1 CDL Toshiba R32 Technical Handbook V10 2020

Download as pdf or txt
Download as pdf or txt
You are on page 1of 62

Pocket Handbook

Of Technical Data
For the TOSHIBA
Range of Products

www.cdlweb.info
Cool Designs Ltd makes every effort to ensure that the information provided within this publication is correct and error free, however we cannot guarantee that it is free of inaccuracies, errors, or
P a g e 1 | 62
omissions. Users should seek to clarify this information for themselves prior to basing any decisions upon such information. TH R32 V10
The equipment listed within this publication are designed for R32 Refrigerant.

R32 refrigerant is a “Mildly Flammable” refrigerant and is categories as being an A2L refrigerant.

Toshiba Indoor units designed for R32 can be coupled to suitable Toshiba R32 or R410A outdoor
units, R410A indoor units CANNOT BE CONNECTED TO R32 outdoor units.

Provide mechanical protection for all installed pipe work, keep joints to a minimum, flare
connections at the outdoor unit is acceptable, it is also acceptable to make the final joint at the
indoor unit via a flare connection, additional joints within the building should be of a
braze type connection.

When working with R32, make sure the area is well vented, if the equipment is located in a
basement area, or a below ground floor “Well area”, utilise additional means of ventilation.

Extract from RAV-GP range installation manual.

The equipment listed is designed to be installed by a qualified f-gas registered engineer.

It is strongly recommended that the installing engineer reads the installation manual provided with
the equipment, before proceeding.

Extract from RAV-GP range installation manual.

P a g e 2 | 62
Index Page

Mechanical Specification RAS R32 4


Performance & Electrical Specification RAS R32 Single Splits 5
Performance & Electrical Specification RAS R32 Multi Splits 5
Acoustic Data RAS Outdoor Units 6
Acoustic Data RAS Indoor Units 6
RAS Multi-Split Combination Examples 7
RAS Auto Restart 8
RAS Fault codes 9
Mechanical Specification RAV DI/SDI R32 10
Performance & Electrical Specification RAV DI/SDI R32 Single Splits 10
Performance & Electrical Specification RAV DI/SDI R32 Multi Splits 11
Acoustic Data RAV DI/SDI Indoor Units 11
Acoustic Data RAV DI/SDI Outdoor Units 11
Replacement Technology 12
Refrigerant Replacement 13
R32 Quantity in Occupied Spaces 14
RAV DI/SDI Twin Split 15
RAV DI/SDI Triple Split 17
RAV DI/SDI Quad Split 19
RAV DI/SDI Multi Split Wiring 20
Common Sensor Characteristics 21
RAV###KRT Indoor Trouble Shooting 22
RAV Indoor units Lamp Indication 24
Fault Codes All Commercial & VRF Systems 28
TCC-Net Central Controller Error Detection 42
“Black Pear” Error Code Cross Reference 42
TCC Link Local Hard-Wired Controller Guidelines 44
System Configuration Menu 45
Optional Control Accessories 48
TCC-Net Control 50
DI/SDI/VRF Control Configuration 53
RAV DI/SDI Data Retrieval Guide 54
RAV DI/SDI Network Addressing 55
RAV DI/SDI Integration with AI System 98
RAV DI/SDI Temperature Sensing 59
Notes 60
Additional Publications 61
Contact Details 62

P a g e 3 | 62
Mechanical Specifications - RAS R32 Outdoor Units

Pipe Sizes Min/Max Max Pre- Add Base


Dimensions Weight
(“) Pipe Sep Height Charge Charge Charge
Model
Separation
(mm) (kg)
Liquid Suction (m) (+/-) (m) (m) (g/m) (kg)
RAS Outdoor Units
RAS-05BAVG-E 0.40
21
RAS-07BAVG-E 0.40
3/8 2/15 N/A 530x660x240
RAS-10BAVG-E1 0.43
23
RAS-13BAVG-E1 0.43
RAS-16BAVG-E 0.80
34
RAS-18BAVG-E 1/2 2/20 20 0.88 550x780x290
RAS-24BAVG-E 1.08 38
RAS-05J2AVG-E
0.40 22
RAS-07J2AVG-E
3/8 2/15 N/A 530x660x240
RAS-10J2AVG-E 12 0.43 23
RAS-13J2AVG-E 0.46 24
RAS-16J2AVG-E 15 0.62 30
RAS-18J2AVG-E 1/2 2/20 0.88 550x780x290 34
RAS-24J2AVG-E 1.08 38
RAS-10PAVSG-E 0.51
1/4 3/8 28
RAS-13PAVSG-E 0.67
RAS-16PAVSG-E 2/20 0.8 550x780x290
20
RAS-18PAVSG-E 34
1/2 1.1
RAS-22PAVSG-E
RAS-24PAVSG-E 15 1.14 43
RAS-10PAVPG-E
3/8 2/25
RAS-13PAVPG-E 1.0 38
RAS-16PAVPG-E 1/2
630x800x300
RAS-2M10U2AVG-E 2 X 3/8 2/20* 10 20 N/A 0.85 38
RAS-2M14U2AVG-E
3/8x2 2/30* 30 1.02 44
RAS-2M18U2AVG-E N/A
RAS-3M18U2AVG-E 3/8x2+1/2x1 2/50* 50 1.05 46
RAS-3M26U2AVG-E 3/8x1+1/2x2
3/70* 1.92 72
RAS-4M27U2AVG-E 3/8X2+1/2x2 15 40 20 890x900x320
RAS-5M34U2AVG-E 3/8X3+1/2X2 3/80* 2.39 78

*RAS Multi Pipe Configuration


Minimum Maximum
Leg Leg Accumulative Liquid
Model Length Length Line Length (m)
(Legs A+B+C+D+E)
(m) (m)
RAS-2M10U2AVG-E 2 15 20
RAS-2M14U2AVG-E 2 20 30
RAS-2M18U2AVG-E 2 20 30
RAS-3M18U2AVG-E 2 25 50
RAS-3M26U2AVG-E 3 25 70
RAS-4M27U2AVG-E 3 25 70
RAS-5M34U2AVG-E 3 25 80
Minimum quantity of Indoors = 2

TOSHIBA TOSHIBA TOSHIBA TOSHIBA

P a g e 4 | 62
Performance & Electrical Specifications - RAS R32 Single Splits

Capacity Max.
Energy Suggested
(kW) Power Soft Running Interconnect
Model Rating Phase Fuse Size
To Start Current Cable
(A) #
Cool Heat (A)
Cool/Heat
RAS Split Systems
RAS-05BAVG-E 1.5 2.0 A+/A+ 2.40 10
RAS-07BAVG-E 2.0 2.5 A+/A+ 3.25 10
RAS-10BAVG-E1 2.5 3.2 A+/A+ 4.20 10
RAS-13BAVG-E1 3.3 3.6 A+/A+ 5.50 10
RAS-16BAVG-E 4.6 5.4 A++/A+ 7.19 16
RAS-18BAVG-E 5.0 5.4 A++/A+ 7.50 16
RAS-24BAVG-E 6.5 7.0 A++/A+ 10.55 16
RAS-05J2AVG-E 1.5 2.0 A++/A+ 2.40 10
RAS-07J2AVG-E 2.0 2.5 A++/A+ 3.25 10
RAS-10J2AVG-E 2.5 3.2 A++/A+ 4.20 10
RAS-13J2AVG-E 3.3 3.6 A++/A+ Indoor/ 5.50 10
RAS-16J2AVG-E 4.2 5.0 A++/A+ 1Ph + N Outdoor Yes 7.19 16 3C+ E
RAS-18J2AVG-E 5.0 5.4 A++/A+ 7.5 16
RAS-24J2AVG-E 6.5 7.0 A++/A+ 10.55 16
RAS-10PAVSG-E 2.5 3.2 A++/A++ 3.97 10
RAS-13PAVSG-E 3.5 4.2 A++/A++ 5.22 10
RAS-16PAVSG-E 4.6 5.5 A++/A+ 7.10 16
RAS-18PAVSG-E 5.0 6.0 A++/A+ 8.05 16
RAS-22PAVSG-E 6.1 7.0 A++/A+ 9.30 16
RAS-24PAVSG-E 7.0 8.0 A++/A+ 11.30 16
RAS-10PAVPG-E 2.5 3.2 A+++/A+++ 3.40 10
RAS-13PAVPG-E 3.5 4.0 A+++/A+++ 4.01 10
RAS-16PAVPG-E 4.5 4.5 A+++/A+++ 6.44 16
Ambient Range; Cooling -15oC to +46oC, Heating -15oC to +24oC
# Suggested fuse sizes are for guidance only, the electrical installation must be completed in-line with current electrical regulations, BS 7671:2018+A1, 2020 – 18th Edition, IET.

Performance & Electrical Specifications - RAS R32 Multi Splits

Max.
Capacity (kW) Energy Suggested
Min-Max Power Soft Running Interconnect
Model Rating Phase Fuse Size
Indoors To Start Current Cable
Cool Heat Cool/Heat (A) #
(A)
RAS Multi Systems
RAS-2M10U2AVG-E 2–2 1.0 – 3.9 1.0 – 4.9 A++/A++ 4.17 10
RAS-2M14U2AVG-E 2–2 1.6 – 4.9 1.3 – 5.2 A++/A++ 4.87 10
RAS-2M18U2AVG-E 2–2 1.7 – 6.2 1.3 – 7.5 A++/A++ 6.96 16
RAS-3M18U2AVG-E 2–3 2.4 – 6.5 1.9 – 8.0 A++/A++ 1Ph + N Outdoor Yes 8.79 16 3C + E
RAS-3M26U2AVG-E 2–3 4.1 – 9.0 2.0 – 11.2 A++/A++ 11.67 16
RAS-4M27U2AVG-E 2–4 4.2 – 9.3 2.9 – 11.7 A++/A++ 13.09 20
RAS-5M34U2AVG-E 2–5 3.7 – 11.0 2.7 – 14.0 A++/A+ 13.64 20
Ambient Range; Cooling -10oC to +46oC, Heating -20oC to +24oC
# Suggested fuse sizes are for guidance only, the electrical installation must be completed in-line with current electrical regulations, BS 7671:2018+A1, 2020 – 18th Edition, IET.

P a g e 5 | 62
Acoustic Data – RAS Outdoor / Indoor Units

RAS Outdoor Units RAS Indoor Units

Cool Heat High Med Low


Model Model
dB(A) dB(A) dB(A) dB(A) dB(A)
RAS-05BAVG-E 48 50 RAS-B05BKVG-E 37 - 22
RAS-07BAVG-E 48 50 RAS-B07BKVG-E 38 - 23
RAS-10BAVG-E1 49 51 RAS-B10BKVG-E 39 - 24
RAS-13BAVG-E1 50 51 RAS-B13BKVG-E 42 - 24
RAS-16BAVG-E1 50 52 RAS-B16BKVG-E 43 - 25
RAS-18BAVG-E1 50 52 RAS-B18BKVG-E 48 - 32
RAS-24BAVG-E1 55 55 RAS-B24BKVG-E 48 - 35
RAS-05J2AVG-E 46 48 RAS-B05J2KVG-E 37 - 19
RAS-07J2AVG-E 46 48 RAS-B07J2KVG-E 38 - 20
RAS-10J2AVG-E 48 50 RAS-B10J2KVG-E 39 - 21
RAS-13J2AVG-E 48 50 RAS-B13J2KVG-E 42 - 21
RAS-16J2AVG-E 49 51 RAS-B16J2AVG-E 43 - 22
RAS-18J2AVG-E 50 52 RAS-B18J2KVG-E 48 - 32
RAS-24J2AVG-E 55 55 RAS-BJ2KVG-E 48 - 32
RAS-10PAVSG-E 46 47 RAS-B10PKVSG-E 39 - 24
RAS-13PAVSG-E 48 50 RAS-B13PKVSG-E 39 - 24
RAS-16PAVSG-E 49 52 RAS-B16PKVSG-E 43 - 26
RAS-18PAVSG-E 49 52 RAS-B18PKVSG-E 44 - 31
RAS-22PAVSG-E 53 52 RAS-B22PKVSG-E 46 - 34
RAS-24PAVSG-E 53 53 RAS-B24PKVSG-E 48 - 35
RAS-10PAVPG-E 46 47 RAS-B10U2FVG-E 39 - 26
RAS-13PAVPG-E 48 50 RAS-B13U2FVG-E 40 - 27
RAS-16PAVPG-E 49 50 RAS-B18U2FVG-E 60 - 34
RAS-2M10U2AVG-E 45 46 RAS-B10J2FVG-E 39 - 26
RAS-2M14U2AVG-E 45 46 RAS-B13J2FVG-E 40 - 27
RAS-2M18U2AVG-E 47 50 RAS-B18J2FVG-E 47 - 34
RAS-3M18U2AVG-E 47 50 RAS-B10PKVPG-E 44 - 20
RAS-3M26U2AVG-E 47 49 RAS-B13PKVPG-E 45 - 20
RAS-4M27U2AVG-E 47 49 RAS-B16PKVPG-E 46 - 22
RAS-5M34U2AVG-E 51 55 RAS-M10U2MUVG-E 37 - 30
RAS-M13U2MUVG-E 38 - 30
RAS-M16U2MUVG-E 40 - 31
RAS-M07U2DVG-E 35 - 27
RAS-M10U2DVG-E 35 - 27
RAS-M13U2DVG-E 37 - 27
RAS-M16U2DVG-E 35 - 25
RAS-M22U2DVG-E 38 - 32
RAS-M24U2DVG-E 39 - 33
Note: Sound measured in Pressure dB(A) Note: Sound measured in Pressure dB(A)

P a g e 6 | 62
RAS Multi-Split System Combination Examples
Indoor Unit Size & Duty
Outdoor Unit Unit 1 Unit 2 Unit 3 Unit 4 Unit 5
05 (2.0kw) 05 (2.0kw)
07 (2.3kw) 05 (1.7kw)
RAS-2M10U2AVG-E 10 (2.67kw) 05 (1.33kw)
4.0 kW 07 (2.0kw) 07 (2.0kw)
10 (2.39kw) 07 (1.61kw)
10 (2.0kw) 10 (2.0kw)
05 (2.0kw) 05 (2.0kw)
07 (2.7kw) 05 (2.0kw)
10 (3.73kw) 05 (1.87kw)
13 (4.0kw) 05 (1.6kw)
RAS-2M14U2AVG-E 07 (2.7kw) 07 (2.7kw)
4.4 kW 10 (3.34kw) 07 (2.26kw)
13 (3.64kw) 07 (1.96kw)
10 (2.8kw) 10 (2.8kw)
13 (2.3kw) 10 (2.1kw)
13 (2.2kw) 13 (2.2kw)
05 (2.0KW) 05 (2.0KW)
07 (2.7KW) 05 (2.0KW)
10 (4.0KW) 05 (2.0KW)
13 (4.86KW) 05 (1.94KW)
16 (4.99KW) 05 (1.81KW)
07 (2.7KW) 07 (2.7KW)
10 (3.94KW) 07 (2.76KW)
13 (4.42KW) 07 (2.95KW)
16 (4.73KW) 07 (2.07KW)
10 (3.4KW) 10 (3.4KW)
13 (3.84KW) 10 (2.96KW)
16 (4.18KW) 10 (2.62KW)
13 (3.4KW) 13 (3.4KW)
16 (3.75KW) 13 (3.05KW)
16 (3.4KW) 16 (3.4KW)
05 (2.0kw) 05 (2.0kw) 05 (2.0kw)
RAS-3M18U2AVG-E
07 (2.7kw) 05 (2.0kw) 05 (2.0kw)
6.8 kW
10 (3.4kw) 05 (1.7kw) 05 (1.7kw)
13 (3.78kw) 05 (1.51kw) 05 (1.51kw)
16 (3.94kw) 05 (1.43kw) 05 (1.43kw)
07 (2.48kw) 07 (2.48kw) 05 (1.84kw)
10 (3.13kw) 07 (2.11kw) 05 (1.56kw)
13 (3.51kw) 07 (1.89kw) 05 (1.40kw)
16 (3.67kw) 07 (1.80kw) 07 (1.33kw)
10 (2.72kw) 10 (2.72kw) 05 (1.36kw)
13 (3.09kw) 10 (2.47kw) 05 (1.24kw)
16 (3.25kw) 10 (2.37kw) 05 (1.81kw)
13 (2.83kw) 13 (2.83kw) 05 (1.13kw)
16 (2.99kw) 13 (2.72kw) 05 (1.09kw)
07 (2.26kw) 07 (2.27kw) 07 (2.27kw)
10 (2.84kw) 07 (1.98kw) 07 (1.98kw)
13 (3.26kw) 07 (1.76kw) 07 (1.76kw)
16 (3.64kw) 07 (1.59kw) 07 (1.59kw)
***Above duty’s (kw) are in the heating mode.***

The above is an example only, for full combination tables covering up to 5 indoor units to 1 outdoor, please contact Cool Designs Technical Support.

P a g e 7 | 62
RAS – Auto Restart Function

The indoor unit is equipped with an automatic restart facility that allows the unit to restart, at the last set operating conditions, after a power
failure. The operation will resume without warning three minutes after power is restored.
This feature is not set up when these systems are shipped from the factory, therefore it will need to be activated by the installing company.

Generally, the process is the same for all RAS products since approx. 2001 and is as follows:

To initiate auto restart:

1. Turn the power on. Green/White, On/Off light will flash.


2. Set the system to operate using the remote controller. Green/White On/Off light will be on constantly.
3. Press and hold down the Operation/Reset button for more than three seconds. (Less than 10 Seconds.)
4. The indoor unit will bleep three times to acknowledge set up. In most cases the green light changes to orange.
5. The system will continue to operate during this set up.
6. After set up the system may be stopped using the remote controller.

To cancel auto restart:

1. The system is operating. Green/White, On/Off light will be on constantly.


2. Stop the system operating using the remote controller. Green/White On/Off light will extinguish.
3. Press and hold down the operation / reset button for three seconds.
4. The indoor unit will bleep three times to acknowledge cancellation.
5. The system will have stopped operating.

This feature cannot be set if the timer is in operation.


The louver will not swing, if it was previously set, when the system auto restarts.

P a g e 8 | 62
Fault Codes – RAS Series

Do Not turn off the power supply before reading the fault codes, doing so will clear the diagnostic memory. Caution
must be taken when removing the access covers as high voltages are present.

Fault codes are displayed through the LEDs flashing at 5 times per second. Note, the green LED will flash once per
second when the system is initially powered.

More specific codes may be obtained, while in the fault mode through the wireless controller
1. Press CHK (12) to enter service mode.

