Guaranteed Technical Particulars

1x300rm XLPE Cable 2xHSCYRaY- 33kV

Sl. Manufacturer’s guaranteed 33kV, 1C x 300rm Underground


No. Description Unit XLPE Copper Cable Specification.
1 Name of the Manufacturer
2 Address of the Manufacturer
3 Standards IEC 60502-2 & IEC 60228
4 Model of the offered cable 2xHSCYRaY
5 Type of the offer cable XLPE Insulated UG Cu Cable with metallic screened and armour
6 Nominal System Voltage KV 33
7 Rated Voltage of Cable KV 18/30 (36)
8 Process of Manufacturing CCV
9 Cores
Number of cores 1 (One)
10 Conductor
Material Copper
Cross sectional area mm2 300
Shape of conductor Stranded Circular Compacted
No. of copper strand no. 61
Diameter of each Cu strand mm 2.52 (approx.)
Overall diameter of Cu conductor mm 19.7 – 21.6
11 Conductor Screen
Material Extruded semi conducting compound
Thickness (minimum) mm 0.6
12 Insulation
Material of insulation Cross Linked Polyethylene (XLPE)
Type of curing Dry Curing
Thickness of Insulation (minimum) mm 8.0
13 Insulation Screen

Material Extruded semi conducting compound


Thickness (minimum) mm 0.6
14 Semiconducting Screen
Material Semi conducting Tape
Thickness (minimum) mm 0.18
15 Metallic Screen Strand
Material Copper
Number of copper screen strands no. 48
Diameter of each copper screen strands mm 1.72
16 Bedding/ Inner Sheath
Thickness mm 1.2 (approx.)
Material Virgin PVC
17 Armour Wire
Material Aluminium Non-magnetic material as per IEC 60502-2
Number of armour wire no. 58±2
Diameter of each armour wire mm 2.0
18 Outer Sheath
Material PVC
Thickness (minimum) mm 2.2
Colour of outer sheath Red
Marking on outer sheath cable length mark in each meter of cable should be Printed
19 Completed Cable
Overall diameter (Approx.) mm 49  ± 3
Weight per meter (kg/m) kg/m 5.5
Maximum length of cable in each drum m 1000 m ±5%
length
20 Minimum Radius of bend around which cable can be laid
Laid direct m 1.02
In ducts m 1.02
In air m 1.02
21 Maximum D.C. Resistance per m of cable at 20°C
of conductor ohm/m 0.0601 x 10 ̄³
of metallic screen ohm/m 0.1624 x 10 ̄³
of armour ohm/m 0.1645 x 10 ̄³
22 Maximum A.C. resistance of conductor per 0.079 x 10 ̄³
ohm/m
meter at maximum conductor temperature
23 Insulation resistance per km of cable
at 20°C Mega ohm 4295
at maximum internal temperature Mega ohm 16315 at 40°C
24 Continues current carrying capacity of the offered cable for the following situations:
a) Cable laid in the ground
One circuit A 524 (Laid direct in flat spaced 0.15m at 20°C)
Two circuit A 424
Three circuit A 366
b) Drawing into ducts
One circuit A 510 (Laid in single duct flat touching at 20°C)
Two circuit A 413
Three circuit A 357
25 Conditions upon which continuous current carrying capacity of offered cable are based
Soil thermal resistivity in k.m/w k.m/w 1.5
Ground temperature in °C °C 20

Air temperature in °C °C 30
Burial depth in m m 0.8
Axial spacing between phase cable in mm mm 150
Type of earth bonding Rod Earthing
26 Star reactance per meter of cable at 50Hz Ohm/m 0.121 x 10 ̄ ³
27 Star capacitance per meter of cable at 50Hz pF/m 249
28 Charging current per conductor per meter at mA 1.408 x 10 ̄ ³
18000/30000 Volts, 50Hz
29 Maximum conductor temperature under °C 90 °C
continuous loading
30 Conductor temperature at the end of short °C <250
circuit
31 Metallic Screen short circuit current capacity kA 16.20 kA (calculation submitted)
for 1 sec
32 Armour short circuit capacity for 1 sec kA 15.49 kA for 1 sec.
33 Short circuit capacity of the conductor of the kA 43.50 kA for 1 sec.
cable for 1 sec
34 Cable Resistance (R), Reactance (X) and Susceptance (B) per km:
a) for positive sequence
Resistance (R) ohm 0.079
Reactance (X) ohm J0.121
Susceptance (B) ohm j14.4047
b) negative sequence
Resistance (R) ohm 0.079
Reactance (X) ohm -j0.121
Susceptance (B) ohm - j14.4047
c) zero sequence
Resistance (R) ohm 0.325
Reactance (X) ohm j0.0612
Susceptance (B) ohm j0.6007