NetAgentA Mini Manual-En.1
NetAgentA Mini Manual-En.1
Copyright Information
Copyright © 2018, Mega System Technologies, Inc.
All rights reserved.
Reproduction without permission is prohibited.
Features:
(1) Provide SNMP MIB to monitor & control UPS
(2) Auto-sense 10M /100M/1000M Fast Ethernet Manage and configure via Telnet,
Web Browser or NMS
(3) Support TCP/IP, UDP, SNMP, Telnet,SNTP, PPP, HTTP, HTTPS, SMTP, FTP,
Modbus, BACnet Protocols
(4) Support SSL/TLS, SSH Encryptions
(5) Providing easy setup and upgrade tools via our Netility software
(6) Send SNMP TRAP ; E-mail and SMS for events notification.
(7) Auto email daily UPS history report
(8) Perform graceful shutdown with our ClientMate software
(9) Add-on optional NetFeeler II for temperature, humidity, water, smoke and door
sensor
(10) Add-on optional WiFi dongle for wireless network access
(11) Add-on optional GPRS modem for SMS notification
1.2 Applications
NetAgentA allows UPS to be monitor on network
When the UPS connects with NetAgentA, the system manager could check each and
every UPS condition by a computer with Browser installed. The manager could monitor
and control the UPS by simply input the IP address of the NetAgentA which connects to
the UPS. When there is a power abnormal condition happens, the NetAgentA could also
send the trap information to the system manager to take proper action.
NetAgentA Provides Shutdown Utilities
When a computer install our shutdown software in the network that connects to the
NetAgentA, when UPS is in AC failure condition or Battery Low condition, the software
would close all the files of the operating system and shutdown gracefully. This could avoid
system corrupt when a power disconnection happened.
NetAgentA for Surrounding Monitoring
NetAgentA with USB ports could connect to optional sensor- USB NetFeeler to get the
surrounding temperature/humidity/smoke/fire signals. These information could also be
revealed on the NetAgentA Web page. When there is an abnormal condition happened, it
could also be sent as a trap to the system manager.
Chapter 2. NetAgentA Series
Model Name Package Contents Internal External RJ45 RS232 ENV USB Single Three
Phase Phase
Amber Red
NOTE : When writing firmware, red led alternating flashing, DO NOT remove any power
D5 D4
Green Blue
Power Communication
On Off Flashing
No Sending/Receiving
Normal
Power Data
Red
UPS connection
Flashing Off
Lost Connecting
connection with UPS
Yellow
On On Off
NetAgentA Mini 9
Status
Red
On On On
Power
Chapter 3 Software Installation
ClientMate:
Shutdown OS Software .
Refer to Chapter 6
SMS Server:
SMS notification Softwar.
Refer to Chapter 9
SNMPView :
Multi monitoring Software. Time Server:
Refer to Chapter 7 Time server software
iMConfig:
Muti-configuration Software.
Refer to Chapter 8
If the PC does not executes CD program automatically, please select from File
Managment
Chapter 4. NetAgentA Setting
4.1 Introduction
NetAgentA can be login via web or HyperTerminal with protocol and encryption of
HTTP/HTTPS/SSH/Telnet. Enter the IP address of NetAgentA to configure and monitor
the UPS status.
HTTP
HTTPS
SSH
TELNET
NOTE 1:Each NetAgentA has its unique serial number / MAC address and Password.
This is available on the label of each unit. This helps to identify the card information on
Netility
NOTE 2: NetAgentA with LCD display may obtain the IP info from it.
IP address 192.168.0.70
192 168 0 70
Subnet Mask: 255.255.255.0
192 168 0 1
When NetAgentA IP is known, enter such IP address on the browser to login. If non-LCD
NetAgentA model, install Netility software to find and configure its IP address.