2. Navigate through TEMP  buttons until all LEDs flash (From 1 to 33),
accompanied by the internal buzzer – compare the displayed
code with the table below.

3. Press CLEAR button to clear the existing fault code (controller displays 7F)

4. Press ON/OFF button to exit service mode.

Block distinction Operation of diagnostic function


Check Check
Block Cause of Operation Air Conditioner status Display flashing error
Code code
TA Sensor open or short circuit or
0C indoor PCB
Operation continues Flashes when error is
TC Sensor open or short circuit or
00 Indoor PCB 0d indoor PCB
detected

11 Indoor fan motor or PCB All OFF


12 Indoor PCB Depend on cause of failure. Depend on cause of failure.
Serial signal and Indoor to outdoor
Indoor unit operates, Flashes when error is
01 connecting 04 communication error, (includes
outdoor unit stops. detected.
cable compressor thermostat).
Over current on inverter circuit,
14 Inverter PCB or Compressor.
All OFF
Flashes after error is
Compressor position detection detected 8 times.
16 error or short circuit of All OFF
compressor windings.
Current detection circuit of
17 inverter PCB error.
All OFF
TE or TS sensor open or short Flashes after error is
18 circuit or outdoor PCB.
All OFF detected 4 times.
02 Outdoor PCB
TD sensor open or short circuit or
19 outdoor PCB.
All OFF
Flashes after error is
1A Outdoor fan error or PCB All OFF detected 8 times.
Record error after detected
TO sensor open or short circuit or
1b outdoor PCB.
Operation continues. 4 times but does not flash
display.
Compressor drive circuit, voltage, Flashes after error is
1C current, frequency abnormal.
All OFF detected 8 times.
Indoor to outdoor
communication error,
Indoor unit operates, Flash when error
07 Indoor/outdoor PCB,
outdoor unit stop detected.
interconnecting cable,
compressor thermostat
Compressor does not rotate, lost Flash after error is
“Others” 1d All OFF
phase, neutral, wiring. detected 8 times.
03 including
Discharge temperature exceeds Flashes after error is
compressor 1E All OFF
117oC detected 4 times.
Compressor high current, power Flash after error is
1F All OFF
supply, compressor, Inverter PCB detected 8 times.
Return signal of outdoor unit
Indoor unit operates Flashes when error is
21 lost, power, indoor/outdoor PCB,
outdoor unit stops detected 11 times.
high temperature on TE, TC.

P a g e 9 | 62
Mechanical Specifications - DI / SDI R32 Single Splits

Max
Pipe Sizes Min/Max Pre- Add Base
height Dimensions Weight
Model Pipe Sep. Charge charge charge
Liquid Suction separation (mm) (kg)
(m) (m) (g/m) (kg)
(+/-) (m)
Commercial Range
RAV-GM301ATP-E 3/8 0.63 29
2/20 15
RAV-GM401ATP-E 1/4 20 34
1/2 10 550X780X290
RAV-GM561ATP-E 0.9 40
5/30
RAV-GM801ATP-E 20 42
35
RAV-GM901ATP-E 1.3 630x800x300 47
RAV-GM1101AT(8)P-E 3/8 5/8
5/50 2.1 890X900X320 68
RAV-GM1401AT(8)P-E 35
RAV-GM1601AT(8)P-E 30 2.4 1340x900x320 94
RAV-GM2241AT8-E
1/2 1 1/8 5/60 80 5.0 1550x1010x370 142
RAV-GM2801AT8-E
RAV-GP561ATP-E 1/4 1/2 30 20 20 1.35 630x799x299 45
3/50
RAV-GP801ATP-E 1.9 1050x1010x370 74
RAV-GP1101AT-E 3.1 1550x1010x370 104
RAV-GP1101AT8-E 2.6 1340x900x320 95
3/8 5/8 30 35
RAV-GP1401AT-E 3/75 3.1 1550x1010x370 104
RAV-GP1401AT8-E
2.6 1340x900x320 95
RAV-GP1601AT8-E

Performance & Electrical Specifications - DI / SDI R32 Single Splits

Ambient Max.
Capacity kW Suggested
Range °C Power Soft Running Interconnect
Model Phase Fuse Size
To Start Current Cable
(A)
(A) #
Cool Heat Cool Heat
Commercial Range
RAV-GM301ATP-E 2.50 3.40 3.75
10
RAV-GM401ATP-E 3.60 4.00 4.64
RAV-GM561ATP-E 5.00 5.30 7.93
1Ph + N 16
RAV-GM801ATP-E 6.70 7.70 10.40
RAV-GM901ATP-E 8.00 9.00 17.00 20
RAV-GM1101ATP-E 9.50 11.20 15 to -15 14.20 20
RAV-GM1101AT8P-E 9.50 11.20 46 to -15 3Ph+N 4.75 10
RAV-GM1401ATP-E 12.00 12.80 1Ph + N 20.75 32
RAV-GM1401AT8P-E 12.00 12.80 3Ph+N 6.90 16
RAV-GM1601ATP-E 14.00 16.00 1Ph + N 29.00 32
Outdoor Yes 3C + E
RAV-GM1601AT8P-E 14.00 16.00 16.10 20
RAV-GM2241AT8-E 20.00 22.40 3Ph + N 9.52 16
15 to -20
RAV-GM2801AT8-E 23.50 27.00 13.03 20
RAV-GP561ATP-E 5.30 5.60 7.66 16
RAV-GP801ATP-E 7.10 8.00 52 to -15 15 to -27 1Ph + N 7.01 16
RAV-GP1101AT-E 10.00 11.20 10.43 20
RAV-GP1101AT8-E 10.00 11.20 46 to -15 15 to -20 3Ph + N 4.52 10
RAV-GP1401AT-E 12.50 14.00 52 to -15 15 to -27 1Ph + N 14.55 25
RAV-GP1401AT8-E 12.50 14.00 6.03 16
46 to -15 15 to -20 3Ph + N
RAV-GP1601AT8-E 14.00 16.00 7.55 16
# Suggested fuse sizes are for guidance only, the electrical installation must be completed in-line with current electrical regulations, BS 7671:2018+A1, 2020 – 18th Edition, IET.

P a g e 10 | 62
Electrical Specifications - DI / SDI R32 Multi Splits

Inter-
Power
Model Outdoor Twin Indoor Triple Indoor Quad Indoor Phase Connecting
To
Cable

Commercial Range
RAV-GM561ATP-E RAV-RM301##-E
RAV-GM801ATP-E RAV-RM401##-E N/A 1Ph-N
RAV-GM901ATP-E tbc N/A
RAV-GM1101ATP-E RAV-RM561##-E RAV-RM301##-E
RAV-GM1101AT8P-E RAV-RM561##-E RAV-RM301##-E 3Ph+N
RAV-GM1401ATP-E RAV-RM801##-E RAV-RM401##-E RAV-RM301##-E 1Ph-N
RAV-GM1401AT8P-E RAV-RM801##-E RAV-RM401##-E RAV-RM301##-E 3Ph+N
RAV-GM1601ATP-E RAV-RM801##-E RAV-RM561##-E RAV-RM401##-E 1Ph+N Outdoor 3C+E
RAV-GM1601AT8P-E RAV-RM801##-E RAV-RM561##-E RAV-RM401##-E
RAV-GM2241AT8-E RAV-RM1101##-E RAV-RM801##-E RAV-RM561##-E 3Ph+N
RAV-GM2801AT8-E RAV-RM1101##-E RAV-RM801##-E RAV-RM561##-E
RAV-GP561ATP-E RAV-RM301##-E
N/A
RAV-GP801ATP-E RAV-RM401##-E N/A
1Ph-N
RAV-GP1101ATP-E RAV-RM561##-E RAV-RM301##-E
RAV-GP1401ATP-E RAV-RM801##-E RAV-RM401##-E RAV-RM301##-E

Acoustic Data – DI/SDI Indoor Units

High Med Low High Med Low


Model Indoor Model Indoor
dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
Commercial Range
RAV-RM301KRTP-E 40 34 29 RAV-RM561BTP-E 33 29 25
RAV-RM401KRTP-E 41 36 30 RAV-RM801BTP-E 34 30 26
RAV-RM561KRT-E 42 39 36 RAV-RM901BTP-E 37 33 30
RAV-RM801KRT-E 45 41 35 RAV-RM1101BTP-E 40 36 33
RAV-RM901KRT-E 47 41 35 RAV-RM1401BTP-E 40 36 33
RAV-RM561UTP-E 32 29 28 RAV-RM1601BTP-E 40 36 33
RAV-RM801UTP-E 35 31 28 RAV-RM401CTP-E 37 35 28
RAV-RM901UTP-E 40 36 33 RAV-RM561CTP-E 37 35 28
RAV-RM1101UTP-E 43 38 33 RAV-RM801CTP-E 41 36 29
RAV-RM1401UTP-E 44 38 34 RAV-RM901CTP-E 42 38 30
RAV-RM1601UTP-E 45 40 36 RAV-RM1101CTP-E 44 38 32
RAV-RM301MUT-E 38 36 30 RAV-RM1401CTP-E 46 41 35
RAV-RM401MUT-E 41 36 32 RAV-RM1601CTP-E 46 42 36
RAV-RM561MUT-E 44 39 35
RAV-RM301SDT-E 39 36 33
Note; Measured in Pressure Db(A)
RAV-RM401SDT-E 39 36 33
RAV-RM561SDT-E 45 40 36

Acoustic Data – DI/SDI Outdoor Units.

Cooling Heating Cooling Heating Cooling Heating


Model Outdoor Model Outdoor Model Outdoor
dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)

Commercial Range
RAV-GM301ATP-E 46 47 RAV-RM401ATP-E 49 50 RAV-RM561ATP-E 46 48
RAV-RM801ATP-E 48 52 RAV-GM901ATP-E 51 52 RAV-RM1101ATP(8)-E 54 57
RAV-RM1401ATP(8)-E 54 57 RAV-GM1601ATP(8)-E 53 55 RAV-GM2241AT8-E 58 60
RAV-GM2801AT8-E 61 63

RAV-GP561ATP-E 46 48 RAV-GP801AT-E 46 48 RAV-GP1101AT-E 49 50


RAV-GP1401AT-E 50 51
Note; Measured in Pressure Db(A)

P a g e 11 | 62
Refrigerant Replacement Technology.

Existing piping connection with different diameter gas and liquid line is possible using the criteria detailed below.

Toshiba Digital and Super Digital R410A and R32 outdoor units have factory fitted filters installed which enables the
reuse of existing pipework.

The existing pipework MUST be in good condition and have a wall thickness on a minimum 1mm.

When utilising R32 equipment, any joints within the building MUST be braze type, the final connection to the indoor
unit can be of the flare type, all pipework MUST be mechanically protected.

Liquid Pipe Size in “ 1/4 (STD) 3/8 (1-size larger)


Gas Pipe Size in “ 3/8 (STD) 1/2 (1-size larger) 3/8 (STD) 1/2 (1-size larger)
Length Pre- Length Pre- Length Pre- Length Pre-
Maximum Pipe Distance charged charged charged charged
m m m m m m m m
RAV-DI
Series 4 – R410A SM30* 20 15 20 15 13 7.5 13 7.5
Series 1 – R32

Liquid Pipe Size in “ 1/4 (STD) 3/8 (1-Size larger)


Gas Pipe Size in “ 3/8 (1-Size larger) 1/2 (STD) 5/8 (1-Size larger) 1/2 (STD) 5/8 (1-Size larger)
Length Pre- Length Pre- Length Pre- Length Pre- Length Pre-
Maximum Distance charged charged charged charged charged
m m m m m m m m m m
RAV-DI SM/RM40* 20 15 20 15 20 15 13 7.5 13 7.5
Series 2 – R410A
SM/RM56* 30 20 30 20 20 10 20 10
Series 1 – R32
RAV-SDI SP/GP40* 30 20 30 20 30 20 20 10 20 10
Series 4 – R410A
SP/GP56* 50 20 50 20 20 10 20 10
Series 1 – R32

Liquid Pipe Size in “ 1/4 (1-Size smaller) 3/8 (STD) 1/2 (1-Size larger)
Gas Pipe Size in “ 1/2 (1-Size smaller) 5/8 (STD) 1/2 (1-Size smaller) 5/8 (STD) 3/4 (1-Size larger) 5/8 (STD) 3/4 (1-Size larger)
Length Pre- Length Pre- Length Pre- Length Pre- Length Pre- Length Pre- Length Pre-
Maximum Distance charged charged charged charged charged charged charge
m m m m m m m m m m m m m m
RAV-DI SM/RM80* 20 20 20 20 30 20 30 20 30 20
Series 4 – R410A SM/GM110* 50 30 50 30 25 15 25 15
Series 1 – R32 SM/GM140* 50 30 50 30 25 15 25 15
RAV-DI
SM160* 50 30 50 30 25 15 25 15
Series 3 – R410A
RAV-SDI SP/GP80* 30 20 30 20 50 30 50 30 50 30
Series 4 – R410A SP/GP110* 75 30 75 30 25 15 25 15
Series 1 – R32 SP/GP140* 75 30 75 30 25 15 25 15

Liquid Pipe Size in “ 1/2 (STD) 5/8 (1-size larger) Code


Gas Pipe Size in “ 7/8 (1-Size smaller) 1- 1/8 (STD) 7/8 (1-Size smaller) 1- 1/8 (STD) Smaller pipe sizes (Performance capacity is
reduced due to the effect of the gas pipe size
Length Pre- Length Pre- Length Pre- Length Pre- being smaller than the standard – 1-size
Maximum Distance charged charged charged charged smaller)
m m m m m m m m Normal pipe size (STD)
RAV-DI GM224* 60 30 60 30 50 20 50 20 Larger pipe size (1-size larger)
Series 1 R32 GM280* 60 30 60 30 50 20 50 20 Not compatible

Replacement technology piping specification RAS


Existing piping connection with different diameter gas and liquid line is possible using the following criteria.

Liquid Pipe Size in “ 1/4 (STD) 3/8 (STD)


Gas Pipe Size in “ 3/8 (STD) 1/2 (STD)
Length Pre- Length Pre-
Maximum Distance charged Charged
m m m m
*10* 15 15
Common Refrigerants
*13* 15 15
MIRAI / for Existing Plant.
*16* 20 15
SEIYA *18* 20 15 R22
*24* 20 15 R407C
*10* 20 15
*13* 20 15
SHORAI *18* 20 15
*22* 20 15
*24* 20 15

P a g e 12 | 62
Conversion of RAV-GM/GP (R32) units for use with R410A

The Current range of Toshiba R32 light commercial RAV-GM (Digital Inverter) and RAV-GP (Super Digital) Inverter outdoor units are
compatible with refrigerant R410A, subject to compliance with current f-gas regulations.

It is the installers responsibility to.

Undertake the conversion from R32 to R410A in full compliance with current f-gas regulations.

Remove the R32 labelling from the outdoor unit and replaced with a suitable R410A label, in accordance with
current f-gas regulations.

Additional
NEW Pre-charged Maximum
charge per Original R32
HP Model Name Pre-charged length (m) Length (m)
meter Charge (kg)
R410A(kg) (a)
(grams) (b)
1 RAV-GM301ATP-E 0.76 15 20 20 0.63
1.5 RAV-GM401ATP-E 1.08 15 20 20 0.9
2 RAV-GM561ATP-E 1.08 20 30 20 0.9
3 RAV-GM801ATP-E 1.56 20 30 40 1.3
4 RAV-GM1101ATP-E 2.52 30 50 40 2.1
4 RAV-GM1101AT8P-E 2.52 30 50 40 2.1
5 RAV-GM1401ATP-E 2.52 30 50 40 2.1
5 RAV-GM1401AT8P-E 2.52 30 50 40 2.1
2 RAV-GP561ATP-E 1.62 20 50 40 1.35
3 RAV-GP801AT-E 2..28 30 50 40 1.9
4 RAV-GP1101AT-E 3.72 30 75 40 3.1
5 RAV-GP1401AT-E 3.72 30 75 40 3.1
4 RAV-GP1101AT8-E 3.12 30 75 40 2.6
5 RAV-GP1401AT8-E 3.12 30 75 40 2.6
6 RAV-GP1601AT8-E 3.12 30 75 40 2.6
8 RAV-GM2241AT8-E 6.0 30 100 80 5.0
10 RAV-GM2801AT8-E 6.0 30 100 80 5.0

Example.

Additional refrigerant charge Real length of liquid pipe Additional refrigerant charge
amount at site exceeding = X (grams) amount per liquid pipe 1m
pre-charged length (a) -Pre-charged length (a) (b)

RAV-GM1101ATP-E installed pipe length 40m


Additional charge 40m – 30m = 10m x 40g (b) = 400grams
Pre-charged 2.52 (kg) + 0.4 (kg) additional charge = 2.92 kg system charge.

Changers to standard units must be safely managed and undertaken in accordance with, EC Regulation 517/2014 (F-Gas
regulations).
And in accordance with The Dangerous Substances and Explosive Atmospheres Regulation 2002 including Hazard Classes H220,
H221 and H280 and Approved Code of Practice (ACOP)

P a g e 13 | 62
R32 in Occupied Spaces

R32 Refrigerant is classified as "A2L" Which is a Refrigerant that is classed as being "Lower
Flammability" rated. Due to the "Lower Flammability" rating R32 installations need to meet the
"Quantity Limit with Minimum Ventilation" - "QLMV"
This quick guide is designed to assist in calculating the maximum quantity of R32 is an occupied
space. In accordance with EN378/2016.

The following assumptions have been used within this calculation:


1) Location Classification:- Class II. Indoor units and pipe work within
conditioned space. Outdoor unit located in machine room. Plant room or
in open air.
2) Access Classification: Class B, Limited number of people some of which
are acquainted with general safety precautions.
May be a room or part of a building.
3) Category Classification: Human Comfort, air treatment for occupants.

The formula used to calculate the quantity of R32 refrigerant safely allowed in an occupied space is:

M = 2.5 x LFL1.25 x ho x √A

The following chart is a “Quick Guidance” to assess the acceptable quantity of R32 in the respective
floor area, full detailed calculation should be carried out for each installation.

Sq. Area Ceiling Wall Window Floor


(m2) (2.2m) kg (1.8m) kg (1m) kg (0.6m) kg
1 1.26 1.03 0.57 0.34
2 1.78 1.45 0.81 0.48
3 2.18 1.78 0.99 0.59
4 2.51 2.06 1.14 0.69
5 2.81 2.30 1.28 0.77
6 3.08 2.52 1.40 0.84
7 3.33 2.72 1.51 0.91
8 3.55 2.91 1.62 0.97
9 3.77 3.09 1.71 1.03
10 3.97 3.25 1.81 1.08
11 4.17 3.41 1.89 1.14
12 4.35 3.56 1.98 1.19
13 4.53 3.71 2.06 1.24
14 4.70 3.85 2.14 1.28
15 4.87 3.98 2.21 1.33
16 5.03 4.11 2.29 1.37
17 5.18 4.24 2.36 1.41
18 5.33 4.36 2.42 1.45
19 5.48 4.48 2.49 1.49
20 5.62 4.60 2.55 1.53

Where the systems refrigerant charge exceeds the above, mechanical ventilation and or refrigerant
leak detectors should be utilised.

