FT1810 - Painel Remoto

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

FT1810 Floor Repeater Display

Product Manual

Overview

The floor repeater display is an indication and operation unit in a fire detection system
with the following functions:
Indication of events Operation
 Alarm  Scrolling through lists
 Trouble  Switch off buzzer

The display on the floor repeater terminal is synchronized with the fire control panel and
displays the same event texts.

Characteristic

 Small floor repeater operating and display panels applied in FC18 fire detection
system
 Large backlight LCD display(192X64), contrast can be adjusted manually
 Communication with controller via FR18-BUS (individual address)
 External 24 VDC power supply required
 In total, up to 32 floor repeater displays can be connected to a FC18 fire alarm
controller
 Flat, elegant housing

Function
 Display of alarms, troubles event (252 items at most)
 Same message layout as the fire control panel
 With the navigation keys an indicated list in the display can be scrolled through
 The internal buzzer can be switched off manually in case of alarm

Building Technologies
Fire safety and security products
Application

Fig.1 Front view

No. Name Function


1. LCD Display of alarms and troubles, when alarm is displayed,
– Manu: manual alarm
– Auto: automatic alarm
2. Alarm light up in case of fire
3. <Silence Buzzer> Silence buzzer
4. <Query> Query alarm/fault information forward/backward
5. Lock Open/close front panel
6. Power Light up when power supply is normal
7. Trouble Light up in case of trouble
8. Buzzer Silence Light up when silence is pressed
9. <Toggle> Switch query between alarm and trouble
10. <Self Test> Check work status of LCD, indicators and buzzer

Fig. 2 Front view of PCB board Fig. 3 Back view of PCB board
Note:
1. Used to adjust contrast of LCD (PCB board should be removed)
2."Reset": press for 5 sec to reset the display
3. Jumper: the 120Ω EOL resistor is connected when jumper switch is at the
position as shown in the figure 3
2
Building Technologies A6V10323189_c_en_--
Fire safety and security products 07.2012
DIP switch
8-digit Dip-switch is used for setting the FT1810 address and switching languages. The first 1-5 digits is for setting
the FT1810 address 0-31, the last 6-8 digits is for switching languages among Chinese, English, Russian, Spain,
Portuguese.

DIP switch DIP switch


Address Language
1 2 3 4 5 6 7 8
0 Off Off Off Off Off Chinese Off Off Off
1 On Off Off Off Off English Off Off On
2 Off On Off Off Off Russian Off On Off
3 On On Off Off Off Spain Off On On
4 Off Off On Off Off Portuguese On Off Off
5 On Off On Off Off

31 On On On On On

Installation

FT1810
+ 24V+

+ 24V+
_ Power
GND
_
GND

G SGND Grounding
+ CAN+

+ CAN+
_ Connect to controller
CAN-
_
CAN-

Fig. 4 Dimension (In:mm) Fig. 5 Connection

Fig. 6 Fig. 7
1. Insert the loop line and external power wire through the floor repeater display.
2. Mark the position for the 3 installation holes on a flat wall (Fig. 4), drill the holes, put expansion bolts in and insert
the screws leaving a small gap for hanging the display.
3. Hang the floor repeater display over those screws through installation holes.
4. Unlock with key and open the front panel (Fig. 6/7), tighten the screws and make sure the display is fixed firmly.
5. Connect cables to terminals referring to the connection diagram (Fig. 5). A 120Ω EOL resistor must be connected
when the display is at the end of FR18-BUS. Refer to internal jumper of FT1810 (Fig. 3).
6. Close the front panel.
7. Lock it with the key and remove the key, put it in a safe place.

3
Building Technologies A6V10323189_c_en_--
Fire safety and security products 07.2012
Dimension
In: mm
215

36

165

Technical data

Operating voltage 24 VDC±20%


Operating current (quiescent) 30 mA
Activation current 110 mA
Operating temperature 0 ... +42 °C
Storage temperature –20 ... +60 °C
Humidity ≤95 % rel.
Communication protocol FR18-BUS(CAN-BUS)
Connection terminals 1.0 ... 1.5 mm2
Color White, RAL 9010
Protection category GB4208-93 IP30

Details for ordering

Type Material No. Part No. Designation Weight


FT1810 S54420-F3-A1 100856216 Floor repeater display 0.75 Kg

Beijing Siemens Cerberus Electronics Limited © Data and design subject to change without notice.
No.1, Fengzhidonglu, Xibeiwang, HaiDian District,
Beijing, 100094, China
Tel: +10 6476 8806
Fax: +10 6476 8899

Doc No. A6V10323189_c_en_-- Manual FD18


Edition 07.2012 100858269