the communication parameter between NetAgentA and UPS.
Parameters are Debug Mode; Port; Speed (Baud), Data Bits;Parity and Stop Bits.
Two encoding formats: ASCII or Hexadecimal.

 Management > Help


This is to help to illustrate each feature/option that NetAgentA offers

 Management > About


 About
It shows NetAgentA’s hardware/firmware and serial number.
 Firmware Update Settings
Default FTP server is set as ftp.icv99.com with its username/password. Click on Update
Now, NetAgentA will connects to the FTP server and upgrade to the latest firmware
version accordingly. Or, it could upgrade per preset time.

To enable NetAgentA’s FTP firmware upgrade, please


download the appropriate firmware version from the
website and upgrade through FTP Client Software.

Update Firmware from FTP Client


-Select on Enable
-Download the appropriate firmware version from website (http://www.megatec.com.tw)
-Unzip the file and known the directory path

Execute ftp + NetAgentA’s IP address


-FTP login

1. Enter username/password that configured on Netility

2. Enter command Is to show available firmware


bin file

3. Enter put command with bin file directory

4. Once complete, enter command quit