For more detailed calculations please contact Cool Designs Technical Support or visit Toshiba Air
Conditioning business club web site: http://www.toshiba-calc.co.uk/r32-charge/

P a g e 14 | 62
Digital / Super Digital Inverter Twin Splits
Indoor Unit A
Indoor Unit B

“T” Joint

Pipe Specifications

Allowable Piping Length (m) Height Difference (m)


Number of
*Total †Branch Pipe ‡Subtractive Outdoor to
Indoor unit’s
bent portions
Model (RAV-) length A or b to piping length Indoor
height
Maximum or
(L+a or L+b) furthest indoor a-b or b-a difference (Δh)
Maximum (+/-) less (Qty)
Maximum Maximum Maximum Maximum
GM561ATP-E
30 10 5 30 0.5 10
GM801ATP-E
GM1101ATP(8)-E
GM1401ATP(8)-E 50 15 10 30 0.5 10
GM1601ATP(8)-E
GM2241AT8-E
60 20 10 30 0.5 10
GM2801AT8-E
GP561ATP-E
GP801AT-E
GP1101AT(8)-E 50 15 10 30 0.5 10
GP1401AT(8)-E
GP1601AT(8)-E
 Data to be ratified by manufacturer.

‡Maximum subtractive distance between pipe branches. Example: -


Example 1 (RAV-GM561/801ATP-E)
Installed length main pipe L to distributor=18m
Example 1 
Installed length branch a=10m (Max. 10m)
Total pipe length L + a 18 + 10= 28m 
Installed length branch b=6m
Subtractive pipe length a – b 10 - 06= 4m 
Example 2 (RAV-GM561/801ATP-E)
Installed length main pipe L to distributor=28m Example 2 
Installed length branch a=14m (Max. 10m) Total pipe length L + a 28 + 14= 42m 
Installed length branch b=2m Subtractive pipe length a – b 14 - 2= 12m 

Example 3 (RAV-GM1101/1401/SP561/801/1101/1401/1601AT(P)-E) 
Installed length main pipe L to distributor=35m 
Installed length branch a=12m (Max. 15m)
Installed length branch b=10m
Example 3 
Total pipe length L + a 35 + 12= 47m 
Example 4 (RAV-
Subtractive pipe length a – b 12 - 10= 2m 
GM1101/1401/SP561/801/1101/1401/1601AT(P)-E)

Installed length main pipe L to distributor=60m Example 4  
Installed length branch a=14m (Max. 15m)
Installed length branch b=2m Total pipe length L + a 60 + 14= 74m 
Subtractive pipe length a – b 14 - 2= 12m 

P a g e 15 | 62
Additional Charge

Main Pipes Branch Pipes


Model (RAV-) Sizes (“) Pre-charge Add Amount Sizes (“) Pre-charge Add Amount
Gas/Liquid Factor (m) (kg/m) – [  ] Gas/Liquid Factor (m) (kg/m) – [ ß ]
GM561ATP-E 1/2 - 1/4 0.020 3/8 – 1/4
GM801ATP-E 0.020
1/2 - 1/4
GM1101ATP(8)-E
5/8 - 3/8 0.035
GM1401ATP(8)-E
0.035
GM1601ATP(8)-E
5/8 - 3/8
GM2241AT8-E
1-1/8 – 1/2 28 0.080 2 0.040
GM2801AT8-E
GP561ATP-E 1/2 - 1/4 0.020
3/8 - 1/4
GP801AT-E 0.020
GP1101AT(8)-E 1/2 - 1/4
5/8 - 3/8
GP1401AT(8)-E 0.035
5/8 - 3/8 0.035
GP1601AT(8)-E
 Data to be ratified by manufacturer.

Gas calculation - [Main pipe] (L-28) x  + [Branch Pipe] (a+b - 4) x ß= additional charge

Example 1
Installed length main pipe L to distributor=38m Example 1 using GM1101ATP-E
Installed length branch a=12m L - 28 x
Total pipe length 38 - 28 =10 x 0.035= 0.35 +
Installed length branch b=10m Branch pipe length a+bxß 12 + 10 - 4 =18 x 0.035= 0.63
Add Amount 0.98 kg

NOTES:

P a g e 16 | 62
Digital / Super Digital Inverter Triple Splits

Indoor Unit A
Indoor Unit C Indoor Unit B

Pipe Specifications

Allowable Piping Lengths (m) Height Difference (m)


‡Subtractive Number of
*Total Length †Branch Piping Piping Length
Indoor Unit bent portions
Model (RAV-) La + Lb La, Lb or Lc to Outdoor to Indoor Height
Lb - La Maximum
La + Lc Furthest Indoor Maximum (+/-) Difference (∆h)
Lb - Lc or Less (Qty)
Maximum Maximum Maximum
Maximum
GM1101ATP(8)-E
GM1401ATP(8)-E 15
GM1601ATP(8)-E
GM2241AT8-E
50 20 10 30 0.5 10
GM2801AT8-E
GP1101AT(8)-E
GP1401AT(8)-E 15
GP1601AT(8)-E
 Data to be ratified by manufacturer.

†Maximum distance of Branch pipe from main pipe distributor to furthest indoor unit.
‡Maximum subtractive distance between pipe branches. Example: -

Example 1 
Example 1
Total pipe length L + a 38 + 12= 50m 
Installed length main pipe L to distributor=38m Installed length branch =12m
Subtractive pipe length a – b 12 - 10= 2m 
Installed length branch b=10m Installed length branch c=12m
Subtractive pipe length c – b 12 - 10= 2m 
Example 2
Installed length main pipe L to distributor=40m Installed length branch a=15m Example 2 
Installed length branch b=4m Installed length branch c=12m Total pipe length L + a 40 + 15= 55m 
Subtractive pipe length a – b 15 - 4= 11m 
Subtractive pipe length c – b 12 - 4= 8m 

P a g e 17 | 62
Additional Charge

Main Pipes Branch Pipes


Model (RAV-) Sizes (“) Pre-charge Add Amount Sizes (“) Pre-charge Add Amount
Gas/Liquid Factor (m) (kg/m) – [  ] Gas/Liquid Factor (m) (g/m) – [ ß ]
GM1101ATP(8)-E 3/8 – 1/4
GM1401ATP(8)-E 5/8 – 3/8 0.035 0.020
1/2 – 1/4
GM1601ATP(8)-E
GM2241AT8-E
1 -1/8 – 1/2 28 0.080 5/8 – 3/8 6 0.040
GM2801AT8-E
GP1101AT(8)-E 3/8 – 1/4
GP1401AT(8)-E 5/8 – 3/8 0.035 0.020
1/2 – 1/4
GP1601AT(8)-E
 Data to be ratified by manufacturer.
Gas calculation - [Main pipe] (L-28) x  + [Branch Pipe] (a+b+c - 6) x ß = additional charge

Example 1 Example 1 above using GM1401ATP(8)-E


Installed length main pipe L to distributor=38m
Installed length branch a=12m Total pipe length L - 28 x 38 - 28 =10 x 0.035= 0.35 +
Installed length branch b=10m Branch pipe length a + b + c x ß 12+10+ 12- 6 =28 x 0.035= 0.98
Installed length branch c=12m
Add Amount 1.33 kg

Example 1 above using GP1101AT-E


Total pipe length L - 28 x 38 - 28 =10 x 0.035= 0.35 +
Branch pipe length a + b + c x ß 12+10+ 12- 6 =28 x 0.020= 0.56
Add Amount 0.91 kg

NOTES:

P a g e 18 | 62
Digital Inverter Quad Splits

Indoor Unit A

Indoor Unit D Indoor Unit C Indoor Unit B

Branch pipe Branch pipe


'T' Joint Branch pipe ‘T’ Joint Branch pipe

'T' Joint

Pipe Specifications

Allowable Piping Lengths (m) Height Difference (m)


‡Subtractive
Branch Piping
*Total Length ¥Branch Piping (c+b) - (d+b) Number of
(L+b+c) or †Branch Piping b+c (c+b) - (e+a) Indoor Unit bent portions
Model (RAV-) (L+b+d) or c, d, e & f to b+d Outdoor to Indoor Height
(c+b) - (f+a) Maximum
(L+a+e) or Furthest Indoor a+e Maximum (+/-) Difference (∆h)
(d+b) - (e+a) or Less (Qty)
(L+a+f) Maximum a+f (d+b) - (f+a) Maximum
Maximum Maximum
(e+a) - (f+a)
Maximum
GM1401ATP(8)-E
50 15 5
GM1601ATP(8)-E
GM2241AT8-E
60 10 20 6 30 0.5 10
GM2801AT8-E
GP1401AT(8)-E
50 15 5
GP1601AT(8)-E
 Data to be ratified by manufacturer.

*Total length of pipe between furthest indoor and outdoor unit.


†Maximum distance of Branch pipe from main pipe distributor to furthest indoor unit.
¥ Maximum pipe distance between Branched pairs
‡Maximum subtractive distance between pipe branches. Example: -

Example 1 Example 1 
Installed length main pipe L to distributor=20m Total pipe length L + b +c 20 + 10 +5= 35m
Installed length branch b=10m Branch length b + d 10 +5= 15m
Installed length branch c=5m Branch length a + e 10 +5= 15m
Installed length branch d=5m Branch length a + f 10 +5= 15m
Installed length branch a=10m Subtractive pipe length c+b - d+b 5+10 - 5+10= 0m
Installed length branch e=5m
Subtractive pipe length c+b - e+a 5+10 - 5+10= 0m
Installed length branch f=5m
Subtractive pipe length c+b - f+a 5+10 - 5+10= 0m
Subtractive pipe length d+b - e+a 5+10 - 5+10= 0m
Subtractive pipe length d+b - f+a 5+10 - 5+10= 0m
Subtractive pipe length e+a - f+a 5+10 - 5+10= 0m

P a g e 19 | 62
Example 2 Example 2 
Installed length main pipe L to distributor=30m Total pipe length L + b +c 30+ 15 + 10 = 55m
Installed length branch b=15m Branch length b + c 15+ 10 = 25m
Installed length branch c=10m Branch length b + d 15+ 6 = 21m
Installed length branch d=6m Branch length a + e 15+ 5 = 20m
Installed length branch a=15m Branch length a + f 15+ 10 = 25m
Installed length branch e=5m Subtractive pipe length c+b - d+b 10+ 15- 6+ 15 = 4m
Installed length branch f=10m Subtractive pipe length c+b - e+a 10+ 15- 5+ 15 = 5m
Subtractive pipe length c+b - f+a 10+ 15- 10+ 15 = 0m
Subtractive pipe length d+b - e+a 6+ 15- 5+ 15 = 1m
Subtractive pipe length d+b - f+a 6+ 15- 10+ 15 = 1m
Subtractive pipe length e+a - f+a 6+ 15- 10+ 15 = 1m

Additional Charge

Main Pipes Branch pipes


Sizes
Model (RAV-) Pre-charge Add amount Sizes Pre-charge Add amount Sizes Add amount
Gas/Liquid (“)
Factor (m) (kg/m) – [  ] Gas/Liquid (“) Factor (m) (g/m) – [ß] Gas/Liquid(“) (g/m) – [γ]

GM1401ATP(8)-E
5/8 – 3/8 0.035 3/8 – 1/4 0.020
GM1601ATP(8)-E 1/2 – 1/4 0.020
GM2241AT8-E
1 -1/8 – 1/2 28 0.080 5/8 – 3/8 4 0.040
GM2801AT8-E 5/8 – 3/8 0.040
GP1401AT(8)-E
5/8 – 3/8 0.035 3/8 – 1/4 0.020 1/2 – 1/4 0.020
GP1601AT(8)-E
 Data to be ratified by manufacturer.

Gas calculation - [Main pipe] (L-28) x  + [Branch Pipe a] (a+b - 4) x ß + [Sub Branch Pipe] (c+d+e+f) x γ = additional charge

Example 1
Installed length main pipe L to distributor=20m Example 1 using GM1401ATP(8)-E
Installed length branch b=10m
Installed length branch c=5m Total pipe length L - 28 x  20 - 28 =-8 x 0.035 = -0.28 +
Installed length branch d=5m Branch pipe length a+b-4xß 10+10- 4 =16 x 0.020 = 0.32 +
Installed length branch a=10m Branch pipe length c+d+e+fx γ 5+5+5+5 =20 x 0.020 = 0.40
Installed length branch e=5m
Installed length branch f=5m Add Amount 0.44 kg

Digital / Super Digital Multi Split System Wiring Schematic


Indoor Unit A Indoor Unit B Indoor Unit C Indoor Unit D

Configuration same for Twin, Triple & Quad combinations.


A common controller will be used, individual controls is not possible.
Lead to Follower power supply, (NO connection on terminal 3 on follower units).

Remote
Controller

Interconnecting Cables
3 Core + Earth Power connected to terminals 
2 Core + Earth Power connected to terminals 
2 Core Control connected to terminals A + B

P a g e 20 | 62
Common Sensor Characteristics

There are eight commonly used sensors in the RAS and RAV systems.
TA = Return Air Sensor; indoor unit TC = Coil Sensor; indoor unit
TCJ = Coil Sensor; indoor unit
TL = Liquid Pipe Sensor (fan speed); outdoor unit TE = Heat Exchange Sensor (defrost); outdoor unit
TD = Discharge Pipe Sensor; outdoor unit TO = Ambient; outdoor unit
TS = Suction; outdoor unit TK = Oil sensor (VRF)

The Ta,Tc,Tcj,Ts,To and TE sensors all share the same resistance versus temperature characteristic. They
differ however in electrical connections and sensing head style; therefore, it is important to quote the full
model type number when ordering any replacement sensors.
The Td, TL and TK sensor has a different resistance characteristic because its sensing range is that much
higher than the others.

Sensor -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 100 ºC


Ta,Tc,Tcj,TE,To, Ts 60.3 45.3 33.8 26.4 20.35 16 12.59 10 8 6.5 5.2 4.3 3.5 2.9 2.4 - KΩ
Td, Tk, TL - - 161 - 99 80.5 63 50 40 - 26.5 - 17.9 - 12.3 3.4 kΩ

Example for location of sensors

TA sensor

P a g e 21 | 62
Indoor Lamp Indication for Trouble Shooting - RAV ###KRT (High Wall Only)

The primary judgement to check whether a fault has occurred in the indoor or outdoor unit is carried out with the following method; method to judge the erroneous position by flashing indication on the display part of the indoor
unit. The indoor unit monitors the operating status of the air conditioner and the blocked contents of self-diagnosis are displayed restricted to the above cases if a protective circuit works.

P a g e 22 | 62
Indoor Lamp Indication for Trouble Shooting – RAV###KRT (High Wall Only)

The primary judgment to check whether a fault has occurred in the indoor unit or outdoor unit is carried out with the following method; method to judge the erroneous position by flashing indication on the display part of the indoor unit. The indoor unit monitors the
operating status of the air conditioner and the blocked contents of self-diagnosis are displayed restricted to the above cases if a protective circuit works.

P a g e 23 | 62
Indoor Lamp Indication for Trouble Shooting - RAV Series

P a g e 24 | 62
Indoor Lamp Indication for Trouble Shooting - RAV Series

Check Code List (Indoor)

P a g e 25 | 62
Indoor Lamp Indication for Trouble Shooting - RAV Series

Check Code List (Outdoor)

P a g e 26 | 62
Indoor Lamp Indication for Trouble Shooting - RAV Series

Apps Store Fault Codes – All Commercial & VRF Systems


Download Toshiba Fault Codes from your Apps Store
or go to web page Toshiba-calc.co.uk/fault-codes/

Example: 1
Local controller displaying fault code E04
Enter E04 and select Find Fault

VRF fault codes can be model specific and may


require condenser model reference in Fault Code

Example: 2
Local controller displaying fault code L29
Condenser displaying sub-code 07
Model of condenser MMY-MAP1604HT8-E
Enter L29071604 and select Find Fault

Please note; codes can be entered with or without character spaces, spaces
ignored in text strings.

