AAS 920 376G Telaire Ventostat T8041 T8042 Web 1485169

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

®

®
Ventostat T8041/T8042
Telaire CO2 Duct Probe Transmitters
Telaire is excited to announce to announce a new
generation of Telaire CO2 transmitters targeting
indoor air quality and energy conservation
applications. The Ventostat® T8041/T8042 duct
mount CO2 transmitters offer accuracy and
versatility at an affordable price. This exceptional
product line touts an unobtrusive form factor
that is easy to install, simple to use, and remains
accurate over the expected life of the device
using Telaire’s patented ABC Logic™ (Automatic
Background Calibration) technology.

Features
• Gas permeable, water resistant diffusion filter
• Simple installation (mounting hardware and prevents particulate and water contamination of
instructions included) the sensor

• Two models with different probe lengths to suit a • RoHS compliant


variety of return air duct sizes
• Lifetime calibration guarantee (ABC Logic™ on)
• Offers standard 0-10 volt or 0-5 volt output
Applications
• Patented absorption infrared/gas sensing engine
provides high accuracy in a compact low-cost CO2 transmitters can be used in a broad range
package of applications including air quality monitoring
in buildings. CO2 concentration levels in
• Patented ABC Logic™ self-calibration system buildings are monitored to provide an indication
eliminates the need for manual calibration in most of occupancy and to drive a ventilation control
applications strategy. An effective DCV (Demand Controlled
Ventilation) strategy will conserve energy and
maintain indoor air quality.

Amphenol
Advanced Sensors
Installation Instructions
1. Before installing the sensor, note the direction of the airflow.
2. Drill/cut one [38.10 mm] 1 ½” hole. Punch/drill two [3.17 mm]
1/8” holes for mounting screws.
3. Slide sensor into [38.10 mm] 1 ½” hole and secure with
screws.
4. Connect the conduit and make necessary wire connections.
5. Install lid, and ensure it snaps into place.

24 AWG
24 VAC

Installation Drawing for T8041 and T8042 (T8042 Installation shown)


Dimensional Drawings

143.66 5.66

77.46 3.05

31.50 [1.24]

77.46 3.05

103.77 4.09
40.19 1.58

T8041 Dimensions (All Dimensions are in MM [Inch].)

143.66 5.66

77.47 3.05

77.46 3.05 31.50 [1.24]

40.19 1.58

205.08 8.07

T8042 Dimensions (All Dimensions are in MM [Inch].)


Model T8041/T8042 Specifications
Technology
The technology is based on the absorption of light
in a gold-plated reflective light pipe or waveguide
diffusion gas chamber. A gas permeable PTFE filter
prevents particulate and water contamination of the
sensor. Light is absorbed in proportion to the CO2
concentration and the remaining light is measured and
Certifications
converted into an analog signal.
RoHS compliance
Measurement Range FCC Part 15,B
0-2000 PPM factory calibrated CE EMC EN61000-6-2, class B, criterion B*
*Deviations of the output signal may occur during strong
Part Numbers electrical fast transients on the power line
T8041 (0-10V), T8041-5V (0-5V), T8042 (0-10V), T8042- Enclosure flammability rating – UL94-5VA
5V
(0-5V) Warm-up Time
< two minutes (operational); 10 minutes to achieve maximum
Duct Air Velocity accuracy
0 to 1500 ft/min (0 to 450 meter/min)
Operating Conditions
Temp Dependence • Temperature: 0ºC to 50ºC (32ºF to 122ºF)
0.2% of full scale per ºC • Humidity: 0 to 95% relative humidity, non-condensing

Stability Storage Conditions


<2% of full scale over the life of the sensor (10 years -40ºC to 70ºC (-40ºF to 158ºF)
typical)
Output
*Accuracy • Analog: 0 to 10V or 0 to 5V
±40 ppm +3% of reading @ 22ºC (72ºF) when compared
with a factory certified reference Power Supply Requirements
18 to 30 VAC RMS, 50/60 Hz or 18 to 42 VDC, polarity
Non-linearity protected.
<1% of full scale @ 22ºC (72ºF)
Power Consumption
Pressure Dependence Typical values (1.65 watts peak, 0.65 watts avg.
0.13% of reading per mm of mercury @ 42 VDC)
*Note: The Telaire product line offers patented ABC Logic™
*Calibration software for self-correction of drift to better than ±20 ppm per
Sensors will be calibrated at zero and span at the year. The system is virtually free of maintenance and typically
factory. Calibration in the field will not be required. has a lifetime of more than 10 years.
Sensors will be shipped with ABC Logic™ turned on.
Physical Requirements
Response Time Dimensions:
Three minutes typical for a 90% step change at low Probe Length : T8041 4.09 in (10.38 cm)
duct speeds T8042 8.07 in (20.51 cm)
Probe Diameter : 1.24 in (3.15 cm)
Sampling Rate Junction Box Depth : 1.58 in (4.02 cm)
Every two seconds Junction Box H x L: 3.05 in x 3.05 in (7.46 cm x 7.46 cm)
Color: Grey (GY6275)

Installation Kit
Included with the transducer are wire nuts, mounting screws
and installation instructions.

Amphenol www.amphenol-sensors.com
© 2014 Amphenol Corporation. All Rights Reserved. Specifications are subject to change without notice.

Advanced Sensors Other company names and product names used in this document are the registered trademarks or
trademarks of their respective owners.

AAS-920-376G-03/2014
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Amphenol:
T8042 T8041 T8041-5V T8042-5V

You might also like