4.3 Netility Installation and Setting
Netility Installation
Netility is tool software that helps the user to search all the available NetAgentA within
network as well as to configure IP address and firmware upgrade. Mount the NetAgentA
Utility CD on CD-ROM and click on Program Installation>Netility>Windows
Netility Software
2. Function
1. Online NetAgentA
List
2.5 Refresh List
2.4 About
When open up Netility , it automatically searches all the available online NetAegntA
within the network with its serial number, IP address, MAC address. Double click on the
specific NetAgentA with valid IP address, it will direct to the NetAgentA’s webpage. (List
refreshes automatically every 2 minutes)
Click on specific NetAgentA , the bottom column shows its hardware , firmware version
and MAC address. It also shows the total NetAgentA number that found by Netility and
selected
Click on NetAgentA
Hardware Version
Firmware Version
2. Click on
Launch Web
User Interface
1.Click on NetAgentA
When select to obtain IP address by DHCP or BOOTP, IP address and other network
parameter will be assign by the network
3. Upgrade message
4. Cancel to exit
2.Click on Download
2.4 About
Here shows the current Netility verison
For example: To shutdown Host 1 (Windows server) and Host 2 (Linux server) after 1
minute when AC power failed.
First, go to UPS Action tab, select event of “AC Power Failed” then select “shutdown Host
1 “ , press on Add. The action will be add in the list. Then the same for Host 2, select event
of “AC Power Failed” and select “shutdown Host 2” from the list and press on Add to be in
the list.
Once action is added, go to Remote Shutdown tab, enter the domain IP for Host 1 and
Host 2, select Telnet or SSH for access and then enter the user name/password of the
server with its shutdown command of the server. For Windows, “shutdown /a “ is the
shutdown command. For Linux, “halt” is the command to shut down. For MAC, it is “sudo
shutdown” as the command.
- Windows : shutdown/?
- Linux : shutdown –help
- MAC : sudo shutdown
Weekly Schedule
This section is to set the time to turn on/off the UPS each day in the week.
Date Schedule
This section is to set the time to turn on/off the UPS on particular days.
The settings here override the settings in Weekly Schedule.
Ethernet
Connection Type
This section is to set communication speed between NetAgentA and Network.
Once click on Apply, NetAgentA will reboot
Stop UPS communication when Ethernet disconnected
This section is to set if to stop UPS communication when NetAgentA disconnects with
Ethernet
Modbus on TCP Device ID:
Enter device ID to read/write data when using Modbus on TCP communication with
Megatec protocol and Modbus Register Table
Dynamic DNS
This is a free service that allows the user to alias a dynamic IP address to a static
hostname. Ensure account/password has been registered from the DNS service provider
Service Provider
Dynamic DNS providers can be select from the list
Domain Name
This is the Domain Name you have created from the above selected DDNS provider
Login Name
This is the Login / Account name that you have created with the selected DDNS provider.
Login Password:
Enter the Password you have assigned to your DDNS Account.
Use external STUN server to get Public IP to register
Choose Yes to ensure that NetAgentA uses the WAN / Public IP to update
the selected DDNS server
If to use iCV99.net as Service Provide which host by Megatec, instruction as below:
1. Ensure NetAgentA is able to connect to Internet. Select icv99.net from the drop down
list of the Service Provider. The Domain Name and Login Name will automatically be
fill-in with serial number of the device. Enter the password of the NetAgentA which is
printed on the NetAgentA label, then click Apply.
1.Select icv99.net
2. Enter password
3. Click Apply
2. If using router, please login to router and direct IP and port number under virtual
server for port forwarding. Kindly refer to router’s manual
Router Configuration
3. After 20 minutes, NetAgentA should be login with its DDNS Domain name
Enter email
Click on Done
PPPoE
Use this option to allow NetAgentA to connect to the Internet directly using your xDSL
modem by PPPoE. Enter the Login name and password to enable the connection. Once
set-up, NetAgentA will connect directly to the Internet , any abnormal connection failure
would also cause to re-dial
Enter Password
Configuration > Wireless LAN
This is to configure NetAgentA Wireless network with compatible USB wireless dongle.
Login to the Wireless Router
(1)SSID : Name it (any)
(2)Authorization:Select WPA2-Personal
(3)WPAEncryption:AES
(4)WPA-PSKKey:Enter any password (8~63 digits ASCII code)
(1)
(2)
(3)
(4)
WPS Button
WPS Setting for the wireless router:
When yellow LED of the NetAgentA is flashing , open up WPS setting page of the
wireless router. With WPS connection mode,
(1)Select ”WPS button”
(2)Click on”Start”
Start WPS Connection
Process
(1)Once NetAgentA is connected with wireless router via WPS, Netility should be
able to find this wireless NetAgentA
(2)Login to NetAgentA’s webpage , under Configuration > Wireless Lan
webpage, it shows
the wireless signal
(With distance of 6-10 meters. Router RT-AC53 still shows with full signal)
At least 8 characters
Trap Notification
Trap Notification
Destination IP Address:
To set receivers IP address for receiving traps sent by NetAgentA. It is valid for up to 8 IP
Addresses.