P a g e 27 | 62
Fault Codes – All Commercial & VRF Systems

Do Not turn off the power supply before reading the fault codes, doing so will clear the diagnostic memory.
Caution must be taken when removing the access covers, as high voltages are present.
Fault diagnosis is available at three locations within the Air Conditioning system. :-
1 Remote Controller - press the check button 2 Multi Controller - rotate the display switch to position 1
3 Central Controller - press the check button (if installed) 4 Outdoor Unit Switch position (variable dependent upon model): –
2 Pipe Super Multi 2, 3 & 8; 3 Pipe Super Multi 2 & 0;
3 Pipe SMI 2 & 0 2 Pipe Modular Multi MMY 1, 1, 1
3 Pipe Modular Multi MMY 1, 1, 1

Code Fault Description


Split A/C equipment indoor to outdoor communication failure / VRF equipment could also be attributed to communication breakdown between
04
condenser PCB's. Likely cause Indoor PCB / condenser PCB / Interconnecting cable damage / transformer used to power condenser PCB
Reverse change in temperature. Detected by indoor evaporator sensor (TC). Likely cause 4-way valve. 4 way reversing valve energised for heating
08
operation only
Frost conditions detected / No temperature change. Detected indoors by evaporator sensor (TC). Likely cause poor airflow, lack of refrigerant,
09
overheating compressor
11 Indoor fan trouble. Detected indoors. Likely cause fan motor, PCB
12 EEPROM Failure on PCB. Detected indoors (replace indoor PCB)

14 Inverter compressor PCB short circuit. Detected at outdoor. Likely cause blown fuses supplying inverter pack, faulty IPDU(inverter board) or
component within inverter pack, electrical fault on inverter compressor
15 Multi-Control box error. Detected indoors (interrogate Multi-Control box for additional faults by setting display switch @ position 1)
17 Abnormal current detection on inverter compressor. Detected at outdoor. (replace IPDU PCB (inverter board))
18 Condenser coil sensor fault. Detected indoors. Likely cause TE/TE1 sensor condition or outdoor PCB fault sensor value 20°c=12.5k ohms
Liquid or compressor discharge sensor fault. Likely cause TL, TD sensor condition or PCB fault TL sensor value 20°c=12.5k ohms TD sensor value
19
20°c=63k ohms
20 Condenser PCB faulty (replace main PCB)
2 pipe VRF & Split A/C equipment High Pressure switch activation 425psi-29bar _ 3 pipe VRF equipment, interrogate condenser PCB for additional fault
21 code. Detected at outdoor. Likely cause split A?C equipment fault HP Switch, restriction in refrigerant flow, fan motor failure, poor airflows / VRF
equipment set condenser interface PCB switches as follows SW1 @ position 2 & SW2 @ position 0 (see sub codes Er21 or ErAd)
22 Excessive high pressure. Detected at outdoor. Likely cause abnormal characteristics of Pd transducer, refrigerant restriction/blockage
80 Multi-Control box Th(A) sensor fault. Likely cause TH(A) sensor or M/C box PCB sensor value 20°c=12.5k ohms
81 Multi-Control box Th(B) sensor fault. Likely cause TH(B) sensor or M/C box PCB sensor value 20°c=12.5k ohms
82 Multi-Control box Th(C) sensor fault. Likely cause TH(C) sensor or M/C box PCB sensor value 20°c=12.5k ohms
83 Multi-Control box Th(D) sensor fault. Likely cause TH(D) sensor or M/C box PCB sensor value 20°c=12.5k ohms
84 Multi-Control box Th(X) sensor fault. Likely cause TH(X) sensor or M/C box PCB sensor value 20°c=12.5k ohms

P a g e 28 | 62
Code Fault Description
87 Phase missing phase. Detected at outdoor. Likely cause abnormal power supply
88 Multi-Control box does not recognise condenser capacity. Likely cause interconnecting cable damage, outdoor PCB fault
89 Indoor capacity to high. Likely cause loss of combination within group of modularised condensers
93 Indoor coil sensor fault. Detected indoors. Likely cause TC1 sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
94 Indoor coil sensor fault. Detected indoors. Likely cause TC2 sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
Communication failure on P&Q network (indoor/outdoor communication). Detected indoors & outdoors. Likely cause network cable condition, PCB
95
failure indoor or outdoor
96 Indoor unit count too high. Detected at outdoor. Likely cause indoor capacity vs. outdoor capacity Incorrect, too many indoor units connected
97 Central control communication error. Detected at central controller & indoors. Likely cause indoor power failure, central address error, cable damage
98 Duplicated zone address. Likely cause incorrectly assigned central control addresses
No communication from indoor to remote controller. Detected by hard-wired remote controller. Likely cause faulty indoor PCB, remote controller or
99
cable damage

0b Indoor float switch open circuit as result of high condensation levels within drip tray. Detected indoors. Likely cause faulty float switch, faulty lift
pump, debris blocking drain
0c Return air sensor fault. Detected indoors. Likely cause TA sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
0d Coil sensor fault. Detected indoors. Likely cause TC sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
1C Outdoor error. Detected indoors (interrogate condenser for additional faults)
1d High Inverter dc current. Detected at outdoor. Likely cause imbalance in compressor voltage, excessive amps by inverter compressor
High compressor discharge temperature. Detected at outdoor. Likely cause low refrigerant, poor refrigerant flow, poor airflows, TD sensor condition
1E
sensor value 20°c=63k ohms
1F High Inverter ac current. Detected at outdoor. Likely cause imbalance in compressor voltage, excessive amps by inverter compressor
Outdoor unit quantity fallen (loss of communication between condensers). Detected at outdoor. Likely cause power interruption, BUS communication
8d
cable condition
8E Outdoor unit’s quantity too high. Detected at outdoor. Likely cause too many condensers connected
8F Outdoor unit address incorrect. Detected at outdoor. Likely cause multiple modularised condenser having SW 9 ON, Interface PCB failure
No temperature change on evaporator. Detected by indoor evaporator sensor TC1. Likely cause miss-wiring, restriction in refrigerant flow, lack of
9A
refrigerant
Insufficient temperature change on evaporator. Detected indoors. Likely cause miss-wiring, restriction in refrigerant flow, lack of refrigerant, TC1, TC2
9F
& TA sensor condition sensor value 20°c=12.5k ohms
A0 Compressor discharge sensor fault. Detected at outdoor. Likely cause TD1/ThD1 sensor condition or Interface PCB sensor value 20°c=63k ohms
High compressor discharge temperature. Detected at outdoor. by TD1. Likely cause low refrigerant, poor refrigerant flow and airflows & TD2 sensor
A1
condition sensor value 20°c=63k ohms
A2 Compressor suction sensor fault. Detected at outdoor. Likely cause TS1/ThS sensor condition or interface PCB sensor value 20°c=12.5k ohms
High compressor suction temperature > 40°C. Detected at outdoor. Likely cause severe gas shortage, TS sensor condition, interface PCB sensor value
A6
20°c=12.5k ohms
High compressor suction temperature > 40°C. Detected at outdoor. Likely cause severe gas shortage, TS sensor condition, interface PCB sensor value
A7 20°c=12.5k ohms
P a g e 29 | 62
Code Fault Description
AA High side pressure sensor fault. Detected at outdoor. (Replace Pd pressure transducer)
Ab Pressure transducer error. Detected at outdoor. Likely cause abnormal running pressures, abnormal PS / Pd characteristics, interface PCB
High compressor discharge temperature @ low inverter speed. Detected at outdoor. Likely cause TD1 sensor condition, insufficient refrigerant sensor
AE
value 20°c=63k ohms
AF Phase rotation incorrect. Detected at outdoor. Likely cause abnormal phase order, missing phase to outdoor unit
Low pressure transducer error or misreading fault. Detected at outdoor. Likely cause incorrect characteristics of suction pressure transducer (PS,
b4
interface PCB faulty
b5 External input activation, refrigerant leak detection system (Call Toshiba's technical helpline for further details 0870 843 0333)
b6 External input activation, refrigerant leak detection system (Call Toshiba's technical helpline for further details 0870 843 0333)
b7 Indoor group follower error. Detected at central controller (interrogate local controller by pressing check for additional fault codes)
b9 Pressure sensor fault. Detected indoors. Likely cause evaporator pressure sensor unplugged, pressure sensor open circuit replace sensor
High compressor discharge temperature. Detected at outdoor. by TD2. Likely cause low refrigerant, poor refrigerant flow and airflows & TD2 sensor
bb
condition sensor value 20°c=63k ohms
Low pressure trip. Detected outdoor by PS transducer. Likely cause suction pressure transducer condition (PS), interface PCB fault restriction in
bE
refrigerant flow, lack of refrigerant
C05 Command sending error. Detected on Central Controller. Likely cause power loss at indoor unit group, network cable condition)
C06 Command receiving error. Detected on Central Controller. Likely cause power loss at indoor unit group, network cable condition)
d1 Master condenser setup alarm. Detected at outdoor. Likely cause multiple inverter outdoor units connected, faulty interface PCB)
d2 Fault within follower condenser. Detected at outdoor. (retrieve additional fault code from follower condensers)
d3 IPDU PCB overheat (inverter board). Detected at outdoor. Likely cause clogged heat-sink fins, poorly secured or faulty IPDU PCB)
d4 Oil sensor fault. Detected at outdoor. Likely cause TK1 sensor condition or outdoor PCB fault sensor value 20°c=63k ohms)
d5 Oil sensor fault. Detected at outdoor. Likely cause TK2 sensor condition or outdoor PCB fault sensor value 20°c=63k ohms)
d6 Oil sensor fault. Detected at outdoor. Likely cause TK3 sensor condition or outdoor PCB fault sensor value 20°c=63k ohms)
d7 Low oil detection. Detected at outdoor. Likely cause TK1, TK2 & TK3 sensor condition, interface PCB, lack of refrigerant sensor value 20°c=63k ohms)
d8 Oil temperature alarm. Detected at outdoor. Likely cause TK1 sensor location or condition, outdoor PCB fault sensor value 20°c=63k ohms
d9 Oil temperature alarm. Detected at outdoor. Likely cause TK2 sensor location or condition, outdoor PCB fault sensor value 20°c=63k ohms
dA Abnormal overheat of heat-sink. Detected at outdoor. Likely cause clogged heat-sink fins, poorly secured or faulty IPDU board
No oil flow detected. Detected at outdoor. Likely cause TK1, TK2 & TK3 sensor location or condition, interface PCB, blockage within SV3C sensor
db
value20°c=63k ohms
High temperature oil alarm. Detected at outdoor. Likely cause TK1 sensor condition, interface PCB fault, high ambient running conditions >43°c
dC
sensor value 20°c=63k ohms
Temperature change when condensers in off cycle. Detected at outdoor. Likely cause PMV passing within condenser, discharge & suction pressure
dd
transducer error (PS & Pd characteristics), interface PCB fault
dE Indoor unit automatic addressing failure. Detected at outdoor. Likely cause indoor PCB configuration error, indoor PCB faulty
dF Outdoor unit automatic address failure. Detected at outdoor. Likely cause interface PCB fault

P a g e 30 | 62
Code Fault Description
Communication error between indoor unit and remote controller. Detected by remote controller. Likely cause indoor PCB, remote controller, incorrect
E01
switch position on rear of remote controller, all switches normally down
E02 Sending error of local remote controller. Detected by remote controller. Likely cause replace remote controller
Communication error between indoor unit and central remote controller. Detected indoors. Likely cause indoor network adapter, central remote
E03 controller
Communication failure between indoor and outdoor units. Detected indoors. Likely cause split A/C=indoor PCB, outdoor PCB, interconnecting cable
E04
condition, compressor klixon open circuit. VRF system=power loss at condenser, U1/U2 network cable condition
E06 Decrease in quantity of indoor units. Detected indoors. Likely cause power loss at indoor unit, indoor PCB fault, A&B controller cable condition
Communication failure between indoor and outdoor units. Detected at outdoor. Likely cause interconnecting cable condition, outdoor PCB switch
E07
position SW30 bit 1 & 2 must be placed in ON position for test
E08 Duplicated indoor address. Detected indoors. Likely cause incorrect setting of BUS addresses when under central control
E09 Duplicated master remote controllers. Detected indoors. Likely cause two local remote controller connected on A&B network
Activation of high-pressure switch on D.O.L (Fixed speed) compressor 1. Detected at outdoor. Likely cause fan motor trouble, poor airflows, restricted
E1
refrigerant flow
e1 80 Multi-Control box 1 Th(A) sensor fault. Likely cause TH(A) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e1 81 Multi-Control box 1 Th(B) sensor fault. Likely cause TH(B) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e1 82 Multi-Control box 1 Th(C) sensor fault. Likely cause TH(C) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e1 83 Multi-Control box 1 Th(D) sensor fault. Likely cause TH(D) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e1 84 Multi-Control box 1 Th(X) sensor fault. Likely cause TH(X) sensor or M/C box PCB sensor value 20°c=12.5k ohms
E10 Communication Error at indoor PCB. Detected indoors. Likely cause replace indoor PCB
Automatic addressing error. Detected at outdoor. Likely cause incorrect self-addressing sequence, repeat self-addressing procedure. Retrieve fault
E12
sub- code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
E12 01 Automatic addressing error. Detected at outdoor. Indoor / Outdoor communication
E12 02 Automatic addressing error. Detected at outdoor. Outdoor / Outdoor communication
Automatic self-addressing failure. Detected at outdoor. Likely cause SW30 bit 1 & 2 in OFF position, switch both ON before self-addressing
E15
commenced, interface PCB failure
Indoor unit count or capacity to high. Detected at outdoor. Likely cause if condenser PCB displays sub code 00=indoor capacity vs. condenser to high.
E16 If sub code at condenser reads 01=indoor unit count/quantity to high. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to
position 1 / 1 / 1 for diagnosis.
E16 00 Indoor unit capacity to high. Detected at outdoor. Likely cause indoor unit capacity to high vs. condenser capacity
E16 01 Indoor unit count to high. Detected at outdoor. Likely cause indoor unit count to high vs. outdoor upper limit
Communication failure between indoor units. Detected indoors. Likely cause indoor power loss, A&B controller cable condition. Twin, triple & Quad
E18
applications E18 can result from E04 fault code
Outdoor header error. Detected at outdoor. Likely cause if condenser PCB displays sub code 00=power loss to indoor units or U1/U2 network cable
E19 condition. If sub code reads 01=incorrect wiring between modularised condensers. Retrieve fault sub-code from condenser interface PCB by placing
rotary dials to position 1 / 1 / 1 for diagnosis.

P a g e 31 | 62
Code Fault Description
E19 00 Outdoor header error. Detected at outdoor. Likely cause power loss to indoor units, U1/U2 network cable condition, SW30 bit 1 & 2 must be ON to test
E19 01 Outdoor header error. Detected at outdoor. Likely cause incorrect wiring between modularised condensers
e2 80 Multi-Control box 2 Th(A) sensor fault. Likely cause TH(A) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e2 81 Multi-Control box 2 Th(B) sensor fault. Likely cause TH(B) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e2 82 Multi-Control box 2 Th(C) sensor fault. Likely cause TH(C) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e2 83 Multi-Control box 2 Th(D) sensor fault. Likely cause TH(D) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e2 84 Multi-Control box 2 Th(X) sensor fault. Likely cause TH(X) sensor or M/C box PCB sensor value 20°c=12.5k ohms
One or more systems connected on network during self-addressing procedure. Detected at outdoor. Likely cause if condenser PCB displays sub code
01=multiple outdoor systems connected on U3/U4 network, miss-wiring or central control relay connecter in-place. If sub code reads 02=indoor units
E20
from other line connected, miss-wiring or central control relay connecter in-place. Retrieve fault sub-code from condenser interface PCB by placing
rotary dials to position 1 / 1 / 1 for diagnosis.
Multiple indoor system line numbers connected on network during self-addressing procedure. Detected at outdoor. Likely cause miss-wiring of indoor
E20 01
network cable, central control relay connecter together during self-address
Multiple outdoor system numbers connected on network during self-address procedure. Detected at outdoor. Likely cause miss-wiring of outdoor
E20 02
units, central control relay/plug connected during self-address
E23 Communication error between outdoor units. Detect outdoors. Likely cause U5/U6 cable condition, interface PCB fault
E25 Duplicated follower outdoor unit address. Detected at outdoor. Likely cause error in manually assigning addresses, allow system to self-address
E26 Decrease in quantity of outdoor units connected. Detected at outdoor. Likely cause power loss at condensers, U5/U6 cable condition
Outdoor follower fault. Detected at outdoor. Likely cause lead condenser OK, follower condenser has suffered fault, retrieve second fault code from
E28
follower condenser
IPDU/PCB board communication error. Detected at outdoor. Likely cause loss in communication between condenser PCB's. Retrieve fault sub-code
E31
from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
Compressor 1 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace Compressor 1
E31 01
IPDU board
Compressor 2 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace Compressor 2
E31 02
IPDU board
Compressor 1 & 2 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 03
Compressor 1 & 2 IPDU board
Communication failure between PCB's within condenser. Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E,
E31 04 MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for E3104 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E
(series 2), MMY-MAP0804HT8-E (series 4) search E31041, E31042 or E31044
E31 04 1 Fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace fan IPDU board
E31 04 2 Fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace fan IPDU board
Compressor 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace Compressor 3
E31 04 4
IPDU board

P a g e 32 | 62
Code Fault Description
Communication failure between PCB within condenser. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E, MMY-AP###2HT8-E
E31 05 or MMY-MAP###4HT8-E therefore example fault code for E3105 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E (series 2), MMY-
MAP0804HT8-E (series 4) search E31051, E31052 or E31054
Compressor 1 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 05 1
Compressor 1 IPDU & fan IPDU board
Compressor 1 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 05 2
Compressor 1 IPDU & fan IPDU board
Compressor 1 & 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 05 4
Compressor 1 & 3 IPDU board
Communication failure between PCB within condenser. Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E,
E31 06 MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for E3106 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E
(series 2), MMY-MAP0804HT8-E (series 4) search E3101, E31062 or E31064
Compressor 2 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 06 1
Compressor 2 IPDU & fan IPDU board
Compressor 2 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 06 2
Compressor 2 IPDU & fan IPDU board
Compressor 2 & 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 06 4
Compressor 2 & 3 IPDU board
Communication failure between PCB within condenser. Detected at outdoor. (4 Series Condenser Compressor 1, 2 & 3 IPDU board communication
E31 07
error). (1&2 Series condenser communication error between PCB within condenser) likely cause phase missing on power supply, replace interface PCB
Communication error between PCB within condenser. Detected at outdoor. Likely cause check communication cable linking all PCB's, phase missing
E31 07 1
on power supply, replace interface PCB
Communication error between PCB within condenser. Detected at outdoor. Likely cause check communication cable linking all PCB's, phase missing
E31 07 2
onpower supply, replace interface PCB
Compressor 1, 2 & 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 07 4
Compressor 1, 2 & 3 IPDU board
E31 08 Fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace fan IPDU board
Compressor 1 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 09
Compressor 1 IPDU & fan IPDU board
Compressor 2 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 0A
Compressor 2 IPDU & fan IPDU board
Compressor 1 & 2 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's,
E31 0B
replace Compressor 1 & 2 IPDU PCB & fan IPDU board
Compressor 3 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's,
E31 0C
replace Compressor 3 IPDU board & fan IPDU board
Compressor 1 & 3 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's,
E31 0d
replace Compressor 1 & 3 IPDU board & fan IPDU board
P a g e 33 | 62
Code Fault Description
Compressor 2 & 3 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all
E31 0E
PCB's, replace Compressor 2 & 3 IPDU PCB & fan IPDU board
Communication error between PCB within condenser. Detected at outdoor. Likely cause check communication cable linking all PCB's, phase missing
E31 0F
on power supply, replace interface PCB
Activation of high-pressure switch or internal overheat (klixon on INVERTER compressor only. Detected at outdoor. Likely cause fan motor trouble,
E5
poor airflows, poor refrigerant flow, insufficient refrigerant
Activation of compressor klixon or contactor overload on D.O.L (Fixed speed compressor 1. Detected at outdoor. Likely cause poor refrigerant flow,
E6
insufficient refrigerant, excessive amps by compressor
Resulting from b6 fault code generated at indoor unit. Detected at outdoor. (b6=External input activation, refrigerant leak detection system (Call
Eb
Toshiba's technical helpline for further details 0870 843 0333)
Inverter compressor low voltage. Detected at outdoor. Likely cause AC fuse disconnection, faulty component within compressor inverter circuit,
Er 14
electrical failure of compressor
Er 1d High Inverter dc current. Detected at outdoor. Likely cause imbalance in compressor voltage, excessive amps by inverter compressor
Inverter compressor trip. Detected at outdoor. Likely cause activation of high-pressure switch 425psi-29bar / internal overheat (klixon) on inverter
Er 21
compressor only
Er A0 Compressor discharge sensor fault. Detected at outdoor. Likely cause TD1/ThD1 sensor condition or Interface PCB sensor value 20°c=63k ohms
Er A1 Compressor discharge sensor fault. Detected at outdoor. Likely cause TD2/ThD2 sensor condition or Interface PCB sensor value 20°c=63k ohms
Er A2 Compressor suction sensor fault. Detected at outdoor. Likely cause TS1/ThS sensor condition or interface PCB sensor value 20°c=12.5k ohms
Er A4 Ambient air sensor fault. Detected at outdoor. Likely cause Th0 sensor condition or interface PCB sensor value 20°c=12.5k ohms
Er A5 Condenser coil sensor fault. Detected at outdoor. Likely cause ThE sensor condition or interface PCB fault sensor value 20°c=12.5k ohms
High compressor discharge temperature. Detected at outdoor. by TD1, TD2, ThD1 & ThD2. Likely cause low refrigerant, poor refrigerant flow and
Er A6
airflows & TD sensor condition sensor value 20°c=63k ohms
High compressor suction temperature > 40°C. Detected at outdoor. Likely cause severe gas shortage, TS sensor condition, interface PCB sensor
Er A7
value 20°c=12.5k ohms
Er AA High side pressure sensor fault. Detected at outdoor. (Replace Pd pressure sensor)
Fixed speed compressor trip (D.O.L). Detected at outdoor. Likely cause activation of high-pressure switch 425psi-29bar / internal overheat (klixon) /
Er Ad
phase rotation PCB / D.O.L contactor overload trip
Er AE Low Pressure trip < 3 psig. Detected at outdoor. by L.P. switch. Likely cause refrigerant loss, restriction in refrigerant flow
Er AF Phase rotation incorrect. Detected at outdoor. Likely cause abnormal phase order, missing phase to outdoor unit
Activation of high pressure switch on D.O.L (Fixed speed) compressor 2. Detected at outdoor. Likely cause fan motor trouble, poor airflows,
F0
restricted refrigerant flow
F01 TCj Coil sensor fault. Detected indoors. Likely cause TCj sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
F02 TC2 or TC Coil sensor fault. Detected indoors. Likely cause TC2 / TC sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
F03 TC1 Coil sensor fault. Detected indoors. Likely cause TC1 sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms

P a g e 34 | 62
Code Fault Description
F04 Td1 sensor fault. Detected at outdoor. Likely cause compressor discharge sensor condition (Td1) or outdoor PCB fault sensor value 20°c=63k ohms
F05 Td2 sensor fault. Detected at outdoor. Likely cause compressor discharge sensor condition (Td2) or outdoor PCB fault sensor value 20°c=63k ohms
TE or TS Sensor fault. Detected at outdoor. Likely cause Heat exchange sensor condition (TE / TE1 / TE2). Suction line sensor condition (TS) or
F06 outdoor PCB fault sensor value 20°c=12.5k ohms. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1
for diagnosis.
F06 01 TE1 Sensor fault. Detected at outdoor. Likely cause Heat exchange sensor condition (TE1) or outdoor PCB fault sensor value 20°c=12.5k ohms
F06 02 TE2 Sensor fault. Detected at outdoor. Likely cause Heat exchange sensor condition (TE2) or outdoor PCB fault sensor value 20°c=12.5k ohms
F07 TL Sensor fault. Detected at outdoor. Likely cause Liquid line sensor condition (TL) or outdoor PCB fault sensor value 20°c=12.5k ohms
F08 TO Sensor fault. Detected at outdoor. Likely cause Ambient air sensor condition (TO) or outdoor PCB fault sensor value 20°c=12.5k ohms
Activation of compressor klixon or contactor overload on D.O.L (Fixed speed compressor 2). Detected at outdoor. Likely cause poor refrigerant flow,
F1
insufficient refrigerant, excessive amps by compressor
F10 TA Sensor fault. Detected indoors. Likely cause Return air sensor condition (TA) or indoor PCB fault sensor value 20°c=12.5k ohms
F12 TS Sensor fault. Detected at outdoor. Likely cause Suction line sensor condition (TS / TS1 / TS2) or outdoor PCB fault sensor value 20°c=12.5k ohms
Compressor IPDU board overheat. Detected at outdoor. Likely cause poor contact to heat-sink, IPDU board fault. Fault sub-code required to
F13 determine which board has suffered overheat 01=IPDU1 overheated 02=IPDU2 overheated 03=IPDU3 overheated. Retrieve fault sub-code from
condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
F13 01 Compressor 1 IPDU board overheat. Detected at outdoor. Likely cause poor contact to heat-sink, replace compressor IPDU board 1
F13 02 Compressor 2 IPDU board overheat. Detected at outdoor. Likely cause poor contact to heat-sink, replace compressor IPDU board 2
F13 03 Compressor 3 IPDU board overheat. Detected at outdoor. Likely cause poor contact to heat-sink, replace compressor IPDU board 3
Outdoor temperature sensor error. Detected at outdoor. Likely cause VRF equipment=Heat exchange (TE) sensor condition/location or Liquid line
F15 (TL) sensor condition/location, outdoor PCB fault Split equipment=Suction sensor (TS) condition/location Heat exchange sensor (TE)
condition/location, outdoor PCB fault sensor value 20°c=12.5k ohms
Pressure sensors miss-reading. Detected at outdoor. Likely cause incorrect characteristics of compressor discharge (Pd) & compressor suction (PS)
F16
pressure sensor or total loss of refrigerant
F22 Td3 sensor fault. Detected at outdoor. Likely cause compressor discharge sensor condition (Td3) or outdoor PCB fault sensor value 20°c=63k ohms
F23 Compressor suction pressure sensor fault. Detected at outdoor. Likely cause Suction transducer (PS) fault, outdoor PCB fault
F24 Compressor discharge pressure sensor fault. Detected at outdoor. Likely cause discharge transducer (Pd) fault, outdoor PCB fault
F29 Indoor PCB fault. Detected indoors. Likely cause replace indoor PCB
Outdoor EEPROM Error. Detected at outdoor. Likely cause VRF equipment=power interruption, replace interface PCB Split equipment=replace
F31
condenser CDB board
Excessive amps drawn by compressor. Detected at outdoor. Likely cause imbalance in voltage supplied from IPDU board to compressor, compressor lock /
H01 seizure. Retrieve sub-code for VRF from condenser to determine which compressor suffered failure 01=compressor1, 02=compressor2 & 03=compressor3.
Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
Excessive amps drawn by compressor 1. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor 1 from inverter IPDU board
H01 01
1, compressor 1 lock / seizure

P a g e 35 | 62
Code Fault Description
Excessive amps drawn by compressor 2. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor 2 from inverter IPDU board
H01 02
2, compressor 2 lock / seizure
Excessive amps drawn by compressor 3. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor 3 from inverter IPDU board
H01 03
3, compressor 3 lock / seizure
High amps drawn by compressor on start-up. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor from IPDU board,
H02 compressor locked / seized. For VRF fault sub-code required to determine which compressor suffered failure 01=compressor1 02=compressor2
03=compressor3. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
High amps drawn by compressor 1 on start-up. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor 1 from IPDU board 1,
H02 01
compressor 1 locked / seized
High amps drawn by compressor 2 on start-up. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor 2 from IPDU board 2,
H02 02
compressor 2 locked / seized
High amps drawn by compressor 3 on start-up. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor 3 from IPDU board 3,
H02 03
compressor 3 locked / seized
Current detected in compressor off cycle. Detected at outdoor. Likely cause replace compressor IPDU board. For VRF fault sub-code required to
H03 determine which compressor suffered failure 01=compressor1 02=compressor2 03=compressor3. Retrieve fault sub-code from condenser interface
PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
H03 01 Current detected in compressor off cycle. Detected at outdoor. Likely cause replace compressor IPDU board 1
H03 02 Current detected in compressor off cycle. Detected at outdoor. Likely cause replace compressor IPDU board 2
H03 03 Current detected in compressor off cycle. Detected at outdoor. Likely cause replace compressor IPDU board 3
Compressor 1 over-heat. Detected at outdoor. Likely cause compressor klixon activation, loss of refrigerant, poor refrigerant flow reducing cooling
H04
effect to compressor
Compressor discharge temperature does not increase while compressor 1 operates. Detected at outdoor. Likely cause compressor discharge sensor
H05
(Td1) condition / location, outdoor PCB fault sensor value 20°c=63k ohms
Low pressure protection operation. Detected at outdoor. Likely cause characteristics of suction pressure transducer (PS), system pump-down,
H06 interface PCB fault)
Abnormal oil level / temperature alarm. Detected outdoor. Likely cause oil balance service valve, refrigerant loss, oil sensor condition (TK1 / TK2 /
H07
TK3 / TK4 / TK5), interface board PCB fault sensor value 20°c=63k ohms)
TK Oil sensor fault. Detected at outdoor. Likely cause oil sensor condition, outdoor PCB fault. Fault sub code required to determine which sensor
H08 (TK1 / TK2 / TK3 / TK4 / TK5 sensor value 20°c=63k ohms). Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position
1 / 1 / 1 for diagnosis.
H08 01 TK1 Oil sensor fault. Detected at outdoor. Likely cause oil sensor condition (TK1), outdoor PCB fault sensor value 20°c=63k ohms
H08 02 TK2 Oil sensor fault. Detected at outdoor. Likely cause oil sensor condition (TK2), outdoor PCB fault sensor value 20°c=63k ohms
H08 03 TK3 Oil sensor fault. Detected at outdoor. Likely cause oil sensor condition (TK3), outdoor PCB fault sensor value 20°c=63k ohms
H08 04 TK4 Oil sensor fault. Detected at outdoor. Likely cause oil sensor condition (TK4), outdoor PCB fault sensor value 20°c=63k ohms
H08 05 TK5 Oil sensor fault. Detected at outdoor. Likely cause oil sensor condition (TK5), outdoor PCB fault sensor value 20°c=63k ohms
Compressor 2 over-heat. Detected at outdoor. Likely cause compressor klixon activation, loss of refrigerant, poor refrigerant flow reducing cooling
H14
effect to compressor

P a g e 36 | 62
Code Fault Description
Compressor discharge temperature does not increase while compressor 2 operates. Detected at outdoor. Likely cause compressor discharge sensor
H15
(Td2) condition / location, outdoor PCB fault sensor value 20°c=63k ohms
TK oil sensors do not detect temperature change while compressors operate. Detected at outdoor. Likely cause oil line (TK1 / TK2 / TK3 / TK4 /
H16 TK5) sensor condition / location, outdoor PCB fault sensor value 20°c=63k ohms. Retrieve fault sub-code from condenser interface PCB by placing
rotary dials to position 1 / 1 / 1 for diagnosis.
TK1 oil sensor does not detect temperature change while compressor 1 operates. Detected at outdoor. Likely cause oil line (TK1) sensor condition /
H16 01
location, outdoor PCB fault sensor value 20°c=63k ohms
TK2 oil sensor does not detect temperature change while compressor 2 operates. Detected at outdoor. Likely cause oil line (TK2) sensor condition /
H16 02
location, outdoor PCB fault sensor value 20°c=63k ohms
TK3 oil sensor does not detect temperature change while compressor 3 operates. Detected at outdoor. Likely cause oil line (TK3) sensor condition /
H16 03
location, outdoor PCB fault sensor value 20°c=63kΩ
TK4 oil sensor does not detect temperature change while compressors operate. Detected at outdoor. Likely cause oil line (TK4) sensor condition /
H16 04
location, outdoor PCB fault sensor value 20°c=63kΩ
TK5 oil sensor does not detect temperature change while compressors operate. Detected at outdoor. Likely cause oil line (TK5) sensor condition /
H16 05
location, outdoor PCB fault sensor value 20°c=63kΩ
Compressor discharge temperature does not increase while compressor 3 operates. Detected at outdoor. Likely cause compressor discharge sensor
H25
(Td3) condition / location, outdoor PCB fault sensor value 20°c=63k ohms
Two or more lead units within group of indoor units. Detected indoors. Likely cause incorrect addressing, alteration in grouped set-up / wiring,
L03
requires re-addressing
L04 Duplicated outdoor line address. Detected at outdoor. Likely cause failure to correctly set line address before auto addressing
Duplicated priority indoor unit, displayed on priority indoor unit. Detected indoors. Likely cause two units configured as priority units, correct
L05
configuration within engineer’s menu 04
Duplicated priority indoor unit, displayed on other than priority indoor unit. Detected indoors. Likely cause two units configured as priority units,
L06
correct configuration within engineering menu code 04
L07 Indoor unit group address incorrectly set. Detected indoors. Likely cause alteration of indoor group set-up, re-address required
L08 Indoor group / addresses unset. Detected at outdoor. Likely cause automatic addressing in-completed
L09 Indoor PCB capacity unset. Detected indoors. Likely cause failure to follow instruction accompanying new PCB
L10 Outdoor PCB capacity unset. Detected at outdoor. Likely cause failure to follow instructions accompanying new PCB
L17 Inconsistency of outdoor unit models. Detected at outdoor. Likely cause incorrect selection on outdoor model references
Flow Selector unit error. Detected indoors. Likely cause indoor unit unable to heat on demand. Check power & communication to F/S Box from local
L18
indoor unit. Incorrectly configured indoor group sharing F/S box
L20 Duplicated central controller address. Detected indoors. Likely cause incorrectly set network address. Engineering code 03
L28 Quantity of outdoor units to high. Detected at outdoor. Likely cause to many outdoor units modularised together
IPDU /PCB communication error. Detected at outdoor. Likely cause Split equipment=faulty or overheating inverter PCB. VRF equipment=loss in
L29 communication between condenser PCB's. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for
diagnosis. Search fault code (without spaces) for diagnosis e.g. L2901

P a g e 37 | 62
Code Fault Description

L29 01 Compressor 1 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace Compressor
1 IPDU board
L29 02 Compressor 2 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace Compressor
2 IPDU board
Compressor 1 & 2 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 03
Compressor 1 & 2 IPDU board
Communication failure between PCB within condenser. Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E,
L29 04 MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for L2904 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E
(series 2), MMY-MAP0804HT8-E (series 4) search L29041, L29042 or L29044
L29 04 1 Fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace fan IPDU board
L29 04 2 Fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace fan IPDU board
L29 04 4 Compressor 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace Compressor
3 IPDU board
Communication failure between PCB within condenser. Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E,
L29 05 MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for L2905 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E
(series 2), MMY-MAP0804HT8-E (series 4) search L29051, L29052 or L29054

L29 05 1 Compressor 1 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
Compressor 1 IPDU & fan IPDU board

L29 05 2 Compressor 1 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
Compressor 1 IPDU & fan IPDU board

L29 05 4 Compressor 1 & 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
Compressor 1 & 3 IPDU board
Communication failure between PCB within condenser. Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E,
L29 06 MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for L2906 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E
(series 2), MMY-MAP0804HT8-E (series 4) search L29061, L29062 or L29064
Compressor 2 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 06 1
Compressor 2 IPDU & fan IPDU board

L29 06 2 Compressor 2 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
Compressor 2 IPDU & fan IPDU board
Compressor 2 & 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 06 4
Compressor 2 & 3 IPDU board
Communication failure between PCB within condenser. Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E,
L29 07 MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for L2907 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E
(series 2), MMY-MAP0804HT8-E (series 4) search L29071, L29072 or L29074 for diagnosis

L29 07 1 Communication error between PCB within condenser. Detected at outdoor. Likely cause check communication cable linking all PCB's, phase missing on
power supply, replace interface PCB
P a g e 38 | 62
Code Fault Description
Communication error between PCB within condenser. Detected at outdoor. Likely cause check communication cable linking all PCB's, phase missing
L29 07 2
on power supply, replace interface PCB
Compressor 1, 2 & 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 07 4
Compressor 1, 2 & 3 IPDU board
L29 08 Fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace fan IPDU board
Compressor 1 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 09
Compressor 1 IPDU & fan IPDU board
Compressor 2 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 0A
Compressor 2 IPDU & fan IPDU board
Compressor 1 & 2 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all
L29 0B
PCB's, replace Compressor 1 & 2 IPDU PCB & fan IPDU board
Compressor 3 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's,
L29 0C
replace Compressor 3 IPDU board & fan IPDU board
Compressor 1 & 3 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all
L29 0d
PCB's, replace Compressor 1 & 3 IPDU board & fan IPDU board
Compressor 2 & 3 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all
L29 0E
PCB's, replace Compressor 2 & 3 IPDU PCB & fan IPDU board
Communication error between PCB within condenser. Detected at outdoor. Likely cause check communication cable linking all PCB's, phase missing
L29 0F
on power supply, replace interface PCB
L30 Auxiliary interlock in indoor unit. Detected indoors. Likely cause external interlock in CN80 socket on indoor unit
P01 Indoor fan motor error. Detected indoors. Likely cause indoor fan motor or wiring to motor
High compressor discharge temperature. Detected at outdoor. by TD1 @ 115°c. Likely cause low refrigerant, poor refrigerant flow and airflows &
P03
TD1 sensor condition sensor value 20°c=63k ohms
High pressure switch activation. Detected at outdoor. Likely cause poor airflows over indoor / out dependant on operation, restriction in refrigerant
P04 flow, non-condensable mixed with refrigerant. Fault sub code required to determine which H.P Switch activated 01=compressor 1 02=compressor 2
03=compressor 3. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
Compressor 1 high pressure switch activation. Detected at outdoor. Likely cause poor airflows over indoor / out dependant on operation, restriction
P04 01
in refrigerant flow, non-condensable mixed with refrigerant
Compressor 2 high pressure switch activation. Detected at outdoor. Likely cause poor airflows over indoor / out dependant on operation, restriction
P04 02
in refrigerant flow, non-condensable mixed with refrigerant
Compressor 3 high pressure switch activation. Detected at outdoor. Likely cause poor airflows over indoor / out dependant on operation, restriction
P04 03
in refrigerant flow, non-condensable mixed with refrigerant
Phase-missing detection / phase order error, compressor inverter High Voltage. Retrieve fault sub-code from condenser interface PCB by placing
P05
rotary dials to position 1 / 1 / 1 for diagnosis. Search fault code (without spaces) for diagnosis e.g. P0501
P05 00 Phase-order incorrect or phase missing. Detected at outdoor. Likely cause issue with power supply to condenser, or phase order wrong, swap L2 & L3