Accept:
Select the trap type of its SNMP version or Inform from drop down list. When SNMPv3 trap
or SNMPv3 Inform is selected, username/password and authentication information are
required.
Community:
Trap receiver and NetAgentA must be same community. (Default is public)
Trap Type:
Select from PPC MIB or RFC1628 MIB (Default is PPC)
MIB file is available in the CD provided with NetAgentA
Severity:
This section is to set Trap level for each receiver. There are three levels as below
Information: To receive all traps.
Warning: To receive only “warning” and “severe” traps.
Severe: To receive only “severe” traps.
( Please refer to NMS manual for Trap levels.)
Description:
This is to make note for administrator’s reference
Events:
This is to select events for NetAgentA to send traps. Click on Select to show the full Events
List. Click on Test to send test trap to ensure all setting is correct
Send Power Restore and Adaptor Restore Traps for X time(s) in X second(s) Interval.
This is to set number of trap to send in preset second when power restore on NetAgentA.
This is to check if the communication between trap receiver and NetAgentA remains well
or not after power recovers
SNMP Inform Request
This is to set the number of times that the NetAgentA can request a response from the
sending Inform host with a preset value. (Default is 3 times and an interval of 5 seconds)
Device Connected
This section is to set the usage power and connection status of other devices which
connects to the same UPS as NetAgentA uses.
To send email notification when event occurs or data log. Encryption supports are
SSL/TLS/STARTTLS
Email Setting
Email Server:
Enter the address of email server
Email Port:
Email Port that use for sending email
Enable SSL on Email Transmission:
Select SSL type for email transmission
SMS Setting
Send SMS When Event Occurs:
Disable :No SMS Service
Use Local Modem:When GSM modem is connected to NetAgentA directly
(Refer to SMS Modem section for its installation)
Use Remote Service:When GSM modem connects to PC with SMS Server
software installed
(Refer to SMS Server section for SMS Server Software installation)
SMS Server:
If select to use Remote Service to send SMS, then enter the IP address of the SMS
Server.
(The PC that installed SMS Server Software)
SMS Port:
If select to use Remote Service to send SMS, enter the port number that SMS Server uses
for sending SMS. (Port 80 is default)
Account Name:
If select to use Remote Service to send SMS, enter SMS Server’s account name if
required
Password:
If select to use Remote Service to send SMS, enter SMS Server’s password if required
Sending test SMS:
When modem and configuration are ready, enter a mobile number to receive testing SMS
Mobile for Event Log
To set the recipient’s mobile number for SMS notification when event or NetFeeler event
occurs. A total of 8 mobile numbers can be assign.
To set permission for each user account for Web,Telnet and FTP access with up to
8 users. Also to enable/disable specific port for HTTP/HTTPS, Telnet/ SSH and FTP
HTTP/HTTPS
Enter specific port number to access or disable for HTTP, HTTP proxy, HTTPS
HTTP/HTTPS Account
User Name:
To set password for NetAgentA Web access.
Password:
To set password for NetAgentA Web access.
Permission:
To set No Access / Read/ Read&Write)
Permission Rule: At least one user account must be Read/Write
Permission Rule : User name with Read and Write cannot be blank
IP Filter:
Only specific IP address could login to NetAgentA
*.*.*.* means any IP address
Auto Logoff after Idle for minute (s). ( 0 is disabled)
NetAgentA webpage will be logoff automatically if it idles for the preset value.
Telnet/SSH
Enter specific port number to access or disable for Telnet/SSH
Telnet/SSH Account
Same as HTTP account/password settings
This is to duplicate the same settings from HTTP
User Name:
To set password for NetAgentA Telnet access.
Password:
To set password for NetAgentA Telnet access.
Permission:
To set No Access / Read/ Read&Write)
Permission Rule: At least one user account must be Read/Write
Permission Rule : User name with Read and Write cannot be blank
IP Filter:
Only specific IP address could login to NetAgentA
*.*.*.* means any IP address
FTP/FTP-SSL
To select the access between FTP and FTP-SSL with specific port number or to disabled it
FTP/FTP-SSL Account
Same as HTTP account/password settings
This is to duplicate the same settings from HTTP
User Name:
To set password for NetAgentA FTP access.