P a g e 39 | 62
Code Fault Description
Phase-missing detection (series 1 & 2) or High D.C. inverter voltage (series 4). Detected at outdoor. Fault Code is outdoor model series specific e.g.
P05 01 MMY-MAP###1HT8-E, MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for P0501 will be (MMY-MAP0801HT8-E (series
1),MMY-MAP0802HT8-E (series 2), MMY-MAP0804HT8-E (series 4) search P05011, P05012 or P05014
P05 01 1 Phase-missing detection. Detected at outdoor. Likely cause error on power supply to condenser
P05 01 2 Phase-missing detection. Detected at outdoor. Likely cause error on power supply to condenser
P05 01 4 High D.C. inverter voltage. Detected at outdoor. Likely cause compressor 1 IPDU board overheat or failure
Phase-order incorrect (series 1 & 2) or High D.C. inverter voltage (series 4). Detected at outdoor. Fault Code is outdoor model series specific e.g.
P05 02 MMY-MAP###1HT8-E, MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for P0502 will be (MMY-MAP0801HT8-E (series
1), MMY-MAP0802HT8-E (series 2), MMY-MAP0804HT8-E (series 4) search P05011, P05012 or P05014
P05 02 1 Phase-order incorrect. Detected at outdoor. Likely cause issue with power supply to condenser, swap L2 & L3 to correct
P05 02 2 Phase-order incorrect. Detected at outdoor. Likely cause issue with power supply to condenser, swap L2 & L3 to correct
P05 02 4 High D.C. inverter voltage. Detected at outdoor. Likely cause compressor 2 IPDU board overheat or failure
P05 03 High D.C. inverter voltage. Detected at outdoor. Likely cause compressor 3 IPDU board overheat or failure
Overheating compressor IPDU / inverter board. Detected at outdoor. Likely cause poorly secured inverter PCB to heat-sink, faulty IPDU. Fault sub
P07 code required to determine which IPDU overheated 01=IPDU1 02=IPDU2 03=IPDU3. Retrieve fault sub-code from condenser interface PCB by
placing rotary dials to position 1 / 1 / 1 for diagnosis.
P07 01 Overheating compressor 1 IPDU / inverter board. Detected at outdoor. Likely cause poorly secured inverter PCB to heat-sink, faulty IPDU board 1
P07 02 Overheating compressor 2 IPDU / inverter board. Detected at outdoor. Likely cause poorly secured inverter PCB to heat-sink, faulty IPDU board 2
P07 03 Overheating compressor 3 IPDU / inverter board. Detected at outdoor. Likely cause poorly secured inverter PCB to heat-sink, faulty IPDU board 3
Indoor float switch open circuit as result of high condensation levels within drip tray, detected indoors. Likely cause faulty float switch, faulty lift
P10
pump, debris blocking drain
P12 Indoor fan motor trouble. Detected indoors. Likely cause fan motor locked, incorrectly configured PCB, indoor PCB fault
Outdoor liquid back detection in condenser while in OFF cycle. Detected at outdoor. Likely cause increase in pressure within dormant condenser,
P13
possible PMV valves passing
High compressor suction or discharge temperature. Detected at outdoor. Likely cause sensor condition (TS1 or TD1, 2 or 3), interface PCB fault,
P15 loss of refrigerant TS1 sensor value 20°c=12.5k ohms TD1,2 & 3 sensor value 20°c=63k ohms. Retrieve fault sub-code from condenser interface
PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
High compressor suction temperature. Detected at outdoor. Likely cause suction sensor condition (TS1), interface PCB fault, loss of refrigerant
P15 01
sensor value 20°c=12.5k ohms
High compressor discharge temperature. Detected at outdoor. Likely cause discharge sensor condition (TD1, TD2 or TD3), interface PCB fault, loss
P15 02
of refrigerant sensor value 20°c=63k ohms
High compressor discharge temperature. Detected at outdoor. by TD2 @ 115°c. Likely cause low refrigerant, poor refrigerant flow and airflows &
P17
TD2 sensor condition sensor value 20°c=63k ohms
High compressor discharge temperature. Detected at outdoor. by TD3 @ 115°c. Likely cause low refrigerant, poor refrigerant flow and airflows &
P18
TD3 sensor condition sensor value 20°c=63k ohms
Incorrect temperature / pressure reading at condenser. Detected at outdoor. Likely cause check characteristics of pressure transducers (PS & Pd)
P19
and temperature sensors (TS1, TE1 & TL), interface PCB fault sensor value 20°c=12.5k ohms

P a g e 40 | 62
Code Fault Description
High pressure protection detected by discharge pressure transducer reading @ 36bar. Detected at outdoor. Likely cause characteristics of discharge
P20
pressure transducer (Pd), interface PCB, poor airflows across condensers
Outdoor fan motor error. Detected at outdoor. Likely cause Split equipment, locked / faulty fan motor, faulty PCB VRF Equipment. Retrieve fault
P22 sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis. Search fault code (without spaces) for diagnosis.
e.g. P2203
Outdoor fan motor error. Detected at outdoor. Likely cause locked / faulty fan motor, faulty fan IPDU PCB. Fan motor has 3 ohms resistance on any
P22 03 2 wires
Outdoor fan motor error. Detected at outdoor. Likely cause locked / faulty fan motor, faulty fan IPDU PCB. Fan motor has 3 ohms resistance on any
P22 34 2 wires
Outdoor fan motor error. Detected at outdoor. Likely cause locked / faulty fan motor, faulty fan IPDU PCB. Fan motor has 3 ohms resistance on any
P22 37 2 wires
P22 E1 Fan IPDU board error. Detected at outdoor. Likely cause error on DC supply voltage to fan IPDU PCB or problem with mains voltage onto condenser
P22 E2 Fan IPDU board error. Detected at outdoor. Likely cause error on DC supply voltage to fan IPDU PCB or problem with mains voltage onto condenser
P22 E3 Fan IPDU board error. Detected at outdoor. Likely cause error on DC supply voltage to fan IPDU PCB or problem with mains voltage onto condenser
Compressor IPDU PCB Short circuit. Detected at outdoor. Likely cause electrical fault on compressor, faulty compressor inverter board. Before
P26 replacing PCB prove compressor is good. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for
diagnosis.
Compressor 1 IPDU PCB Short circuit. Detected at outdoor. Likely cause electrical fault on compressor 1, faulty compressor 1 inverter board. Before
P26 01
replacing PCB prove compressor is good
Compressor 2 IPDU PCB Short circuit. Detected at outdoor. Likely cause electrical fault on compressor 2, faulty compressor 2 inverter board. Before
P26 02
replacing PCB prove compressor is good
Compressor 3 IPDU PCB Short circuit. Detected at outdoor. Likely cause electrical fault on compressor 3, faulty compressor 3 inverter board. Before
P26 03
replacing PCB prove compressor is good
Compressor position detection error. Detected at outdoor. Likely cause fault on compressor, faulty compressor inverter board. Before replacing
P29 inverter, PCB prove compressor is good. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for
diagnosis.
Compressor 1 position detection error. Detected at outdoor. Likely cause fault on compressor 1, faulty compressor 1 inverter board. Before
P29 01
replacing inverter, PCB prove compressor is good
Compressor 2 position detection error. Detected at outdoor. Likely cause fault on compressor 2, faulty compressor 2 inverter board. Before
P29 02
replacing inverter, PCB prove compressor is good
Compressor 3 position detection error. Detected at outdoor. Likely cause fault on compressor 3, faulty compressor 3 inverter board. Before
P29 03
replacing inverter, PCB prove compressor is good
Indoor unit other than lead indoor suffering fault. Detected on central controller. Likely cause to diagnose retrieve fault code from local remote
P30
controller to indoor group
Indoor unit other than lead indoor suffering fault. Detected indoors. Likely cause to diagnose retrieve fault code from local remote controller to
P31
indoor group

P a g e 41 | 62
Error Detected by - TCC-Link Central Controller

Check Code Wireless Remote

Outdoor 7 Segment Display Sensor Block Display Judging


Central Check Code Name
AI Central Device
Control
Device Auxiliary Code Controller O T R F

C05 --- --- --- --- Sending error in TCC-Link central control device TCC-LINK
C06 --- --- --- --- Receiving error in TCC-Link central control device TCC-LINK
Batch alarm of general-purpose equipment HA control interface
C12 --- --- --- ---
control interface I/F
Differs according to error contents of unit with occurrence of alarm Group control follower unit error
P30 --- TCC-LINK
--- (L20 is displayed) Duplicated central control addresses

Black Pear Error Code Cross Reference.


Black Pear Toshiba Description Black Pear Toshiba Description
Error Code Error Code Error Code Error Code
1005 C05 Sending error in TCC-Link central control device 3001 F01 Indoor TCCJ sensor error
1006 C06 Receiving error in TCC-Link central control device 3002 F02 Indoor TC2 sensor error
1012 C12 Batch alarm of general-purpose equipment control interface 3003 F03 Indoor TC1 sensor error
Communication error between indoor and remote controller (Detected at
2001 E01 3004 F04 TD1 sensor error
remote controller side)
Communication error between indoor and remote controller (Detected at 3005 F05 TD2 sensor error
2003 E03
indoor side) 3006 F06 TE1 sensor error
2004 E04 Communication circuit error between indoor / outdoor (Detected at indoor side) 3007 F07 TL sensor error
2006 E06 Decrease of number of indoor units. 3008 F08 TO sensor error
2007 E07 Communication circuit error between indoor / outdoor (Detected at outdoor side) 3010 F10 TA sensor error
2008 E08 Duplicated indoor addresses 3012 F12 TS1 sensor error
2009 E09 Duplicated master remote controllers 3013 F13 TH sensor error
2010 E10 Communication error between indoor Boards 3015 F15 Outdoor temperature sensor misconnection (TE1-TL)
2012 E12 Automatic address start error 3016 F16 Outdoor pressure sensor misconnection (Pd – Ps)
2015 E15 No indoor automatic address 3023 F23 Ps sensor error
2016 E16 Over capacity / Number of connected indoor units 3024 F24 Pd sensor error
2018 E18 Communication error between indoor header and follower units. 3029 F29 Indoor other error
2019 E19 Outdoor header unit’s quantity error 3031 F31 Outdoor EEPROM error
2020 E20 Other line connected during automatic address 4001 H01 Compressor break down
2023 E23 Sending error in communication between outdoor units 4002 H02 Magnetic switch error / Overcurrent relay operation / Compressor error (lock)
2025 E25 Duplicated follower outdoor address 4003 H03 Current detection circuit error
2026 E26 Decrease of number of connected outdoor units 4004 H04 Compressor 1 case thermal operation
2028 E28 Follower outdoor unit error 4006 H06 Low pressure protection operation
2031 E31 IPDU Communication error 4007 H07 Low oil level protection
4008 H08 Oil level temperature sensor error
4014 H14 Compressor 2 case thermal operation
4016 H16 Oil level detection circuit error / Magnetic switch error / Overcurrent relay error

P a g e 42 | 62
Black Pear Error Code Cross Reference.
Black Pear Toshiba Description Black Pear Toshiba Description
Error Code Error Code Error Code Error Code
6003 L03 Duplicated indoor header units 7001 P01 Indoor fan motor error
6004 L04 Duplicated outdoor line address 7003 P03 Discharge temperature TD1 error
Duplicated indoor units with priority 7004 P04 High-pressure switch detection error
6005 L05
(Displayed in indoor unit with priority) 7005 P05 Phase-missing detection / Phase order error
Duplicated indoor units with priority 7007 P07 Heat sink overheat error
6006 L06
(Displayed in unit other than indoor unity with priority) 7010 P10 Indoor overflow error
6007 L07 Group line in individual indoor unit 7012 P12 Indoor fan motor error
6008 L08 Indoor group/Address unset 7013 P13 Outdoor liquid back detection error
6009 L09 Indoor capacity unset 7015 P15 Gas leak detection
6010 L10 Outdoor capacity unset 7017 P17 Discharge temperature TD2 error
6020 L20 Duplicated central control addresses 7019 P19 4-way valve inverse error
6028 L28 Maximum number of outdoor units exceeded 7020 P20 High pressure inverse error
6029 L29 Number of IPDU’s error 7022 P22 Outdoor fan IPDU error
6030 L30 Auxiliary interlock in indoor unit 7026 P26 Giant Transistor short circuit protection error
6031 L31 IC error 7029 P29 Compressor position detection circuit error
7030 P30 Follower indoor unit error (Group error)
7031 P31 Follower indoor unit error (Group error)
Special Black Pear Error Codes
6999 Unit does not exist on the system
8000 No error detected
255 No error detected.

Notes

P a g e 43 | 62
TCC-net Local Hard Wired Controller Guidelines

RAV & VRF

RBC-AS41E RBC-ASC11E RBC-MTSC1

RBC-AMT32-E RBC-AMS41-E

RBC-AMS51-ES RBC-AMS54/55-ES
RBC-AMS51E RBC-AMS54/55E-ES

P a g e 44 | 62
System Configuration Menu
Hard wired remote controllers which allow access to the configuration menu are:
RBC-ASC11-E, RBC-AMT32-E, RBC-AMS41-E, RBC-AMS51E, RBC-AMS54/55E-ES.

RBC-AS41E, Infra-Red Remotes and Central Controllers Cannot be utilised for setting configuration items.
A number of items are configurable by a wired controller – if an indoor unit without a wired controller requires configuration, a wired
remote can be temporarily connected for the procedure to be undertaken. In order to access the men u.
TEST

Press + SET + CL for 4 seconds (RBC-AMT32/AMS41)

 The indoor units to be configured will be chosen by pressing the UNIT button.
 The indoor unit being configured runs its fan and swings its louvers (if possible).
 Use SET TEMPERATURE up/down buttons to scroll through the configurable items Use TIMER up/down buttons to choose the
 configuration value for Use
 SET to confirm configuration value Use CL to undo an incorrect setting provided that configurable item has not been changed)
 Use CHECK to return to normal operation. EXAMPLES of COMMON CONFIGURABLE OPTIONS

ITEM DESCRIPTION VALUE DEFAULT


0000: Inactive 0001: 150 H
Filter sign displayed after selected time has elapsed – or by external
01 Filter alarm time 0002: 250 H 0003: 500 H 0002
pressure switch (CN70) 0004: 1000 H 0005: External switch
02 Dirty environment Allows filter alarm time to be halved if used in a dirty environment 0000: Standard 0001: Dirty 0000
03 Network address When under network control. 0099: Unset 0001 to 0064 available 0099
Priority Setting for
04 0 = Normal 1= Priority (This remote has priority of mode setting 0000 = Standard 0001 = Priority 0000
Remote Controller
0002; +2oC
06 Stratification control Increases effective return air temperature setting in heating mode (0 to 10K) 0000 to 0010 Floor type
0000; 0ºC
0C Preheat Preheat indication on display 0000 = available 0001 = unavailable 0000
0000 except
0d Auto mode Enable or disable Auto mode 0000 = available 0001 = unavailable
SMMSe
0E SHRMi only Used when multiple indoor units are served via a single FS box 0000 = normal 0001= multiple units 0000
0F Heat Mode Enable or disable Heat Mode 0000 = available 0001 = unavailable 0000
0000: 1-way cassette (s models)
0001: 4-way cassette
0002: 2-way cassette
0003: 1-way cassette (y models)
0004: duct (standard)
0005: slim duct
0006: duct (high static)
10 Indoor unit model Must be set when replacing indoor printed circuit board 0007: ceiling
0008: hi wall
0010: console
0011: concealed floor
0014: 4-way compact cassette (600 x 600)
0013: tall cabinet
0016: fresh air intake
0050: air to air heat exchanger
MM RAV MM RAV
0004 =005* - 0012 =027* 80*
0001 =007* - 0013 =030* 90*
0003 =009* 30* 0015 =036* 110*
0005 =012* - 0017 =048* 140*
0006 - 40* 0018 =056* 160*
0007 =015* - 0021 =072* 224*
11 Indoor unit capacity 0000 will generate a (L09) fault 0009 =018* 56* 0023 =096* 280*
0011 =024* - - - -
Air to air heat exchanger Type
3
0 0 0 1 = 150m /h 0 0 0 6 = 800m3/h
0 0 0 2 = 250m3/h 0 0 0 7 = 1000m3/h
0 0 0 3 = 350m3/h 0 0 0 8 = 1500m3/h
0 0 0 4 = 500m3/h 0 0 0 9 = 2000m3/h
0 0 0 5 = 650m3/h
DI/SDI indoor and outdoor units are automatically addressed, this
12 System number value may be set manually but it must be done via the wired 0001: outdoor unit 1 0002: outdoor unit 2 0099
controller – on an individual basis. Settings are 0001 to 0030
Indoor units connected to a common outdoor unit (e.g. twinned
13 Indoor unit number indoor units) will have the same system number - settings are 0001 0001: indoor unit 1 0002: indoor unit 2 0099
to 0064. Automatically allocated – but may be manually overridden.
Allows selection of master indoor unit within group. 0000: single indoor unit 0001: group
14 Group master/slave 0099
Automatically allocated but may be manually overridden. master 0002: group slave
Compensation for missing temperature sensor (split systems ONLY)
15 Temperature Sensor 0022 0022
other settings produce F03 fault code
0015
0015 = all speeds available
16 Indoor Fan Indoor fan speed selection. Binary addition. except high static
1 = auto; 2 = low; 4 = medium; 8 = high
0008
0000 = no shift, 0001 = 1 k shift, -
17 Set point shift Cooling temperature set point shift. (shifted by 1 to 10 k) 0010 = 10 k shift 0000
0000: disabled, 0001: swing only
19 Louver functions None, swing only, swing and auto (where applicable)
0004: all options
1b Compressor on time Compressor minimum on time (0 = 5 minutes 1 = 4 minutes) 0000: 0 – 5 min 0001: 1 - 4 min. 0000
1E Dead band - auto Changeover sensitivity in automatic mode. (1 to 10 k adjustable) 0000: 0 K, 0010: 10 K 0003

P a g e 45 | 62
ITEM DESCRIPTIPON VALUE DEFAULT
1F Max. Setting Cooling mode maximum temperature setting (18 – 29oC) 0018 = 18oC, 0020 = 20oC 0029 = 29oC 29 o C
20 Min. Setting Cooling mode minimum temperature setting (18 – 29oC) 0018 = 18oC, 0020 = 20oC 0029 = 29oC 18 o C
21 Max. Setting Heating mode maximum temperature setting (18 – 29oC) 0018 = 18oC, 0020 = 20oC 0029 = 29oC 29 o C
22 Min. Setting Heating mode minimum temperature setting (18 – 29oC) 0018 = 18oC, 0020 = 20oC 0029 = 29oC 18 o C
23 Max. Setting Dry mode maximum temperature setting (18 – 29oC) 0018 = 18oC, 0020 = 20oC 0029 = 29oC 29 o C
24 Min. Setting Dry mode minimum temperature setting (18 – 29oC) 0018 = 18oC, 0020 = 20oC 0029 = 29oC 18 o C
25 Max. Setting Auto mode maximum temperature setting (18 – 29oC) 0018 = 18oC, 0020 = 20oC 0029 = 29oC 29 o C
26 Min. Setting Auto mode minimum temperature setting (18 – 29oC) 0018 = 18oC, 0020 = 20oC 0029 = 29oC 18 o C
28 Auto restart Enable or disable 0000: disabled 0001: enabled 0000
29 Humidifier condition Operating condition of humidifier 0000: Usual 0001: Condition ignored 0000
0000: Filter input
2A CN70 Selection of optional error input (CN70) 0002
0001: Alarm input, 0002: None
0015= all modes
2d Modes available Binary addition of modes available. 0015
1 = fan; 2 = cool; 4 = dry 8 = heat
Making or breaking terminals 1 and 2 of CN61 (indoor PCB) External 0000 = group starts when made
External On / Off
2E switching option, remove jumper 01 master indoor PCB allows stops when open 0001 = enable 0000
control
continuous contact switch- link 01 in place; pulse switch required when made, disable when open
Through remote controller and CN32 indoor PCB
31 External fan control 0000 = disable, 0001 = enabled 0000
Used for setting ON/OFF control for VN-M units when paired with A/C systems
0000: return air sensor
32 Sensor location Return air/room sensor OR in local controller 0000
0001: remote sensor
33 Unit of temperature Celsius or Fahrenheit 000 = Celsius, 0001 = Fahrenheit 0000
0000: temperature setting
36 Remote controller Temperature display 0001: temperature room sensing 0000
0000: None 0001: Pump ON
40 Drain pump Drain pump control 0003
0002: None 0003: Pump OFF
45 Anti-smudge 4-way cassette anti smudge effect via louver position 0000 = enabled, 0001 = disabled 0000
AP015, 018 AP024
1-Way Cassette 3.5 3.8 0000
Airflow Correction 0000
4.0 4.0 0001
Ceiling height (m)
4.2 4.2 0003
AP007 to AP030 AP36 to AP056
2-Way Cassette
2.7 2.7 0000
Airflow correction 0000
3.2 3.0 0001
Ceiling height (m)
3.8 3.5 0003
- RAV56* RAV80* RAV90*,110*,160*
AP005 to AP012 AP015 to AP018 AP024 to AP030 AP036 to AP056
4-Way Cassette
4-way 3-way 2-way 4-way 3-way 2-way 4-way 3-way 2-way 4-way 3-way 2-way
Airflow correction 0000
Ceiling height (m) 2.7 2.8 3.0 2.8 3.2 3.5 3.0 3.3 3.6 3.9 4.2 4.5 0000
- - - 3.2 3.5 3.8 3.3 3.5 3.8 4.2 4.4 4.6 0001
- - - 3.5 3.8 - 3.6 3.8 - 4.5 4.6 - 0003
- RAV40* RAV56*
4-Way Compact AP007 to AP012 AP015 AP018
Cassette
5d 2.7 2.9 3.2 0000 0000
Airflow correction
Ceiling height (m) - 3.2 3.4 0002
- 3.5 3.5 0003
- RAV40*-56* -
Slim Ducted AP0054 AP0074 to AP0184 AP0244 to AP0274
Airflow correction 10 Pa 10 Pa 10 Pa 0000
0000
External static 20 Pa 20 Pa 20 Pa 0001
pressure 35 Pa 35 Pa 35 Pa 0003
50 Pa 50 Pa 50 Pa 0006
RAV40*-56* RAV80* RAV110*-160*
AP007 to AP018 AP024 to AP030 AP036 to AP058 RAV40* 0001
30 Pa 30 Pa 30 Pa 0001 RAV-80* 0001
Standard Ducted 40 Pa 40 Pa 40 Pa 0000 RAV110* 0003
Airflow correction
50 Pa 50 Pa 50 Pa 0003 RAV140* 0003
External static
pressure 65 Pa 65 Pa 65 Pa 0002 RAV160* 0003
80 Pa 80 Pa 80 Pa 0004 AP007-018 0001
100 Pa 100 Pa 100 Pa 0005 AP024-030 0000
120 Pa 120 Pa 120 Pa 0006 AP036-058 0003
VN-M (HE1) Maximum Fan Speed Selection 0000: High 0001: Extra High 0000
60 Timer lock Locks timer in wired local controller – maintaining last setting 0000: unlocked, 0001: locked 0000
62 Anti-smudge 4-way cassette – ant smudge via fan speed (Coanda effect) 0001
69 Louver Louver restriction when cooling 0000 = restricted to horizontal positions 0000
0001 = full range of movement
GM1
GM56 GM80 GM110
40
Setting for air
6E Smart Cassette ONLY. Standard 0000 0000 0000 0000 0000
direction kit (1)
3-way air flow 0000 0000 0080 0075
2-way air flow 0090 0090 0080 0070
77 Dual set point RBC-AMS54/55E-ES ONLY 0000 = Available 0001 = Unavailable 0000
GM1
GM56 GM80 GM110
40
Setting for air According to
Smart Cassette ONLY. Standard 0000 0072 0075 0070
direction kit (2) capacity type.
3-way air flow 0060 0060 0050 0048
88 2-way air flow 0050 0050 0040 0038
8b Heating Correction Heating output reduction split systems only 0000: None, 0001: Correction 0000
Run group in HEAT mode after setting defrost is conducted automatically.
Forced Defrost 0000 = disabled 0001 = enabled 0000
8C Value is reset automatically back to 0000
0000 = fan off, pump on
Fan & Pump Fan and pump operation during oil retrieval mode (VRF cassettes ONLY) 0003
A0 0003 = fan on, pump on
b3 Soft Cooling RBC-AMS54/55E-ES 0000 = Unavailable 0001 – Available 0001
0000 = None 0001 = Occupancy sensor
Occupancy Sensor Where applicable 0000
b5 provided
0000 = Invalid, 0001 = 30min.
Occupancy sensor Enable / Invalid. Absence time judgement time. 0002 = 60min. 0004 = 120min. 0002
b6 0005 = 150min.
b7 Occupancy sensor Operation at absent time. 0000 = Standby 0001 = Operation stop 0000
C2 Energy save Outdoor unit energy demand 1% increments 50 to 100% 0050 ~ 0100 0075
0000 = disable
0006: = RAV40*
0009: = RAV56*
CE Replace indoor PCB 4-Way cassette unit capacity code 0012: = RAV80* 0000
0015: = RAV110*
0017: = RAV140*
0018: = RAV160*
d0 Power Saving Mode Whether the power saving mode can be set by the remote controller 0000 = Invalid 0001 = Valid 0001

P a g e 46 | 62
ITEM DESCRIPTION VALUE DEFAULT
d3 Self-clean operation Self-clean dry operation 0000 = disable 0001 = enable 0001
E6 Wireless Channel Compact Cassette. Channel selection 0000 = A channel, 0001 = B channel 0000
0001 = Standard, 0002 = Dual swing
F0 Swing mode Compact Cassette. Louver swing options 0003 = Cycle swing
0001
0000 Full swing
F1 Louvre lock Flap 1
0001 Fixed position 1 (Horizontal Discharge)
F2 Louvre lock Flap 2 0002 Fixed position 2
4-Way cassette 5 fixed positions 0000
F3 Louvre lock Flap 3 0003 Fixed position 3
0004 Fixed position 4
F4 Louvre lock Flap 4
0005 Fixed position 5 (Downward Discharge)
F6 Application control kit Presence of Application Control Kit (TCB-PCUC1/2E-1) 0000 = None, 0001 = Exist 0000

Note: Some options are model specific.

Notes

P a g e 47 | 62
Optional Control Accessories
ITEM RAV VRF VN ESTIA RAS DESCRIPTION DETAILS
Full Control Including Service Function
RBC-AMT32E   Standard Remote Controller
Full Control Including Service Function and
RBC-AMS41E   Remote Controller Built-in Timer
Programmable 24/7 Day Timer
Includes Timer and Backlight Display, Power Save
RBC-AMS51E-ES*   LITE-Vision Plus Remote Controller
Functions, Multilingual.
Programmable Timer, Backlight, Multilingual, Dual Set
RBC-AMS54*/55E-ES   Remote Controller Built-in Timer
Point, Soft Cooling & Return Back Functions.
Wired Controllers

Ideal for Hotel and Base use Applications, (No Service


RBC-AMS41E2*   Simplified Controller
Function Available)
Ideal for Hotel and Base use Applications, (Service
RBC-ASC11E   Compact Local Controller
Function Available)
Ideal for Hotel and Base use Applications, (No Service
RBC-MTSC1   Colour Smart Touch Local Remote
Function Available)
NRC-01HE  VN-M Remote Controller Remote controller for Air to Air Heat Exchangers.
RBC-RWS20E  Remote Controller for RAS Wired Remote Controller for RAS Ducted Units
Use with Central Controllers, BMS-CM1280TLE, BMS-
TCB-EX21TLE   Scheduled Timer
SM1280ETLE, TCB-CC163TLE2,RBC-AMT32E, NRC-01HE
HWS-AMS54E  Standard Air to Water Remote Estia Air to water Remote Controller
Automatic control of Room Temperature Sensing
TCB-TC41LE    Auto-configurable Remote Sensor
Comfort Condition of system.
Replacement Corner Pocket with Built-in Receiver and
RBC-AX32(W/WS-E)   4-Way Cassette Corner Receiver
Remote Controller
Controllers

7-Series Compact Cassette Corner Replacement Corner Pocket with Built-in Receiver and
Wireless

RBC-AX32UM(W)-E  
Receiver Remote Controller
RBC-AX32UW(W)-E  2-Way Cassette Receiver Replacement Receiver and Remote Controller
RBC-AX33CE   Under Ceiling Receiver Replacement Receiver and Remote Controller
TCB-AX32E2   Independent External Receiver Receiver and Remote Controller for all Models
TCB-CC163TLE2*    16 Zone On-Off Controller Enables the Switching On and Off by Volt Free Contact
BMS-CM1280TLE*    Compliant Manager Enables Full Control of up to 128 Indoor Units.
Central Controllers

TCB-SC643TLE     64 Zone Central Remote Enables Full Control of up to 64 Indoor Units.


128 Zone, Smart Manager with Data Smart Manager with Remote Access via Web Browser
BMS-SM1280ETLE   
Analyser and Data Analysis Features.
128 Zone, Colour Touch Screen with Full Control of up to 128 Indoor Units with Remote
BMS-CT1280E    
Data Analyser Access via Web Browser and Data Analysis Features.
512 Zone, Colour Touch Screen with Full Control of up to 512 Indoor Units with Remote
BMS-CT512E    
Data Analyser Access via Web Browser and Data Analysis Features.
64 Zone, Colour Touch Screen Colour Touch Screen Central Remote Controller to
RBC-TBPTS   
Central control up to 64 Indoor Units
7-Series Compact Cassette Occupancy Sensor (PIR)
TCB-SIR41UM-E  
Occupancy Sensor
Allows connection of RAV units to the TCCJ Link
TCB-PCNT30TLE2  Network Adaptor U3/U4 TCCJ Link
Network
Connects a RAV unit to the old AI Network.
TCB-PCNT20E  Network Adaptor XY AI Network

TCB-PX30MUE  Terminal Box Enclosure when used with all RAV Cassette Units.

Interface to provide an output to enable an external


RBC-SMF1   Fan Interface
fan from the indoor unit.
Interface to Indicate the Mode of Operation, Output
RBC-SMIM2   Indicator Module Mode
for Cool, Heat and Fan Only.
Interface to indicate Unit Operation and Stopping
RBC-SMIM3   Indicator Module ON/OFF and Fault
Fault.
Indicator Module ON/OFF, Stopping Interface to Indicate Unit Operation and Stopping
RBC-SMIM4  
Fault and Unit Enable Fault, also has connections to Enable the Unit.
Interface to Connect to a 0 to 10v or Resistance Based
RBC-FDP3-PE   BMS Interface
BMS, also has Modbus Functionality.
Indoor Interfaces

Interface to Connect to a 0 to 10v or Resistance Based


RBC-TSI1   Monitoring and Control Interface
BMS, also has Modbus Functionality.
Interface to Accept 230v Input from a Timer for
RBC-IT2-PE  Timer Interface
R22/R407C Systems.
Connects to “HA” Socket on Indoor Unit.
RBC-IT3-PE  Daiseikai / Avant Timer Interface

TCB-PCOS1E2   1
 Application Control PCB Compatible models, RAV-SM/SP/GP + VN-M (HE1)

TCB-PCM03E  External Input PCB Interface to Provide External ON/OFF for Estia System

Interface to Provide an Output for Estia Fault/Run.


TCB-PCIN3E  Output PCB

Connects to CN61 at indoor PCB on RAV allowing


TCB-IFGSM1E  GSM Control Interface remote ON/OFF, Operation Status and Alarm
Monitoring.
Operation Status of Indoor Units via Indoor PCB
TCB-KBCN600PE   Operation Status
“CN61” socket.
Volt Free Interface for VN-M##HE units to Control
RBC-VNL1  Unit Interface Lead
ON/OFF, Fan Speed and Damper Position.
Remotely Switches Unit ON/OFF, via NO VOLT
RBC-CN61   On/Off Interface
interface, Connects to indoor PCB “CN61” Socket.
Connects to the “CN61” socket on Indoor PCB,
On/Off Interface with Operation
CDL-BMS01   allowing for remote VOLT FREE On/OFF, System
and Fault
Operation and System Fault via 12volt Interface
Notes: * No longer available, 1 VN-M####HE1 only

P a g e 48 | 62
Optional Control Accessories
ITEM RAV VRF VN ESTIA RAS DESCRIPTION DETAILS
TCB-PCDM4E  Power Peak Control Power Peak Cut Control
Operation/Error Output Display, Compressor Operation
TCB-PCIN4E  Operation Output Display
Interfaces

Control.
Outdoor

Night Set Back Control, Snowfall Fan Control, External


TCB-PCM04E  Operation Control
ON/OFF, Operation Mode Control.
Peak Power Cut and Noise Reduction, Output for
TCB-PC0S1E2*  Outdoor Control
Compressor Operation. (*Not applicable to all units.)
15m Extension Lead Kit for 3 Series SHRM/i/e Flow
RBC-FSEX15  3 Series Flow Selector Lead
Selector Box.
Other Accessories

Provides ON/OFF Control from Wired Remote or


RBC-SMT1  2
 2
Timer Interface Lead
Central Remote Controllers. (*excludes RBC-AS41E2)
Kit to Convert VRF Floor/Chassis units to Connect with
RBC-CK1  VRF to RAV Conversion Kit
RAV Outdoor Units (R410A ONLY).
Kit to Convert VRF Tall Floor Units to Connect with
RBC-CK2  VRF to RAV Conversion Kit
RAV Outdoor Units (R410A ONLY).
RAVSP804/1604 Peak-Cut Control, Night Operation,
TCB-KB0S2E  Optional Connection Interface
Compressor Status.
CDL-BMS02   Modbus Interface Modbus Interface for control of up to 64 indoor units
CDL-BMS03   BACnet Interface BACnet interface for control of up to 64 indoor units
Trend interface for control of up to 64 indoor units,
BMS Interfaces

CDL-BMS04   Trend Interface


requires IQ3/IQ4
Control panel for 64 indoor unit’s c/w data logging,
OASIS-064EM1   Control Solution
web server & optimisation
Control panel for 128 indoor unit’s c/w data logging,
OASIS-128EM1   Control Solution
web server & optimisation
Connect the system to a Modbus Building Management
TCB-IFMB641TLE   Modbus Interface
System control up to 64 indoor units
Toshiba RAS WIFI interface, suitable for:
RB-N103S-G   WIFI Connection
Daiseikai-10,13,16, Shorai –18,22,24, Seiya- 24
Toshiba RAS WIFI interface, suitable for:
WIFI Interfaces

RB-N105S-G   WIFI Connection Shorai-10,13,17, Seiya-05.07,10,16,18, Console-


10,13,18
Toshiba RAV-VRF WIFI interface, maximum quantity of
BMS-IWF0320E   WIFI Connection
indoor units 32, IOS or Android App.
Intensishome WIFI Universal Interface Infrared Remote
RBC-IS-IF-Wifi-1    WIFI Connection
RAS/RAV/VRF
Intensishome WIFI Interface for Wired Remotes
RBC-TO-RC-Wifi-1   WIFI Connection
RAV/VRF.
Leak detection concentration sensor with White
TCB-LDS1   White Ref. Leak Detector
Faceplate and remote 12 V transformer
Leak detection sensor with Stainless Steel Faceplate
TCB-LDS2   Stainless Steel Ref. Leak Detector
Refrigerant Leak Detection

and remote 12 V transformer


Leak detection concentration sensor with White
RBC-RCS1   White Ref. Leak Detector
Faceplate
Leak detection concentration sensor with Stainless
RBC-RCS2   Stainless Steel Ref. Leak Detector
Steel Faceplate
Leak detection transformer 12 V and cable kit (use
TCB-LD12V   Remote Power Supply
with TCB-LDS1/TCB-LDS2)
External Leak Detection and Pump
TCB-LD1   Leak Detection Panel VRF SHRMi/SMMSi
Back panel
External Leak Detection and Pump
TCB-LD2   Leak Detection Panel VRF SHRMe/SMMSe
Back Panel
Refrigerant Leak Detection
RBC-RP1   Repeater Panel
Repeater Panel
TCB-GFC1603UE   Fresh air filter chamber 4- Smart Cassette only way
TCB-GFC1602UE   Fresh air filter chamber 4-way standard cassette only
TCB-SP1603UE   Spacer for height adjustment 4- Smart Cassette only way
Auxiliary Options

TCB-SP1602UE   Spacer for height adjustment 4-way standard cassette only


TCB-BC1603UE   Air discharge direction kit 4- Smart Cassette only way
TCB-BC1602UE   Air discharge direction kit 4-way standard cassette only
4-way smart cassette, 4-way standard cassette,
TCB-FF101URE2   Auxiliary fresh air flange
compact cassette, slim duct
TCB-SF56C6BPE   Spigot shaped flange Suitable for RAV-SM40#/56#BTP-E1-MMD-AP007#/018~HP1-E
TCB-SF80C6BPE   Spigot shaped flange Suitable for RAV-SM80#BTP-E1-MMD-AP024#/030#BHP1-E
TCB-SF160C6BPE   Spigot shaped flange Suitable for RAV-SM110#/160#BTP-E1-MMD-AP036#/056#BHP1-E
Note: 2 Check with Technical for Compatibility - For additional control options contact Cool Designs Technical Support.