Password:
To set password for NetAgentA FTP access.
Permission:
To set No Access / Read/ Read&Write)
Permission Rule: At least one user account must be Read/Write
Permission Rule : User name with Read and Write cannot be blank
IP Filter:
Only specific IP address could login to NetAgentA
*.*.*.* means any IP address
SSL Information
NetAgentA supports HTTPS protocol and varies SSL encryptions version for network
connection. User may upload its Public Key and Certification for authentication
HTTPS Protocols
Select the encryption version
SSL v2
SSL v3
SSL v1.0
SSL v1.1
SSL v1.2
Once click on Apply, NetAgentA will reboot
SSL Information
This is to upload the SSL certificate. When both public key and certificate are uploaded to
NetAgentA web server, the communication will be encrypted by SSL
(To communicate via Https, make sure to enable Https port 443.)To create its own public
key and certification, please refer to OpenSSL software in the CD
https://192.168.66.133
:
BACnet
BACNet Device
Configure the device ID and access port number for the NetAgentA when using BACnet
for communication
Notification
Enter the IP address of the PC that to be notify by BACnet software when event occurs
Configuration > SMS Modem
When compatible GPRS modem connects with NetAgentA , it is able to send SMS
notification when event occurs
Modem Setup Procedure
Modem Led
When all done, click on Apply. Modem Information and Status can be check from
Information> SMS Modem Status
Once click on Apply ,NetAgentA will reboot
Send Message
Cellular Phone number:
Enter mobile number
SMS Content(Max.70 Characters):
Enter the SMS content text and select coding. Unicode or Character
Configuration > NetFeeler
NetFeeler is the external optional environmental sensor. It is to detects temperature,
humidity and water. NetFeeler has RF receiver built-in to work with extension sensors
such as smoke, security sensor.
NetFeeler
NetFeeler
Humidity/Temperature Critical value:
To set the lowest and highest critical values for temperature and humidity. NetFeeler will
send a warning message when it detects temperature or humidity values below and above
these settings.
Security Label
NetFeeler may connect up to 7 security sensors that communicate via RF. This section is
to set the location or name of each sensor.
Date/Time
NetAgentA to synchronize with external or internal Time Server for correct date and time.
System Time
System Time(yyyy/mm/dd hh:mmm:ss):
To display the current system time/date of NetAgentA. Or click on Adjust Now to adjust to
the correct time/date automatically
Time Between Automatic Updates:
To set an interval for time synchronization.
Time Server:
Time server can be select from the drop down list , or add other time server manually.
Time Zone(Relative to GMT):
To select its GMT time zone
Language
This page is to set the language interface for NetAgentA.
Interface Language
To set the language of NetAgentA web pages. When first start login to the webpage of
NetAgentA, NetAgentA will auto detects the OS language of the PC and shows the same
language on its web pages. Users may choose the language per preference
Note: Users will have to enable cookies before they use this function.
Email Preference
Select language preference when receive emails and SMS.
Languages supported by NetAgentA
English 繁體中文
Deutsch 簡體中文
Português 한글
Español 日本語
Français Русский
Italiano ไทย
Türkçe Polska
Save/Restore
Save Current Configuration
Click on Save to save the configuration to your PC. The text file will have a default format
of YYYY_MMDD_####.cfg. Administrator permission required.
Restore previous configuration
Use this function to restore a *.cfg configuration that has been saved earlier. Click
Browse… to the location of the file and click Restore.
Reset to factory default
This function will reset all settings to its default value.
Event Log
Event List
It shows record of all events, giving the Date/Time of the event with detailed description of
each. Event can be check on specific date from the calendar
Event census
Here is to present the event statistically on the selected date
Data Log
It records UPS Input Voltage/Output Voltage/ Frequency/ Loading/Capacity/
Temperature..etc in detailed list. When NetFeeler is connected, status will be available
too.
Log Information > Battery Test Log
Debug Information
Command can send automatically by NetAgentA, or manually enter the command to UPS.
Sent Information
This column shows the real time sent command
Received Information
This display the response that NetAgentA receives from UPS
Port Information
This is to configure the communication parameter between NetAgentA and UPS.
Parameters are Debug Mode; Port; Speed (Baud), Data Bits;Parity and Stop Bits.
Two encoding formats: ASCII or Hexadecimal.