NOTES

P a g e 49 | 62
TCC-Net Control

Features

 2 wire, screened, non-polarised controller connection
 Infrared control available for cassette, under ceiling, high wall, ducted models
 Remote temperature sensing available, Unit, Wired controller, Separate room sensor
 Automatic addressing of groups and twins
 Optional control of external fan, (RBC-SMF1)
 High ceiling compensation (code 5d)
 Time for filter warning is configurable (code 01)
 Each mode of operation (auto – heat – cool – dry) may have a different temperature set point
 Auto restart is configurable (code 28)

Cassette PCB

 DC fan motor with feedback circuit
 Red LEDs indicate communication with local controller 
and PCB activity when illuminated.
 Wired or infrared control (or both)
 Drain pump and float switch

Wired controller (RBC-AMT32/41)

1. Mode of operation 11. Frost protection 21. TEST


2. Louver 12. Numeric display 22. Setting
3. Fixed louver 13. Remote controller sensor 23. Error
4. Filter 14. Not used 24. Servicing
5. Not used 15. Set Temperature 25. Inspect
6. Self-clean function 16. Central control 26. Timer function
7. Defrosting 17. Save Operation 27. Numeric display
8. Ready 18. Ventilation operation 28. Operation reservation
9. Heating ready 19. Numeric display 29. Days of the week
10. Not used 20. Air speed 30. Special holiday

32. On/OFF button 42. Set button


33. Fan button 43. Test button
34. Mode button 44. Filter reset button
35. Vent button 45. Day button
36. Louver button 46. Program button
37. Unit button 47. Grille button
38. Save button 48. Schedule button
39. Swing/Fix button 49. Temperature buttons
40. Time button 50. ON/OFF Light
41. Clear button

P a g e 50 | 62
Wired controller (RBC-AMS55E-ES)

Standard Display

Detailed Display

Icon List

Buttons

1 Monitor button 7 F2 function button


2 Menu button 8 Power button (On/Off)
3 Cancel (Back) button a LED illuminated when unit is on

4-5 Temperature buttons b Temperature sensor


6 F1 function button

P a g e 51 | 62
Group control

 Indoor units may be supplied from any phase.
 Up to 8 indoor units per group.
(When TCB-TC41LE remote temperature sensor/
second remote controller is added to a “Group”
the quantity of indoor units drops from 8 to 7.)
 Automatic addressing.
 Any indoor unit may be designated as the “Lead Unit”.
 Pre-heat indication.
 Filter indication.

Automatic addressing
This takes place when power is applied and can last up to 5 minutes – the address will be selected automatically.

If a replacement indoor PCB is fitted, the missing address will be re-applied.

The powered controller screen shows the demarcation lines – and does not indicate that the system is either
configuring itself – or is ready to use. If the remote temperature sensor is selected (configuration item 32), the
associated symbol will appear when the system is ready for use. If a 9th indoor unit (which can be a protocol
converter) is added to a group, the controller will continue to show the demarcation lines.

Adding a system to an existing group (or powering a group up at different times) will require manual configuration
(the fault codes will provide guidance).

Identifying an indoor unit



 Stop operation
 Press TEST (43) and VENT (35) for 4 seconds
 ALL is displayed
 Indoor fans of the entire group are now energised
 Press UNIT (37) to scroll through group
 Indoor fan of selected indoor unit runs
 Press TEST (43) to exit.

Test operation

 System must be stopped
 Press TEST (43) for 4 seconds
 Controller displays TEST
 Press the ON/OFF (32) button to start operation
 Select MODE (34) of operation
 HEAT or COOL
 Press the ON/OFF (32) button to stop test
 System will automatically revert to normal operation after 1 hour
 Press the TEST (43) button to leave TEST function

P a g e 52 | 62
Controller Configuration - Remote Controller RBC-AMT32E & RBC-AMS41E

Quick Reference Guide


To assist service engineers working on Toshiba air conditioning equipment, there is a large quantity of data available
via the standard remote controller, either the RBC-AMT32E or the RBC-AMS41E, this data is NOT available via an
Infrared remote or the RBC-AS21E2 simplified remote controllers.
Accessing the data is a simple process of pressing a sequence of buttons on the remote controller.

Fault Code Guide


Current fault codes are displayed automatically on the left of the remote controller,
(Four figure display in Black) fault code history can be accessed by pressing “TEST &
SET” together and holding for 4 seconds. Each controller will hold four fault codes per
unit controlled, the first displayed fault code is the youngest and the fourth will be the
oldest. To scroll through the fault’s, use the “TEMP” buttons.
 Refer to the Technical Handbook for fault code diagnosis and descriptions

System Data
System data can be obtained by pressing “TEST & CL ” together and holding for
4 seconds. Codes are displayed on the right of the remote display.
To scroll through the codes use the “TEMP” buttons. Data is displayed on the left of
the remote controller. Data is available for “0, 1, 2, 3 & 4 Series” Digital/Super Digital
inverter and VRF equipment (Mini SMMS, SHRM, SHRMi, SMMS & SMMSi).

Controller Configuration - Remote Controller RBC-AMS51/54/55E-ES

Quick Reference Guide


To access this section on the RBC-AMS51/54/55E-ES

 Code: *** Unit 1 - 1


Fault Code Guide
Current fault codes are displayed automatically on the top of the remote controller,
(four figure display in Black) fault code history can be accessed by entering the
“field Setting Menu”
Press and hold the ” “ button and the ” “button at the
same time for more than 4 seconds to display the “Field setting menu” scroll down to
”Alarm History”. The history holds 10 fault codes per unit controlled.

System Data
System data can be obtained by entering the “Field Setting Menu” and
scroll down to “Monitor Function”
When in monitor mode scroll through the data using the up/down
buttons.

P a g e 53 | 62
System Data
System data can be obtained by pressing “TEST & CL” together and holding for
4 seconds. Codes are displayed on the right of the remote display.
To scroll through the codes, use the “TEMP” buttons. Data is displayed on the left of
the remote controller. Data is available for “0, 1, 2, 3 & 4 Series” Digital/Super Digital
inverter and VRF equipment (Mini SMMS/e, SHRM, SHRMi, SHRMe, SMMS, SMMSi &
SMMSe).

Data Retrieval Guide - Remote Controllers RBC-AMT32E, RBC-AMS41E & RBC-AMS51/54 / 55E-ES

Digital/Super Digital “1” Series R32

Code Indoor Data Code Outdoor Data


00 Room Temp (Control Temp) (°C) 60 TE Sub-cooled Liquid Temp (°C)
01 Room Temp (Remote Controller) (°C) 61 TO Ambient Temp (°C)
02 TA Return Air Temp (°C) 62 TD Discharge Temp (°C)
03 TCJ Coil Liquid Temp (°C) 63 TS Suction Temp (°C)
04 TC Coil Vapour Temp (°C) 65 THS Inverter Heat Sink Temp (°C)
07 Fan Speed (rpm) 6A Operation Current (x1 1/0) (A)
F2 Fan Run Time (x 100h) 6D TL Liquid Temp (°C)
F3 Filter Duration Timer (x 1h) 70 Compressor Frequency (rps)
72 Fan Speed (Lower) (rpm)
73 Fan Speed (Upper) (rpm)
F1 Compressor Run Time (x 100h)

NOTES

P a g e 54 | 62
Network Addressing DI/SDI

Terminology
Terms for explaining DI/SDI used in section are redefined to:-
Indoor Unit No. N-n =outdoor unit line address N (Max30) –indoor unit address n (max64)
Group address 0=single (not group control)
1=Lead unit in group control
2=sub unit in group control

Lead unit:
The representative of multiple indoor units in group operation sends/receives signal to/from the remote controllers and
sub indoor units. It has no relation with an indoor unit which communicates serially with the outdoor units. Also this unit
communicates with the central controller. The operation mode and setup temperature range are reflected on the remote
controller LCD. (Except air direction adjustment of louver)

Sub unit:
Indoor units other than master unit in group operation. Basically, sub units do not send/receive signals to/from the
remote controller.

Header unit (Representative unit) (Master twin):


This unit communicates with the indoor unit (follower) which serial-communicates with the outdoor units and sends/receives
signal (command from compressor) to/from the outdoor units as the representative of the cycle control in the outdoor units
of the identical line address within the minimum unit which configures one of the refrigerating cycles of twin.

Follower unit (Subordinate unit) (Sub twin):


Indoor units excluding the header unit in Twin. This unit communicates with Header indoor unit in the identical line address
and performs control synchronized with Header unit. This unit does not perform the signal send /receive operation with
the outdoor units. No judgement for serial signal error.

Basic configuration
The basic DI/SDI connection configuration of each type of model is shown below.

Address re-setup for group control


After turning on the power and finishing automatic address setting, check the Indoor Unit No using the wired
remote controller. If the line address is not unified in the devices in a refrigerant line, unify the line address
using the wired remote controller. If group control is used, assign the group address “1” to any one of the
indoor units and “2” to the rest of the units. Confirm that each indoor unit in a group has a unique Indoor Unit
No (E08 error is not indicated on the wired remote controller).

P a g e 55 | 62
Standard configuration (One outdoor unit)

In this case, address setting can be made by using auto addressing.

Group configuration (single only)

In this case, address setting can be made by using auto addressing.


Single Single Single Single Single
Outdoor Outdoor Outdoor Outdoor Outdoor
unit unit unit unit unit

3-1 1-1 2-1 4-1 8-1


Indoor Indoor Indoor Indoor Indoor
unit unit unit unit unit

Sub/Header Master/Header Sub/Header Sub/Header Sub/Header

Max. 8 units
Remote
controller

Multiple Group configuration (combination of single/twin/triple)

In this case, manual re-addressing is required.


Single Single Twin Triple
Outdoor Outdoor Outdoor Outdoor
unit unit unit unit

1-1 2-1 3-1 4-3 4-1 4-2 4-3


Indoor Indoor Indoor Indoor Indoor Indoor Indoor
unit unit unit unit unit unit unit
Sub/Header Sub/ Sub/ Sub/Header Master/ Sub/ Sub/Header
Header Header Header Header

Max. 8 units
Remote
controller
Example of after Automatic address setting

Change the setting manually for correct operation

P a g e 56 | 62
Network Addressing DI/SDI
Connection and Address re-setup example for central control

“1:1Model” Connection Interface TCB-PCNT30TLE2


When controlling the super-digital inverter and the digital inverter, the adaptor named “1:1 model” connection interface (TCB-
PCNT30TLE2) is necessary.
SDI series 4 4-way discharge cassette type, etc. need metal case TCB-PX30MUE additionally for fixing. Some of Hi-wall Type
does not need “1:1Model” Connection Interface. Please refer to installation manual of each model.

Cabling connection of control wiring

Attach an adaptor per 1 group in the group control operation (including individual control).
Connect the adaptor to the Master indoor unit in the group control.

Central central control wiring


control
devices
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit

U3 U4 U3 U4

TCB-PCNT Indoor Indoor Indoor TCB-PCNT Indoor Indoor


30TLE control control control 30TLE control control
P.C.
(Adapter) P.C. board P.C. board P.C. board (Adapter) board P.C. board

A B A B A B A B A B

Master Sub Sub Master Sub

Remote Remote
controller controller

A central control connection example of a system where both VRF and DI/SDI are used is shown below. The VRF and
DI/SDI subsystems are connected through the central control wiring and to the central control devices.

Central Control Central Control


Device1 Device2
U1 U2 U1 U2
U3 U4
U3 U4
central control wiring

Header Follower Header Follower


U3 U4 U3 U4 U3 U4 U3 U4 ODU ODU

ODU ODU ODU ODU


123 123
Sub/Follower
U1 U2 U5 U6 U1 U2 U5 U6

U1 U2 U5 U6 U1 U2 U5 U6

123
123 123
U1 U2 U1 U2 U1 U2 U1 U2 U1 U2

U3 U4 Indoor Indoor U3 U4 Indoor

IDU IDU IDU IDU IDU


PCB PCB PCB

A B A B A B A B A B
TCB-PCNT30TLE2 TCB-PCNT30TLE2 A B
A B A B

Header Follower Master/Header Master/Header


RMTC RMTC RMTC RMTC
RMTC
RMTC RMTC

Individual Group Individual Individual Twin Single

VRF DI/SDI

P a g e 57 | 62
Network Addressing DI/SDI and VRF Systems

When the central control is performed for indoor units using twin control in a group operation, it may be required to
change the group address. (Adapter is attached to the Lead indoor unit.)
Reason: The central control device communicates with each individual indoor unit, the Lead indoor unit of the group
control and the Lead indoor unit of the twin control. However, as the address is automatically set up, which
unit will become the Lead unit is indefinite. Therefore, if the unit attached with adapter does not become the
Lead indoor unit, the central control function will become unavailable.

System A System B System C


Central Central control wiring
control
devices

Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor

*Adapter Indoor Indoor *Adapter Indoor Indoor Indoor *Adapter Indoor


(Master) (Sub) (Follower)
(Sub (Master

Master) Sub)
*TCB-PCNT30TLE

Remote Remote Remote


controller controller controller

Central control is possible. Central control is impossible. Central control is possible.

Code 12 Line address outdoor 0001 0002 0003 0004 0005 0006
Code 13 Indoor unit address 0001 0001 0001 0001 0001 0001
Code 14 Group address 0001 0002 0002 2 0002 0002 0000

* A wired remote controller (RBC-AMT32E,


RBC-AMS41E, RBC-AMS51/54/55E-ES.) is
required for address change.

Address setup procedure (when using DI/SDI only, or using DI/SDI and VRF)
When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor unit respectively in the
group operation even if multiple refrigerant lines are provided, the automatic address setup completes with power -ON of the outdoor unit
after group construction check (refer to the note below). The operation of the remote controller is not accepted while automatic address
works. (Approx.4 to 5 minutes)
CAUTIONS
1. Set up address after the wiring has been completed.
2. “1:1Model” Connection Interface TCB-PCNT30TLE2 is necessary for DI/SDI for central control. Some Hi-wall Type do not
need “1:1Model” Connection Interface. Please refer to the installation manual of each model. Connect the central control
devices to U3/U4 wires of the central control system.
3. When “1:1Model” Connection Interface is used for the group control or twin, triple or quad system, the interface must be connected
to the Master unit of the indoor unit. (Connection to Sub unit is unavailable). One “1:1Model” Connection Interface per one group.

4. In group operation, be sure to turn on power supplies to all indoor units in group control within 3 minutes. When power supply
of the Master unit is not turned on, there is a possibility that the Master unit exchanges with Sub unit. (If Master unit is
exchanged, the central control is unavailable.)

Note)
If group construction is abnormal, the automatic address sequence starts automatically.
Normal condition is below.
1. There is no duplicated indoor unit address.
2. There is no invalid indoor unit address.
3. Individual unit and master/sub units are not intermingled.
4. Only a unit for Individual.
5. A master indoor unit and 1 or more sub indoor units for group.

P a g e 58 | 62
Integration with AI Network Control

TCC-net models use a different language to AI – however a TCC-net group can be linked to an AI network, using a
protocol converter. This device is not standard and should be fitted on site – a group requires
only one protocol converter to communicate with a network.

An LED flashes to indicate communication with the network.

The Protocol converter provides terminals X-Y for


the network connection – it also has the 7-way DIP switch used
to give a network address – the method is identical to that
used for AI indoor units.

The network address may also be set by a wired controller


from the configuration menu.
The protocol converter is counted as an indoor unit – only 7
indoor units may therefore be group controlled in this way.

Second Controller

 Options available
2 x wired controllers
1 wired + 1 infrared controller
Full group control from either
Connection may be anywhere within group
Changes updated

The sub-controller must be set – this can be done from either controller. The choice of sub-controller makes
little difference unless it is required to act as the temperature sensor

Temperature Sensing

Wired controllers are able to supply a temperature value to the indoor unit. This may be more representative than
the standard, return air sensor but is not available from sub controllers of either type. To set the room sensor:

 Wired controller – selected from configuration menu code “32” (0001), or via the “bit switch 4” on the RBC-AS41 simplified remote.

The remote sensor. This is connected to terminals A-B whether or not a wired controller is used. The indoor unit must, in
this case, be set to use the standard, return air sensor (Configuration code “32” - 0000), – this sensor automatically takes
over in this case. This value will be used to provide control to all indoor units within the group.

P a g e 59 | 62
NOTES

P a g e 60 | 62
Additional “Pocket Quick Reference Guides” are available
covering;

Pocket Handbook R32 AC Products.


VN-M (HE & HE1) Units, Air to Air Heat Exchangers.
RBC-AMT32 Standard Wired Remote Controller.
AMS41E Wired Remote Controller with 7-day timer.
RBC-AMS51/54/55E-ES Back Light Wired Remote Controller with 7-Day
Timer.
RBC-ASC11E Compact Simple Controller.
RBC-MTSC1 Mini Touch Screen
R410A VRF Addressing / Commissioning.
R410A SMMSe Heat Pump Calculating the Refrigerant Charge.
R410A SHRMe Heat Recovery Systems.
R410A Single Fan Mini VRF.
FPD3 – Full AHU Control Interface.
FDP3 – Modbus AHU Control Interface.
RBC-RASNC – RAS Central Controller Interface.
CDL-VN-M CO2 Kit.
CDL-BMS01 Interface.
WIFI options Interface and “Applications”.

Future Publications coming soon.

RBC-TBPTS Colour Smart Touch Screen Central Remote Controller.


RBC-TSI1 Universal Monitoring and Control Interface including Modbus.
RBC-IS-IR-WIFI-1 Intensishome WIFI Universal Controller.
RBC-TO-RC-Wifi-1 Intensishome WIFI Toshiba RAV/VRF.

You will also find Single Sheet Literature for all the current Toshiba Air
Conditioning Units on our web site, along with Installation, Owners and
Service manuals.

http://www.cdlweb.info

P a g e 61 | 62
Contact details:

Cool Designs Ltd


Technical Support
07590 775510 / 07706 293028
Monday – Friday 07.30 to 19.30

Email: [email protected]
Web site: www.cdlweb.info

TOSHIBA Air Conditioning


24/7 technical support
0870 843 0333 (Option 7)

Text back service


07624 803 017
(Type fault code in lower case no spaces)

Try our on-line training videos on YouTube.


Cool Designs Ltd reserves the right to change the product specifications, data and images without notice

Cool Designs Ltd makes every effort to ensure that the information provided within this publication is correct and error free, however we cannot guarantee that it is free of inaccuracies, errors or
P a g e 62 | 62
omissions. Users should seek to clarify this information for themselves prior to basing any decisions upon such information.

You might also like